Appendix A
Specifications
General Specifications
Conforms to the CPU Unit specifications.
Item
Connectable temperature sensor (see note 1)
Current Transformer detection current
No. of input points (loops)
Temperature control mode
Setting/Indication accuracy
(see note 2, 3 and 4)
Influence of temperature:
For ambient temperature change from 0 to 23 to 55
°
C
Influence of voltage:
For change from
−
15% lower to
10% higher than rated voltage
C200H-TC00
@
C200H-TC10
@
Thermocouple (R, S, K, J, T, E, B, N, L, U) Platinum resistance thermometer (JPt100,
Pt100)
0.1 to 4.9 A (with a heater burnout detecting current difference of 0.5 A min.)
Indication accuracy:
±
5% FS
±
1 digit max.
Two points (two loops, each of which consists of a temperature sensor and a CT)
PID, ON/OFF (selectable with a switch on the rear panel)
(PID control with feed-forward circuitry with auto-tuning)
±
0.5% of set (designated) value or
±
2
°
C whichever larger
±
1 digit max.
±
0.5% of set (designated) value or
±
1
°
C whichever larger
±
1 digit max.
Thermocouples R and S
±
1% of set (designated) value or
±
10
°
C, whichever is larger,
±
1 digit max.
Other Thermocouples
±
1% of set (designated) value or
±
4
°
C, whichever is larger,
±
1 digit max.
Platinum Resistance Thermometer
±
1% of set (designated) value or whichever is larger,
CT Input
±
0.25 A
±
±
1 digit max.
1 digit max.
CT Input
±
0.25 A
±
1 digit max.
0.0
°
to 999.9
°
C/
°
F (in units of 0.1
°
C/
°
F) (during ON/OFF control action)
0.0
°
to 999.9
°
C/
°
F (in units of 0.1
°
C/
°
F)
0 to 9999 s (in units of 1 s)
±
2
°
C,
0 to 9999 s (in units of 1 s)
Hysteresis
Proportional band
Integral (reset) time
Derivative (rate) time
Control period
Sampling period
1 to 99 s (in units of 1 s)
500 ms
Output refresh period
Display refresh period
Input shift range
Alarm output setting range
No. of banks
500 ms
500 ms
–99.9
°
to 999.9
°
C/
°
F (in units of 0.1
°
C/
°
F)
–999
°
to 9,999
°
C/
°
F (in units of 1
°
C/
°
F)
8 banks
Internal current consumption 5 VDC, 0.33 A max.
External supply voltage
Dimensions (see note 4)
Weight
24 VDC
+10%
/
–15%
, 0.2 A min.
34.5 mm (W) x 130 mm (H) x 120.5 mm (D)
360 g
–99.9
°
to 999.9
°
C/
°
F (in units of 0.1
°
C/
°
F)
Note 1.
Set with the switch on the rear panel. See Appendix B Sensor Temperature Measurement Range for the measurable temperature range.
2.
The set value and designated value coincide with each other.
3.
The indication accuracy of thermocouples R and S at a temperature of 200
°
C max., that of thermocouples K and T at a temperature of –100
°
C max, and that of thermocouple U are all
±
4
°
C,
±
1 digit max. The indication accuracy of thermocouple B at a temperature of 400
°
C or below is not guaranteed.
4.
At an ambient temperature of 23
°
C.
5.
See Appendix D Dimensions.
65
Specifications
Appendix A
Output Characteristics
Open-collector Output (Pulse) C200H-TC
@
01
External supply voltage
Max. load voltage
Max. load current
Residual voltage when ON
Leakage current when OFF
24 VDC
+10%
/
–15%
24 VDC max.
100 mA max.
3 V max.
0.3 mA max.
Voltage Output (Pulse) C200H-TC
@
02
Output voltage
Max. load current
Current Output (Linear) C200H-TC
@
03
Output current
Permissible load impedance
Current value accuracy
12 VDC
40 mA (with short-protective circuit)
4 to 20 mA
600
Ω
max.
4
±
0.3 to 20
±
1 mA
66