Technical data
Appendix A Technical data
A.1 Corrigo Ardo
A.1.1
General data
Supply voltage
Power consumption
Ambient temperature
Ambient humidity
Storage temperature
24 V AC (21…27 V AC 50…60 Hz / 20…36 V DC
See
Table B-2 in Appendix B Model overview
0…50 °C
Max. 95 % RH
-20…70 °C
Protection class
Connection
Memory backup
Display
Mounting
Casing
Dimensions (WxHxD)
Battery type
Battery life
Operating system
IP20
Disconnectable terminal strips, 4 mm 2
Built-in long life battery gives long backup time of all settings incl. real time
Backlit LCD, 4 rows of 20 characters
DIN-rail or cabinet
Standard Euronorm (8.5 modules wide)
149 x 121 x 60 mm incl. terminals
CR2032 replaceable Lithium cell
Min. 5 years
EXOrealC
A.1.2
Communication ports
TCP/IP
RS485
EXOline, Modbus, BACnet/IP, CLOUDigo
EXOline, Modbus, BACnet MS/TP
A.1.3
Inputs & Outputs
Analog inputs (AI)
Digital inputs (DI)
Universal inputs (UI)
Analog outputs (AO)
Digital outputs (DO)
For PT1000, Ni1000, Ni1000LG sensors (accuracy ± 0.4 °C) or 0…10 V DC (accuracy ± 0.15 % of full output signal). 12 bit resolution in the A/D conversion.
For potential-free contacts
Can be set to act as either analog input or digital input with specifications as above
0…10 V DC, 1 mA, short-circuit protected
Mosfet outputs, 24 V AC or DC, 2 A continuous. Max. 8 A in total.
Corrigo manual, Rev. D 167 (196)
Technical data
A.2 Corrigo Vido
A.2.1
General data
Supply voltage
Power consumption
Ambient temperature
Ambient humidity
Storage temperature
Protection class
Memory backup
Display
Mounting
Dimensions (WxHxD)
Battery type
Battery life
Operating system
85…265 V AC, 50/60 Hz
See
Table B-4
in
Appendix B Model overview
0…50 °C
Max. 95 % RH
-20…70 °C
IP20, IP40 when mounted in cabinet
Built-in long life battery gives long backup time of all settings incl. real time
Backlit LCD, 4 rows of 20 characters
DIN-rail, cabinet or on wall
146.7 x 97.6 x 76.0 mm incl. terminals
CR2032 replaceable Lithium cell
Min. 8 years
EXOrealC
A.2.2
Communication ports
TCP/IP
RS485
EXOline, Modbus, BACnet/IP, CLOUDigo
EXOline, Modbus, BACnet MS/TP
A.2.3
Inputs & Outputs
Analog inputs (AI)
Digital inputs (DI)
Universal inputs (UI)
Analog inputs/outputs (UA)
Digital outputs (DO)
For PT1000, Ni1000, Ni1000LG sensors. 12 bit resolution in the A/D conversion.
For potential-free contacts
Can be set to act as either analogue inpue or digital input with specifications as above
Configurable as output (0…10 V DC, 2…10 V DC, 10…0 V DC or 10…2 V DC, 8 bit D/A (shortcircuit protected) or input (0…10 V DC)
7x relay, 230 V AC, 1 A load per relay, max 7 A total
168 (196) Corrigo manual, Rev. D