System Operations. Bosch Solution 2000, SOLUTION 3000

Add to My manuals
150 Pages

advertisement

System Operations. Bosch Solution 2000, SOLUTION 3000 | Manualzz

Control Panel System Operations | en

31

6

6.1

System Operations

This section explains the general operations of the system: arming and disarming the system in the three modes, isolating zones, initiating codepad alarms, and determining a fault.

Operations described in this chapter are based on use with the IUI–SOL–ICON codepad. For the IUI-SOL-TEXT codepad, follow the prompts on the codepad display.

Arming the system in AWAY Mode

Arming the system in AWAY Mode is normally performed when you leave the premises and require that all zones are activated in a ready state to detect an intrusion.

There are two different methods to arm the system in AWAY Mode. You can always use method one. You can use method two only if Option 2 is enabled in Location 497 (refer to

Consumer Options 2, page 142).

If you must isolate a zone (or zones) before arming the system in AWAY Mode, refer to

Isolating zones, page 35.

Notice!

Single button arming in AWAY mode reports as user code number 00.

To arm the system in AWAY Mode (method one):

1.

Enter your code and press [AWAY].

2.

Two beeps sound, the AWAY indicator lights, and Exit Time starts.

To arm the system in AWAY Mode (method two):

Notice!

Select Option 2 in Location 497 to enable single button arming in AWAY Mode (refer to

Consumer Options 2, page 142).

6.2

1.

Press and hold [AWAY].

2.

When two beeps sound, release the button. The AWAY indicator lights and Exit Time starts.

If a zone is not sealed at the end of Exit Time, the zone is automatically isolated and its indicator is lit on the codepad. The zone becomes an active part of the system again as soon as it is resealed. For example, if a window is open when Exit Time expires, the window is not an active part of the system until it is closed. Opening the window after Exit Time expires causes an alarm.

Forced Arming

Arming the system when a zone is not sealed is known as forced arming. Refer Zone Options 2,

page 101 to enable forced arming for each zone.

If the AWAY indicator does not light and a long beep sounds when you attempt to arm the system in AWAY Mode, forced arming is not permitted. If this is the case, you seal all zones or manually isolate them before you can arm the system.

Disarming the system from AWAY Mode

When you enter the premises after the system is armed in AWAY Mode, you must disarm the system from AWAY Mode to disable detection devices that activate the sirens, strobe, and bell outputs.

If there was an alarm prior to disarming the system from AWAY Mode, a zone indicator flashes, indicating a previous alarm in that zone.

Bosch Security Systems, Inc.

Installation Guide 2017.10 | 03 | F.01U.298.026

32

en | System Operations

6.3

Control Panel

To disarm the system from AWAY Mode:

1.

Enter your code and press [AWAY].

2.

Two beeps sound and the AWAY indicator is extinguished.

Arming the System in STAY Mode 1

STAY Mode 1 is used when you need to arm the perimeter and unused areas of the premises to detect a would-be intruder entering the premises, while at the same time being able to move freely within an area that is automatically isolated.

Only the installer can program zones to be automatically isolated in STAY Mode 1. Refer to

Zone Options 2, page 101 for more information on setting zones to be automatically isolated in

STAY Mode 1.

There are two methods to arm your system in STAY Mode 1. You can always use method one.

You can use method two only if Option 2 is enabled in Location 497 (refer to Consumer

Options 2, page 142).

If the system reports to a base station, it sends a STAY Mode 1 Arm Report (Contact ID Event

Code 441).

Entry Guard Time for STAY Mode

When arming the system in STAY Mode 1, an optional entry time called Entry Guard Time for

STAY Mode can be used to delay the sirens, strobe, and bell outputs if a zone that is not automatically isolated activates an alarm. Entry Guard Time for STAY Mode is the delay time used for all zones, except 24-Hour zones, when the system is armed in STAY Mode 1 or STAY

Mode 2. For more information, refer to Entry Guard Time for STAY Mode, page 135.

If the Entry Guard Time for STAY Mode is programmed and a zone that was not automatically isolated is activated, the codepad beeps twice per sec until the Entry Guard Time for STAY

Mode expires or the system is disarmed. If the alarm is not reset before Entry Guard Time for

STAY Mode expires, the strobe, bell, and siren outputs are activated into alarm.

Notice!

Single button arming in STAY Mode 1 reports as User Code number 00.

To arm the system in STAY Mode 1 (method one):

1.

Enter your code and press [STAY].

2.

Two beeps sound and the STAY indicator is lit. Exit Time starts.

The indicators for any zones that are programmed to be automatically isolated in STAY Mode 1 begin to flash until Exit Time expires. At the end of Exit Time, the zone indicators are extinguished and the codepad sounds one short beep.

To arm the system in STAY Mode 1 (method two):

1.

Press and hold [STAY].

2.

When two beeps sound, release the button. The STAY indicator is lit and Exit Time starts.

The indicators for any zones that are programmed to be automatically isolated in STAY Mode 1 flash until Exit Time expires. At the end of Exit Time, the zone indicators are extinguished and the codepad sounds one short beep.

If a zone is not sealed at the end of Exit Time, the zone is automatically isolated and is lit constantly on the remote codepad. The zone becomes an active part of the system again as soon as it is resealed. For example, if a window is open when Exit Time expires, the window does not become an active part of the system until it is closed. Opening the window after Exit

Time expires causes an alarm.

Forced Arming

2017.10 | 03 | F.01U.298.026

Installation Guide Bosch Security Systems, Inc.

Control Panel

6.4

System Operations | en

33

Arming the system when a zone is not sealed is known as forced arming. Refer to Zone Options

2, page 101 to enable forced arming for each zone.

If the STAY indicator does not light and a long beep sounds when you attempt to arm the system in STAY Mode 1, forced arming is not permitted. If this is the case, you must seal all zones or manually isolate them before you can arm the system.

Disarming the system from STAY Mode 1

There are two methods to disarm the system from STAY Mode 1. You can always use the first method. You can use method two only if Option 4 is enabled in Location 497 (refer to

Consumer Options 2, page 142).

To disarm the system from STAY Mode 1 (method one):

1.

Enter your code and press [STAY].

2.

Two beeps sound and the STAY indicator is extinguished. The system is now disarmed.

To disarm the system from STAY Mode 1 (method two):

A flashing zone indicator represents a previous alarm in that zone. If this is the case, a valid

User Code is required to disarm the system using method one. To enable method two, Option

4 in Location 497 must be enabled.

1.

Press and hold [STAY].

2.

When two beeps sound, release the button. The STAY indicator is extinguished and the system is disarmed.

Notice!

Single button disarming from STAY Mode 1 reports as User Code 00.

6.5

Arming the system from STAY Mode 2

STAY Mode 2 is used when you need to arm the perimeter and unused areas of the premises to detect a would-be intruder from entering the premises, while at the same time being able to move freely within an area that is automatically isolated.

You can program zones to be automatically isolated in STAY Mode 2 using an Installer Code

function (refer to Installer Code Functions, page 41) or a Master Code function (Master Code

Functions, page 51).

If the system reports to a base station, it sends a STAY Mode 2 Arm Report (Contact ID Event

Code 456).

Entry Guard Time for STAY Mode

When arming the system in STAY Mode 2, an optional entry time called Entry Guard Time for

STAY Mode can be used to delay the sirens, strobe, and bell outputs if a zone that is not automatically isolated activates an alarm. Entry Guard Time for STAY Mode is the delay time used for all zones, except 24-Hour zones, when the system is armed in STAY Mode 1 or STAY

Mode 2. For more information, refer to Entry Guard Time for STAY Mode, page 135.

If the Entry Guard Time for STAY Mode is programmed and a zone that was not automatically isolated is activated, the codepad beeps twice per sec until the Entry Guard Time for STAY

Mode expires or the system is disarmed. If the alarm is not reset before Entry Guard Time for

STAY Mode expires, the strobe, bell, and siren outputs are activated into alarm.

Notice!

Single button arming from STAY Mode 2 reports as User Code 00.

Bosch Security Systems, Inc.

Installation Guide 2017.10 | 03 | F.01U.298.026

34

en | System Operations

6.6

Control Panel

To arm the system in STAY Mode 2:

1.

Press and hold [0].

2.

When two beeps sound, release the button. The STAY indicator is lit and the Exit Time starts.

The indicators for any zones that are programmed to be automatically isolated in STAY Mode 2 flash until the Exit Time expires. At the end of Exit Time, the zone indicators are extinguished and the codepad sounds one short beep.

If a zone is not sealed at the end of Exit Time, the zone is automatically isolated and is lit constantly on the remote codepad. The zone becomes an active part of the system again as soon as it is resealed. For example, if a window is open when Exit Time expires, the window does not become an active part of the system until it is closed. Opening the window after Exit

Time expires causes an alarm.

Forced Arming

Arming the system when a zone is not sealed is known as forced arming. Refer to Zone Options

2, page 101 to enable forced arming for each zone.

If the STAY indicator does not light and a long beep sounds when attempting to arm the system, forced arming is not permitted. If this is the case, you must seal all zones or manually isolate them before you can arm the system.

Disarming the system from STAY Mode 2

There are two methods to disarm the system from STAY Mode 2. You can always use the first method. You can use method two only if Option 4 is enabled in Location 497 (refer to

Consumer Options 2, page 142 ).

To disarm the system from STAY Mode 2 (method one):

1.

Enter your code and press [STAY].

2.

Two beeps sound and the STAY indicator is extinguished. The system is now disarmed.

To disarm the system from STAY Mode 2 (method two):

A flashing zone indicator represents a previous alarm in that zone. If this is the case, a valid

User Code is required to disarm the system using method one. To enable method two, Option

4 in Location 497 must be enabled.

1.

Press and hold [0].

2.

When two beeps sound, release the button. The STAY indicator is extinguished and the system is disarmed.

Notice!

Single button disarming from STAY Mode 2 reports as User Code 00.

6.7

6.8

Codepad duress alarm

A codepad Duress Alarm is used as a silent holdup alarm when 9 is added to the end of a valid

User Code being used to disarm the system.

A Duress Alarm (Contact ID Event Code 121) is useful only if your system reports to a monitoring station because domestic reporting format cannot decipher the type of alarm that occurred. You can select Option 2 in Location 498 to use 3 instead of 9 to activate a Duress

Alarm (refer to Consumer Options 3, page 143).

Codepad panic alarm

An audible codepad Panic Alarm activates when a user presses either [1] and [3] or [STAY] and [AWAY] simultaneously.

2017.10 | 03 | F.01U.298.026

Installation Guide Bosch Security Systems, Inc.

Control Panel System Operations | en

35

6.9

6.10

6.11

Select Option 1 in Location 493 to program the codepad Panic Alarm as silent (refer to System

Options 2, page 139). A codepad Panic Alarm transmits Contact ID Event Code 120 if the

system reports to a base station receiver.

Codepad fire alarm

An audible codepad Fire Alarm activates when a user presses [4] and [6] on the remote codepad simultaneously. A distinct fire sound emits through the horn speaker to indicate this type of alarm. The fire sound is different than the burglary sound.

Select Option 2 in Location 493 to program the codepad Fire Alarm as silent (refer to System

Options 2, page 139). A codepad Fire Alarm transmits a Contact ID Event Code 110 to a base

station receiver.

Codepad medical alarm

An audible codepad Medical Alarm activates when a user presses [7] and [9] simultaneously.

Select Option 4 in Location 493 to program codepad Medical Alarm as silent (refer to System

Options 2, page 139). A codepad Medical Alarm transmits a Contact ID Event Code 100 to a

base station receiver.

Isolating zones

Isolating zones allows you to manually disable one or more zones before arming the system in

AWAY Mode, STAY Mode 1, or STAY Mode 2. When a zone is isolated, access is allowed into that zone when the system is armed without activating an alarm.

For example, you might want to isolate a zone before arming the system because a zone passive infrared (PIR) detector is activating false alarms or because you need to leave a pet inside a particular zone while you are away.

You can isolate zones using one of two methods. By default, the standard isolation method is used. Standard isolation does not require a User Code. The other method requires a valid User

Code. The ability to isolate zones is determined by the priority level assigned to each User

Code holder. Some User Code holders cannot isolate zones. Refer to User Code Priority, page

89 for more information.

Zones that are manually isolated using this method transmit a Zone Bypass Report (Contact ID

Event Code 573) for each isolated zone when the system is armed. A Zone Bypass Restore

Report is transmitted when the system is disarmed.

When you select a 24-Hour Fire Zone to be isolated, a Contact ID Event Code 571 is sent. If you select another 24-Hour Zone to be isolated, a Contact ID Event Code 572 is sent. A Zone

Bypass Report is transmitted once the 24-Hour Zone is isolated. A Zone Bypass Restore

Report is transmitted when the system is disarmed or the isolated zone is restored.

You can isolate zones manually using these two methods, and you can also isolate zones automatically as programmed by the installer.

How to isolate zones automatically in STAY Mode 1, refer to Zone Options 2, page 101.

How to isolate zones automatically in STAY Mode 2, refer to STAY Mode 2 Automatically Bypass

Zones, page 106.

6.11.1

Standard isolating

Standard isolating allows any operator to isolate zones because no code is required.

1.

Press [STAY] twice. Three beeps sound and the STAY indicator flashes.

2.

Enter the number of the zone to be isolated and press [STAY]. The indicator for the zone flashes. 24-Hour zones are automatically isolated as soon as you press [STAY]. All other

Burglary Zones are automatically isolated only after the system is armed.

Bosch Security Systems, Inc.

Installation Guide 2017.10 | 03 | F.01U.298.026

36

en | System Operations

6.11.2

6.12

Control Panel

3.

Repeat Step2 for each zone you want to isolate.

Notice!

As each zone is selected to be isolated, the corresponding zone indicator flashes. If you make a mistake, enter the incorrect zone number and press [STAY]. This zone is no longer selected to be isolated and the zone indicator is extinguished.

4.

Press [AWAY].

Two beeps sound and the system returns to the disarmed state.

The indicators for the selected zones continue to flash until the next time the system is disarmed.

Example:

To manually isolate zones 1, 3, and 4, press: [STAY][STAY][1][STAY][3][STAY][4][STAY]

[AWAY]

Code to isolate

The code to isolate method permits only those User Code holders with a priority level that includes Code to Isolate. The standard isolating method is disabled for any User Code with this priority level set.

1.

Press [STAY].

2.

Enter your code and press [STAY]. Three beeps sound and the STAY indicator flashes. If you attempt to enter isolating mode with a User Code that is not set for Code to Isolate, the system ignores the attempt.

3.

Enter the number of the zone to be isolated and press [STAY]. The indicator for the zone flashes. 24-Hour zones are automatically isolated as soon you press [STAY]. All other

Burglary zones are automatically isolated only after the system is armed.

4.

Repeat Step3 for each zone you want to isolate.

Notice!

As each zone is selected to be isolated, the corresponding zone indicator flashes. If you make a mistake, enter the incorrect zone number and press [STAY]. This zone is no longer selected to be isolated and the zone indicator is extinguished.

5.

Press [AWAY].

Two beeps sound and the system returns to the disarmed state.

The indicators for the selected zones continue to flash until the next time the system is disarmed.

Example

To manually isolate zones 1, 3, and 4, press: [STAY][User Code][STAY][1][STAY][3][STAY][4]

[STAY][AWAY]

Fault analysis mode

When a system fault occurs, the FAULT or MAINS indicator flashes and the codepad beeps once per minute.

If the AC MAINS supply fails, the MAINS indicator flashes until the AC MAINS supply is restored. Press [AWAY] once to acknowledge the fault and stop the codepad from beeping once every minute.

2017.10 | 03 | F.01U.298.026

Installation Guide Bosch Security Systems, Inc.

Control Panel System Operations | en

37

3

4

5

To enter Fault Analysis Mode to determine a system fault other than the AC MAINS supply:

1.

Press and hold [5] until two beeps sound. The FAULT indicator remains lit and the STAY and AWAY indicators flash. The lit zone indicators indicate the type of fault that occurred.

2.

If necessary, press the button corresponding to the indicator to further determine the fault. (Refer to the table Fault Analysis Conditions below.)

3.

To exit from Fault Analysis Mode, press [AWAY]. The STAY and AWAY indicators are extinguished and the FAULT indicator remains lit.

Fault Indicators

Fault Description Zone

Indicator

1

2

System Fault

Press

Button

1

Zone

Indicator

Fault Condition

3

4

1

2

5

7

8

9 to 16

Battery Fail

Date and Time

RF Receiver Fail

Output 1 to 3 Fail

Telephone Line Fail

Power Supply Fail

Onboard Tamper

RF Repeaters 1 to 8 Fail (Solution

2000 N.A.)

1 to 16 Zones 1 to 16 RF Low Battery

6

RF Low Battery

(Solution 2000

N.A.)

2

Zone Tamper Alarm 3

Sensor Watch Fault 4

RF Sensor Missing

(Solution 2000

N.A.)

5

Communication Fail 6

1 to 16

1 to 16

1 to 16

Zones 1 to 16 Tamper Alarm

Zones 1 to 16 Sensor Watch Fail

Zones 1 to 16 RF Sensor Watch Fail

7 Output and

Codepad Fail

7

8 Keyfob Low Battery 8

Table 6.1: Fault Indicators

1

2

3

4

5

6

Receiver 1 Fail

Receiver 2 Fail

Receiver 3 Fail

Receiver 4 Fail

IP Module 1 Fail

IP Module 2 Fail

1 to 2

3 to 6

Output Expanders 1 to 2 Fail

Codepads 1 to 4 Fail

1 to 16 Keyfobs 1 to 16 Low Battery

6.13

When working with a text codepad, press [5] to enter [Fault Analysis], you can page up or page down to view the fault items, and press [AWAY] to exit from Fault Analysis Mode.

Fault descriptions

1 – System Fault

The system FAULT indicator lights when any of the faults listed in the table System FAULT

Indicators below occurs. In Fault Analysis Mode, press [1] to determine the fault that occurred.

Bosch Security Systems, Inc.

Installation Guide 2017.10 | 03 | F.01U.298.026

38

en | System Operations Control Panel

2 – RF Device Low Battery

This fault occurs when any of the RF wireless devices report a low battery condition to the control panel. While in Fault Analysis Mode, press the [2] key until two beeps sound. This displays the zone reporting the RF Low Battery fault.

3 – Zone Tamper Fail

This fault occurs when any zone with tamper becomes an open or short circuit. Press the [3] key until two beeps sound. This displays the zone reporting the tamper fail fault.

4 – Sensor Watch Fault

A sensor watch fault registers when one or more detection devices failed to detect any movement during the disarmed state for the time programmed in Locations 476 and 477(refer

to Sensor Watch Report, page 114). The fault clears once the zone in question detects

movement and resets. Press the [4] key until two beeps sound. This displays the zone reporting the sensor watch fault.

5 – RF Sensor Missing

An RF sensor missing registers when one or more RF detection devices fails to communicate to the RF radio receiver for the time period programmed in Location 393 RF Supervision Time.

The fault clears once the RF device in question successfully transmits to the RF radio receiver.

While in Fault Analysis Mode, press the [5] key. This displays the RF detection device reporting the RF sensor watch fault.

6 – Communication Fail

A communication fail registers when the control panel fails to communicate with the receiving party (such as a monitoring company, mobile phone). The communication fault clears once the control panel successfully reports to the receiving party.

A communication fail also registers when network module is disconnected or tampered.

To determine which receiver or module failed to communicate, press the [6] key.

In Fault Analysis Mode, press [6] to show which communication fault occurred: 1 – Receiver 1;

2 – Receiver 2.

7 – Output and Codepad Fail

The output fault registers when any output expander B308 is disconnected or tampered.

The codepad fault registers when any codepad is tampered or disconnected from the control panel.

To determine which fault occurred, press the [7] key.

8 – Keyfob Low Battery

This fault occurs when any of the RF keyfobs report a low battery condition to the control panel. To determine which keyfob failed, press the [8] key. Only keyfob 1 to 16 faults display on the codepad through zone indicator 1 to 16.

System FAULT indicators

Indicator FAULT description

1

Low battery

This fault registers when the system detects a low capacity backup battery. The system automatically performs a battery test every 4 hours and every time you arm the system.

2

Date and time

This fault registers when the system is powered down.

2017.10 | 03 | F.01U.298.026

Installation Guide Bosch Security Systems, Inc.

Control Panel

6.14

System Operations | en

39

Indicator FAULT description

3

RF receiver fault

This fault registers when the RF wireless receiver unit detects RF jamming, the

RF wireless receiver is disconnected from the control panel or failed, or the RF receiver’s cover tamper switch is activated.

4

5

7

8

Warning Device fault

This fault registers when the system detects output 1-3 as warning device

(Horn Speaker, Siren Running, Strobe) is disconnected or short. This fault clears once all outputs are reconnected. This feature is enabled by selecting

Option 2 in Location 492 (refer to System Options 1, page 138).

Telephone line fault

This fault registers when the system detects the telephone line is disconnected from the control panel. This feature is enabled by selecting Option 1 in

Location 176.

Power Supply fail

This fault occurs when AUX power supplies fail, +12V power fails, or SDI2 Bus power fails. Contact your installer as soon as this fault displays.

Onboard Tamper

This fault occurs when the system detects the control panel is tampered.

9-16

RF Repeater Tamper/Fail

The RF repeater 1 to 8 fault registers once the system detects that the wireless repeater is disconnected or the repeater tamper is triggered.

AC MAINS Failure

An AC MAINS supply failure automatically flashes the MAINS indicator. If the AC MAINS supply is disconnected continuously for longer than 2 min, the remote codepad beeps the codepad buzzer once per min. If the control panel is programmed to report an AC MAINS failure to a base station receiver, an AC Fail Report (Contact ID Event Code 301) is transmitted.

The MAINS indicator stops flashing when the AC MAINS supply is reconnected. When the AC

MAINS supply is connected continuously for 2 min, the codepad stops the once per min beep and an AC Fail Restore Report is transmitted to the base station receiver.

If the Enable AC Fail in 1 Hour option (1) is selected in Location 494 (refer to System Options

3, page 139), the codepad flashes the MAINS indicator when the AC MAINS supply is

disconnected, but does not activate the report or the codepad buzzer unless the AC MAINS supply is disconnected continuously for 1 hour.

If the Ignore AC MAINS Fail option (2) is selected in Location 494 (refer to System Options 3,

page 139) the codepad does not indicate when the AC MAINS supply fails, but the control

panel still reports an AC Fail Report, if enabled.

Inquire cloud status

You can inquire cloud status only with the alphanumeric codepad IUI-SOL-TEXT.

When the control panel is connected to the cloud module B4xx-M, go to menu 721 Network

Module to select B4xx-M and set it to enable.

Inquire the cloud status to check connection status to the cloud service and to view the module UID.

Bosch Security Systems, Inc.

Installation Guide 2017.10 | 03 | F.01U.298.026

40

en | System Operations

How to view the cloud status and UID

1.

Enter your Installer Code or User Code, followed by [#].

2.

Press [1][2][3], the cloud status is shown.

3.

Press [#], the UID is shown.

4.

Press [-] to exit.

Control Panel

2017.10 | 03 | F.01U.298.026

Installation Guide Bosch Security Systems, Inc.

advertisement

Key Features

  • Supports up to 8 zones for comprehensive coverage
  • Stay and Away arming modes for customizable protection
  • Panic, fire, and medical alarms for emergency situations
  • Remote arming and disarming via telephone or A-Link Plus Software
  • Event Memory Recall Mode for easy review of system activity
  • Fault Analysis Mode for quick troubleshooting

Related manuals

Frequently Answers and Questions

How many zones does the Bosch Solution 2000 support?
The Bosch Solution 2000 supports up to 8 zones.
Does the Bosch Solution 2000 have a panic alarm?
Yes, the Bosch Solution 2000 has a panic alarm that can be activated from any keypad.
Can the Bosch Solution 2000 be armed and disarmed remotely?
Yes, the Bosch Solution 2000 can be armed and disarmed remotely via telephone or A-Link Plus Software.
How do I reset the Bosch Solution 2000 to factory default settings?
To reset the Bosch Solution 2000 to factory default settings, enter Installer Code 961.
Download PDF

advertisement

Table of contents