Zone Information. Bosch Solution 2000, SOLUTION 3000

Add to My manuals
150 Pages

advertisement

Zone Information. Bosch Solution 2000, SOLUTION 3000 | Manualzz

Control Panel Zone Information | en

91

13

13.1

Item

Day Alarm Zones

13.1.1

13.1.2

13.1.3

Zone Information

Day Alarm Information

Location Option Default New

0265 1 = Zone 1

2 = Zone 2

4 = Zone 3

8 = Zone 4

0

This location has four programming options. You can select any combination of the options by programming a single value. Calculate this value by adding the option bit numbers together.

Day Alarm allows some zones to be monitored when the system is disarmed. Indications are available at any of the programmable outputs, including the codepad buzzer. This function accommodates latching and non-latching Day Alarm Output Event Types.

When the system is armed in AWAY Mode, STAY Mode 1, or STAY Mode 2, zones programmed as Day Alarm Zones activate the sirens and report just as non-Day Alarm Zones do. When Day

Alarm is activated, it ignores any zone Pulse Count settings programmed for that zone (that is, the zone Pulse Count is only relevant when the system is armed).

Example

You can set up a Day Alarm at the front door of a shop with a pressure mat or electronic beam that is activated when a customer enters the shop. When a customer walks on the pressure mat or breaks the electronic beam, the codepad buzzer beeps.

Day Alarm Resetting

An output that is programmed for Day Alarm Resetting operates when a zone programmed for

Day Alarm is activated. The output is reset after the zone is resealed. This occurs only when

the system is disarmed. Refer to 0,14 Day Alarm Resetting in Output Event Types, page 123

for more information.

Day Alarm Latching

An output that is programmed for Day Alarm Latching operates when a zone programmed for

Day Alarm is activated. The zone indicator and the latching output resets when [AWAY] is pressed. This occurs only when the system is disarmed. Refer to 0,15 Day Alarm Latching in

Output Event Types, page 123 for more information.

Day Alarm Operation

If a zone is programmed for Day Alarm, the zone can be isolated in the normal way so that it does not register as a Day Alarm Zone when the system is disarmed. You can use only Zones 1 to 4 as Day Alarm Zones.

You can program the STAY indicator to indicate whether Day Alarm is turned on or off by

selecting Option 8 in Location 496 (refer to Consumer Options 1, page 141). When Day Alarm

is on, the STAY indicator flashes once every 3 seconds.

You can program an output to mimic a zone for monitoring Zones 5 to 8. Refer to Output Event

Types, page 123.

To turn Day Alarm on:

Press and hold [4] until three beeps sound.

To turn Day Alarm off:

Press and hold [4] until two beeps sound.

Bosch Security Systems, Inc.

Installation Guide 2017.10 | 03 | F.01U.298.026

92

en | Zone Information

13.2

Control Panel

EOL Resistor Value

7

8

9

4

5

6

1

2

3

Location 266

0 No EOL

1K (brown, black, red)

1K5 (brown, green, red)

2K2 (red, red, red)

3K3 (orange, orange, black, brown) 1%

3K9 (orange, white, red)

4K7 (yellow, violet, red)

5K6 (green, blue, red)

6K8 (blue, grey, black, brown) 1%

10K (brown, black, orange)

10

11

12

12K (brown, red, orange)

22K (red, red, orange)

Normal open

13

14

Reserved

Split EOL (3K3/6K8) with tamper (1K)

15 Split EOL 1% resistors

You can program the control panel for different end-of- line (EOL) resistor values. This is a global parameter that affects all zones simultaneously. This feature allows you to install the control panel at an existing site without changing the EOL resistors. This feature also increases the security of the system because eleven possible EOL resistor values can be used, which makes it extremely difficult to tamper with the system.

For No EOL, it is short as normal status and it is unsealed when the system activates an alarm.

Connections for EOL Resistors

2017.10 | 03 | F.01U.298.026

Installation Guide Bosch Security Systems, Inc.

Control Panel Zone Information | en

93

1

3

NC

Zone 1

NO

Zone 1

Zone 1

(3K3 EOL)

NC

Zone 5 (Solution 2000)

Zone 9 (Solution 3000)

(6K8 EOL)

NC

TAMPER NC

NC TAMPER

4

2

NC Zone 1

NC

NC

Zone 5 (Solution 2000)

Zone 9 (Solution 3000)

(6K8 EOL)

Zone 1

(3K3 EOL)

13.3

13.3.1

Callout - Description

1 – Zone without resistor (Location 266 = 0 (No EOL), Location 266 = 12 (Normal open))

2 – Single Zone input (Location 266 = 1k, 1k5, 2k2, 3k3, 3k9, 4k7, 5k6, 6k8, 10k, 12k, 22k)

3 – Double Zone with tamper (Location 266 = 14 (Split EOL3K3 / 6K8 with tamper))

4 – Double Zone input (Location 266 = 15 (Split EOL 3k3 / 6k8))

Zone Programming

The programming information for each zone is stored in six locations divided into three groups. The first three locations determine how the zone operates, the next two locations set up a number of zone options, and the last location stores the communicator reporting information for the zone.

Zone Operating Information

These locations store the Zone Type (for example, Delay-1, Instant, or 24-Hour), the Zone

Pulse Count, and the Zone Pulse Count Time. The Zone Pulse Count specifies the number of times the zone must activate within the time specified in the Zone Pulse Count Time. Refer to

Zone Types, page 97, Zone Pulse Count, page 99, and Zone Pulse Count Time, page 100 for

more information.

Zone Options

These two locations allow you to select from a number of options. Refer to Zone Options 1,

page 100 and Zone Options 2, page 101 for more information.

Zone Reporting Information

This information includes the locations for the Zone Report Options.

The Zone Report Options location enables you to specify how a zone reports to a base station

receiver. Refer to Zone Report Options, page 102 for more information.

Zone Defaults

You can program Zones 1 to 16 as any zone type.

Bosch Security Systems, Inc.

Installation Guide 2017.10 | 03 | F.01U.298.026

94

en | Zone Information

Location 267 to 378

Zone #01 (Default = Delay-1)

Zone Type

Zone Pulse Count

Zone Pulse Count Time

Zone Options 1

Zone Options 2

Zone Report Options

Zone #02 (Default = Handover)

Zone Type

Zone Pulse Count

Zone Pulse Count Time

Zone Options 1

Zone Options 2

Zone Report Options

Zone #03 (Default = Handover)

Zone Type

Zone Pulse Count

Zone Pulse Count Time

Zone Options 1

Zone Options 2

Zone Report Options

Zone #04 (Default = Handover)

Zone Type

Zone Pulse Count

Zone Pulse Count Time

Zone Options 1

Zone Options 2

Zone Report Options

Zone #05 (Default = Instant)

Zone Type

Zone Pulse Count

Zone Pulse Count Time

2017.10 | 03 | F.01U.298.026

Installation Guide

Control Panel

1

0

0

1

14

1

1

14

1

1

0

0

0

0

0

Bosch Security Systems, Inc.

Default

2

0

0

1

14

1

1

0

0

1

14

1

288

289

290

291

292

294

281

282

283

284

285

287

295

296

297

Location

267

268

269

270

271

273

274

275

276

277

278

280

Control Panel

Location 267 to 378

Zone Options 1

Zone Options 2

Zone Report Options

Zone #06 (Default = Instant)

Zone Type

Zone Pulse Count

Zone Pulse Count Time

Zone Options 1

Zone Options 2

Zone Report Options

Zone #07 (Default = Instant)

Zone Type

Zone Pulse Count

Zone Pulse Count Time

Zone Options 1

Zone Options 2

Zone Report Options

Zone #08 (Default = 24-hr Tamper)

Zone Type

Zone Pulse Count

Zone Pulse Count Time

Zone Options 1

Zone Options 2

Zone Report Options

Zone #09 (Default = Not used)

Zone Type

Zone Pulse Count

Zone Pulse Count Time

Zone Options 1

Zone Options 2

Zone Report Options

Zone #10 (Default = Not used)

Bosch Security Systems, Inc.

Installation Guide

Zone Information | en

95

0

1

15

0

14

1

1

12

1

9

0

0

0

0

0

1

14

1

0

0

0

1

12

1

Default

1

14

1

2017.10 | 03 | F.01U.298.026

323

324

325

326

327

329

316

317

318

319

320

322

302

303

304

305

306

308

309

310

311

312

313

315

Location

298

299

301

96

en | Zone Information

Location 267 to 378

Zone Type

Zone Pulse Count

Zone Pulse Count Time

Zone Options 1

Zone Options 2

Zone Report Options

Zone #11 (Default = Not used)

Zone Type

Zone Pulse Count

Zone Pulse Count Time

Zone Options 1

Zone Options 2

Zone Report Options

Zone #12 (Default = Not used)

Zone Type

Zone Pulse Count

Zone Pulse Count Time

Zone Options 1

Zone Options 2

Zone Report Options

Zone #13 (Default = Not used)

Zone Type

Zone Pulse Count

Zone Pulse Count Time

Zone Options 1

Zone Options 2

Zone Report Options

Zone #14 (Default = Not used)

Zone Type

Zone Pulse Count

Zone Pulse Count Time

Zone Options 1

2017.10 | 03 | F.01U.298.026

Installation Guide

Control Panel

0

1

15

0

14

1

1

14

1

Default

15

0

0

15

0

0

1

14

1

1

14

1

15

0

0

0

1

15

0

Bosch Security Systems, Inc.

337

338

339

340

341

343

344

345

346

347

348

350

Location

330

331

332

333

334

336

351

352

353

354

355

357

358

359

360

361

Control Panel Zone Information | en

97

13.3.2

8

9

6

7

3

4

5

Zone Type

0

1

2

Location 267 to 378

Zone Options 2

Zone Report Options

Zone #15 (Default = Not used)

Zone Type

Zone Pulse Count

Zone Pulse Count Time

Zone Options 1

Zone Options 2

Zone Report Options

Location

362

364

365

366

367

368

369

371

Default

14

1

15

0

0

1

14

1

Zone #16 (Default = Not used)

Zone Type

Zone Pulse Count

Zone Pulse Count Time

Zone Options 1

372

373

374

375

15

0

0

1

Zone Options 2 376 14

Zone Report Options 378 1

The Solution 2000 control panel supports up to 8 zones. The Solution 3000 control panel supports up to 16 zones. Zone 9-16 can only be used in Solution 3000 control panels when the

EOL Resistor Value is set as 14 or 15.

Zone Types

The zone types are listed in the table below.

Description

Instant

Handover

Delay-1

Delay-2

Reserved

Reserved

24-Hour Medical

24-Hour Panic

24-Hour Holdup

24-Hour Tamper

Bosch Security Systems, Inc.

Installation Guide 2017.10 | 03 | F.01U.298.026

98

en | Zone Information Control Panel

Zone Type

10

11

12

13

Description

Reserverd

Keyswitch

24-Hour Burglary

24-Hour Fire

14 Chime Only

15 Not Used

0 – Instant Zone

When the Country Code is set as Australia (refer to Country Codes, page 73), an Instant Zone

(Contact ID Event Code 130) immediately sounds the sirens and sends the zone alarm reports if it is unsealed after the Exit Timer expires.

Arming Report is sent after the Exit Timer expires.

If an Instant Zone is not restored when the time the system is disarmed, a Zone Restore

Report is automatically sent to the receiving party.

1 – Handover Zone

A Handover Zone (Contact ID Event Code 130) acts as an Instant Zone if it is activated by itself. If a Handover Zone is activated after a Delay Zone, the remaining Delay Time is handed over from the Delay Zone to the Handover Zone.

Handover can be sequential or non-sequential. The default settings is sequential handover.

You can disable sequential handover by disabling Option 8 in Location 494 (refer to System

Options 3, page 139).

Handover Zone is not restored when the system is disarmed, a Zone Restore Report is automatically sent to the receiving party.

2 – Delay-1 Zone

A Delay-1 Zone (Contact ID Event Code 130) has a delay time determined by the value in

Locations 466 and 467 (refer to Entry Time 1, page 134). After Entry Time expires, the system

activates an alarm.

If a Delay-1 Zone is not restored when the system is disarmed, a Zone Restore Report is automatically sent to the receiving party.

3 – Delay-2 Zone

A Delay-2 Zone (Contact ID Event Code 130) has a delay time determined by the value in

Locations 468 and 469 (refer to Entry Time 2, page 134). After Entry Time expires, the system

activates an alarm.

If a Delay-2 Zone is not restored when the system is disarmed, a Zone Restore Report is automatically sent to the receiving party.

6 – 24-Hour Medical Zone

A 24-Hour Medical Zone (Contact ID Event Code100) is always ready to activate the horn speaker, bell, and strobe, whether the system is armed or disarmed. A Medical Report is transmitted to the base station receiver. A 24-Hour Medical Zone does not send a Restore

Report until the zone is restored.

7 – 24-Hour Panic Zone

A 24-Hour Panic Zone (Contact ID Event Code 120) is always ready to activate the horn speaker, bell, and strobe, whether the system is armed or disarmed. A Panic Report is transmitted to the base station receiver. A 24-Hour Panic Zone does not send a Restore

Report until the zone is restored.

2017.10 | 03 | F.01U.298.026

Installation Guide Bosch Security Systems, Inc.

Control Panel

13.3.3

Zone Information | en

99

8 – 24-Hour Holdup Zone

A 24-Hour Holdup Zone (Contact ID Event Code122) is always ready to activate the horn speaker, bell, and strobe, whether the system is armed or disarmed. If you want the holdup

alarm to be silent, select Option 4 in the first Zone Options location (refer to Zone Options 1,

page 100). A 24-Hour Holdup Zone does not send a Restore Report until the zone is restored.

9 – 24-Hour Tamper Zone

A 24-Hour Tamper Zone (Contact ID Event Code137) is always ready to activate the horn speaker, bell, and strobe, whether the system is armed or disarmed. A 24-Hour Tamper zone does not send a Restore Report until the zone is restored.

11 – Keyswitch Zone

Use a Keyswitch Zone to connect a keyswitch to operate the system. The zone number is reported as a User Code when arming and disarming using this method of operation, refer to

Keyswitch Zone Options, page 103 for more information. (Contact ID Event Code 409 for

Keyswitch Away Arm and Keyswitch Disarm, 442 for Keyswitch Stay 1 Arm).

12 – 24-Hour Burglary Zone

A 24-Hour Burglary Zone (Contact ID Event Code133) is always ready to activate the horn speaker, bell, and strobe, whether the system is armed or disarmed. A 24-Hour Burglary zone does not send a Restore Report until the zone is restored.

13 – 24-Hour Fire Zone

A 24-Hour Fire Zone (Contact ID Event Code 110) is always ready to activate the horn speaker, bell, and strobe, whether the system is armed or disarmed. A distinct fire sound is emitted through the horn speaker to indicate this type of alarm. This fire sound is completely different from the burglary sound. A 24-Hour Fire zone does not send a Restore Report until the zone is restored.

14 – Chime Zone

A Chime Zone is not a burglary zone. It can never sound the sirens or transmit reports. Its

purpose is to map the zone to a programmable output (refer to 4,5 Global Chime in Output

Event Types, page 123) to indicate if the zone is sealed or unsealed.

Chime zones require EOL resistors and are registered at a codepad. These zones do not affect the operation of forced arming.

15 –Zone Not Used

If a zone is not used, program the zone type location to 15. An EOL resistor is not required if this zone type is used. This zone type never sounds the sirens or transmits the reports.

Zone Pulse Count

Zone pulse count is the number of times a zone must be activated before the zone registers an alarm. The number can vary from 0 to 15. The zone pulse count value is relative to the time frame (that is, the number of pulses that must be present during a particular time frame).

Zone Pulse Count = 0, means the Zone Pulse Count function is disabled. Refer to Zone Pulse

Count Time, page 100 for more information.

Notice!

A zone that is programmed with a pulse count activates an alarm when it is continuously unsealed for 10 sec. A 24- Hour Fire Zone programmed with a pulse count activates an alarm when it is continuously unsealed for 30 sec.

Zone Pulse Count Handover

Zone pulse count handover operates only with Zone Pulse Count Time options 8 to 15.

Bosch Security Systems, Inc.

Installation Guide 2017.10 | 03 | F.01U.298.026

100 en | Zone Information Control Panel

Any zone that registers one active pulse automatically increments any other zone pulse count that already registered at least one activate pulse during its respective time. To enable this

feature, select Option 4 in Location 494 (refer to System Options 3, page 139).

Notice!

24-Hour Zones cannot receive any handover pulses from other zones. 24-Hour Zones can handover pulses to other zones.

13.3.4

13.3.5

Zone Pulse Count Time

Zone pulse count time is the time frame or period over which the programmed number of pulses must register to activate an alarm.

20 ms Option

3

4

5

0

1

2

Loop Response Time

(sec)

0.5

1

2

3

4

5

6

7

10

15

Table 13.1: Zone Pulse Count Times

150 ms Option

8

9

10

11

12

13

14

15

50

60

90

Loop Response Time

(sec)

20

30

40

120

200

For zone pulse count time, options 0 to 7 have a zone loop response time of 20 ms and options 8 to 15 have a zone loop response time of 150 ms. Loop response time is the length of time a zone must be unsealed before it can register as a valid pulse.

Inertia sensors should use options 0 to 7 and PIR detectors should use options 8 to 15.

Zone Options 1

This location has four programming options. You can select any combination of the options by programming a single value. Calculate this value by adding the option bit numbers together.

Option

1

Description

Lockout Siren/Lockout Report

2

4

Delay Alarm reporting

Silent Alarm

8 Sensor Watch

1 – Lockout Siren and Lockout Report

Lockout refers to certain activations per arming cycle (that is, a zone programmed for Lockout can activate the sirens or communication module for certain times as programmed).

2017.10 | 03 | F.01U.298.026

Installation Guide Bosch Security Systems, Inc.

Control Panel Zone Information | en 101

13.3.6

4

8

Option

1

2

Bosch Security Systems, Inc.

The next time the system is armed, the zone can activate the sirens and reports once more.

Restore signals are sent when the system is disarmed.

Lockout Siren and Lockout Report are separate for each zone. If a zone's siren or report is locked out, the other zone's siren or report still can be activated.

Use Location 379 to set the number of times the siren is allowed to activate before it is locked

out (refer to Swinger Shutdown Count for Siren, page 104).

Use Location 380 to set the number of times the communication module is activated to send

reports before lockout takes effect (refer to Swinger Shutdown Count for Report, page 105).

Use Location 492 to resend the Zone Reports when the report is unlocked out as Smart

Lockout Allowed in System Options 1, page 138.

When the smart lockout is allowed, the Lockout Report becomes unlocked and sends Alarm

Reports if the locked zone is activated again before the Siren Running Time (refer to Siren Run

Time, page 136a) is expired and if any other zone is activated

2 – Delay Alarm Reporting

Select this option to allow the reporting of alarms on selected zones to be delayed so that a user can enter a code to cancel alarms that are not required to report. All sounding devices

(horn speaker, strobe, and bell outputs) operate as soon as the alarm occurs, but the communication module does not operate until the delay time programmed in Locations 474

and 475 expires (refer to Delay Alarm Reporting Time, page 135).

During the same arming cycle, only the first Zone Alarm Report can be delayed.

4 – Silent Alarm

Select this option to program a zone as silent. A silent zone does not activate the horn speaker, bell, or strobe outputs. It activates the Silent Alarm output. The report and all other programmable outputs function according to the parameters programmed for the zone.

8 – Sensor Watch

Sensor watch allows the control panel to recognize when detection devices might have stopped working. This feature monitors the operation of a zone over the time period

programmed in Locations 476 and 477 (refer to Sensor Watch Time, page 135).

This value specifies how many 24-hour periods a zone can remain continuously sealed before it registers as a Sensor Watch fault. The number of hours required to fulfill these 24-hour periods is calculated only when the system is disarmed. Every time the system is armed in the

AWAY Mode, STAY Mode 1, or STAY Mode 2, the Sensor Watch Timer pauses its count. The

Sensor Watch Timer continues its count the next time the system is disarmed.

Example

If the Sensor Watch Time is programmed for 2 days and the premises is armed for 12 hours and disarmed for 12 hours each day, it takes 4 days before a zone can register a Sensor Watch fault.

Zone Options 2

This location has four programming options. You can select any combination of the options by programming a single value. Calculate this value by adding the option bit numbers together.

Description

Isolate in STAY Mode 1

Zone Isolation Allowed

Forced Arming Allowed

Zone Restore Report

Installation Guide 2017.10 | 03 | F.01U.298.026

102 en | Zone Information

13.3.7

Control Panel

5

6

3

4

7

Option

0

1

2

1 – Isolate in STAY Mode 1

If this option is selected, the zone can be automatically isolated when the system is armed in

STAY Mode 1.

If this option is not selected and the system is armed in STAY Mode 1, the zone activates an alarm when activated as it normally would in AWAY Mode.

You can specify a global entry time for all zones, except for 24-Hour Zones, when the system is

armed in STAY Mode 1. You program this time in Locations 472 and 473 (refer to Entry Guard

Time for STAY Mode, page 135). The Entry Guard Timer overrides the delay time programmed

for a Delay Zone. If you program the Entry Guard Timer as 0, each zone acts according to its programmed zone type.

Refer to Arming the System in STAY Mode 1, page 32 for more information.

2 – Zone Isolation Allowed

If this option is selected, the operator can isolate the zone before arming the system. If this option is not selected, the zone cannot be manually isolated. When a zone is manually

isolated, a Zone Bypass Report (Contact ID Event Code 573) is sent. Refer to Isolating zones,

page 35 for more information.

When a zone is automatically isolated in STAY Mode, a Zone Bypass Report is not sent.

When isolating 24-Hour Zones, the system automatically sends a Zone Bypass Report when the zone is selected to be isolated. All non-24-Hour zones send a Bypass Report only when the system is armed.

4 – Forced Arming Allowed

If this option is selected, the system can be armed with the zone unsealed. If this option is not selected, the system does not allow the User Code holder to arm the system until the zone is

sealed or manually isolated. Refer to Isolating zones, page 35 for more information.

8 – Zone Restore Report

If this option is selected, the zone sends Restore Reports when the zone is restored. If this option is not selected, the zone does not send Restore Reports when the zone is restored.

If a non-24-Hour zone is not restored when the system is disarmed, the system automatically sends a Zone Restore Report for that zone. All 24-Hour zones send a Zone Restore Report only when the zone is restored.

Zone Report Options

By default, a zone reports only to Receiver 1. The table below lists the reporting options for the zone.

Description

No reports allowed

Report to Receiver 1

Report to Receiver 2

Report to Receiver 3

Report to Receiver 4

Report to Receiver 1,2,3,4

Report to Receiver 1 (2,3,4 backup)

Report to Receiver 1 (2 backup) and Receiver 3 (4 backup)

2017.10 | 03 | F.01U.298.026

Installation Guide Bosch Security Systems, Inc.

Control Panel Zone Information | en 103

13.3.8

Keyswitch Zone Options

The table below lists the options available to Keyswitch Zones. If you program a zone as a keyswitch input (Zone Type 11), program the selected Keyswitch Zone options in the location normally used for Zone Options 1.

4

5

6

Option

0

1

2

Description

Latching arm and disarm in AWAY Mode

Latching arm in AWAY Mode

Latching disarm from AWAY Mode, STAY Mode1, or STAY Mode 2

Latching arm and disarm in STAY Mode 1

Latching arm in STAY Mode 1

Latching disarm from STAY Mode 1 or STAY Mode 2

8

9

10

Momentary arm and disarm in AWAY Mode

Momentary arm in AWAY Mode

Momentary disarm from AWAY Mode, STAY Mode1, or STAY Mode 2

12

13

Momentary arm and disarm in STAY Mode 1

Momentary arm in STAY Mode 1

14 Momentary disarm from STAY Mode 1 or STAY Mode 2

0 – Latching Arm and Disarm in AWAY Mode

The system is armed or disarmed from AWAY Mode when using the latching keyswitch input.

1 – Latching Arm in AWAY Mode

The system is armed in AWAY Mode when using the latching keyswitch input. Disarming the system is not permitted from the Keyswitch Zone.

2 – Latching Disarm from AWAY Mode, STAY Mode1, or STAY Mode 2

The system is disarmed from AWAY Mode, STAY Mode 1, or STAY Mode 2 when using the latching keyswitch input. Arming the system is not permitted from the Keyswitch Zone.

4 – Latching Arm and Disarm in STAY Mode 1

The system is armed or disarmed in STAY Mode 1 when using the latching keyswitch input.

Arming and disarming the system in AWAY Mode is not permitted from the Keyswitch Zone.

5 – Latching Arm in STAY Mode 1

The system is armed in STAY Mode 1 when using the latching keyswitch input. Arming the system in AWAY Mode or disarming the system is not permitted from the Keyswitch Zone.

6 – Latching Disarm from STAY Mode 1 or STAY Mode 2

The system is disarmed from STAY Mode 1 or STAY Mode 2 when using the latching keyswitch input. Arming the system in STAY Mode 1 or STAY Mode 2, or arming and disarming the system in AWAY Mode is not permitted from the Keyswitch Zone.

8 – Momentary Arm and Disarm in AWAY Mode

The system is armed or disarmed from AWAY Mode when using the momentary keyswitch input.

9 – Momentary Arm in AWAY Mode

The system is armed in AWAY Mode when using the momentary keyswitch input. Disarming the system is not permitted from the Keyswitch Zone.

Bosch Security Systems, Inc.

Installation Guide 2017.10 | 03 | F.01U.298.026

104 en | Zone Information Control Panel

10 – Momentary Disarm from AWAY Mode, STAY Mode 1, or STAY Mode 2

The system is disarmed from either AWAY Mode, STAY Mode 1, or STAY Mode 2 when using the momentary keyswitch input. Arming the system is not permitted from the Keyswitch Zone.

12 – Momentary Arm and Disarm in STAY Mode 1

The system is armed or disarmed in STAY Mode 1 when using the momentary keyswitch input.

Arming and disarming the system in AWAY Mode is not permitted from the Keyswitch Zone.

13 – Momentary Arm in STAY Mode 1

The system is armed in STAY Mode 1 when using the momentary keyswitch input. Arming the system in AWAY Mode or disarming the system is not permitted from the Keyswitch Zone.

14 – Momentary Disarm from STAY Mode 1 or STAY Mode 2

The system is disarmed from STAY Mode 1 or STAY Mode 2 when using the momentary keyswitch input. Arming the system in STAY Mode 1 or STAY Mode 2, or arming and disarming the system from AWAY Mode is not permitted from the Keyswitch Zone.

Wiring Diagram for Keyswitch Zone Wiring Diagram for Keyswitch Zone Using

Split EOL with Tamper

1

2

1 – EOL

2 – Keyswitch (Momentary/Toggle)

Table 13.2: Wiring Diagram for Keyswitch Zone

1

1 – EOL

2 – Keyswitch (Momentary/Toggle)

2

13.3.9

Zone Source

Zone source is a new feature for zone programming. It defines the zone/input is onboard zone, or RF zone, or expanded B228 zone. Defaulted zone source is Onboard.

Zone Source for zone 1 to 16 are stored in Location 0754 to 0769.

For Solution 2000, only Onboard zone is available.

For Solution 3000, select Option 0 or 1 for Zone 1 - 8; select Option 0, or 1, or 2 for Zone 9 -

16.

Option

0

1

2

Description

Onboard

RF

B228

13.4

Swinger Shutdown Count for Siren

Item Location

Swinger Shutdown Count

For Siren

0379

Option

1 – 15 = Number of times siren operates until lockout

Default New

3

2017.10 | 03 | F.01U.298.026

Installation Guide Bosch Security Systems, Inc.

Control Panel Zone Information | en 105

13.5

Location 379 determines the number of times the sirens can be activated before lockout options take effect. This location has no effect unless you program at least one zone for

lockout siren. Refer to Zone Options 1, page 100 for more information.

Only alarms activated from zone inputs can increment the Swinger Shutdown Counter. Alarms such as Codepad Panic, Access Denied, and other system alarms do not affect the Swinger

Shutdown Count.

Lockout Siren is separate for each zone, If a zone's siren is locked out, another zone's siren can still be activated.

Example

Zone1 and 2 are programmed for Lockout Siren with a Swinger Shutdown Count of 2. If Zone

1 activates an alarm, the Swinger Shutdown Count is incremented by one after the end of

Siren Run Time from 0 to a swinger shutdown count of 1.

After the Siren Run Time is reset from the previous alarm, Zone 2 activates an alarm and activates the sirens. After the sirens are reset, the swinger shutdown count for Zone 2 is incremented to 1 and the swinger shutdown count for Zone1 is still 1.

If Zone 1 activates an alarm again after the sirens are reset from Zone 2, the Swinger

Shutdown Count for Zone 1 is incremented to 2, which locks out Zone 1 only from sounding the sirens until the system is reset, armed or disarmed.

At this point, Zone 1’s Swinger Shutdown Count for Sirens is reset to 0.

Swinger Shutdown Count for Report

Item Location Option Default New

Swinger Shutdown Count

For Report

0380 1 – 15 = Number of times report operates until lockout

6

Location 380 determines the number of times the zone alarm report can be activated before lockout options take effect. This location has no effect unless you program at least one zone

for lockout report. Refer to Zone Options 1, page 100 for more information.

Only alarms activated from zone inputs can increment the Swinger Shutdown Counter. Alarms such as Codepad Panic, Code Retries, and other system alarms do not affect the Swinger

Shutdown Count.

Lockout Report is separate for each zone. If a zone's report is locked out, another zone's report can still be activated. Each zone has a standalone Swinger Shutdown Count for Report.

This counter increases by 1 when a zone reports a new alarm or tamper event.

Use Location 492 to set smart lockout. When a zone report is locked out, if smart lockout is enabled, lockout events on this zone are not reported if no alarm is sounding. If an alarm is ongoing, events are reported as configured.

Notice!

If Lockout Report is enabled for any zone, the last restore signal is not transmitted until the system is disarmed.

Example

Zones 1 and 2 are programmed for lockout report with a Swinger Shutdown Count of 6. If

Zone 1 activates an alarm, the Swinger Shutdown Count increments to 1 when the control panel sends the report.

If Zone 1 reactivates the report, the Swinger Shutdown Count is incremented to 2. If Zone 1 reactivates the report three more times, the Swinger Shutdown Count is 5.

Bosch Security Systems, Inc.

Installation Guide 2017.10 | 03 | F.01U.298.026

106 en | Zone Information Control Panel

13.6

Item

STAY Mode 2

Automatically Bypass

Zones

If Zone 2 activates an alarm, the Swinger Shutdown Count for Zone 2 is incremented to 1.

Swinger Shutdown Count for Zone 1 is still 5. If Zone 1 reactivates again, it locks out Zone 1 from activating the report. When smart lockout is enabled, if any zone activates the siren before siren running time is expired, Zone 1 reactivates and can still send a report.

STAY Mode 2 Automatically Bypass Zones

STAY Mode 2 Automatically Bypass Zones can be programmed in Location 381 - 384. It can

also be done by master code function. Refer to Setting STAY Mode 2 Bypass Zones, page 47 for

more information.

Zone 9 – 16 is only for Solution 3000.

Location

0381

Default New

0

0382

0383

0384

Option

1 = Zone 1

2 = Zone 2

1 = Zone 5

2 = Zone 6

1 = Zone 9

2 = Zone 10

1 = Zone 13

2 = Zone 14

4 = Zone 3

8 = Zone 4

4 = Zone 7

8 = Zone 8

4 = Zone 11

8 = Zone 12

4 = Zone 15

8 = Zone 16

0

0

0

13.7

Zone Status Reporting Options

Item Location Option

Zone Status Reporting

Options

0392 0 = No Zone status reports allowed

1 = Report to Receiver 1

2 = Report to Receiver 2

3 = Report to Receiver 3

4 = Report to Receiver 4

5 = Report to Receiver 1,2,3,4

6 = Report to Receiver 1 (2,3,4 backup)

7 = Report to Receiver 1 (2 backup) and

Receiver 3 (4 backup)

This location is set by default to report only to Receiver 1.

Default New

1

2017.10 | 03 | F.01U.298.026

Installation Guide Bosch Security Systems, Inc.

advertisement

Key Features

  • Supports up to 8 zones for comprehensive coverage
  • Stay and Away arming modes for customizable protection
  • Panic, fire, and medical alarms for emergency situations
  • Remote arming and disarming via telephone or A-Link Plus Software
  • Event Memory Recall Mode for easy review of system activity
  • Fault Analysis Mode for quick troubleshooting

Related manuals

Frequently Answers and Questions

How many zones does the Bosch Solution 2000 support?
The Bosch Solution 2000 supports up to 8 zones.
Does the Bosch Solution 2000 have a panic alarm?
Yes, the Bosch Solution 2000 has a panic alarm that can be activated from any keypad.
Can the Bosch Solution 2000 be armed and disarmed remotely?
Yes, the Bosch Solution 2000 can be armed and disarmed remotely via telephone or A-Link Plus Software.
How do I reset the Bosch Solution 2000 to factory default settings?
To reset the Bosch Solution 2000 to factory default settings, enter Installer Code 961.
Download PDF

advertisement

Table of contents