Features. Mitsubishi LDT 323V

Add to My manuals
64 Pages

advertisement

Features. Mitsubishi LDT 323V | Manualzz

Through Flexible and Various Options,

To be Built up the Suitable Functions.

Electronic Trip Relay

Main setting module

1

WS1

WS2

WS3

General use

WM1

WM2

WM3

Generator protection use

WB1

WB2

WB3

Special use

1

2

3

LTD + STD + INST / MCR LTD + STD + INST / MCR INST / MCR only

Note : *For optimum protective coordination with upstream and/or downstream protective devices such as fuses and OCRs, WF relay (WF1/WF2/WF3) are provided.

As for the details about WF relay, please make inquiries.

Optional setting module

2

With optional setting modules, GFR, ER etc are added easily.

G1 E1 AP N5

Ground fault protection (GFR)

Earth leakage (ER)

(1)

2nd Additional Pre-alarm

Neutral pole

(2)

50% protection

Note (1) : combination with ZCT

(2) : With "N5" optional module, Neutral pole protection will be changed from 100% (standard) to 50%.

Power supply

3

It is neccessary for Display and

LEDs. (see page 19, 20.)

P1 100-240V AC•DC

P2 24-60V DC

P3 100-240V AC / 100-125V DC with output contact

P4

P5

24-60V DC with output contact

100-240V DC with output contact (SSR)

Additional function

EX1 Extension module DP1 Display TAL Temperature alarm

The TAL is operated by an unusual temperature of the breaker contacts.

Module for display and communication

Current,Voltage,Power,

Harmonics,Trip current,etc.

Note : The VT unit is required to display the measured data except the load current.

MCR-SW MCR switch

Making current release is possible with MCR switch.

■ Secure protection by actual effective value detection

For spread of electronic devices such as inverter, the actual effective value detection method is adopted, which is strong against deformed waveform and is detected from each phase independently .

Distorted current

Effective value conversion

Sin wave current

With interchangeable & add-on modules, flexible functions built up.

Network

Personal

Computer

MELSECNET/10

Interface card

PLC

By using various application software for PLC, users can also connect to the network

SCADA system.

MELSECNET/10

CC-Link ® / PROFIBUS-DP / MODBUS ®

Interface

Unit

I/O Unit

AE-SW

MDU

Eco Monitor Pro ME110NSR

Note : Some device types are excluded.

Interface unit

CC-Link

®

PROFIBUS-DP MODBUS

®

(RS-485)

BIF-CC BIF-PR BIF-MD

Communication items

Current, Voltage, Power, Harmonics, etc

Measurement / alarm Tripping cause/current

Alarm (PAL,TAL,Self diagnosis)

Breaker ON,OFF

Breaker control

Spring charge

ON/OFF

Breaker status

Drawout position

Note : The VT unit is required to display the measured data except the load current.

I/O unit

BIF-CON

ON, OFF, Spring charge, Digital input

Option to interface unit

I/O unit enables to turn ON/OFF the breaker and the spring charge via network.

And by addition of the drawout position switch, it is possible to transmit the breaker drawout position.

Display unit for Panel board

DP2

It has the same function as the breaker display unit.

In the case where the breaker is installed in the panel, it becomes possible to view the measurement information from the outside of the panel board.

Note : The VT unit is required to display the measured data except the load current.

VT unit

VT

VT unit enables to measure voltages, electric powers, harmonics and etc.

Electronic Trip Relay type code

Main setting module

WS1, WB1, WM1 AE630–1600-SW,

AE2000–3200-SW,

AE4000-SW

WS2, WB2, WM2 AE2000-SWA,

AE4000-SWA,

AE5000-SW

WS3,WB3,WM3 AE6300-SW

Optional setting module

G1: Ground fault protection

N5: Neutral pole 50% protection

E1: Earth leakage protection

AP: 2nd Additional Pre-alarm

NA: Without optional setting

Power supply

P1: AC

DC100-240V

P2: DC24-60V

P5: DC100-240V with output contact (SSR)

WS : General use

WM : Generator protection use

WB : INST/MCR only

P3: AC100-240V / DC100-125V with output contact

P4: DC24-60V with output contact

Additional function

Extension module(EX1)

Display(DP1)

Display onto panel board(DP2)

VT unit(VT)

Network

BIF-CC

BIF-PR

BIF-MD

Temperature alarm(TAL)

MCR switch(MCR-SW)

The safety of valuable circuits can be securely maintained.

Higher short circuit protection performance by improving breaking capacity

In case of 690V AC, Icu = Ics improved from 50 kA to 65 kA for AE630-SW~AE2000-SWA from 50 kA to 75 kA for AE2000-SW~AE4000-SWA from 50 kA to 85 kA for AE4000-SW~AE6300-SW

Wider choice coordination range by improving rated short-time withstand current

Icw (1s) improved from 65 kA to 75 kA for AE2000-SW~AE4000-SWA from 85 kA to 100 kA for AE4000-SW~AE6300-SW

(Former model) (New model)

(AE630-SW~AE2000-SWA)

(Former model) (New model)

(AE2000-SW~AE4000-SWA)

(Former model) (New model)

(AE4000-SW~AE6300-SW)

(Former model) (New model)

(AE2000-SW~AE4000-SWA)

(Former model) (New model)

(AE4000-SW~AE6300-SW)

AE630-SW

AE1000-SW

690V AC

AE1250-SW

AE1600-SW

600V AC

AE2000-SWA

~ 500V AC

AE2000-SW

AE2500-SW

AE3200-SW

AE4000-SWA

690V AC

600V AC

~ 500V AC

65

65

65

75

75

85

690V AC 85

AE4000-SW

AE5000-SW

AE6300-SW

600V AC 85

~ 500V AC 130

0 20 40 60 80 100 120 140

(kA)

Icu=Ics

Higher safety by improving insulation performance

Rated impulse withstand voltage (Uimp) for the main circuit is improved from 8 kV to 12 kV.

AE630-SW

AE1000-SW

AE1250-SW

AE1600-SW

AE2000-SWA

1s

2s

3s

AE2000-SW

AE2500-SW

AE3200-SW

AE4000-SWA

1s

2s

3s

AE4000-SW

AE5000-SW

AE6300-SW

1s

2s

3s

0

(Former model)

20 40

50

60

65

60

65

75

75

100

80

85

85

100

(kA)

Icw

(New model)

Higher reliability by High operating durability

Mechanical

The new models are sharply improved in mechanical durability compared to the former model.

Former model

New model

10000

AE630-SW AE1000-SW

AE1250-SW AE1600-SW

25000

25000

AE2000-SWA

AE2000-SW AE2500-SW

AE3200-SW

AE4000-SWA

AE4000-SW AE5000-SW

AE6300-SW

2000

0

5000

5000

10000

10000

(3-Pole)

10000 15000

20000

20000

20000 25000

(times)

Electrical

The new models (V2

) are sharply improved in electrical durability compared to the former model.

✽ V2:High durability models

Former model

New model (V2)

5000

AE630-SW AE1000-SW

AE1250-SW AE1600-SW

AE2000-SWA

1500 (3200A: 1000)

AE2000-SW AE2500-SW

AE3200-SW

AE4000-SWA

500

5000

6000

0 2000 4000 6000

8000

8000

12000

10000 12000

(times/500V AC)

For convenience

3 sizes

Size1

AE630

-SW

AE1000

-SW

AE1250

-SW

AE1600

-SW

AE2000

-SWA

Size2

AE2000

-SW

AE2500

-SW

AE3200

-SW

AE4000

-SWA

Size3

AE4000

-SW

AE5000

-SW

AE6300

-SW

Compact size AE2000-SWA!

The compact AE2000-SWA can reduce the panel size.

Volume and weight

AE2000-SS

(Former)

AE2000-SWA

(New)

The former model (AE-SS) can be retrofitted.

It is same as the former model (AE-SS) in installation dimension and outline dimension, and the former model can be replaced with the new one.

ACB main body with drawout frame can be replaced.

It can be installed to the existing connection bus bar without any special connection kit.

(Except AE2000-SWA, AE4000-SWA)

Interchangeable

Bus bar

Zero arc space

Arc exhaust to the outside of the breaker is drastically reduced for safer operation.

(AE630-SW~AE4000-SWA models

≤ 600V AC)

(refer to page 54 : Insulation distance)

Former model New model

Reverse connection available

Line and Load is not defined on the Main circuit terminals.

Therefore, reverse connection is available without any limitation.

Fixed type

AE-SW Series

3

9

4

6

8

2

7

AE1600-SW 3P

1

5

1 Arc extinguishing chamber

2 Control circuit terminal block

3 Electronic trip relay

4 OFF button

5 ON button

6 Padlock hook

7 Charging indicator

8 ON/OFF indicator

9 Manual reset button(Optional)

In case of the fixed type,Lifting hooks (HP) are attached.

9

Drawout type

AE-SW Series

3

4

7

8

5

AE1600-SW 3P

2

6

1

1 Cradle

2 Control circuit terminal block

3 Lifting hole

4 Charging handle

5 Drawout position indicator

6 Extension rail

7 Position lock

8 Aperture for the drawout handle

9 Drawout handle

In case of the drawout type, Drawout handle is attached.

Skeleton

10

7

9

8

3 4 5 6

28

31

30

29

1 2

12 11

26 27

13

24 25

14

15

21

22 23

16

18

17

20

19

Product introduction

1 2

Type Standard

AE630-SW

AE1000-SW

AE1250-SW

AE1600-SW

AE2000-SWA

AE2000-SW

AE2500-SW

AE3200-SW

AE4000-SWA

AE4000-SW

AE5000-SW

AE6300-SW

6

Mechanical accessories

Push button cover

Counter

Cylinder lock

Terminal cover

Door frame

Dust cover

Interphase barrier

Mechanical interlock

Door interlock

IEC 60947-2

EN 60947-2(CE)

VDE

JIS C 8201-2-1

GB 14048.2(CCC)

(Shipping Approvals)

LR

GL

BV

DNV

ABS

CCS

NK

7

Electronic trip relay

General use

WS type

Generator protection use

WM type

Special use

WB type

Optional

G1:Ground fault protection

E1:Earth leakage protection

AP:2nd Additional Pre-alarm

N5:Neutral pole 50% protection

3

Connection

Drawout type

Horizontal terminal

Vertical terminal

Front terminal

Fixed type

8

Relay accessories

Extension module

Display

Temperature alarm

MCR switch

Neutral CT

External ZCT

VT unit

1 Air circuit breaker

2 Cradle

3 CC-Link ® Interface unit

4 PROFIBUS-DP Interface unit

5 MODBUS ® Interface unit

6 I/O unit

7 Extension module

8 ETR unit

9 Main setting module

10 Optional setting module

11 Door frame (DF)

12 Dust cover (DUC)

13 Push button cover (BC-L)

14 Auxiliary switch standard (AX)

15 Auxiliary switch high capacity type (HAX)

16 Shunt trip device (SHT)

17 Closing coil (CC)

18 Under voltage trip device (UVT)

19 UVT-controller (U-CON)

20 Condenser trip device (COT)

21 Motor charging device (MD)

22 Counter (CNT)

23 Cylinder lock (CYL)

24 Door interlock (DI)

25 Mechanical interlock (MI)

26 Safety shutters (SST)

27 Safety shutter lock ( SST-LOCK)

28 Cell switch (CL)

29 Interphase Barrier (BA)

30 Horizontal terminal

31 Vertical terminal

4

Drawout type accessories

Cell switch

Shorting b-contact

Lifting hooks

Safety shutter

Safety shutter lock

Mis-insertion preventor

Test jumper

9

Network

CC-Link ® Interface unit

PROFIBUS-DP Interface unit

MODBUS ® Interface unit

I/O unit

5

Electrical accessories

Auxiliary switch

Motor charging device

Closing coil

Shunt trip device

Under voltage trip device

Condenser trip device

advertisement