Wireing diagram. Mitsubishi LDT 323V

Add to My manuals
64 Pages

advertisement

Wireing diagram. Mitsubishi LDT 323V | Manualzz

● The following diagram shown accessories fully equiped.

L1 L2 L3 N

Extension terminals

Power supply

Less than 2m

RS1 RS2 513 P1 P2 97 C1 A1

See Fig.1.

D2 D1 413 U1

Electronic trip relay(ETR)

Reset circuit Power circuit

Alarm contacts

SHT CC

UVT M

Main circuit

N1 N2 Z1 Z2

NCT * ZCT *

* Voltage forbid to be applied

FG

Dielectric test forbidden

P4 574 564 554 544 534 524 98 C2 A2 DT2

Short bar

DT1 414 U2

Open to trip

(less than 2m)

Electronic trip relay Control power circuit / alarm contact

OCR alarm

Electrical operation circuit

Terminal description

13

11

14

12

U1 U2

413 414

~

~

53

51

54

52

Auxiliary switch "a"

Auxiliary switch "b"

Motor charging

Charged signal

D1

DT1 DT2

A1

D2

A2

Voltage Input terminal of UVT

Trip terminal of UVT (Remote trip)

Closing coil

Shunt trip C1 C2

97

P1

P4

98

P2

OCR alarm

Power supply for ETR

FG of power supply (FG:Frame Ground)

Alarm reset (Trip cause LED, alarm contact) RS1 RS2

513

Z1

, 524 ~ 574

Z2

Alarm contacts

For external ZCT

For Neutral CT

(Note) N1 N2

Extension terminals

For external display DP2

For Interface unit

For VT unit

Note; Do not connect the NCT type CW-40LM (for AE-SS series).

CC

M

UVT

AX

AL

CLS

SBC

CL

Accessory Symbols

SHT Shunt tripping device

Closing coil

Motor(Motor charging device)

UVT coil

Auxiliary switch

OCR alarm switch

Charge limit switch

Shorting b-contact

Cell switch

Internal wiring

External wiring (user's wiring)

Control circuit connecter (drawout type)

51 41 31 21 11 53 43 33 23 13

Breaker

341 331 321 311

52 42 32 22 12 54 44 34 24 14

Breaker

344 342 334 332 324 322 314 312

Cell switch

Auxiliary switch(normal close) Auxiliary switch(normal open)

Fig.1

UVT controller wiring

100-120V AC type

200-240V AC type

DC types

380-460V AC type input input

D2 D1

+

IN2 IN1 external unit

OUT4 OUT3

D2 D1

Cell switch

Note;

● On the drawout type, the cables should have the length which allow the control circuit terminal block to be moved to the left or right by 5mm.

When a coil load is connected in the same control circuit as the ETR, surge absorbers are required to absorb the surge voltage.

● OCR alarm (AL)

The contact output of the OCR alarm(Standard type AL) is the one-pulse output and the output time is 30~50ms.

For this reason, this output needs self-holding circuit.

Closing coil (CC)

As CC is one-pulse driven, it is not necessary to insert AXb for burning prevention purposes.

Inserting AXb will cause anti-pumping function to be ineffective.

Under voltage trip device (UVT)

Use the switch that can open and close DC150V, 0.5A to remote trip.

Remote trip terminal has short bar at shipment, so remove it before using this function.

Disconnect the voltage input wires during dielectric testing of main circuit.

● voltage. (longer than 1sec.)