5Information for the specialist - Configuration . Regin VCA283DW-4, VCA283W-4, VCV203DWM-2, VCA152DW-4, VCA152W-4
Werbung
Werbung
Information for the specialist - Configuration
5 Information for the specialist - Configuration
5.1 Configuration of the Corrigo
The configuration of the Corrigo is made in Application tool, a free PC-based software available on www.regincontrols.com
The controller doesn't need to be connected to the computer while configuring. All settings are made in the tool and then uploaded to the controller.
An infinite number of configurations can be stored in the computer memory for later use.
A communication cable is required in order to upload the configuration to the controller. The controller must also be powered up and the application selected in order for it to be configured.
5.1.1
Predefined configurations for Corrigo
There are predefined configurations available for easy configuration. They can be selected in the internal text display, in the web interface or can be downloaded as atf-files on Regin's webpage. The atf-files can be used in Application tool for further offline modification and adaption.
The predefined configurations are a part of Regin's Ready-Steady-Go concept which makes it much easier and faster to configure the controller.
Predefined configurations in internal text display
Use the internal text display in the Corrigo to select a predefined configuration.
1. Start from the start menu.
Vent controller 5.0
2020-01-08 14:29
System: Normal run
Sp:22.0 Act: 22.5°C
2. Press the right button [ ► ] 7 times until you reach the menu to select the configuration.
Choose Config File
None
3. Select the configuration you want. Available configurations depend on the number of IOs in the hardware.
94 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
4. Select add-ons. Available add-ons depends on the used hardware and selected configuration.
CO2 fan add-on
No
CO2 damper add-on
No
Extended run add-on
No
Fire alarm add-on
No
Free cooling add-on
No
5. Activate the configuration
Load configuration
No
Predefined configurations in web interface
Figure 5-1 Predefined configuration in web interface
Predefined configurations as atf-files
Predefined configurations can be downloaded as atf-files from Regin’s website ( www.regincontrols.com
).
The atf-files can be opened in Application tool and synchronized to the controller.
5.1.2
Application tool
Application tool is used both to configure, monitor and make changes in the application. The start screen gives an overview about what functions are available. For a description of the functions, see table
below.
For configuration and ventilation settings see
chapter 5.5 Configuration - Functions
and
Corrigo manual, Rev. D 95 (196)
Information for the specialist - Configuration
Figure 5-2 Application tool start screen
Table 5-1 Application tool: Menu items
Overview
Ventilation
Additional function
Inputs/Outputs
Configuration
Time control
Alarm status
An overview of the functions and values in the application
Configure setpoints, temperatures etc. Monitoring of ventilation unit.
Configuration of an extra controller.
Read values from all inputs and outputs.
Configuration of the BAS (Building Automation System). Switch on and off functions, define sequences etc.
Configure when the system should be working. Also possible in the display and in the web interface.
Check and acknowledge the alarms in the application.
96 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
5.2 Work flow for configuration and commissioning the Corrigo
1. Start by configuring the controller in Application tool or in the web interface. Both user-interfaces can be used to configure the controller in the same way. All following information is based on Application tool, but also applies to the web interface. Go through all the steps under the Configuration menu, see table
below.
function/application you choose to set up. Therefore, not all menu items are available for all applications.
Table 5-2 Configuration menu in Application tool
Configuration menu item
System
Device list
Functions
Analog inputs
Digital inputs
Analog outputs
Digital outputs
Raw values
Description
General settings, Communication settings, Unit settings, Save and restore settings
Activation of the different devices in the BAS (Building Automation System)
Activation of functions in the BAS. Configuration of sequences A to J
Configuration of Analog inputs
Configuration of Digital inputs
Configuration of Analog outputs
Configuration of Digital outputs
Read raw values from the controller and expansion units
2. Go to Ventilation menu in Application tool after the configuration is done. In the Ventilation menu you will set values and parameters for the application, see table below.
Table 5-3 Ventilation menu in Application tool
Ventilation menu item
Actual/Setpoint
Temperature control
Fan control
Demand control
Fire/Smoke
Humidity control
PID controllers
Energy consumption
Manual/Auto
Status
Description
Read the actual values and setpoints from the controller. Change setpoints.
Setting of parameters and values for Sequence A to J, Step controllers, Freeze protection, Exchanger, Pretreatment and Summer mode
Setting of values for fans and compensation curves
Setting of values for CO
2
, Recirculation, Free cooling and Support control
Setting of values for Fire and Smoke dampers and alarms
Setting of values for humidity control
Setting of P, I and D- values for Room, Extract air, Sequence A to J, Supply air fan,
Extract air fan, CO
2
, Freeze protection, Defrosting and Humidity
Read information about SFP, power usage for fans and accumulated power usage for today, last 7 days, current and previous year.
Setting of Manual or Auto control of units, functions and sequences.
Read status for the Ventilation unit and Sequences A to J
3. Load the application into the controller and commission. The application can be loaded from the web interfaceor Application tool.
In Application tool, go to the Tools menu at the top and select Load program .
Corrigo manual, Rev. D 97 (196)
Information for the specialist - Configuration
5.3 Configuration - System
Start with configuration of the system which contains the configuration of:
✓ General settings
✓ Communication settings
✓ Serial Ports
✓ BACnet
✓ TCP/IP
✓ Display port
✓ Unit settings
✓ CLOUDigo
✓ Save and restore
Figure 5-3 System configuration in Application tool
5.3.1
General settings
Under General is information about the controller, and some general settings can be made.
Change language
The display language can be changed either by the front display, in the web interface or in Application tool.
Front display menu:
Choose language
English
Web interface: pressing the [[ ► ]] button four times when the start display is shown.
98 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Account settings ► Language
Application tool:
Configuration ► System ► General ► Language
Start screen
There are several different start screens to choose from. The start screen can be changed in Application tool at: Configuration ► System ► General
Type 1, Show headline, date/time, vent. mode, supply temp / setp.
Vent controller 5.0
2019-08-01 11:28
System: Normal speed
Sp: 32.8°C Act:33.1°C
Second line: Date and time
Third line: Status of the unit
Fourth line: Supply temperature and setpoint
Type 2, Show headline, vent. mode, supply temp / setp, sequence A to C
Vent controller 5.0
System: Normal speed
Sp: 32.8°C Act:33.1°C
A 100 B 100 C 100
Second line: Status of the unit
Third line: Supply temperature and setpoint
Fourth line: Output signal of the sequences A to C
Type 3, Show headline, vent. mode, supply temp / setp, SAF / EAF pressure
Vent controller 5.0
System: Normal speed
Sp: 32.8°C Act:33.1°C
SAF: 2000 EAF: 2000
Second line: Status of the unit
Third line: Supply temperature and setpoint
Fourth line: SAF- and EAF- pressure
Type 4, Show headline, date/time, vent. mode
Vent controller 5.0
2019-08-01 11:28
System: Normal speed
Second line: Date and time
Third line: Status of the unit
Corrigo manual, Rev. D 99 (196)
Information for the specialist - Configuration
Type 5, Show headline, date/time
Vent controller 5.0
2019-08-01 11:28
Second line: Date and time
Automatic switch between summer and winter time adjustment
The internal clock is normally configured for automatic summer / winter time adjustment. When enabled, the clock will be set forward one hour at 02:00 am on the last Sunday of March and adjusted back one hour at 03:00 am on the last Sunday of October.
The function can be disabled in Application tool: Configuration ► System ► General
Automatic logoff
If the access level is set to Operator or Admin , the user will automatically be logged off after a set time of inactivity. The time is settable in units of 5 seconds in Application tool. The default is 60 units = 5 minutes
The automatic log off can be disabled in Application tool: Configuration ► System ► General ► Time before automatic logoff in display (unit 5s) (min)
5.3.2
Port 1 and Port 2
The controller can have one or two serial ports. In a controller with two serial ports, both ports have the same functions. However, they can not both be configured to have the same function at the same time, except that both can be slaves.
Table 5-4 Available settings for Port configuration
Types of communication
✓ EXOline slave (Default)
✓ EXOline master
✓ Modbus slave
✓ Modbus master
✓ BACnet MSTP slave
✓ EFX master
Available formats
✓ 8N1 – 8 bit, no parity, 1 stop bit
✓ 8E1 – 8 bit, even parity, 1 stop bit
✓ 8O1 – 8 bit, odd parity, 1 stop bit
(Default)
✓ 8N2 – 8 bit, no parity, 2 stop bit
✓ 8E2 – 8 bit, even parity, 2 stop bit
✓ 8O2 – 8 bit, odd parity, 2 stop bit
Available Baud rates
✓ 9600 (Default)
✓ 14400
✓ 19200
✓ 28800
✓ 38400
✓ 57600
✓ 76800
✓ 115200
The default settings of the ports is EXOline slave:
Function port1
EXOline slave
Format 8O1
Baud 9k6
Table 5-5 Port 1 and 2: Function default values
Function
EXOline slave
EXOline master
Modbus slave
Connection to
Application tool or SCADA system
Pressure transmitters, Expansion units or Room units
SCADA system via Modbus or master controller
Format
8O1
8O1
8N1
Baud
9600
9600
9600
100 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Table 5-5 Port 1 and 2: Function default values (continued)
Function
Modbus master
BACnet MS/TP slave
Connection to
Fans, Rotary exchanger, Pressure transmitters, Damper actuators and Wireless receivers
BACnet SCADA or BACnet master controller
Format
8N1
8O1
Baud
9600
9600
5.3.3
Modbus slave
Set the Modbus address for the Modbus slave.
5.3.4
BACnet
The controller is capable of communication via the BACnet -protocol, using either IP or MS/TP data link formats.
In order to connect a controller to a BAS (Building Automation System) via BACnet/IP, a controller with a
TCP/IP port is required. To connect to a BAS via BACnet MS/TP, a controller with an RS485 communication port is required.
function/application you choose to set up. Therefore, not all menu items are available for all applications.
Figure 5-4 All BACnet settings
Table 5-6 BACnet settings
Variable
BACnet/IP
BACnet device name
BACnet device ID
BACnet/IP UDP port number
Function
On/Off
Description
The BACnet/IP protocol is disabled as default. Choose On to enable the protocol.
Name of the controller Editable
The ID of a device, used to identify it on the
BACnet network
The ID number must be unique, and can not be duplicated anywhere on the BACnet network. Editable.
47808
Corrigo manual, Rev. D 101 (196)
Information for the specialist - Configuration
Table 5-6 BACnet settings (continued)
Variable
BBMD address
BACnet MS/TP highest master address
BACnet MS/TP MAC
Function Description
The address is entered as host:port , where host can be the host’s name if DNS is configured. If DNS is not configured, the host address should be entered in the format xxx.xxx.xxx.xxx
, followed by the port number (default setting 47808).
Example: mybbmd: 47808 (with DNS configured) or 10.100.50.99:47808
The BBMD address (BACnet/IP Broadcast
Management Device) is used for discovering devices that are attached to different
BACnet/IP subnets and separated by an
IP-router. Editable.
127
0
The max master address is the MAC address of the highest master device on the BACnet MS/TP network segment.
Setting this number above the highest
MAC address will decrease network performance. Editable.
The MAC address of the device. This needs to be unique only to the subnet to which the device is attached. Editable.
5.3.5
CLOUDigo
The Corrigo can be connected to Regin's cloud server CLOUDigo for access to the controller from any computer.
Set Active to On to be able to connect to CLOUDigo.
Read more about CLOUDigo at Regin's webpage, www.regincontrols.com.
5.3.6
Display port
Two different external displays can be used with the Corrigo.
controller from power and connect it again.
Display
E3-DSP
ED-T43L-V
Description
External text display with menu buttons.
External touch display. 4.3 inch.
Both displays can be found on www.regincontrols.com
5.3.7
Unit settings
Choose units for the system.
Function
Temperature
Flow
Pressure
Unit
°C or °F m 3 /h, CFM, m 3 /s or l/s
Pa or in.wg
102 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
5.3.8
Save and restore
It is possible to save all settings in a separate memory area of the controller and restore it afterwards. Two different settings can be stored; local settings and factory settings. The saved settings are available after a reset of the application, see
chapter 6.3 Loading the application .
Varible
Save settings local
Restore settings to local
Save factory settings
Total restore to factory settings
Function
Yes/No
Yes/No
Yes/No
Yes/No
5.3.9
Controller address (PLA : ELA)
Description
Saving of the current configuration as local
“user” settings
Restore the saved settings.
Saving the current configuration as factory settings
Go back to the factory settings the controller was delivered with.
Figure 5-5 Changing the controller address and IP settings
The controller uses PLA:ELA addresses when connecting to Application tool and when multiple controllers are connected in a network. Application tool normally uses the addresses PLA = 254 and ELA = 254, so if an address is changed, the new address must also be entered in Application tool. If several controllers are connected in a network, all the units must have the same PLA address, but each unit must have a unique
ELA address.
The address can be changed in the Application tool in the menu Tools ► Change controller address, see
Figure 5-5 Changing the controller address and IP settings
above.
Corrigo manual, Rev. D 103 (196)
Information for the specialist - Configuration
5.3.10 IP-configuration
IP configuration can be made both in Application tool or in the built-in display.
The Dynamic Host Configuration Protocol (DHCP) is a network protocol used on Internet Protocol (IP) networks for dynamic distribution of network configuration parameters, such as IP addresses, DNS servers and other services.
The controller can be configured to either obtain an IP address from a DHCP server (dynamic) or the address can be set manually (static).
Three additional functions can be activated on the network interface:
✓ BACnet IP communication
✓ Connection to the Cloud-server
✓ Modbus TCP
If you wish to set a static IP address for the controller, enter the IP address you wish to use along with the subnet mask, gateway address and DNS server address. In Application tool you go to the Tools menu and choose Change IP settings, see figure
Figure 5-5 Changing the controller address and IP settings
above.
In the display you do as follows below:
TCP/IP
DHCP: Yes
Set static IP
Running IP
-
IP
192.168.001.234
Subnet mask
255.255.255.000
Running subnet mask
-
Running gateway
-
Running DNS1
192.168.001.001
Running DNS2
192.168.001.001
5.4 Configuration - Device list
Different kind of devices can be connected to the Corrigo, i.e. transmitters, fans/frequency converters and expansion units.
It is possible to change the name of the Device in the Name field
104 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Figure 5-6 Device list
5.4.1
Fan (Modbus)
The Corrigo only supports frequency controlled fans with Modbus communication. The fan can be set to three different speeds: Low, Normal and High .
Table 5-7 Fan models and configuration
Model
✓ Vacon
✓ Lenze
✓ Yaskawa/Omron
✓ Emerson
✓ LS iG5A
✓ LS iS7
✓ EBM - PAPST
✓ DANFOSS FC101
✓ ABB ACSxxx
✓ Ziehl blue
Function
✓ Disabled
✓ Supply air fan
✓ Extract air fan
Name
Optional: name the fan
5.4.2
Rotary exchanger (Modbus)
A rotary heat exchanger can be connected to the controller. Three different models can be used.
Table 5-8 Rotary exchanger models and configuration
Model
✓ RHC 200 (Reflex- Winkelmann)
✓ VariMax25M (IBC control)
✓ OJ DHRX
Function
Sequence A to J
Name
Optional: Name the rotary exchanger
Corrigo manual, Rev. D 105 (196)
Information for the specialist - Configuration
5.4.3
Pressure transmitter (Modbus / EXOline)
Regin's differential pressure transmitter Presigo can be connected to the controller. Two generations of
Presigo are available (PDT... and PTDX) and they are available with one or two pressure sensors. Presigo can be configured as expansion unit (1…10) (under Configuration ► Device list ► Device x ► Function) and will expand the number of available I/O:s.
Presigo model
PDT...C
PDT...C-2
PDT...C
PDT...C-2
PDTX...
PDTX...-2
Generation
1
1
2
1
1
2
Pressure sensors
1
2
1
1
2
2
Communication
Modbus
Modbus
EXOline
EXOline
Modbus
Modbus
Expansion with I/O:s
2 x UI
2 x UI
2 x UI
2 x UI
2 x UI, 2 x UO
2 x UI, 2 x UO
5.4.4
Damper actuator
The controller supports two different kinds of damper actuators
Table 5-9 Damper models and configuration
Model
✓ Belimo Brand
✓ Siemens
Function
✓ Sequence A to Sequence J
✓ Recirculation air damper
✓ Outdoor air damper
✓ Exhaust air damper
✓ Fire damper
Name
Optional: Name the damper actuator
5.4.5
Expansion unit (EXOline)
In order to connect additional inputs and outputs to the controller, a communication device needs to be configured. It is possible to connect two expansion units, giving a maximum number of 28*3 = 84 inputs/ outputs. I/O-expansion units or controllers configured as expansion units can be connected.
Expansion unit
IO-A15MIXW-3-BEM
IO-A28MIXW-3-BEM
IO-V19MIXW-1-BEM
Number of I/O:s
15 I/O:s
28 I/O:s
19 I/O:s
5.4.6
Wireless receiver (Modbus)
To be able to use wireless transmitters and sensors in the installation, a wireless receiver must be connected to the Corrigo. There are two receivers available, with different numbers of sensors that can be connected.
Wireless Receiver
RCW-M
RCW-M32
Number of sensors
16
32
No further settings are necessary to communicate with the wireless receiver.
106 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
5.4.7
Room unit (EXOline/Modbus)
The temperature, fan speed and CO
2
-level in a room can be controlled via a room unit connected to the
Corrigo. There are nine different room units to choose from with different features (see table below).
The room units communicate via EXOline and are connected to the serial ports or display port.
In Application tool, they are configured as expansion units 1…10.
Article
ED-RU
ED-RU-O
ED-RU-F
ED-RU-FO
ED-RU-DO
-
ED-RU-DFO ✓
Occupancy button
-
ED-RU-DOS ✓
ED-RU-H -
ED-RU-
DOCS
ED-RUD-2
-
-
-
-
-
3-step fan control
-
-
-
-
-
-
-
-
Built-in CO
2 sensor
-
-
-
-
-
-
Setpoint knob
-
-
-
-
-
-
-
-
-
Multi-function button
Hidden setpoint
-
-
-
-
-
-
-
-
-
Display
-
-
-
-
-
EXOline (E)/
Modbus (M)
E
E
E
E
E
E
E
E
E
M
5.5 Configuration - Functions
This is where you activate the functions that will be used in the BAS (Building Automation System). It is also where you set up sequence A to J. All functions are more thoroughly described in chapter
4 Information for the specialist - Function descriptions
.
tion you choose to set up. Therefore, not all menu items are available for all applications.
5.5.1
Function activation
In this section you choose control types and turn on or off functions in the BAS (Building Automation
System).
Corrigo manual, Rev. D 107 (196)
Information for the specialist - Configuration
Temperature control type
Figure 5-7 Temperature control type
Table 5-10 Temperature control types
Application
Supply air
Supply air outdoor compensated
Room cascade
Extract air cascade
Room (summer) else supply air
Description More information
The supply air controller output is either a heating demand or a cooling demand depending on if the supply temperature is over or under the setpoint. This demand is then divided into up to 10 sequences, A to
J. Each sequence can be configured as heat, cool, exchanger, damper, compensation or not used and each sequence has it own PID-settings.
Function description:
Sequences:
chapter 4.3 Temperature sequences
Function description:
chapter Supply air outdoor compensated
Sequences:
chapter 4.3 Temperature sequences
The supply air temperature setpoint is temperature compensated using a control curve. The temperature for compensation is configurable between all temperature sensors.
The supply air temperature is kept at the setpoint value by controlling the output signals for sequence A to J.
Cascade control of room temperature and supply air temperature to achieve a constant, settable room temperature.
The room temperature is kept at the setpoint value by controlling the output signals for sequence A to J.
Function description:
Sequences:
Cascade control of extract air temperature and supply air temperature to achieve a constant, settable room temperature.
The extract air temperature is kept at the setpoint value by controlling the output signals for sequence A to J.
Function description:
Sequences:
chapter 4.3 Temperature sequences
Summer mode dependent switching between supply air temperature control and room temperature control.
When the summer mode function is off, temperature compensated supply air temperature control will be active, otherwise (in summer) cascaded room temperature control. Summer mode function is used for switching control mode.
Function description:
(summer) else supply air outdoor compensated
108 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Table 5-10 Temperature control types (continued)
Application
Extract air (summer) else supply air
Room outdoor compensated
Extract air outdoor compensated
Extract air dependent supply air
Description More information
Summer mode dependent switching between supply air temperature control and extract air temperature control
When the summer mode function is off, temperature compensated supply air temperature control will be active, otherwise (in summer) cascaded extract temperature control. Summer mode function is used for switching control mode.
Function description:
(summer) else supply air outdoor compensated
The extract air temperature can be compensated when the outdoor temperature increases.
A difference between extract air temperature and supply air temperature can be configured to maintain that the supply air temperature setpoint follows the extract air temperature.
Function description:
chapter Room outdoor compensated
Function description:
chapter Extract air outdoor compensated
A difference between extract air temperature and supply air temperature can be configured to maintain the supply air temperature setpoint to follow extract air temperature.
Function description:
chapter Extract air dependent supply air
Read more about the temperature control functions in
Fan control type
Table 5-11 Fan control types
Application
Pressure
Flow
Manual
External
Supply air pressure and extract air fan slave
Description
Control of the fan speed using pressure transmitters.
Instead of giving a pressure setpoint value, it is possible to use an airflow volume value in m 3 /h.
The value from the pressure transmitter is recalculated to a volume flow and the fans will be controlled to give a constant flow.
Use the manual setting if you want to manually set the speed of the fan
More information
Function description:
Function description:
Function description:
Use the external setting if you have an external device that controls the fan speed, e.g. a 0…10 V device.
Function description:
The speed of the supply air fan is controlled by a pressure transmitter which is placed in the supply air duct. The extract air fan does not have a pressure transmitter, instead you let the output for the extract air fan follow the control signal for the supply air fan. A scaling factor can be added if the characteristics of the extract air fan are not the same as the characteristics of the supply air fan.
(Only pressure control of the supply air fan is possible using this function.)
Function description:
chapter Supply air pressure and extract air fan slave
Corrigo manual, Rev. D 109 (196)
Information for the specialist - Configuration
Table 5-11 Fan control types (continued)
Application
Supply air pressure with extract air flow slave
Extract air pressure with supply air fan slave
Description More information
The speed of the supply air fan is controlled by a pressure transmitter which is placed in the supply air duct. The extract air fan is controlled by the supply air flow, in order to achieve a balanced ventilation. A pressure transmitter which is placed in the supply air fan cone (SAF flow) gives a measured value of the present supply air flow. A corresponding pressure transmitter is placed in the extract air fan cone and gives a measured value of the extract air flow.
The supply air flow is the setpoint used for control of the extract air fan. A scaling factor can be added if the extract air fan does not have the same characteristics as the supply air fan.
Function description:
chapter Supply air pressure with extract air flow slave
The speed of the extract air fan is controlled by a pressure transmitter which is placed in the extract air duct. The supply air fan has no pressure transmitter. Instead, the supply air fan output is made to follow the extract air fan control signal. A scaling factor can be added if the supply air fan characteristics are not the same as the characteristics of the extract air fan (only pressure control of the extract air fan is possible using this function).
Function description:
chapter Extract air pressure with supply air fan slave
Extract air fan pressure with supply air flow slave
The speed of the extract air fan is controlled by a pressure transmitter which is placed in the extract air duct. The supply air fan is controlled by the extract air duct flow in order to achieve a balanced ventilation. A pressure transmitter placed in the extract air fan cone (EAF flow) provides a measurement of the current extract air flow. A corresponding pressure transmitter is placed in the supply air fan cone, providing a measurement of the supply air flow.
The supply air fan is controlled using the extract air flow as a setpoint. A scaling factor can be added if the supply air fan does not have the same characteristics as the extract air fan.
Function description:
chapter Extract air fan pressure with supply air flow slave
Read more about fan control types in
Fan levels
A frequency controlled fan is the only type of fan that works with the Corrigo. The fan can be set to Low,
Normal or High speed. The selection of the fan speed defines which IOs and time channels will be active in the application.
The fans will always start directly with the desired speed.
There are four different fan speed levels to choose from in Application tool:
✓ Normal
✓ Low - Normal
✓ Normal - High
✓ Low - Normal- High
Variable speed control uses an analogue output per fan or Modbus communication for controlling a frequency converter.
For more information about frequency converters, see
Appendix F Frequency converters and EC controllers for heat exchangers
110 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
The fans are normally controlled by the timer channels for slow, normal and high speed but can also be started via digital input or communication.
The extract air fan and the supply air fan have individual start and stop delays which are normally set so that the extract air fan is started before the supply air fan. If there are not enough digital outputs for individual control, both fans will have to be started using the signal for the supply air fan, and the delay will be created using an external time relay.
Fan compensation
When running pressure/flow control or manual frequency control, it is also possible to for the pressure/flow or output to be temperature compensated.
This compensation can be made depending on any analogue input such as supply air, extract air, room, outdoor temperature, humidity, CO
2 and so on. There are three equal compensation functions available.
It is possible to compensate either one or both of the fans at the same time and it is possible to set which fan should then be compensated, the supply fan or the extract air fan.
Read more about fan compensation in
Support control
Support control is normally used when room temperature control or extract air control has been configured.
When extract air control is configured a room sensor must be installed.
Support control can also be configured to start only with the supply air fan. In this mode, the extract air fan is not active. This requires a digital output to be configured, which controls the recirculation damper to open completely so the supply air fan can circulate the air to and from the room.
Read more about support control in
CO
2
control
In applications with varying occupancy the fan speeds or mixing dampers can be controlled by the air quality as measured by a CO
2 sensor.
With the CO
2 function it’s possible to start and stop the fans, compensate the fan speed and in combination with mixing damper let in more outdoor air depending on the CO
2 value. This can be configured with the
CO
2 control settings, see
Read more about the CO
2
function in 4.4.3 Demand controlled ventilation
.
Table 5-12 CO
2 control settings
Fan stop/start function
Mixing damper function
Fan start/stop + mixing damper
When the function is activated with start/stop function and the CO
2 value rises above settable start value the fans will start at configured speed (default: normal speed), if they are not already running.
If demand controlled ventilation is activated in combination with mixing dampers, and the
CO
2
-value rises above the setpoint value the dampers controlled by a sequence with CO
2 function will be overtaken by the CO
2 controller and let in more outdoor air. The function is controlled by a PI-controller.
If demand controlled ventilation is activated in combination with mixing dampers, and the
CO
2
-value rises above the setpoint value the dampers controlled by a sequence with CO
2 function will be overtaken by the CO
2 controlled by a PI-controller.
controller and let in more outdoor air. The function is
Inputs and outputs
AI CO
2
-sensors
Corrigo manual, Rev. D 111 (196)
Information for the specialist - Configuration
Free cooling
This function is used during the summer to cool the building night-time using cool outdoor air, thereby reducing the need for cooling during the day and saving energy.
Free cooling requires an outdoor sensor or an intake temperature sensor and either a room sensor or an extract air sensor. If both an outdoor sensor and an intake sensor is configured it uses the outdoor sensor for the function.
Free cooling is only activated when all the start conditions below are fulfilled.
✓ Less than four days have passed since the unit was last in running mode.
✓ The outdoor temperature during the previous running period exceeded a set limit (22°C).
✓ It is between 00:00 and 07:00:00 in the day (settable).
✓ The timer outputs for Normal speed, Extended running, Normal and External switch are Off .
✓ A timer channel will be On sometime during the next 24 hours.
If an intake sensor is used and/or an extract air sensor is selected and ALL the start conditions are fulfilled, free cooling is activated and will run for 3 minutes (settable) to ensure that the temperature measurement when using an extract air sensor reflects the corresponding room temperature and that the intake temperature sensor senses the outdoor temperature even if it is placed in the fresh air inlet duct. If an outdoor sensor and a room sensor is selected, the unit will not start free cooling as long as all the temperatures are not within the start and stop temperature intervals.
Read more about free cooling in
Inputs and outputs
AI
AI
DO
Outdoor temperature sensor or Intake temperature
Room sensor or Extract air sensor
Free cooling operation
Recirculation
Recirculation is a function for distributing the air in the room using the supply air fan. The function can be used even when there is no heating or cooling demand. When using recirculation control, the extract air fan stops (but can also be set to run) and a recirculation damper opens which allows the air to circulate through the unit.
Recirculation is activated either via a digital input signal or by connecting it to Extra time channel 4 (
Application tool - Time control). If timer output for Low/Normal/High speed is activated during recirculation via Extra time channel 4 , Low/Normal/High speed gets priority. If timer output for Low/Normal/
High speed is activated during recirculation activated by a digital input, recirculation gets priority.
Either a digital output (Recirculation damper) or an analogue output sequence (A toJ) can be used as an on/ off output signal.
Recirculation control can be configured as either air circulation (temperature control inactive) or air circulation with temperature control. (Only heating, only cooling or both heating and cooling). Recirculation control has its own setpoint. However, the other settings are the same as for normal operation, i. e. if normal operation has been configured as room control, room control will also be used during recirculation.
Read more about Recirculation in
Pretreatment
Control of dampers and pump for preheated or pre-cooled outdoor air via an underground intake channel.
112 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
The digital output Pretreatment is set to preheating when the unit is started and the outdoor temperature is below the set heating start limit or to precooling when the outdoor temperature is above the set cooling start limit. If the outdoor temperature exceeds the set heating start limit by more than 1°C, preheating will be aborted, as well as if the outdoor temperature falls below the cooling start limit by 1°C.
Read more about pretreatment in
Extra controller
An extra controller can be used as an independent temperature control circuit for control of for example separate zones. The circuit can be configured to heating or cooling. It has an analog input signal for temperature sensors and an analogue output signal (0…10 V). There is also a digital output signal which is activated when the analogue output signal is above 1 V and deactivated when the analogue signal is below
0.1 V. The circuit can be configured to be active all the time or to be active only when the unit is running or when defrosting.
Read more about the extra controller in
Fire / Smoke
Fire dampers are normally configured to open on fire alarm but can be configured to be normally open instead. It is possible to configure which speed the fans should have when in fire mode – however, this is not possible when the fire function has been set to Running via normal start/stop conditions . Setting the fan speed to -1 % will deactivate the fan speed selection. Read more about the fire/smoke function in
Inputs and outputs
DO
DO
DO
DI
DI
Outdoor air damper
Exhaust air damper
Fire damper
Fire alarm
Fire damper end switch monitoring
Humidity control
Humidity control can be configured as Humidification, Dehumidification or both Humidification and
Dehumidification.
Two humidity sensors can be connected, a room sensor for control and an optional duct sensor for maximum limiting. The limit sensor can be omitted.
The humidity control is handled by a PI-controller.
The humidity sensors must give 0…10 V DC for 0…100 % RH.
Read more about Humidity control in
Humidification
Dehumidification
An analogue output is used to control a humidifier. The output will increase on decreasing humidity. A digital output can also be used to start a humidifier.
An analogue output ( Humidity ) is used to control a dehumidifier. The output will increase on increasing humidity. A digital output can also be used to start a dehumidifier.
Humidification + Dehumidification An analogue output ( Humidity ) is used to control a humidifier. The output will increase on decreasing humidity.
For dehumidification it’s configurable which sequence that should be activated for dehumidification through condensation. The output will increase on increasing humidity. This signal overrides the cooling signal from the temperature controller so the output can be activated for dehumidification even if the temperature controller demand is zero.
Corrigo manual, Rev. D 113 (196)
Information for the specialist - Configuration
Filter monitoring
Turn on filter monitoring to monitor the flow through the filter. Analog filter guards may be made air flow dependent. This means that a higher pressure drop is permitted across a filter at a higher air flow. For this purpose, X and Y coordinates are used to set the linear function that should be followed at a pressure drop alarm.
Read more about filter monitoring in
Extended operation
The digital inputs for extended running can be used to force the unit to start in reduced, normal or high speed although the timer says the running mode should be Off . This digital input has always higher priority than running via time schedule.
The unit will run for the set time. If the running time is set to 0 the unit will only run as long as the digital input is closed.
Read more about extended operation in
chapter 4.10 Extended operation and External stop
External stop
The signal External switch will stop the unit, even if the timer or one of the signals Extended Operation, Low ,
Extended Operation, Normal or Extended Operation, High says it should stay in running mode.
Read more about external stop in
chapter 4.10 Extended operation and External stop
Extra fan motor control
External control of an external fan motor can be configured. The fan is started via either a digital input, time channel 4 or when the unit is started.
Read more about extra fan motor control in
1
2
Control mode
0
Start / Stop
Only on DI
When unit is running
Time channel 4
A digital output activates the fan motor. A digital input is available for run time indication/motor protection.
Damper
The outdoor air and exhaust air ducts close-off dampers can be controlled by digital outputs or be hardwired to the supply air fan relays for normal, reduced and high speed in such a fashion that the damper is open when the supply air fan is running. When using pressure controlled fans the digital activation signal is activated as soon as the fan has start conditions. This signal can be used to open the close-off damper.
Damper location to choose from:
✓ Outdoor
✓ Outdoor + Exhaust
✓ Exhaust
Read more about dampers in
114 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Automatic restart after power on
This function makes it possible to block automatic restart of the unit at power-up. At power-up, the B-alarm
Restart blocked after power on is generated. Once this alarm has been acknowledged, the unit will start. See more about alarms in
5.5.2
Sequences
Figure 5-8 Application Tool - Configuration - Functions
There are ten sequences (A to J) that can be configured in the Corrigo. Each sequence will have their own
PID-settings and a PWM digital output signal (Pulse Width Modulation).
The sequence types that can be configured are:
✓ Not used
✓ Heating
✓ Cooling
✓ Exchanger
✓ Damper
✓ Fan setpoint compensation
The default settings are:
✓ A = Heating
✓ B = Exchanger
✓ C = Cooler
✓ D to J = Not used tions you make in other menus.
Read more about sequences in
chapter 4.3 Temperature sequences
Corrigo manual, Rev. D 115 (196)
Information for the specialist - Configuration
Heater sequence
The table below shows the possible settings for a Heater sequence. Not all settings are visible for any type of heater.
Table 5-13 Sequence alternatives
Application tool
Name
Type of sequence
Type of heater
Setting alternatives
Free choice
Heating
✓ Inactive
✓ Water
✓ Electric
✓ DX (Direct exchanger)
Type of freeze protection
Freeze protection temperature sensor
✓ None
✓ Temperature sensor
✓ Freeze guard
✓ Sensor + Guard
✓ None
✓ 1
✓ 2
✓ 3
Yes / No Pump control
Pump stop mode
Type of pump indication
Digital start output
Actuator runtime (s)
Period time for PWM-signal (s)
Sequence output when recirculation/ support
✓ Always running
✓ Auto
✓ None
✓ Alarm
✓ Run Indication
Yes / No
Writable. Default 255 s
Writable. Default 60 s
Sequence output min limit (%)
Sequence output max limit (%)
Sequence output when the unit is stopped
(%)
Sequence output when fire mode
Sequence output when smoke mode
✓ 0 %
✓ 100 %
✓ Auto
Writable
Writable
Writable
0, 1, Auto
0, 1, Auto
Note
Cooler sequence
The table below shows the possible settings for a Cooler sequence. Not all settings are visible for any type of cooler.
Table 5-14 Sequence alternatives
Application tool
Name
Type of sequence
Type of cooler
Setting alternatives
Free choice
Cooling
✓ Inactive
✓ Water
✓ DX (Direct exchanger)
✓ DX with exchanger control
Note
116 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Table 5-14 Sequence alternatives (continued)
Application tool
Pump control
Pump stop mode
Setting alternatives
Yes / No
Type of pump indication
Digital start output
Actuator runtime (s)
Period time for PWM-signal (s)
Sequence output when recirculation/ support
✓ Always running
✓ Auto
✓ None
✓ Alarm
✓ Run Indication
Yes / No
Writable. Default 255 s
Writable. Default 60 s
Sequence output min limit (%)
Sequence output max limit (%)
✓ 0 %
✓ 100 %
✓ Auto
Writable
Writable
Sequence output when the unit is stopped
(%)
Writable
Note
Exchanger sequence
The table below shows the possible settings for an Exchanger sequence. Not all settings are visible for any type of heater.
Table 5-15 Sequence alternatives
Application tool
Name
Type of sequence
Type of exchanger
Setting alternatives
Free choice
Exchanger
Digital start output
Actuator runtime (s)
Period time for PWM-signal (s)
Exchanger alarm
Defrosting mode
✓ Inactive
✓ Rotating
✓ Plate
✓ Liquid
Yes / No
Writable. Default 255 s
Writable. Default 60 s
Yes / No
✓ No defrosting
✓ Defrosting temperature monitoring
Yes / No Freeze prevention rotation exchanger
Sequence output when recirculation/ support
Sequence output min limit (%)
Sequence output max limit (%)
✓ 0 %
✓ 100 %
✓ Auto
Writable
Writable
Sequence output when the unit is stopped
(%)
Writable
Note
Corrigo manual, Rev. D 117 (196)
Information for the specialist - Configuration
Damper sequence
The table below shows the possible settings for a Damper sequence. Not all settings are visible for any type of heater.
Table 5-16 Sequence alternatives
Application tool
Name
Type of sequence
Digital start output
Actuator runtime (s)
Period time for PWM-signal (s)
Exchanger alarm
Enable enthalpy control
CO2 control
Setting alternatives
Free choice
Damper
Yes / No
Writable. Default 255 s
Writable. Default 60 s
Yes / No
Yes / No
✓ No
✓ CO2 sequence 1
✓ CO2 sequence 2
CO2 control mode ✓ Decreasing
✓ Increasing
Sequence output when recirculation/ support
Sequence output min limit (%)
Sequence output max limit (%)
Sequence output when the unit is stopped
(%)
✓ 0 %
✓ 100 %
✓ Auto
Writable
Writable
Writable
Note
Fan setpoint compensation sequence
The table below shows the possible settings for a Fan setpoint compensation sequence. Not all settings are visible for any type of heater.
Table 5-17 Sequence alternatives
Application tool
Name
Type of sequence
Type of setpoint compensation
Setting alternatives
Free choice
Fan setpoint compensation
✓ Inactive
✓ Decrease
✓ Increase
Yes / No Digital start output
Sequence output when recirculation/ support
Sequence output min limit (%)
Sequence output max limit (%)
Sequence output when the unit is stopped
(%)
✓ 0 %
✓ 100 %
✓ Auto
Writable
Writable
Writable
Note
118 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Starting order heating/cooling
Setting of the order of the sequences is made in Configuration ► Functions ► Sequence heating/cooling.
It is possible to define a specific start order for the different sequences for heating and cooling demand.
The selectable number, 1…10, defines the start order of the sequences. If two sequences have the same start order they will work in parallel.
Start order heating shows only sequences which can work as a heating sequence, such as:
✓ Heater
✓ Exchanger
✓ Damper
✓ Fan setpoint compensation
Start order cooling shows only sequences which can work as a cooling sequence, such as:
✓ Cooler
✓ Exchanger
✓ Damper
✓ Fan setpoint compensation
The following picture (
5-9 ) shows the default settings of the configured sequences A=Heater, B=Exchanger
and C=Cooler, where the Exchanger (SEQ. B) starts first in heating mode followed by the Heater (SEQ. A).
In cooling mode, the Exchanger (SEQ. B) starts first followed by the Cooler (SEQ. C).
Output (%)
100% = 10 V
Sequence order 2 1 1 2
SEQ. C SEQ. B SEQ. B SEQ. A
Sequence capacity (%)
Sequence output (%)
Figure 5-9 Sequence order
0-100% 0-100% 0-100% 0-100%
Sequence settings
These settings are used the define the start of the sequences when the unit starts. There are two different modes to start the unit:
✓ Normal start up
✓ Warm (Heat) start up
Normal start up:
The sequence control starts at 100% for the heating sequence which is selected at the parameter At start up begin temperature control at 100% in . The default setting is Heating 1 , which means it starts at 100% for heating sequence 1 which is the exchanger in the default configuration.
Corrigo manual, Rev. D 119 (196)
Information for the specialist - Configuration
Warm start up:
If the outdoor temperature is lower than the settable limit Warm start up if outdoor temperature < (°C) the unit will start in the warm start mode. A second sequence will start at 100% in this mode if the unit starts. The default setting is Heating 2 , which means it starts at 100% for the heating sequence 2 which is the heater in the default configuration
Table 5-18 Sequence settings
Application tool
At start up begin temperature control at
100 % in
Setting alternatives
✓ Heating 1 0%
✓ Heating 1…10
Writable Warm start up if outdoor temperature < (°
C)
If warm start up begin temperature control at 100 % in
✓ Heating 1 0%
✓ Heating 1…10
Note
Temperature control
Table 5-19 Temperature control
Application tool
Room temperature sensor
Room temperature average
Setting alternatives
None / 1…16
Outdoor temperature sensor
✓ No
✓ Minimum
✓ Maximum
✓ Average
✓ Average remove min / max
✓ Median
✓ No
✓ Intake air
✓ Outdoor
✓ Outdoor + intake air
Yes / No
Yes / No
Yes / No
Extract air temperature sensor
Supply air temperature sensor
Exhaust air temperature sensor
Activate summer mode ✓ No summer setpoint
✓ Switch with calendar
✓ Switch with change-over
✓ Switch with digital output
✓ Switch with outdoor temp
External setpoint device
Efficiency presentation
Min temperature difference to show efficiency (°C)
✓ No
✓ TG - R4
✓ TBI - PT1000
Yes / No
Writable (Default 2)
Min outdoor temperature to show efficiency
(°C)
Writable (Default -100)
Cooling recovery mode On / Off
Temperature difference to start cooling recovery (°C)
Fan speed compensated temperature setpoint
Writable (Default 0)
Defrosting exchanger
✓ None
✓ Low
✓ High
✓ Low & High
Yes / No
120 (196)
Note
How to display the room temperature value.
Which temperature the outdoor sensor measures
Corrigo manual, Rev. D
Information for the specialist - Configuration
Table 5-19 Temperature control (continued)
Application tool
Defrosting temperature sensor
Setting alternatives
✓ Defrosting sensor
✓ Exhaust air temperature
Extract air fan speed when Defrosting with stopped supply air
✓ Auto
✓ Low
✓ Normal
✓ High
Note
Change-over 1 and 2
Select the change-over sequence for heating and/or cooling.
Read more about change-over in
Step controller 1 and 2
Application tool
Step controller sequence
Setting alternatives
Off
Sequence A…J
Change-over
Step control
Number of steps
Sequential / Binary
1…4
Block output if sequence feedback alarm Yes / No
Read more about step control in
5.5.3
Fan control
Read more about fan control in
Application tool
Fan
Setting alternatives
Kitchen function
Flow presentation
✓ Supply air + Extract air
✓ Supply air
✓ Extract air
Yes / No
Yes / No
Supply air fan indication ✓ None
✓ Alarm
✓ Run indication
Extract air fan indication
Extract air fan slaved by exchanger supply air flow
Flow calculation supply air K-factor
✓ None
✓ Alarm
✓ Run indication
Yes / No
Writable
Flow calculation supply air X-factor
Flow calculation extract air K-factor
Flow calculation extract air X-factor
Flow calculation exchanger supply air Kfactor
Flow calculation exchanger supply air Xfactor
Writable
Writable
Writable
Writable
Writable
Note
Note
The K-factor is usually printed on the fan
The K-factor is usually printed on the fan
The K-factor is usually printed on the fan
Corrigo manual, Rev. D 121 (196)
Information for the specialist - Configuration
Application tool
Flow calculation exchanger extract air Kfactor
Flow calculation exchanger extract air Xfactor
External flow setpoint
Step control of fans
Setting alternatives
Writable
Writable
Switch point step 1-2 SAF (%)
Switch point step 2-3 SAF (%)
Switch point step 1-2 EAF (%)
Switch point step 2-3 EAF (%)
Hysteresis (%)
Yes / No
✓ No
✓ 1 step
✓ 2 step
✓ 3 step
Writable
Writable
Writable
Writable
Writable. Default 5
Note
The K-factor is usually printed on the fan
Fan compensation curve 1, 2 and 3
Read more about the fan compensation curve in
Application tool
Fan level
Mode
Fan
Sensor
Setting alternatives
✓ All levels
✓ Low speed
✓ Normal speed
✓ High speed
✓ Low + Normal speed
✓ Normal + High speed
✓ Inactive
✓ In all modes
✓ When defrosting
✓ Supply air fan + extract air fan
✓ Supply air fan
✓ Extract air fan
✓ Outdoor temperature
✓ Intake air temperature
✓ Supply air temperature
✓ Exhaust air temperature
✓ Extract air temperature
✓ Room temperature 1…10
✓ Pressure supply air
✓ etc.
Description
External flow setpoint
Application tool
Operation mode
Setting alternatives
✓ SAF
✓ EAF
✓ SAF and EAF
Writable (default 1) Factor EAF SAF
Read more about External flow setpoint in
Note
The factor is used if there is a difference between the SAF and EAF flow properties.
122 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Support control
Set if the extract fan will be running or not during support control.
Support control is normally used when room temperature control or extract air control has been configured.
When extract air control is configured a room sensor must be installed.
Support control can also be configured to start only with the supply air fan. In this mode, the extract air fan is not active. This requires a digital output to be configured, which controls the recirculation damper to open completely so the supply air fan can circulate the air to and from the room.
Read more about support control in
Fire / Smoke
Read more about fire and smoke control in
Application tool Setting alternatives
Operation mode when fire alarm ✓ Stopped
✓ Continuous run
✓ Running via normal start/stop conditions
✓ Supply air fan run
✓ Extract air fan run
Supply air fan setpoint type when fire alarm
✓ Auto
✓ Manual setpoint
✓ Manual output
✓ Low speed setpoint
✓ Normal speed setpoint
✓ High speed setpoint
Manual setpoint (Pa), (m 3 /h), (%)
Manual output (%)
Writable
Writable
Extract air fan setpoint type when fire alarm ✓ Auto
✓ Manual setpoint
✓ Manual output
✓ Low speed setpoint
✓ Normal speed setpoint
✓ High speed setpoint
Outdoor air damper function when fire alarm
✓ Normal function (follow the fan)
✓ Always open
✓ Always closed
Exhaust air damper function when fire alarm
✓
✓
Normal function (follow the fan)
Always open
✓ Always closed
Fire damper mode
✓ Not active
✓ Dampers normally closed
✓ Dampers normally opened
Fire damper test
✓ No test
✓ Test when unit running
✓ Test when unit stopped
Operation mode when smoke alarm ✓ Stopped
✓ Continuous run
✓ Running via normal start/stop conditions
✓ Supply air fan run
✓ Extract air fan run
Supply air fan setpoint when smoke alarm ✓ Auto
✓ Manual setpoint
✓ Manual output
✓ Low speed setpoint
✓ Normal speed setpoint
✓ High speed setpoint
Note
Corrigo manual, Rev. D 123 (196)
Information for the specialist - Configuration
Application tool
Extract air fan setpoint when smoke alarm
Setting alternatives
✓ Auto
✓ Manual setpoint
✓ Manual output
✓ Low speed setpoint
✓ Normal speed setpoint
✓ High speed setpoint
Outdoor air damper function when smoke alarm
✓
✓
Normal function (follow the fan)
Always open
✓ Always closed
Exhaust air damper function when smoke alarm
✓ Normal function (follow the fan)
✓ Always open
✓ Always closed
Note
CO
2
control
Setting of the fan speed for CO
2 control on the supply and extract fan.
Read more about CO
2 control in
chapter 4.4.3 Demand controlled ventilation
Application tool Setting alternatives
Setpoint supply air fan when CO2 control ✓ Low speed
✓ Normal speed
✓ High speed
Setpoint extract air fan when CO2 control ✓ Low speed
✓ Normal speed
✓ High speed
Note
5.5.4
Recirculation
Recirculation of air using a supply air fan and (optionally) extract air fan and a recirculation damper with or without temperature control. Used as a recovery function or during heating with support control during the night. Recirculation control is available as an analog or a digital function.
Read more about recirculation in
Application tool
Enable supply air temperature control when recirculation
Setting alternatives
✓ No temperature control
✓ Heating + cooling
✓ Heating
✓ Cooling
Enable the night cooling function when recirculation
Use extra time channel 4 to start recirculation
Run extract air fan during recirculation
Yes / No
Yes / No
Yes / No
Fixed setpoint or setpoint offset when circulation run
✓ Fixed setpoint
✓ Setpoint offset
Note
5.5.5
Humidity control
It is possible to use either humidification or dehumidification, or to use combined humidification and dehumidification.
Read more about humidity control in
124 (196) Corrigo manual, Rev. D
Application tool
Select sequence for dehumidify
Type of output
Setting alternatives
Sequence A to J
✓ None
✓ Analog
✓ Step
✓ Analog + step
Information for the specialist - Configuration
Note
5.5.6
Filter monitoring
Read more about filter monitoring in
Application tool
Type
Filter placement
Filter alarm reset
Filter alarm time (month)
Filter alarm supply air limit X1 (m 3 /h)
Filter alarm supply air limit X2 (m 3 /h)
Filter alarm supply air limit Y1 (Pa)
Filter alarm supply air limit Y2 (Pa)
Filter alarm extract air limit X1 (m 3 /h)
Filter alarm extract air limit X2 (m 3 /h)
Filter alarm extract air limit Y1 (Pa)
Filter alarm extract air limit Y2 (Pa)
Setting alternatives
✓ Sensor
✓ Guard
✓ Sensor + guard
✓ Supply air
✓ Extract air
✓ Supply air + Extract air
Yes/No
Writable
Writable (Default 0)
Writable (Default 2000)
Writable (Default 10)
Writable (Default 150)
Writable (Default 0)
Writable (Default 2000)
Writable (Default 10)
Writable (Default 150)
Note
5.5.7
Extended operation
The digital inputs for extended running can be used to force the unit to start in low, normal or high speed although the timer says the running mode should be Off . This digital input has always higher priority than running via time schedule
The unit will run for the set time. If the running time is set to 0 the unit will only run as long as the digital input is closed.
Read more about extended operation in
chapter 4.10 Extended operation and External stop
Application tool
Extended operation low speed
Extended operation normal speed
Extended operation high speed
Extended operation stop delay (min)
Setting alternatives
Yes/No
Yes/No
Yes/No
Writable
Note
5.5.8
Pretreatment
Damper and pump control for preheating or precooling of the outdoor air via an underground intake channel.
Select if pretreatment should be activated during free cooling.
Corrigo manual, Rev. D 125 (196)
Information for the specialist - Configuration
Read more about pretreatment in
and about free cooling in
.
5.5.9
Extra controller
Read more about extra controller in
Application tool
Start / Stop function
Control mode
Type of freeze protection
Pump control
Pump running mode
Type of feedback
Digital start output
Extra contr. output when recirculation/ support
Sequence output min limit (%)
Sequence output max limit (%)
Setting Alternatives
✓ Always running
✓ Unit running
✓ When defrosting
✓ Extra time channel 1…3
✓ Heating
✓ Cooling
Freeze protection temperature 1…3
Yes / No
✓ Always running
✓ Auto
✓ None
✓ Alarm
✓ Run indication
Yes / No
✓ 0
✓ 1
✓ Auto
Writable (Default 0)
Writable (Default 100)
Note
5.5.10 Extra fan motor control
Read more about extra fan motor control in
chapter 4.4.4 Extra fan motor control
Application tool
Type of feedback fan motor 1 (2)
Start/stop function fan motor 1(2)
Setting Alternatives
✓ None
✓ Alarm
✓ Run indication
✓ Digital input
✓ Unit running
✓ Extra time channel 4
Note
5.5.11 Extra indications & outputs
Application tool
Extra time channel
Run indication
Sum alarm outputs
Free cooling running
Setting alternatives
✓ No
✓ 1…4
Yes / No
✓ None
✓ A / B alarm
✓ A - alarm + B - alarm
✓ A - alarm + B / C - alarm
Yes / No
Note
126 (196) Corrigo manual, Rev. D
Application tool
Analog signal output
Information for the specialist - Configuration
Note Setting alternatives
✓ None
✓ Outdoor temperature
✓ Intake air temperature
✓ Supply air temperature
✓ Exhaust air temperature
✓ Extract air temperature
✓ Room temperature 1…16
✓ Defrosting temperature
✓ etc.
Writable (Default -50)
Writable (Default 150)
Writable (Default 0)
Temperature at Vmin (°C)
Temperature at Vmax (°C)
Alarm output
Alarm name
5.5.12 Extra sensors & inputs
Application tool
Alarm acknowledgements
Extra sensors
Extra alarm
Setting Alternatives
Yes / No
✓ No
✓ 1…5
✓ Off
✓ 1…10
Note
5.5.13 Room unit
A room unit, ED-RUx, can be configured via Application tool.
Application tool
Temperature to show in ED-RUx
Function on/off button
Fan speed extended run
Extended operation (min)
Minimum setpoint adjustment (°C)
Maximum setpoint adjustment (°C)
Setting alternatives
✓ Room temperature of the display
✓ Room temperature from sensor connected to controller
✓ Outdoor temperature
✓ Supply air temperature
✓ Extract air temperature
✓ No function
✓ Not used
✓ On / Off function
✓ On/Off/Extended operation function
✓ Low speed extended run
✓ Normal speed extended run
✓ High speed extended run
Writable (Default: 60)
Writable (Default -3)
Writable (Default 3)
Note
5.5.14 Alarms
Set the Alarm delay time at start up. Default: 60 s.
Read more about alarms in
chapter 3.6 Alarm events and alarm handling
and
Corrigo manual, Rev. D 127 (196)
Information for the specialist - Configuration
5.6 Configuration - Inputs and Outputs
Any control signal can be bound to any in- and output, the only restriction being that digital signals cannot be bound to analog inputs and vice versa. It is up to the user doing the binding to make sure that activated functions are bound to appropriate in- and outputs.
iour of the controller. Alarm 194 - Internal alarm will then become active i.
5.6.1
Analog inputs, AI
All analogue inputs are for Pt1000, Ni1000LG, Ni1000 or 0…10 V.
Input signals can be compensated e.g. for wiring resistance.
The raw value will show the actual, uncompensated input value.
See
Appendix C Input and output lists
for a complete list of inputs and outputs.
N Mode to Off or Manual . In this case it's not necessary to configure a physical input, the application will work with the manual value instead.
The settings that can be selected / configured are:
Table 5-20 Analog inputs
Variable
Device
Settings
Terminal
Name
Signal type
Sensor type
Min input (V)
Max input (V)
Min signal (°C)
Max signal (°C)
Filter factor
✓ Controller
✓ Expansion unit 1…10
✓ Off
✓ AI 1…32
✓ UAI 1…4, 27, 28
✓ UI 1, 2
✓ Temperature
Writable
Read only
✓ Pt1000
✓ Ni1000LG
✓ Ni1000
✓ 0…10 V
Writable (Default 0)
Writable (Default 10)
Writable (Default 0)
Writable (Default 100)
Writable (Default 0,2)
Note
Select a controller or an expansion unit
The number of terminals are depending on Corrigo model
Free choice
The filter factor is the damping you want the program to work with in order to reduce the influence of potential signal fluctuations on the sensor input.
A new value is calculated using the following formula:
New value = old value * filter factor + raw value * (1 - filter factor)
Compensation (°C) Writable (Default 0)
128 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Table 5-20 Analog inputs (continued)
Variable
Mode
Manual (°C)
Actual value (°C)
Settings
✓ Off
✓ Manual
✓ Auto
Writable (Default 0)
Read only
Note
5.6.2
Digital inputs, DI
To simplify adaptation to external functions, all digital inputs can be configured to be either normally open,
NO, or normally closed, NC. The inputs are as default normally open, i. e. if the input is closed, the function connected to the input in Corrigo is activated.
See
Appendix C Input and output lists
for a complete list of inputs and outputs.
configured to either NO or NC themselves. For example, you can choose if the fire alarm input should be activated when it is closed or opened. Therefore, there is a risk that the signal is changed twice and the result is the opposite of the desired.
The settings that can be selected / configured are:
Table 5-21 Digital inputs
Variable
Device
Terminal
Name
NC / NO
Mode
Actual value (°C)
Settings
✓ Controller
✓ Expansion unit 1…10
✓ Off
✓ DI 1…8
✓ UDI 1…4
✓ UI 1, 2
Writable
✓ NO
✓ NC
✓ Off
✓ Manual
✓ Auto
Read only
Note
Select a controller or an expansion unit
The number of terminals are depending on Corrigo model
Free choice
✓ NC (Normally closed )
✓ NO (Normally open)
5.6.3
Analog outputs, AO
See
Appendix C Input and output lists
for a complete list of inputs and outputs.
iour of the controller. Alarm 194 - Internal alarm will then become active i.
Corrigo manual, Rev. D 129 (196)
Information for the specialist - Configuration
Table 5-22 Analog outputs
Variable
Device
Terminal
Name
Range output
Settings
✓ Controller
✓ Expansion unit 1…10
✓ Off
✓ AO 1…5
Writable
✓ 0…10 V
✓ 2…10 V
✓ 10…2 V
✓ 10…0 V
Note
Select a controller or an expansion unit
The number of terminals are depending on Corrigo model
Free choice
5.6.4
Digital outputs, DO
Digital outputs can be NC (Normally Closed) or NO (Normally Opened).
See
Appendix C Input and output lists
for a complete list of inputs and outputs.
iour of the controller.
Alarm 194 - Internal alarm will then become active.
Table 5-23 Digital outputs
Variable
Device
Terminal
Name
NC / NO
Settings
✓ Controller
✓ Expansion unit 1…10
✓ Off
✓ DO 1…7
Writable
✓ NO
✓ NC
Note
Select a controller or an expansion unit
The number of terminals are depending on Corrigo model
Free choice
✓ NC (Normally closed )
✓ NO (Normally open)
5.7 Configuration - Raw values
Read the raw values from all I/Os for the controller and/or expansion unit.
5.8 Ventilation
tion you choose to set up. Therefore, not all menu items are available for all applications.
5.8.1
Actual / Setpoint
[Application tool ► Ventilation ► Actual/Setpoint]
Read and adjust setpoints for:
✓ Temperature
✓ Room controller
130 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
✓ Extract air controller
✓ Supply air controller
✓ Humidity
✓ CO
2
✓ Supply air fan
✓ Extract air fan
✓ Step controller
✓ Freeze protection
✓ Exchanger
Temperature
Table 5-24 Setpoints for temperature control
Variable
Actual control type
Outdoor temperature (°C)
Intake air temperature (°C)
Supply air temperature (°C)
Average room temperature (°C)
Extract air temperature (°C)
Exhaust air temperature (°C)
Setpoint adjustment (°C)
Actual setpoint supply air (°C)
Setpoint supply air (°C)
Actual setpoint room (°C)
Setpoint room air (°C)
Actual setpoint extract air (°C)
Setpoint extract air (°C)
R
R
R
R
W
R
W
R
W
R
W
R
R
Read/Write Default value
R
0
18
21
21
Min/Max Note
-20/150
-20/150
-20/150
Room controller
Table 5-25 Setpoints for room control
Variable
Room temperature (°C)
Setpoint adjustment (°C)
Setpoint offset low speed (°C)
Setpoint offset high speed (°C)
Setpoint room air (°C)
Setpoint summer room (°C)
Actual setpoint room (°C) R
Outdoor temperature limit cascade/ supply air (°C)
W
Setpoint outdoor curve X1 (°C) W
W
W
W
W
W
Read/Write Default value
R
0
0
0
21
24
13
-20
Min/Max Note
-20/150
-20/150
-20/40
-40/40
Corrigo manual, Rev. D 131 (196)
Information for the specialist - Configuration
Table 5-25 Setpoints for room control (continued)
Variable
Setpoint outdoor curve Y1 (°C)
Setpoint outdoor curve X2 (°C)
Setpoint outdoor curve Y2 (°C)
Setpoint outdoor curve X3 (°C)
Setpoint outdoor curve Y3 (°C)
Setpoint outdoor curve X4 (°C)
Setpoint outdoor curve Y4(°C)
Controller output (%)
W
W
W
W
R
Read/Write Default value
W 22
W
W
5
20
20
20
30
22
Min/Max
10/40
-40/40
10/40
-40/40
10/40
-40/40
10/40
Note
Extract air controller
Table 5-26 Setpoints for extract air control
Variable
Extract air temperature (°C)
Setpoint adjustment (°C)
Setpoint offset low speed (°C)
Setpoint offset high speed (°C)
Setpoint extract air (°C)
Setpoint summer Extract air (°C)
Actual setpoint extract air (°C) R
Outdoor temperature limit cascade/ supply air (°C)
W
Setpoint outdoor curve X1 (°C)
Setpoint outdoor curve Y1 (°C)
W
W
Setpoint outdoor curve X2 (°C)
Setpoint outdoor curve Y2 (°C)
Setpoint outdoor curve X3 (°C)
Setpoint outdoor curve Y3 (°C)
Setpoint outdoor curve X4 (°C)
Setpoint outdoor curve Y4(°C)
Controller output (%) R
W
W
W
W
W
W
W
W
W
W
W
Read/Write Default value
R
0
0
0
21
24
13
-20
22
5
20
20
20
30
22
Min/Max Note
-10/10
-50/50
-50/50
-20/150
-20/150
-40/40
-40/40
10/40
-40/40
10/40
-40/40
10/40
-40/40
10/40
Supply air controller
Table 5-27 Setpoints for supply air control
Variable
Supply air temperature (°C)
Setpoint adjustment (°C)
Setpoint offset low speed (°C)
Setpoint offset high speed (°C)
Setpoint supply air (°C)
Read/Write Default value
R
W
W
0
0
W
W
0
18
Min/Max Note
-10/10
-50/50
-50/50
-20/150
132 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Table 5-27 Setpoints for supply air control (continued)
Variable
Setpoint summer supply air (°C)
Neutral zone (°C)
Min limit supply air
Max limit supply air
Reduction of min limit supply air if active DX-cooling (°C)
Actual setpoint supply air (°C)
Setpoint delta T extract air-supply air (°C)
Setpoint outdoor curve X1 (°C)
Setpoint outdoor curve Y1 (°C)
Setpoint outdoor curve X2 (°C)
Setpoint outdoor curve Y2 (°C)
Setpoint outdoor curve X3 (°C)
Setpoint outdoor curve Y3 (°C)
Setpoint outdoor curve X4 (°C)
Setpoint outdoor curve Y4(°C)
Controller output (%)
W
W
W
W
W
W
W
W
R
Read/Write Default value
W 24
W
W
0
12
W
W
30
5
R
W -2
-20
22
5
20
20
20
30
22
Min/Max
-20/150
0/10
10/150
10/150
0/30
-40/150
-40/40
10/40
-40/40
10/40
-40/40
10/40
-40/40
10/40
Note
Humidity
Table 5-28 Setpoints for humidity control
Variable
Humidity outdoor (%rH)
Humidity room/extract air (%rH)
Humidity supply air (%rH)
Setpoint humidity room/extract air
(%rH)
Humidity control signal (%)
R
R
Read/Write Default value
R
W 50
R
Min/Max Note
0/100
CO
2
Table 5-29 Setpoints for CO
2 control
Variable
CO2 room/extract air (ppm)
Setpoint mixing damper (ppm)
Read/Write Default value
R
W 1000
Min/Max Note
0/2000
Corrigo manual, Rev. D 133 (196)
Information for the specialist - Configuration
Fans
Table 5-30 Setpoints for fans
Variable
Setpoint low speed supply air fan
(%)
Setpoint low speed extract air fan
(%)
Setpoint normal speed supply air fan (%)
Setpoint normal speed extract air fan (%)
Setpoint high speed supply air fan
(%)
Setpoint high speed extract air fan
(%)
Setpoint low speed supply air fan
(Pa)
Setpoint low speed extract air fan
(Pa)
Setpoint normal speed supply air fan (Pa)
Setpoint normal speed extract air fan (Pa)
Setpoint high speed supply air fan
(Pa)
Setpoint high speed extract air fan
(Pa)
Setpoint low speed supply air fan
(m 3 /h)
Setpoint low speed extract air fan
(m 3 /h)
Setpoint normal speed supply air fan (m 3 /h)
Setpoint normal speed extract air fan (m 3 /h)
Setpoint high speed supply air fan
(m 3 /h)
Setpoint high speed extract air fan
(m 3 /h)
Read/Write Default value
W 25
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
25
50
50
75
75
250
250
500
500
750
750
1000
1000
2000
2000
3000
3000
0/10000
0/10000
0/10000
0/10000
0/10000
0/10000
0/60000
0/60000
0/60000
Min/Max
0/100
0/100
0/100
0/100
0/100
0/100
0/60000
0/60000
0/60000
Note
Supply air fan
Table 5-31 Setpoints for supply air fan
Variable
Actual level
Pressure supply air (Pa)
Flow supply air (m 3 /h)
Actual setpoint compensation (Pa, m 3 /h, %)
Actual setpoint (Pa, m 3 /h, %)
Output signal (%)
R
R
R
R
Read/Write Default value
R
R
Min/Max Note
134 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Table 5-31 Setpoints for supply air fan (continued)
Variable
Bus values SAF-1…5 Frequency
(from frequency converter)
Current (from frequency converter)
(A)
Power (from frequency converter)
(W)
Error (from frequency converter)
R
R
R
Read/Write Default value
R
Min/Max Note
Extract air fan
Table 5-32 Setpoints for extract air fan
Variable
Actual level
Pressure extract air (Pa)
Flow extract air (m 3 /h)
Actual setpoint compensation (Pa, m 3 /h, %)
Actual setpoint (Pa, m 3 /h, %)
Output signal (%)
Bus values EAF-1…5 Frequency
(from frequency converter)
Current (from frequency converter)
(A)
Power (from frequency converter)
(W)
Error (from frequency converter)
R
R
R
R
R
R
R
R
Read/Write Default value
R
R
Min/Max Note
Step controller 1 and 2
Table 5-33 Setpoints for stepcontroller 1 and 2
Variable
Actual binary step
Read/Write Default value
R
Min/Max Note
Freeze protection
Table 5-34 Setpoints for freeze protection
Variable Read/Write Default value
Freeze protection temperature 1…3
(°C)
R
Min/Max Note
Corrigo manual, Rev. D 135 (196)
Information for the specialist - Configuration
Exchanger
Table 5-35 Setpoints for exchanger
Variable
Defrosting temperature (°C)
Efficiency exchanger (%)
Read/Write Default value
R
R
Min/Max Note
5.8.2
Temperature control
[Application tool ► Ventilation ► Temperature control]
Read more about temperature control in
chapter 4.2 Temperature control
Sequences
Read more about sequences in
chapter 4.3 Temperature sequences .
Table 5-36 Setpoints for sequence A to J
Variable
Digital start output start point (%)
Digital start output stop point (%)
Pump stop delay (min)
Pump-kick hour (h)
Pump running when outdoor temperature < (°C)
Hysteresis to allow pump stop (°C) W
Max fan compensation (%) W
Read/Write Default value
W 10
W
W
1
5
W
W
15
10
1
100
Min/Max
0/100
0/100
0/600
0/23
-40/100
0/100
0/100
Note
Step controller 1 and 2
Read more about step control in
.
Table 5-37 Setpoints for step controller 1 and 2
Variable
Min switch time (s)
Step 1 start point (%)
Step 1 stop point (%)
Step 2 start point (%)
Step 2 stop point (%)
Step 3 start point (%)
Step 3 stop point (%)
Step 4 start point (%)
Step 4 stop point (%) W
Block DX-cooling if outdoor temperature < (°C)
W
W
W
W
W
Read/Write Default value
W 60
W
W
W
10
5
45
40
70
65
95
90
1
Min/Max
0/300
0/100
0/100
0/100
0/100
0/100
0/100
0/100
0/100
-40/150
Note
136 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Table 5-37 Setpoints for step controller 1 and 2 (continued)
Min/Max Variable
Block step 1 if supply air fan output signal < (%)
Block step 2 if supply air fan output signal < (%)
Block step 3 if supply air fan output signal < (%)
W
W
Block step 4 if supply air fan output signal < (%)
Block step 1 if outdoor temperature
< (°C)
W
W
Read/Write Default value
W 0
0
0
0
13
Block step 2 if outdoor temperature
< (°C)
W
Block step 3 if outdoor temperature
< (°C)
W
13
13
13 Block step 4 if outdoor temperature
< (°C)
W
Block all step if outdoor temperature
< (°C)
W
Hysteresis for decreased output (%) W
0
0,5
0/100
0/100
0/100
0/100
-40/150
-40/150
-40/150
-40/150
-40/150
0/100
Note
Freeze protection 1, 2 and 3
Read more about freeze protection in
.
Table 5-38 Setpoints for freeze protection 1, 2 and 3
Variable Read/Write Default value
Alarm limitation running mode (°C) W 7
P-band running mode (°C)
Setpoint standby mode (°C)
W
W
5
25
Min/Max
-40/150
0/100
-40/150
Note
Exchanger
Read more about exchangers in
chapter 4.3.2 Exchanger (Sequence B) .
Table 5-39 Setpoints for exchanger
Variable
Start delay exchanger (s)
Start delay with 100 % exchanger
(s)
Start alarm delay (s)
Outdoor start/stop exchanger temperature (°C)
Hysteresis (°C)
Defrosting setpoint min limit (°C)
Min time deicing (min)
W
W
W
W
W
Read/Write Default value
W 0
W 2
60
10
0,2
-3
5
Min/Max
0/3600
0/3600
0/3600
-40/150
0/10
-40/150
0/60
Note
Corrigo manual, Rev. D 137 (196)
Information for the specialist - Configuration
Table 5-39 Setpoints for exchanger (continued)
Variable Read/Write Default value
W -100 Stop supply air fan if outdoor temp
< (°C)
Hysteresis to stop defrosting (°C) W 4
Min/Max
-100/150
0/10
Note
Pretreatment
Read more about pretreatment in
Table 5-40 Setpoints for Pretreatment
Variable
Pretreatment output
Activate preheater when outdoor temperature < (°C)
Activate precooler when outdoor temperature >(°C)
Hysteresis (°C)
W
W
Min difference between outdoor and intake air temperature
W
Pretreatment block time if difference below min (h)
W
Min run time (min) W
Read/Write Default value
R
W 8
19
1
1
6
5
Min/Max
-40/150
-40/150
0/10
0/20
0/24
0/600
Note
Summer mode
Read more about summer mode in
chapter Room (summer) else supply air outdoor compensated
and
Extract air (summer) else supply air outdoor compensated
.
Table 5-41 Setpoints for Summer mode
Variable
Date for start of summer period
Month for start of summer period
Date for end of summer period
Month for end of summer period
Outdoor temp for switch between summer / winter (°C)
Outdoor temp hysteresis for switch between summer / winter (°C)
Read/Write Default value
W 1
W
W
4
1
W
W
10
13
W 0,5
Min/Max
1/31
1/12
1/31
1/12
0/99
0/99
Note
5.8.3
Fan control
[Application tool ► Ventilation ► Fan control]
138 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Fans
Table 5-42 Setpoints for fans
Variable
Actual level supply air fan
Actual level extract fan
Setpoint low speed supply/extract air fan (%)
Setpoint normal speed supply/ extract air fan (%)
Setpoint high speed supply/extract air fan (%)
Setpoint low speed supply/extract air fan (Pa)
Setpoint normal speed supply/ extract air fan (Pa)
Setpoint high speed supply/extract air fan (Pa)
Setpoint low speed supply/extract air fan (m 3 /h)
W
W
W
W
W
W
Setpoint normal speed supply/ extract air fan (m 3 /h)
Setpoint high speed supply/extract air fan (m 3 /h)
W
W
Flow supply air (m 3 /h)
Flow extract air (m 3 /h)
Slave factor
Offset supply air fan when free cooling (Pa, m 3 /h, %)
Offset extract air fan when free cooling (Pa, m 3 /h, %)
W
Offset supply air fan when recirculation (Pa, m 3 /h, %)
W
Offset extract air fan when recirculation (Pa, m 3 /h, %)
W
R
R
W
W
Read/Write Default value
R
R
W 25
50
75
250
500
750
1000
2000
3000
1
0
0
0
0
Min/Max Note
0/100
0/100
0/100
0/10000
0/10000
0/10000
0/60000
0/60000
0/60000
0/1
-30000/
30000
-30000/
30000
-30000/
30000
-30000/
30000
Supply air fan
Table 5-43 Setpoints for supply air fan
Variable
Start delay (s)
Stop delay (s)
Speed during stop delay (%)
Speed change delay (s)
W
W
W
Outdoor air damper stop delay (s) W
Read/Write Default value
W 60
180
50
10
0
25 Min pressure for supply air fan indication (Pa)
W
Min flow for supply air fan indication
(m 3 /h)
W 500
Actual setpoint compensation (Pa) R
Min/Max
0/3600
0/3600
0/100
0/60
0/3600
0/10000
0/60000
Note
Corrigo manual, Rev. D 139 (196)
Information for the specialist - Configuration
Table 5-43 Setpoints for supply air fan (continued)
Variable
Actual setpoint compensation (m 3 / h)
Actual setpoint compensation (%) R
SAF speed min limit (%) W
SAF speed max limit (%) W
Read/Write Default value
R
0
100
Min/Max Note
Extract air fan
Table 5-44 Setpoints for extract air fan
Variable
Start delay (s)
Stop delay (s)
Speed during stop delay (%)
Speed change delay (s) W
Exhaust air damper stop delay (s) W
Min pressure for extract air fan indication (Pa)
W
Min flow for extract air fan indication
(m 3 /h)
W
Actual setpoint compensation (Pa) R
Actual setpoint compensation (m h)
3 / R
Actual setpoint compensation (%) R
EAF speed min limit (%) W
EAF speed max limit (%) W
Read/Write Default value
W 0
W
W
30
0
10
0
25
500
0
100
Min/Max
0/3600
0/3600
0/100
0/60
0/3600
0/10000
0/60000
Note
Fan compensation curve 1, 2 and 3
Read more about fan compensation in
Table 5-45 Setpoints for fan compensation curve 1, 2 and 3
Variable Min/Max
Lower point X
Read/Write Default value
W 15
Lower point Y (Pa, m 3 /h, %)
Middle point X
Middle point Y (Pa, m 3 /h, %)
Higher point X
Higher point Y (Pa, m 3 /h, %)
W
W
W
W
W
0
20
0
25
0
-30000/
30000
-30000/
30000
-30000/
30000
-30000/
30000
-30000/
30000
-30000/
30000
Note
140 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
5.8.4
Demand control
[Application tool ► Ventilation ► Demand control]
CO2
Read more about demand control and CO
2 in
chapter 4.4.3 Demand controlled ventilation
Table 5-46 Setpoints for CO2
Variable
Start limit fan start/stop (ppm)
Stop hysteresis fan start/stop (ppm) W
Demand control
Min time for CO2 control (min)
R
W
Read/Write Default value
W 800
160
20
Min/Max
0/2000
0/2000
0/600
Note
Recirculation
Read more about recirculation in
Table 5-47 Setpoints for recirculation
Variable
Setpoint recirculation (°C)
Setpoint offset recirculation (°C)
Change to outdoor air when room air > (°C)
Outdoor air damper opened
Read/Write Default value
W 18
W
W
0
25
R
Min/Max
-20/150
0/50
10/50
Note
Free cooling
Read more about free cooling in
.
Table 5-48 Setpoints for free cooling
Variable
Free cooling mode
Running when day outdoor temperature > (°C)
Read/Write Default value
R
W 22
W 18 Stop when night outdoor temperature > (°C)
Stop when night outdoor temperature < (°C)
W 10
Stop when room temperature < (°C) W
Free cooling start hour (h) W
Free cooling stop hour (h)
Time to block heat output after free cooling (min)
W
W
18
0
7
60
Fan-kick temperature check (s) W 180
Min/Max
10/40
10/40
10/40
10/40
0/23
1/24
0/600
0/3600
Note
Corrigo manual, Rev. D 141 (196)
Information for the specialist - Configuration
Table 5-48 Setpoints for free cooling (continued)
Variable
Fan-kick interval time (min)
Read/Write Default value
W
Start when extract - outdoor > (°C) W
60
2
Min/Max
0/600
1/5
Note
Support control
Read more about support control in
.
Table 5-49 Setpoints for support control
Variable
Support control mode
Min time for support control (min) W
Start heating room temperature (°C) W
Read/Write Default value
R
20
15
Stop heating room temperature (°C) W
Setpoint heating (°C) W
Start cooling room temperature (°C) W
Stop cooling room temperature (°C) W
Setpoint cooling (°C) W
21
30
30
28
12
Min/Max
0/600
10/40
10/40
-20/150
10/40
10/40
-20/150
Note
5.8.5
Fire / Smoke
[Application tool ► Ventilation ► Fire/Smoke]
Read more about fire and smoke control in
chapter 4.6.2 Fire/smoke dampers
.
Table 5-50 Setpoints for Fire/Smoke
Variable
Run fire damper (s)
Test interval fire damper (d)
Test hour fire damper (h)
Feedback fire damper
Fire damper
Status fire damper
Fire alarm
Smoke alarm
R
R
R
R
R
Read/Write Default value
W 90
W
W
1
0
Min/Max
0/300
0/7
0/24
Note d = day
5.8.6
Humidity control
[Application tool ► Ventilation ► Humidity control]
Read more about humidity control in
.
142 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Table 5-51 Setpoints for humidity control
Variable Read/Write Default value
Max limit humidity supply air (%rH) W 80
Neutral zone between humidification and dehumidification
Max deviation room/extract air humidity (%rH)
W
W
20
10
Digital output start point (%rH)
Digital output stop point (%rH)
Hysteresis for max limit humidity supply air (%rH)
W
W
W
15
5
20
Min/Max
0/100
0/100
0/100
0/100
0/100
0/100
Note
5.8.7
PID controllers
[Application tool ► Ventilation ► PID controllers]
Table 5-52 Setpoints for PID-control
Variable
Room controller
Extract air
Sequence A to J
Supply air fan
Read/Write
W
W
W
W
Extract air fan
CO2
Freeze protection 1, 2 and 3
Defrosting
Humidity
W
W
W
W
W
Default value Pband
Default value Itime (s)
100 °C
100 °C
10 °C
300
300
100
60 ✓ 500 Pa
✓ 1000 m 3 /h
(flow)
60 ✓ 500 Pa
✓ 1000 m 3 /h
(flow)
100 ppm
100 °C
16 °C
100 %rH
100
100
240
300
Default value D-time (s)
0
0
0
0
-
-
0
0
5.8.8
Energy consumption
[Application tool ► Ventilation ► Energy consumption]
SFP (Specific fan power)
Table 5-53 Setpoints for SFP
Variable
SFP (kW/m 3 /s)
SFP day average
SFP month average
Frequency converter loss
R
R
Read/Write Default value
R
R
Min/Max Note
Corrigo manual, Rev. D 143 (196)
Information for the specialist - Configuration
Power usage fans
The sum of power for all configured fans (SAF or EAF).
Table 5-54 Setpoints for power usage fans
Variable
Power usage fans (kW)
Read/Write Default value
R
Min/Max Note
Today and last 7 days
Total accumulated power usage for today and the last seven days.
Table 5-55 Setpoints for Today and last 7 days
Variable
Today (kWh)
Yesterday (kWh) R
1...6 days before yesterday (kWh) R
Read/Write Default value
R
Min/Max Note
This year
Total accumulated power usage for each month and total for the current year.
Table 5-56 Setpoints for This year
Variable
January (kWh)
February (kWh)
March (kWh) etc...
Total (kWh)
R
R
R
R
Read/Write Default value
R
Min/Max Note
Last year
Total accumulated power usage for each month and total for the previous year.
Table 5-57 Setpoints for This year
Variable
January (kWh)
February (kWh)
March (kWh) etc...
Total (kWh)
R
R
R
R
Read/Write Default value
R
Min/Max Note
144 (196) Corrigo manual, Rev. D
5.8.9
Manual / Auto
[Application tool ► Ventilation ► Manual/Auto]
Ventilation unit
Table 5-58 Settings for ventilation unit
Variable
Unit operation
Manual setpoint
Service stop
Standby mode
BMS override
Alternatives
✓ Off
✓ Manual
✓ Auto
✓ Low speed
✓ Normal speed
✓ High speed
✓ Stop
✓ Starting up
✓ Low/Normal/High speed
✓ Support heating
✓ Support cooling
✓ CO2 mode
✓ Free cooling
✓ Cool down mode
✓ Fire mode
✓ Smoke mode
✓ Recirculation mode
✓ Defrosting mode
✓ Inactive
✓ Active
✓ On
✓ Off
✓ Off
✓ Low
✓ Normal
✓ High
✓ Stop
✓ Stop with support control
✓ Free cooling
✓ Recirculation
Fan controls
Table 5-59 Settings for fan controls
Variable
Supply air fan
Alternatives
✓ Off
✓ Manual output
✓ Auto
✓ Manual setpoint
✓ Low speed
✓ Normal speed
✓ High speed
Manual setpoint (Pa, m3/ h, %)
Writable
Manual output (%)
Extract air fan
Writable
✓ Off
✓ Manual output
✓ Auto
✓ Manual setpoint
✓ Low speed
✓ Normal speed
✓ High speed
Corrigo manual, Rev. D
Information for the specialist - Configuration
Note
Note
145 (196)
Information for the specialist - Configuration
Table 5-59 Settings for fan controls (continued)
Variable Alternatives
Manual setpoint (Pa, m3/ h, %)
Writable
Manual output (%) Writable
Sequence A to J
Table 5-60 Settings for sequence A to J
Variable
Mode
Manual (%)
Actual value (%)
Alternatives
✓ Off
✓ Manual
✓ Auto
Writable
Read only
Sequence A to J analog
Table 5-61 Settings for sequence A to J analog
Variable
Mode
Manual set (%)
Controller output (%)
Alternatives
✓ Off
✓ Manual
✓ Auto
Writable
Read only
Note
Note
Note
Change-over 1 and 2, Supply air fan, Extract air fan, Humidity control, Step controller
1 and 2, Temperature output
Table 5-62 Settings for change-over, Supply air fan, Extract air fan, Humidity control, Step controller, Temperature output
Variable
Mode
Manual set (%)
Controller output (%)
Alternatives
✓ Off
✓ Manual
✓ Auto
Writable
Read only
Note
Sequence A to J start, Sequence A to J pump
Table 5-63 Settings for sequence A to J start and pump
Variable
Mode
Start
Alternatives
✓ Off
✓ Manual
✓ Auto
Read only
Note
146 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Supply and Extract air fan start/step 1, Supply and extract air fan step 2 and 3
Table 5-64 Settings for supply and extract air fan start/Step 1, step 2 and 3
Variable
Mode
Start
Alternatives
✓ Off
✓ Manual
✓ Auto
Read only
Note
Dampers
✓ Recirculation air damper
✓ Outdoor air damper
✓ Exhaust air damper
✓ Fire damper
Table 5-65 Settings for dampers
Variable
Mode
Start
Alternatives
✓ Off
✓ Manual
✓ Auto
Read only
Alarms
✓ Sum alarm 1
✓ Sum alarm 2
✓ Alarm output
Table 5-66 Settings for alarms
Variable
Mode
Start
Alternatives
✓ Off
✓ Manual
✓ Auto
Read only
Extra time channels 1…4
Table 5-67 Settings for extra time channels 1…4
Variable
Mode
Start
Alternatives
✓ Off
✓ Manual
✓ Auto
Read only
Note
Note
Note
Corrigo manual, Rev. D 147 (196)
Information for the specialist - Configuration
Free cooling indication
Table 5-68 Settings for free cooling indication
Variable
Mode
Start
Alternatives
✓ Off
✓ Manual
✓ Auto
Read only
Pretreatment start
Table 5-69 Settings for Pretreatment start
Variable
Mode
Start
Alternatives
✓ Off
✓ Manual
✓ Auto
Read only
Running indication
Table 5-70 Settings for running indication
Variable
Mode
Start
Alternatives
✓ Off
✓ Manual
✓ Auto
Read only
Note
Note
Note
Humidity control start
Table 5-71 Settings for humidity control start
Variable
Mode
Start
Alternatives
✓ Off
✓ Manual
✓ Auto
Read only
Note
Change-over 1 and 2 (Change-over 1 and 2 start)
Table 5-72 Settings for change-over start
Variable
Mode
Start
Alternatives
✓ Off
✓ Manual
✓ Auto
Read only
Note
148 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
Outdoor controlled exchanger
Table 5-73 Settings for outdoor controlled exchanger
Variable
Mode
Start
Alternatives
✓ Off
✓ Manual
✓ Auto
Read only
Note
5.8.10 Status
Status for the ventilation unit and sequences A to J.
Ventilation unit
Sequence A to J
✓ Actual mode
✓ Schedule mode
✓ External stop
✓ Extended operation
✓ Extended operation time left (min)
✓ Manual mode HMI
✓ Manual mode HMI time left (s)
✓ Free cooling mode
✓ Support control mode
✓ Night operation active last night
✓ Summer mode
✓ Fire alarm input
✓ Smoke alarm input
✓ Frost risk
✓ Internal alarm (alarm 194)
✓ Duplicated AO
✓ Duplicated DO
✓ Current configuration file
✓ Analog output (%)
✓ Start
✓ Pump
5.9 Additional function
[Application tool ► Additional function]
5.9.1
Extra controller
An extra controller (independent temperature control circuit) can be added to the Corrigo to control e.g. a separate zone. The controller can be configured to heating or cooling. All the setpoints for the extra controller are in this menu.
Read more about the extra controller in
Setpoints extra controller
Table 5-74 Actual/Setpoint
Variable
Temperature extra controller (°C)
Setpoint extra controller (°C)
Controller output (%)
Read/Write Default value
R
W
R
18
Min/Max Note
-20/150
Corrigo manual, Rev. D 149 (196)
Information for the specialist - Configuration
Table 5-75 Temperature control
Variable
Digital start output start point (%)
Digital start output stop point (%)
Pump stop delay (min)
Pump-kick hour (h)
Pump running when outdoor temperature < (°C)
W
W
W
W
Hysteresis to allow pump stop (°C) W
Read/Write Default value
W 10
1
5
15
10
1
Table 5-76 PID controller
Variable
P-band (°C)
I-time (s)
D-time (s)
Table 5-77 Manual/Auto
Variable
Controller mode
Alternatives
Manual set (%)
✓ Off
✓ Manual
✓ Auto
Writable
Writable Controller output (%)
Extra controller start mode
✓ Off
✓ Manual
✓ Auto
Read only Start
Extra controller pump mode
Start
✓ Off
✓ Manual
✓ Auto
Read only
Read/Write Default value
W 33
W 100
W 0
Min/Max
0/100
0/100
0/600
0/23
-20/150
0/10
Note
Min/Max
0/1000
0/9999
0/9999
Description
Note
5.9.2
Motor control 1 and 2
Table 5-78 Control
Variable
Stop delay motor control (min)
Read/Write Default value
W 0
Table 5-79 Manual/Auto
Variable
Mode
Alternatives
Motor
✓ Off
✓ Manual
✓ Auto
Read only
Min/Max
0/600
Note
Note
150 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
5.10 Inputs / Outputs
[Application tool ► Inputs/Outputs]
In this section, the values for all used Inputs and outputs are displayed.
For wireless sensors, the low battery indication and signal strength (RSSI) are displayed.
5.11 Time control
Corrigo has a year-based clock function. This means that a week-schedule with holiday periods for a full year can be set. The clock has an automatic summertime/wintertime change-over.
It has individual schedules for each weekday plus a separate holiday setting. Up to 24 individual holiday periods can be configured. A holiday period can be anything from one day up to 365 days. Holiday schedules take precedence over other schedules.
This menu displays time, date and weekday, and it permits the setting of time and date.
Time is shown in 24 hour format.
Date is shown in the format YY:MM:DD.
Figure 5-10 Time channels
Each day has up to four individual running periods. For three-speed fans and pressure controlled fans there are daily individual schedules for low speed, normal speed and high speed, each with up to four running periods.
Up to 4 digital outputs can be used as timer controlled outputs . Each with individual week-schedules with two activation periods per day. These outputs can be used to control lighting, door locks etc.( Configuration ►
Digital outputs ► Extra time channel 1…4 )
Corrigo manual, Rev. D 151 (196)
Information for the specialist - Configuration
In the time schedules, four periods are available for each day of the week. Also, four periods are available for days that are configured as holidays in the holiday schedule. During the periods the assigned circuit is working with the corresponding setpoint. Outside of a period the system is off.
On On
Off
B2
Figure 5-11 Time schedule
E2
Off
B1 E1
Off
Begin/End
The above figure shows an example of period states. It is not possible for periods to overlap each other.
Holiday schedules take precedence over other schedules.
✓ For 24 hour running, set a period to 00:00 - 24:00.
✓ To inactivate a period, set the time to 00:00 - 00:00. If all periods of a day are set to 00:00 - 00:00, the unit will not run that day.
✓ If you want to run the unit from one day to another, e.g. from Monday 22:00 to Tuesday 09:00, the desired running time for both must be entered.
speed, and normal speed takes precedence over low speed.
See more about Time control in
5.11.1 Extra time channels
Up to four digital outputs can be used as timer controlled outputs. Each with individual week-schedules with four activation periods per day.
Only the time channels which have been configured, i.e. have been wired to a digital output or an additional function, will be shown.
( Configuration ► Digital outputs ► Extra time channel 1…4 )
5.11.2 Holiday calendar
The system operator can define specific periods of operation or non-operation throughout the year. During these defined periods, the settings in the week schedule do not apply. The holiday calendar includes 24 periods. All holiday periods are working with a special day plan with a maximum of 4 periods.
A holiday period can be any number of consecutive days from 1…365. The dates are in the format: MM:DD.
152 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
5.11.3 Time settings in display and web interface
The times can also be set using the built-in display and the web interface, see
5.12 Alarm status
5.12.1 Alarm handling
Alarms are indicated by the red alarm LED on the front of the unit or on the external display (E3-DSP or
ED-T43L-V).
All alarms can be monitored, acknowledged and blocked using the display and buttons, via an external display (E3-DSP, ED-T43L-V ), via Application tool or via the web interface. There is also a digital input for acknowledging all alarms.
The alarm settings can be changed in Application tool or in the web interface.
Table 5-80 Inputs and outputs
Inputs and outputs
DI Alarm acknowledgement
5.12.2 Alarm configuration
The alarm configuration menu permits configuration of the priority for all alarms. A complete alarm list with default settings and actions, can be found in
Appendix D Alarm list . It contains all the default alarm texts and
priorities.
Priority
Alarms can be given different priority levels A-alarm , B-alarm and C-alarm or Not active . Digital outputs can be bound to act as alarm outputs for A-alarms or B/C-alarms or both A- and B/C-alarms. The digital outputs can be inverted, so that an inoperative alarm gives a high output and vice versa. A- and B- alarms must be acknowledged to reset. C- alarms automatically reset as soon as there is no longer a cause for alarm.
The alarm priority that is shown in the display in the event of an alarm can only be changed using
Application tool.
Alarm text
The alarm text that is shown in the display in the event of an alarm can be changed using Application tool or the web interface.
Stop function
Each alarm offers the possibility to choose whether an activated alarm should stop the controller or not. The controller can also be set to run at reduced speed during alarms. The latter option can only be configured using Application tool. Automatic restart will take place when the alarm has been acknowledged.
For some alarm types such as electric heating high temperature limit and water heating frost protection it would be dangerous to not stop the unit on alarm. Therefore, for such alarm types, the program will always reset the stop function to Active even if the operator should choose Inactive .
Corrigo manual, Rev. D 153 (196)
Information for the specialist - Configuration
Unfortunately it is not possible to remove the display text concerning the stop function for these alarm types. This is because the available program space demands that all alarms are treated in the same way in the display.
ttiivvee, or unexpected malfunctions may occur.
Sum alarm
There are two sum alarm functions with two digital outputs:
Inputs and outputs
DO
DO
Sum alarm 1
Sum alarm 2
The function of the outputs can be individually configured in Configuration ► Functions ► Extra indications & outputs .
Sum alarm outputs
None
A/B-alarm
A-alarm + B-alarm
A-alarm + B/C-alarm
DO Sum alarm 1
Not available
Active on A/B-alarm
Active on A-alarm
Active on A-alarm
DO Sum alarm 2
Not available
Not available
Active on B-alarm
Active on B/C-alarm
Alarm output
There is one alarm output function with configurable alarm connected to one digital output:
Inputs and outputs
DO Alarm output
External alarms
There are 11 possible external alarms. One digital input called External alarm and 10 digital inputs called
Extra alarm .
5.13 Starting and stopping the Corrigo
5.13.1 Start and stop conditions in priority
The unit will start and stop depending on the following conditions in this priority:
1. Service stop (only via display with admin authority)
2. Run in fire mode
3. Stop in fire mode
4. Run in smoke mode
5. Stop in smoke mode
6. Stop due to alarm
7. External stop (DI)
154 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
8. Low/normal/high speed due to alarm
9. Start high speed (DI)
10.Start normal speed (DI)
11.Start low speed (DI)
12.Start recirculation (DI)
13.External start/stop (via communication), support control (heat / cool / CO
2
) is enabled if external stop with support control is selected
14.Start recirculation (via communication)
15.Start free cooling (via communication)
16.Start/stop in manual mode (off, low, normal, high), manual mode, only one variable used in display,
Modbus, BACnet etc.
17.Start high speed via time channel
18.Start normal speed via time channel
19.Start low speed via time channel
20.Start support control (heat / cool / CO
2
) via normal start condition
21.Start recirculation via time channel
22.Start free cooling via normal start condition
Possibility to block automatic restart at power - on
The function Automatic restart at power-on makes it possible to block automatic restart of the unit at powerup. At power-up, the B-alarm Restart blocked after power on is generated.
Once this alarm has been acknowledged, the unit will start. ( Configuration ► Functions ► Function activation )
5.13.2 Start sequence
Start of the unit will run according to the following sequence:
1. If the controller is configured for water heating and has an outdoor temperature sensor and the outdoor temperature is below a configurable temperature (Full heat at start when outdoor temp is below, default: +3 ºC) the heating valve is opened and the heating circulation pump is started (sequence for heat start is configurable). ( Configuration ► Functions ► Sequence settings )
2. Signals for outdoor air and exhaust air dampers are activated.
3. If the controller is configured with a heat exchanger the heat exchanger will be run at 100% capacity
(sequence for normal start is configurable) for a pre-set time (Start delay with 100% exchanger, default
2 s). ( Ventilation ► Temperature control ► Exchanger )
4. The extract air fan or the pressure control of the extract air fan will be started after a preset time
(Extract air fan start delay, default 0 s).( Ventilation ► Fan control ► Extract air fan ► Start delay (s) )
5. The supply air fan or the control of the supply air pressure will be started after a preset time (Supply air fan start delay, default 60 s).( Ventilation ► Fan control ► Supply air fan ► Start delay (s) )
6. Thereafter temperature control according to the configured control mode is started. Electric heating, if configured, is not started until a run signal from the supply air fan or flow switch has been received.
And not yet activated pumps will be started.
7. When all fans and pumps is running and exchanger has run for a pre-set time a pre-set delay (Start alarm delay, default 60s) will be activated before the alarm handling system is activated and the unit is in normal running mode. ( Configuration ► Functions ► Alarms )
Corrigo manual, Rev. D 155 (196)
Information for the specialist - Configuration
5.13.3 Stop sequence
Stopping of the unit will run according to the following sequence:
1. Deactivation of the alarm handling system.
2. Electric heating, if configured, is shut down.
3. After individually set delay times the fans are stopped; Supply air fan stop delay (Default 180 s),
Extract air fan stop delay (Default 30 s) ( Ventilation ► Fan control ► Extract/Supply air fan ► Stop delay
(s) )
4. Outdoor air and exhaust air dampers are shut down. Outdoor air damper close delay: 0-300 seconds
(Default: 0 s), Exhaust air damper close delay: 0-300 seconds (Default: 0 s)( Ventilation ► Fan control ►
Extract/Supply air fan ► Stop delay (s) )
5. Actuator signals are set to zero and the pumps are stopped.
6. If shutdown mode (Frost protection when stopped) is configured, it will be activated.
exchanger will continue to run during the stop sequence until everything else is stopped
5.14 Changing the battery
The controller has an internal battery to ensure the operation of the memory and real-time clock in the event of a power failure. When the alarm Internal Battery is activated and the battery LED lights up red (24 V models), the battery has become too weak and needs to be changed. Nonetheless, due to a backup capacitor, the controller will function at least 10 minutes without power supply.
proper ESD protection. Therefore, this should be handled by qualified personnel.
An earthed wristband must be used during this procedure.
5.14.1 24 V models (Corrigo Ardo)
1. Remove the cover by pressing down the locking torques at the edge of the cover using a small screwdriver, and at the same time pulling the cover outwards.
156 (196) Corrigo manual, Rev. D
Information for the specialist - Configuration
2. Grip the battery firmly with your fingers and lift it upwards until it rises from its holder.
3. Press the new battery firmly down into place.
type CR2032.
5.14.2 230 V models (Corrigo Vido)
The 230 V models should not be opened by the user. Please contact Regin if you need to change the battery.
Corrigo manual, Rev. D 157 (196)