6 Information for the installer
6.1 Installation
6.1.1
Corrigo Ardo (24 V)
The controller can be mounted in a DIN-standard casing (minimum 9 modules), on a DIN-rail in a cabinet or, using a suitable front-mounting kit, in a cabinet door or other control panel.
Figure 6-1 Corrigo Ardo voltage.
instructions given in this manual.
Wiring examples Corrigo Ardo
For a complete list of terminals, see
The pictures below show examples for 24 V Corrigo Ardo
158 (196) Corrigo manual, Rev. D
Figure 6-2 Wiring example
Inputs and outputs 24 V Corrigo Ardo
There is a list of input and outputs in
Appendix C Input and output lists
that can be used to help you keep track of which inputs and outputs you need to configure.
Analog inputs
Analogue inputs must refer to an Agnd terminal.
Analogue inputs can, depending on the configuration, be used for either PT1000 / Ni1000 temperature sensors or for 0…10 V DC analogue input signals, for example from a pressure transmitter.
Digital inputs
Digital inputs must refer to +C on terminal 4. Digital inputs may only be wired to voltage-free contacts. Any external voltage applied to a digital input may harm the unit.
Universal inputs
A universal input can be configured to act as either an analogue input or as a digital input.
A universal input configured as an analogue input can, depending on the configuration, be used for either
PT1000 / Ni1000 temperature sensors or for 0…10 V DC analogue input signals, for example from a pressure transmitter.
Universal inputs configured as an analogue input must refer to an Agnd terminal.
A universal input configured as a digital input must, just like other digital inputs refer to C+ on terminal 4. It may only be wired to voltage-free contacts.
Corrigo manual, Rev. D 159 (196)
Analog outputs
Analogue outputs must refer to a Agnd terminal.
All analogue outputs can be individually set to any one of the following output signals:
✓ 0…10 V DC
✓ 2…10 V DC
✓ 10…0 V DC
✓ 10…2 V DC the same transformer pole is used as reference for all the equipment. The equipment may otherwise not function as intended and may also suffer damages.
Digital outputs
Digital outputs should normally refer to G
DO on terminal 10.
G
DO is internally connected to G on terminal 1 and supplies 24 V AC or DC depending on the choice of supply voltage.
All the digital outputs are controlled by MOSFET transistors. The outputs are internally connected with G
0 and can deliver max 2 A per output. However, the total power for all the DOs must not exceed 8 A.
A number of different wiring alternatives are possible depending on the type of supply voltage to the controller and the relay type.
Figure 6-3 24 V AC supply and 24 V AC relays
Figure 6-4 24 V DC supply and 24 V DC relays
160 (196) Corrigo manual, Rev. D
Figure 6-5 24 V AC supply and 24 V DC relays
Figure 6-6 24 V DC supply and 24 V AC relays
6.1.2
Corrigo Vido (230 V)
The controller can be mounted in a DIN-standard casing (minimum 9 modules), on a DIN-rail in a cabinet or, using a suitable front-mounting kit, in a cabinet door or other control panel. The 230 V ( Corrigo Vido) models can also be mounted directly on a wall.
Corrigo manual, Rev. D 161 (196)
8x Pt1000 / Ni1000
UI3
UI4
DI1
DI2
AO1
AI1
AI2
AI3
AI4
UI1
UI2
17
18
19
20
21
22
23
24
25
26
27 0..10V In/Out
AO2
Gnd
AO3
28
29
30
0..10V In/Out
0..10V Out / PWM*
31 B
MBUS*
32 A
N
N
L
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
DO7
DO6
DO5
DO4
DO3
DO2
DO1
TCP/IP E N
P1
A B ext.
Display
Figure 6-7 Corrigo Vido
* Depending on model voltage.
instructions given in this manual.
Inputs and outputs 230 V Corrigo Vido models
There is a list of input and outputs in Appendix C Input and output lists
that can be used to help you keep track of which inputs and outputs you need to configure.
Analog inputs
Analog inputs must refer to a ground, Gnd, terminal.
Analog inputs are intended for use with PT1000 / Ni1000 sensors as a temperature sensor.
Digital inputs
Digital inputs must refer to a ground, Gnd, terminal.
Universal inputs
A universal input can be configured to act as either an analogue input or as a digital input.
162 (196) Corrigo manual, Rev. D
A universal input configured as an analogue input can be used with PT1000 / Ni1000 temperature sensors.
A universal input configured as an analogue input must refer to a ground, Gnd, terminal.
A universal input configured as a digital input must refer to a ground, Gnd, terminal.
Universal analog
Universal analog I/O:s can be configured as either analog inputs or analog outputs.
Analog outputs must refer to a ground, Gnd, terminal. The outputs can be individually set to any one of the following output signals:
✓ 0…10 V DC
✓ 2…10 V DC
✓ 10…0 V DC
✓ 10…2 V DC
Digital outputs
The relays are voltage-free and must receive power from a single pole for each relay.
Figure 6-8
6.1.3
Expansion units EXOline
The communication between master and expansion units takes place via EXOline. The slave units will be assigned the address 241:1 and 241:2 during initialisation (PLA:ELA).
Corrigo manual, Rev. D 163 (196)
Figure 6-9 Expansion units EXOline
6.2 Commissioning
Before the controller can be used, inputs and outputs as well as a number of parameters must be configured.
All configuring must be done in Application tool that can be downloaded from http://www.regincontrols.
com or in the web interface.
6.2.1
Configuration using Application tool
Application tool is a PC-based, free configuration software tool, available at Regin's website www.
regincontrols.com
The tool is used to configure and commission the controller .
The controller doesn't need to be connected to the computer while configuring. All settings are made in the tool and then uploaded to the controller.
An infinite number of configurations can be stored in the computer memory for later use.
A communication cable is required in order to upload the configuration to the controller. The controller must also be powered up and the application selected in order for it to be configured.
Predefined configurations can be downloaded as atf-files from Regin’s website, www.regincontrols.com
.
These atf-files can be opened in the tool and synchronized to the controller.
6.2.2
Configuration in the web interface
When the Corrigo is connected to an external display or computer with a browser and a connection to the internet, an internal web interface will be shown. The web interface can be used to configure, change setpoints, and monitor the controller.
164 (196) Corrigo manual, Rev. D
Figure 6-10 Start screen for the web interface
6.3 Loading the application
Reset the controller by pressing the reset button, using for example a paper clip.
Figure 6-11 Resetting the controller
Corrigo manual, Rev. D 165 (196)
Load the application into the controller and commission. The application is loaded from Application tool.
In Application tool, go to the Tools menu at the top and select Reload controller .
166 (196) Corrigo manual, Rev. D