USER MANUAL MOTOR DRIVES

ACCESSORIES

12.4.2. Configuration

Protocol

Default Baud

Default Station ID

Fieldbus Port

Inverter Port

MetasysN2 MODBUS RTU

9600 8N1

11

38400 8N2

1

12.4.3. RS485 Connector

The communications port includes a positive pole (+), a negative pole (-) and the ground (G).

Figure 115: RS485 connector for Metasys ® N2

12.4.4. LEDs on the ASP485 ProtoCessor Module

BLUE

[L8] [L7]

COMMS

ORANGE

[L6]

RUN

[L5]

YELLOW

[L4] [L3]

NO DEFAULT

RED

[L2] [L1]

ERROR

LED COLOUR DESCRIPTION

L8

L7

L6

BLUE

BLUE

ORANGE

ON: Field Port packet received

OFF: Field Port response sent

ON: Inverter Port Send Poll

OFF: Inverter Port Receive Valid Response

ON (flashing 2Hz) : ProtoCessor is running normally

OFF: ProtoCessor is not running

L5 ORANGE Not Used

L4

L3

L2

L1

YELLOW

YELLOW

RED

RED

ON: MODBUS Slave address set by DIP-switch

OFF: MODBUS Default Address at factory default = 11

ON: Baud Rate set by DIP-switch

OFF: Baud Rate at factory default = 9600

ON: Bad Poll, No Map Descriptor found

OFF: Once Exception response has been sent [*]

ON: Panic

OFF: No Panic has occurred

[*] If you receive a poll for data that does not exist, you turn that LED on briefly.

Basically, the system received a valid poll, but could not find a corresponding data point.