Additional Installation Tips
6.5 Cable and Bus Termination RS-485
•
•
•
If maximum transfer distance and maximum transfer speed is needed, shielded and twisted pair cable should be used. The mutual capacitance may not exceed 52.5 pF/m, and the cable area should be at least 0.25 mm 2
(AWG 24).
0 V, the reference voltage for communication should be included in the cabling. With two-way communication use two pairs; one pair for communication and one pair for 0 V.
The shield must be grounded at one end. The other end is usually grounded, but with longer distances or when there is a difference in the ground potential, the shield should be connected to the ground via 0.1 μF/250 V film capacitor to prevent ground current in the braided shield. A number of manufacturers recommend that the shield be grounded at each node. Various manufacturers have different systems for bus termination.
Depending on the recipients’ design, the bus wires may be on the same level or require pull-up or pull-down to ensure that no faulty signals are detected when the bus is in resting mode (all transmitters are disconnected).
Beijer Electronics, MAEN276 27
Head office
Beijer Electronics AB
Box 426
201 24 Malmö, Sweden www.beijerelectronics.com / +46 40 358600
advertisement
Related manuals
advertisement
Table of contents
- 7 1 Safety Precautions
- 7 General
- 7 Hazardous Materials
- 8 Disposal Requirements Under WEEE Regulations
- 8 UL and cUL Installation
- 9 IECEx/ATEX Certificate and Dust Rating
- 9 Conditions of Safe Use for Zone 2/22 ATEX/IECEx
- 9 During Installation
- 10 During Use
- 10 Service and Maintenance
- 10 Dismantling and Scrapping
- 11 2 Installation
- 11 Installation Process
- 13 Protective Connector Shield Installation Process
- 14 Connections to the Controller
- 14 Other Connections and Peripherals
- 15 3 Technical Data
- 17 4 Chemical Resistance
- 17 Metal Casing
- 19 5 Operator Panel Drawings
- 19 Connectors
- 19 Power Supply
- 19 COM A
- 20 LAN A / LAN B
- 20 COM B
- 21 BoX2 extreme Outline
- 23 6 Additional Installation Tips
- 23 Grounding the operator panel
- 23 To Achieve Better EMC Protection
- 25 Safety
- 26 Galvanic Isolation
- 27 Cable and Bus Termination RS