Mounting the Module in a PLC Station Rack. Schneider Electric TSX / PMX / PCX 57 PLCs, Hardware
Mainos
Mainos
General Setup Rules
Mounting the Module in a PLC Station Rack
Introduction The TSX CCY 1128 module can be mounted in any of the available slots in a TSX
RKY •• rack on a TSX 57/PMX 57/PCX 57 PLC station, except for the slots specifically for the power supply and processor modules.
Illustration The diagrams below show the procedure for mounting a module from the Premium range in the TSX RKY •• rack.
3
2
1
Procedure The following table describes the operations to be performed:
2
3
Step
1
Operation
Position the pins on the rear of the module in the locating holes at the bottom of the rack.
Rotate the module to bring it into contact with the rack.
Attach the module to the rack by tightening the screw at the bottom of the module. Maximum tightening torque for the screw: 2.0 N.m
10