Encoder Input Specifications. Schneider Electric TSX / PMX / PCX 57 PLCs, Hardware
广告
广告
Electrical Specifications of the Module
General Specifications
Table of General
Specifications of the Module
The following table gives the general specifications of the module.
Description of parameter
Current consumption of the module
Value
Typical
0.66 A On internal 5V
(with module internal fan running)
On sensor/ preactuator 24 V
(auxiliary inputs and track outputs)
15 mA
On 10...30V
(when using an SSI absolute encoder and single 24V power supply)
11 mA
Maximum
1 A
18 mA
20 mA
Power dissipated in the module
Sensor/preactuator supply monitoring
7 W (1)
Yes
10 W (2)
Insulation resistance > 10 MOhms at 500 VDC
Dielectric strength with ground or PLC logic 0V 1000V rms - 50/60 Hz for
1 min
Operating temperature
Storage temperature
Relative humidity (without condensation)
Operating altitude
0 to 60°C
-25°C to 70°C
5% to 95%
0 to 2000 m
(1) Under normal operating conditions: one auxiliary input active, 24 VDC supply voltage, standard RS 422 signals.
(2) Under extreme operating conditions: 100% of auxiliary inputs active, 30 VDC supply voltage, etc.