Precautions for Safe Use . Omron NB-series NB7W-TW00B, NB-series NB5Q-TW00B
Anúncio
Anúncio
Precautions for Safe Use
● When unpacking the NB Units, check carefully for any external scratches or other damage.
Also, shake the Units gently and check for any abnormal sound.
● The NB Unit must be installed in a control panel.
● The mounting panel must be between 1.6 and 4.8 mm thick. Tighten the Mounting Brackets evenly to a torque of between 0.5 and 0.6 N·m to maintain water and dust resistance. If the tightening torque exceeds the specified value, or the tightening is not even, deformation of the front panel may occur. What is more, make sure the panel is not dirty or warped and that it is strong enough to hold the Units.
● Do not let metal particles enter the Units when preparing the panel.
● Do not connect an AC power supply to the DC power terminals.
● Use a DC power with a slight voltage fluctuation and that will provide a stable output even if the input is momentarily interrupted for 10 ms.
Rated Power Supply Voltage: DC 24 V (Allowable range DC 20.4~27.6 V)
● Do not perform a dielectric voltage test.
● Making the connection by using terminal screws crimping on a twisted-pair cable with a crimping range of 12~26 AWG, and only 6.5 mm of insulation peel of the cable needs to be peeled off.
Tighten the terminal screws to a torque of between 0.3 and 0.5 N·m. Make sure the screws are properly tightened.
● To prevent malfunctions caused by noise, ground the Unit correctly.
● Do not touch the packaging part of the circuit board with your bare hands. Discharge any static electricity from your body before handling the board.
● When using the No. 6 pin of the serial communication port COM1 connector for a voltage of DC+5V, make sure the supply equipment's current capacity is below 250mA before using it. The DC+5V voltage output of the NB Unit is +5V±5%, and the maximum current is 250mA.
● Turn OFF the power supply before connecting or disconnecting cables.
● Always keep the connector screws firmly tightened after the communication cable is connected.
● The maximum tensile load for cables is 30 N. Do not apply loads greater than this.
● Confirm the safety of the system before turning ON or OFF the power supply,
or pressing the reset button.
● The whole system may stop depending on how the power supply is turned ON or OFF. Turn
ON/OFF the power supply according to the specified procedure.
● Reset by pressing the reset button, or restart the power supply, once the DIP switch settings are changed.
● To ensure the system’s safety, make sure to incorporate a program that can confirm the normal functionality of the NB Unit before running the system.
● Start actual system application only after sufficiently checking screen data, macros and the operation of the program at the host side.
● Don’t press the touch panel with a force greater than 30 N.
● Do not use a screwdriver or any other tool to press the touch panel.
● Confirm the safety of the system before pressing the touch panel.
● Signals from the touch switches may not be input if the touch switches are pressed consecutively at high speed. Confirm that the PT has detected the input of a touch switch before pressing any other touch switch.
● Do not accidentally press the touch panel when the backlight is not lit or when the display does not appear. Make sure of the safety of the system before pressing the touch panel.
11
● To use numeric input functions safely, always make maximum and minimum limit set- tings.
● Before initializing screen data, confirm that existing data is backed up at the NB-Designer.
● When changing the password with the system menu, do not reset or turn OFF the power supply until writing is finished. Failure to save the password may cause the screen to fail to function.
● When using an equipment monitor, confirm the safety of the system before carrying out the following operations: y Changing monitor data; y Changing operation mode; y forced y Changing the current value or the set value;
● Do not connect a USB connector to any device that is not applicable.
● Before connecting a USB connector to a device, make sure that the device is free of damage.
● Commercially available and the recommended USB HUBs are different from the general specifications of the NB Unit. The Unit may not function well in an environment subject to noise, static electricity. Therefore, when using a USB HUB, employ sufficient noise and static electricity insulation measures, or install it at a site free of noise or static electricity.
● While downloading or uploading screen data or system programs, do not perform the following operations that may corrupt the screen data or the system program: y Turning OFF the power supply of the NB Unit. y Pressing the PT’s reset switch.
● Dispose of the Units and batteries according to local ordinances as they apply.
● When exporting products with lithium primary batteries containing perchlorate at 6ppb or above to or delivering them through California, USA, the following precautionary measures have to be publicized.
Perchlorate material – applicable through special processing. Refer to http://www.dtsc.ca.gov/hazardouswaste/perchlorate
NB-Series products contain lithium primary batteries. When exporting products containing this kind of batteries to or delivering them through California, USA, label all the product packages as well as the appropriate delivery packages.
● Do not use benzene, paint thinner, or other volatile solvents, and do not use chemically treated cloths.
● Do not dispose the Units together with general waste at waste yards. When disposing them, follow the related local ordinances or rules.
● Customers may not replace the backlight lamp inside the NB Unit. Please contact OMRON’s customer service center.
● Deterioration over time can cause the touch points to move. Calibrate the touch panel periodically.
● Water and oil resistance will be lost if the front sheet is torn or is peeling off. Do not use the Unit, if the front sheet is torn or is peeling off.
● The rubber packing will deteriorate, shrink, or harden depending on the operating environment.
Inspect and replace the rubber packing periodically.
● The communication cables of the COM1 and COM2 connectors are not interchangeable. Confirm the pins of the ports before carrying out communications.
● Periodically check the installation conditions in applications where the PT is subject to contact with oil or water.
12