Chapter 1 – Introduction. ABB POWER LEADER PMCS Network Architecture
Add to My manuals80 Pages
advertisement
Power Management Control System
Chapter 1 – Introduction
Chapter 1 – Introduction
1–1 Typical Systems
The PMCS software is capable of operating on either of two platforms:
1. PMCS running on a Modbus-based host PC, or
2. PMCS running on an Ethernet-based host PC.
Determine where the PMCS will be based using the following flowchart:
Should I base my host PC on Modbus or Ethernet?
Figure 2 shows a Modbus and Ethernet network.
Figure 3 shows a Modbus/commnet network.
Figure 4 shows an Ethernet/Modbus/commnet network, demonstrating the integration of all three protocols.
Figure 5 shows an example of an Ethernet-based host servicing native Ethernet devices, Modbus devices via the
Ethernet Gateway, and Commnet devices via the Modbus
Concentrator device.
NOTE:
Some types of IEDs must be wired on dedicated private serial network segments, one
IED per serial Modbus line. Figure 2a illustrates this configuration. The IEDs that require dedicated Modbus segments are the EPM 9650Q,
EPM 3720, ML PQM, and EPM 7330.
Is there an existing
Ethernet or plans for a future Ethernet?
No
Base PMCS on Modbus.
Yes
Base PMCS on Ethernet.
After you determine the appropriate base (Ethernet or
Modbus) for the PMCS software, the general network architecture will fall into one of the forms illustrated in
Figures 1 through 4. These figures offer samples of various network architecture configurations possible with PMCS.
Protocols Utilized
Ethernet
Direct
Modbus via
Ethernet
Modbus
Direct
Commnet
Figure 1
Figure 2
Figure 3
Figure 4
Figure 5 ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
As the above table shows, Modbus RTU is required in all instances, whether it is being used as a stand-alone network, supporting commnet IEDs, or serving as a slave to an Ethernet-based host.
Figure 1 presents the Power Management Control System operating on a Modbus-only network.
Figure 1. Modbus-only network.
H o st o th er
PC
...
Ethernet
...
Ethernet
G ate w ay
...
M o dbus
M ultilin
565
EPM
3720
PLC
90/70
PLC
90/30
M ultilin
269+
...
Figure 2. Commercial Ethernet and Modbus network.
3
Power Management Control System
Chapter 1 – Introduction
Figure 2a. Substation Ethernet and Modbus network.
Figure 5. Ethernet-based host services Ethernet, Modbus, and commnet networks.
Figure 3. Modbus and commnet network.
H o st
...
Ethernet
Ethernet
G ate w ay
...
M o dbus
C o m m n et
M o dbus
C o ncent rator other
PC
EPM
3720
M ultilin
269+
...
PLC
90/30
...
C o m m n et d evice s
Figure 4. Ethernet, Modbus, and commnet network.
1–2 Master-Slave Organization
The PMCS in either a Modbus-host or an Ethernet-host configuration is a master-slave network. The host is considered to be the master, with the attached networks of
IEDs serving as its slaves.
This relationship means that the communications are always initiated at the host; an IED will not speak without being asked to. The master requests information, the slave replies.
The PMCS DDE Server receives a request from a client application for some data, perhaps a relay waveform capture. The Server routes the request to the correct IED, the IED replies to the Server, and the Server passes the information back to the client that originally requested it.
For further details, refer to the PMCS Network and Device
Configurator DDE Server User’s Guide
, GEH-6510.
4
Power Management Control System
Chapter 1 – Introduction
1–3 Required Hardware
Several pieces of hardware are required to build a network based on PMCS. They are the host computer and the network interface card, each of which is described below.
Once the host computer is operating and its interface card is installed, it is time to attach the power management
IEDs to the network. These IEDs are described in Section
1–8.
Host Computer
The heart of the PMCS is software running on a host PC.
Regardless of whether the host PC is based on an Ethernet or Modbus network, its functions include the following:
• Communication management
• Primary user interface
• Data collection, storage, and retrieval
• Event reporting with time and date stamp
• Energy calculations and trending
• Network IED status
• Alarming and reporting
The minimum requirements for the host PC are presented in GEH-6514, Read This Book First.
Ethernet Network Card
The Ethernet network card provides the interface between the host PC and the Ethernet network. With the host communicating over Ethernet, another interface is required to communicate with RS-485 networks, where most power management IEDs reside. (Some recent power management IEDs, such as the EPM 7700, have built-in
Ethernet capability. Install these devices using standard
Ethernet networking procedures.)
This interface between Ethernet and RS-485 is provided by the Ethernet Gateway. See Section 1–4 for more information on Ethernet, and Section 1–1, Figures 2 and
4, for examples of how the Ethernet Gateway is used to integrate RS-485 networks into the Ethernet network.
1–4 Compatibility & Interconnection with Existing
Ethernet Networks
PMCS and the Ethernet Gateway require TCP/IP to be installed on the host computer. The drivers for the
TCP/IP protocol are included with Windows 2000 SP2, which is required to run PMCS, so any customer running
PMCS should have these drivers available.
Consult your LAN personnel or system integrator for information on integrating PMCS with an existing
Ethernet-based network.
The communications interface is the connection between the host PC and the network of IEDs. Your host will require either an Ethernet communications card, an RS-
485 communications card, or an RS-232/RS-485 converter.
An Ethernet-based host PC requires an Ethernet network card. A Modbus-based host PC requires an RS-485 interface card or an RS-232/RS-485 converter. These are described below.
RS-485 Interface Card or RS-232/RS-485 Converter
The RS-485 interface card provides the interface between the host PC and the Modbus network and terminates the network at the host computer. This standard RS-485 interface card provides eight RS-485 ports. PMCS supports up to 256 RS-485 communication ports. See Sections 2–1,
2–4, and 2–7 for more details on using multiple RS-485 networks with PMCS.
For more modest needs, a single RS-485 network can be provided by an RS-232/RS-485 converter, a self-contained
IED that converts signals between RS-232 and RS-485. This
IED plugs into the RS-232 port on the back of the host PC and is less expensive than an RS-485 interface card.
1–5 Operation During Power Outage
PMCS will not lose any data in the event of a power outage; however, communications will be interrupted until power is restored.
Should control power to a Modbus Concentrator be lost,
PMCS will be unable to communicate with any commnet
IEDs downstream from the Concentrator until power is restored. No data will be lost, but communications will be interrupted.
The same is true of the Ethernet Gateway; as the linchpin connecting the host to the network of IEDs, if a Gateway loses control power, the host will be unable to communicate with any IEDs attached to the Gateway until power is restored.
You can avoid this situation by providing uninterruptable power supplies (UPS) to the host computer and by providing secure control power to the IEDs, either with
UPS systems or battery backups (different IEDs have different requirements). Refer to individual user guides for information on control-power requirements.
5
Power Management Control System
Chapter 1 – Introduction
1–6 Time & Date Stamping
PMCS stamps each event with a time and date code for precise reference. The time and date are set by the DDE
Server and passed across the network to each IED, so that all IEDs are synchronized.
Additionally, some PMCS IEDs support IRIG time synchronization. If IRIG is used in a PMCS system, it is recommended that the host PC be IRIG time synched as well to maintain synchronization between the IEDs and the PMCS DDE Server.
1–7 Remote System Operation
PMCS also offers the ability to use modems to reach across wide areas to remote facilities or substations. For instance, you could use PMCS at a central location to collect power management data from IEDs in a factory, warehouse, or substation in another state or control the lights, air conditioning, or protective relays in your facility from across the country.
An example of this scenario is shown in Figure 5.
Host
RS-485 wiring
Modbus device
RS-232/RS-485
Converter
RS-232 wiring
Mo de m
Radio Frequency transmission,
Fiber optic connection,
Leased line or phone line connection
...
RS-485 wiring
Mo de m
RS-232 wiring
RS-232/RS-485
Converter
Modbus device
Figure 6. Example of remote operation using modems.
56kbps phone modems, radio frequency (RF) modems, and fiber optic modems (FOM) may be used with PMCS.
While it is possible to use dial-up lines to connect to distant
RS-485 networks, the vagaries of the phone system and the excessive long-distance charges preclude using this as a twenty-four-hour-a-day connection. Leased lines dedicated to this purpose provide a viable alternative to a constant long-distance telephone connection.
For further information on using modems for long-range operation of PMCS, contact your GE sales representative.
6
Power Management Control System
Chapter 1 – Introduction
1–8 Supported IEDs
PMCS supports a wide variety of GE and third-party power management IEDs. These IEDs are listed in
Table 1, along with their function, communications
protocol, and maximum communications speed for
Modbus-based IEDs (Commnet IEDs must communicate through the Modbus Concentrator).
239 Motor Protection Relay
269 Plus Motor Management Relay
565 Feeder Management Relay
735 Feeder Relay
GE-Zenith Generator PLC (Series 90-70)
GE-Zenith MX200 (Microprocessor Controller)
EPM 7330
EPM 3710 Meter
EPM 3720 Meter
EPM 7300 Meter
EPM 7700 Meter
EPM 5000P Meter
EPM 5200P Meter
EPM 5300P Meter
EPM 5350P Meter
EPM 9450Q Meter
EPM 9650Q Meter
GE Fanuc PLC 90/30
GE Fanuc PLC 90/70
GE Fanuc PLC Micro 90
Universal Relay
MicroVersaTrip-C and -D Trip Units
Modbus Concentrator
POWER LEADER Electronic Power Meter
POWER LEADER Junction Box
POWER LEADER Repeater
Power Quality Meter (PQM)
Function
Protection/Control
Protection/Control
Protection/Control
Protection/Control
Metering/Control
Protection/Control
Metering
Metering
Metering
Metering
Metering/Control
Metering
Metering
Metering
Metering
Metering/Control
Metering/Control
Protection/Control
Protection/Control
Protection/Control
Protection/Control
Metering/Protection
Communications
Metering
Communications
Communication
Metering
Communications Protocol (Modbus Speed)
Modbus RTU (19.2 Kbaud)
Modbus RTU (2400 baud)
Modbus RTU (9600 baud)
Modbus RTU (19.2 Kbaud)
Modbus RTU (19.2 Kbaud)
Modbus RTU (19.2 Kbaud)
Modbus RTU (19.2 Kbaud)
Modbus RTU (19.2 Kbaud)
Modbus RTU (19.2 Kbaud)
Modbus RTU (19.2 Kbaud)
Modbus RTU (19.2 Kbaud)
Note: Native Ethernet device.
Modbus RTU (9600 baud)
Modbus RTU (9600 baud)
Modbus RTU (9600 baud)
Modbus TCP (Ethernet 10BaseT, RJ-45)
Modbus RTU (38.4 Kbaud)
Modbus TCP (Ethernet 10BaseT, RJ-45)
Modbus RTU (38.4 Kbaud)
Modbus TCP (Ethernet 10BaseT, RJ-45)
Modbus RTU (19.2 Kbaud)
Modbus RTU (19.2 Kbaud)
Modbus RTU (19.2 Kbaud)
Modbus RTU (19.2 Kbaud) commnet (requires Modbus Concentrator)
Modbus RTU (19.2 Kbaud)
Modbus (19.2 Kbaud) or commnet
(commnet requires Modbus Concentrator) commnet (requires Modbus Concentrator) commnet (requires Modbus Concentrator)
Modbus RTU (19.2 Kbaud on 1 or 2 ports)
7
Power Management Control System
Chapter 1 – Introduction
RS-485 Repeater
369 Motor Management Relay
EPM 7500 Electronic Power Meter
EPM 7600 Electronic Power Meter
Motor Manager II (MMII)
EPM7430D/EPM7450D (Futura)
Spectra Electronic Control Module
Spectra MVT for GEK Frame MCCB
SR469 Motor Management Relay
SR489 Generator Management Relay
SR745 Transformer Management Relay
SR750 Feeder Management Relay
SR760 Feeder Management Relay
POWER LEADER MDP Overcurrent Relay
POWER LEADER Modbus Monitor
POWER LEADER Meter
Function
Communications
Metering/Control
Protection/Control
Protection/Control
Protection/Control
Protection/Control
Protection
Metering/Protection
Protection/Control
Protection/Control
Protection/Control
Protection/Control
Protection/Control
Protection
Monitoring
Metering
Communications Protocol (Modbus Speed)
Modbus RTU (19.2 Kbaud)
Modbus RTU (19.2 Kbaud)
Modbus RTU (19.2 Kbaud)
Modbus RTU (19.2 Kbaud)
Modbus RTU (19.2 Kbaud)
Modbus RTU ( 9600 baud) commnet (requires Modbus Concentrator) commnet (requires Modbus Concentrator)
Modbus RTU (19.2 Kbaud on 1 or 2 ports)
Modbus RTU (19.2 Kbaud on 1 or 2 ports)
Modbus RTU (19.2 Kbaud on 1 or 2 ports)
Modbus RTU (19.2 Kbaud on 1 or 2 ports)
Modbus RTU (19.2 Kbaud on 1 or 2 ports)
Modbus (19.2 Kbaud) or commnet
(commnet requires Modbus Concentrator)
Modbus RTU (19.2 Kbaud on 1 or 2 ports) commnet (requires Modbus Concentrator)
Table 1. IEDs supported by PMCS.
2 The POWER LEADER Ethernet Gateway is not listed in Table 1. The Ethernet Gateway is an alternate host for the RS-485 networks used when the
PMCS resides on the Ethernet level.
8
advertisement
Related manuals
advertisement
Table of contents
- 11 Welcome to PMCS!
- 11 What is Power Management?
- 11 Benefits of Power Management
- 11 What is PMCS?
- 12 How Does PMCS Work?
- 12 Using This Guide
- 13 Chapter 1 – Introduction
- 13 1–1 Typical Systems
- 14 1–2 Master-Slave Organization
- 15 1–3 Required Hardware
- 15 Host Computer
- 15 RS-485 Interface Card or RS-232/RS-485 Converter
- 15 Ethernet Network Card
- 15 1–4 Compatibility & Interconnection with Existing Ethernet Networks
- 15 1–5 Operation During Power Outage
- 16 1–6 Time & Date Stamping
- 16 1–7 Remote System Operation
- 17 1–8 Supported IEDs
- 19 Chapter 2 – Network Design
- 20 2–1 Modbus Rules
- 21 2–2 Ethernet Configuration Rules
- 22 T
- 22 Table 3. Ethernet configuration rules2–3 Ethernet Network Considerations
- 23 10Base-T specifications and rules
- 23 10Base-FL specifications and rules
- 24 2–4 Commnet Configuration Rules
- 25 2–5 Modbus Wiring Rules – Diagrams
- 29 2–6 Commnet Wiring Rules – Diagrams
- 31 2–7 Performance Recommendations
- 31 The Ideal Network
- 31 Modbus performance recommendations
- 31 Commnet performance recommendations
- 31 2–8 Addressing the IEDs
- 35 2–9 Multiple RS-485 Networks – Addressing
- 35 2–10 System Expansion
- 35 2–11 Case Studies
- 35 Case Study One
- 37 Case Two
- 39 Case Three
- 40 Case Four
- 43 Case Five
- 47 Chapter 3. Network Wiring and Construction
- 48 3–1 Wiring Requirements
- 49 Type of Wire
- 49 Termination
- 49 Shield Grounding
- 49 3–2 Modbus – Commnet Integration
- 49 Wiring Concerns
- 51 3–3 Modbus – Ethernet Integration
- 51 3–4 Local Configuration of IEDs
- 51 3–5 Applying Power to the System
- 51 3–6 Software Loading and Startup
- 52 Chapter 4 –Trouble-Shooting
- 52 4–1 Communication Network Trouble-Shooting
- 53 4–2 Host Trouble-Shooting
- 53 4–3 IED Trouble-Shooting
- 53 4–4 Equipment Trouble-Shooting
- 53 4–5 Product Service Procedure
- 54 4–6 Trouble-Shooting Guide
- 59 Overview
- 59 239 Motor Protection Relay
- 59 269+ Motor Management Relay
- 60 565 Feeder Management Relay
- 60 735 Feeder Relay
- 61 MX200 (Microprocessor Controller)
- 61 Generator PLC (Series 90-70)
- 61 Electronic Power Meter EPM 7330