Chapter 3. Network Wiring and Construction. ABB POWER LEADER PMCS Network Architecture

Add to My manuals
80 Pages

advertisement

Chapter 3. Network Wiring and Construction. ABB POWER LEADER PMCS Network Architecture | Manualzz

Power Management Control System

Chapter 3 – Network Wiring and Construction

Chapter 3. Network Wiring and

Construction

Once the network has been carefully laid out on paper and IED addresses have been planned, you need to check the following wiring requirements before beginning assembly of the system.

WARNING:

Network wiring and grounding rules described herein apply primarily to commercial and industrial installations. Substation installations will exist in the presence of dangerously elevated ground potential relative to points outside of the station grid as well as large electromagnetic induction fields. Additionally, large ground faults can elevate substation ground potentials. Follow local utility best-practices and safety procedures to prevent risk of shock or electrocution to personnel and damage to equipment that could result in a loss of protection and communications.

CAUTION:

The recommended installation practice is to implement optical fiber for connections between buildings to provide electrical isolation. This eliminates harmful ground loops caused by differences in the ground potential between structures.

CAUTION:

Data line surge protection is recommended for network components such as hubs, computers, or modems connected to IEDs with copper wire, especially installations where the data communication cable is exposed (i.e., not encased in conduit) or runs parallel to power conductors. PMCS IEDs are routinely installed in areas exposed to heavy electromagnetic fields (EMF), which can induce damaging surges in data communication lines. Data line surge protection is not required for fiber optic connections.

37

Power Management Control System

Chapter 3 – Network Wiring and Construction

3–1 Wiring Requirements

Each type of network (Ethernet, Modbus, and commnet) has unique wiring requirements. These rules are

summarized in Table 13. Further detail is provided

following the table.

WARNING:

The National Electrical Code (NEC) and all applicable local codes must be followed when installing wiring.

Network Wiring Required

Ethernet 10Base-T or 10Base-FL

CAT-3, 4, or 5 UTP, Rated 300V. A 600V requirement may be satisfied by applying

600V tubing to the cable.

Modbus

Indoors/outdoors in conduit above grade

Belden 3074F – Data Tray 600 V industrial twinax 18 AWG (7X26); or

Belden 9841 – 300 V Communication cable

24 AWG (7X32); or

Alpha 6412 – 300 V Communication cable

24 AWG (7x32).

NOTES:

Use one of the above approved cables that meet the NEC and UL requirements for the application. A 600 V requirement may be satisfied by using the

Belden 3074F or by applying 600 V tubing to either the Belden 9841 or Alpha 6412. No substitutions are permitted.

Commnet Indoors/outdoors in conduit above grade

Belden 8719 – 600 V shielded instrumentation cable, 16 AWG (19X29).

Shield Grounding Termination

See 10Base-T or 10Base-FL wiring standards. Check with your LAN administrator.

See 10Base-T or 10Base-FL wiring standards. Check with your LAN administrator.

Each commnet segment’s cable shield must be grounded at the Modbus

Concentrator at the port to which it is connected.

N/A: no termination is needed on commnet segments.

Below-grade applications

5

Belden 83702.

Each RS-485 network should be grounded at the host and at the RS-485 OUT port of each IED, with no continuity between wire-segment shields. (See Section 2–4, rule 4)

The RS-485 cables must be terminated at each end of the network. The terminator should be a 120-ohm,

1/2

-watt resistor, 5%. (See section titled

Termination in this chapter for specific details on Connect

Tech RS-485 card and

Ethernet Gateway.)

Table 13. Wiring requirements.

5

Belden 83702 is rated for direct burial and air plenum, non-conduit applications, but the length limits for this cable are two-thirds of the lengths specified in the configuration rules of Chapter 2.

38

Power Management Control System

Chapter 3 – Network Wiring and Construction

Type of Wire

Ethernet

10Base-T applications may use any appropriate Category 3,

4 or 5 UTP cable, provided it is rated at least 300V.

Category 3 cable is sufficient for 10 Mbps applications such as PMCS. Category 5 cable supports 100 Mbps network applications. Category 4 cable is not widely available, having been superseded by Category 5 cable in the marketplace. Any of these cables may be used in 600 volt applications by applying 600V tubing to the cable.

Modbus

Belden 9841 or Alpha 6412 may be used for applications under 300 V that are indoors or outdoors in conduit above grade. These cables may be also be used for 600 V requirements by applying 600 V tubing to them. Belden

3074F may be used for applications greater than 300 V which are indoors or outdoors in conduit above grade.

Commnet

Belden M8719 shielded instrumentation cable #16 AWG wire (shielded, twisted-pair) is recommended for commnet wiring for applications indoors or outdoors in conduit above grade.

For below-grade applications, Belden 83702 shielded 16

AWG cable is recommended. Belden 83702 is rated for direct burial and air plenum, nonconduit applications, but the length limits for this cable are two-thirds of the lengths specified in the configuration rules of Section 2-1.

For example, a network segment connecting up to four IEDs may have a total cable length of no more than 667 feet of Belden 83702, versus the 1000-foot limit on total cable length for Belden 8719.

for its four RS-485 ports. No terminating resistor is needed at the POWER LEADER Ethernet

Gateway.

See Figure 9 for an example of the cable run terminated at

the final IED on the network.

Shield Grounding

Modbus

The RS-485 cable shield must be grounded at only a single point on each RS-485 wire. Connect the shield to the ground terminal at the Ethernet Gateway or RS-485 interface card. Connect the cable shield to the shield terminal at each IED on the RS-485 network except the

Multilin 565, which does not have isolated communication ports (Modbus Rule 5, Section 2–4).

Commnet

The commnet cable shield must be grounded at only a single point in each commnet segment. This is done at the

POWER LEADER Modbus Concentrator. Each commnet port on the Modbus Concentrator has a ground terminal, and each commnet segment should be grounded at the port to which it is connected.

Figure 28 shows a POWER LEADER Modbus Concentrator

connected to a series of commnet IEDs. The shield of the cable to the downstream IEDs is grounded at the Modbus

Concentrator on its internal shield-ground terminal strip.

Termination

RS-485 cables must be terminated at each end of the network with a 120-ohm,

1/2

-watt, 5% tolerance resistor.

3–2 Modbus – Commnet Integration

The rules regarding the number of IEDs per Modbus

Concentrator and wiring-distance limits are explained in

Chapter 2. The rules expressed in this section are more low-level and concern the physical connections of commnet IEDs to a Modbus Concentrator. You must follow these rules to provide for proper shielding and communications.

IMPORTANT NOTE FOR CONNECT TECH

CARD USERS:

The Connect Tech RS-485 card recommended for use with PMCS systems requires a 600-ohm rather than a 120-ohm resistor. Use the 600-ohm resistor at the Connect

Tech card only. The other end of the Modbus network(s) should be terminated with the usual

120-ohm resistor.

IMPORTANT NOTE FOR ETHERNET

GATEWAY USERS:

The POWER LEADER

Ethernet Gateway provides internal termination

Wiring Concerns

No commnet segment should have more than one wiring connection at any point, such as the Modbus

Concentrator, a Junction Box, or a Repeater. You must avoid this condition, which is known as looping.

Examples of correct wiring conditions and various illegal

looping conditions are illustrated in Figure 28 through

Figure 32. Figure 28 illustrates correct commnet wiring.

Figure 29 through Figure 32 show illegal looped wiring.

You can correct looping by removing either of the looped connections indicated by the large Xs in the figure.

39

Power Management Control System

Chapter 3 – Network Wiring and Construction

You must never connect a single commnet segment to the

Modbus Concentrator at more than one point or to more than one port on the Modbus Concentrator.

Figure 28 represents the correct wiring scheme for a

commnet segment – linear, one IED to the next, connected to the concentrator at one port only.

Figure 29 through Figure 32 show various incorrect wiring

schemes – commnet segments that are ‘looped’ and nonlinear. Avoid these wiring situations as they will cause communication errors.

g

P O W E R LE A D E R

M odbus Concentrator

Commnet Connections

X

Commnet Connections

- + Shld - +Shld - +Shld - + Shld or

X

commnet

IED commnet

IED commnet

IED g

P O W E R L E A D E R

M odbus Concentrator

Commnet Connections commnet

IED

Figure 30. Incorrect wiring. Looping to two Modbus

Concentrator commnet ports.

Commnet Connections

- + Shld - +Shld - +Shld - + Shld

Shield Ground commnet

IED commnet

IED commnet

IED commnet

IED

Figure 28. Commnet shield grounding wired correctly.

To

Modbus

Concentrator

Commnet

Segment

X

POWER

LEADER

Junction/Outlet Box or

X

commnet

IED commnet

IED commnet

IED commnet

IED

Figure 31. Incorrect wiring. Looping on segment connected to Junction Box.

g

P O W E R LE A D E R

M odbus Concentrator

Commnet Connections

X

Commnet Connections

- + Shld - +Shld - +Shld - + Shld or

X

commnet

IED commnet

IED commnet

IED commnet

IED

Figure 29. Incorrect wiring. Looping on one Modbus

Concentrator commnet port.

Commnet

Segment

To

Modbus

Concentrator

X

or

In

Out

POWER

LEADER

Repeater

X

commnet

IED commnet

IED commnet

IED commnet

IED

Figure 32. Incorrect wiring. Looping on segment connected to POWER LEADER Repeater.

40

Power Management Control System

Chapter 3 – Network Wiring and Construction

3–3 Modbus – Ethernet Integration

Ethernet comes into play only as an alternative platform for the host PC. It is most often used when an existing

Ethernet network is in place or being installed for datanetworking purposes, or when Ethernet-only devices such as the EPM 7700 are to be used with PMCS.

To communicate with the Modbus networks (and any commnet segments beneath them), a host PC based on

Ethernet requires an Ethernet Gateway. Rather than use an RS-485 interface card, connect the Modbus networks to the RS-485 ports on the Ethernet Gateway, which is connected to the Host PC via Ethernet, over which it communicates data from the Modbus networks.

The Ethernet Gateway offers a more nearly plug-and-play format, with fewer wiring complexities and rules than the

Modbus Concentrator. See GEH-6505, Ethernet Gateway User

Guide

, for detailed information on installing and configuring the Ethernet Gateway.

3–4 Local Configuration of IEDs

You must properly configure each IED connected to the

PMCS. Be sure to set the IED address at the IED and at the host software, set the communication speed, and configure any necessary settings.

For detailed directions on setting addresses, communication speed, and protection parameters, refer to the user guide for each IED.

3–5 Applying Power to the System

WARNING:

Voltages hazardous to personnel and equipment may be present at the power connections.

Once you’ve installed the PMCS network, you should apply power to the network from the bottom up. Follow this procedure when applying power to the system for the first time:

1. Make sure that all communications wiring has been correctly connected to each IED and that the system matches the plan exactly, meeting all rules and requirements explained in this manual.

2. Make sure that all wiring for control power to IEDs has been correctly installed and that the correct control voltage is present at each IED.

3. If commnet IEDs are installed, apply control power to the IEDs and then to the Modbus Concentrator to which they are attached.

4. Apply control power to any Modbus RTU IEDs.

5. Apply control power to the Ethernet Gateway, if one is being used.

6. Turn the computer on and start the PMCS software according to the instructions in the software manuals.

3–6 Software Loading and Startup

Refer to the Power Management Control System software installation procedures in GEH-6514, Read This Book First.

41

advertisement

Related manuals

Download PDF

advertisement

Table of contents