PTQ-DNPS
Quantum / Unity Platform
Distributed Network Protocol Interface Module
Application Reference Guide
April 22, 2008
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Please Read This Notice
Successful application of this module requires a reasonable working knowledge of the Schneider Electric
Quantum / Unity hardware, the PTQ-DNPS Module and the application in which the combination is to be used. For this reason, it is important that those responsible for implementation satisfy themselves that the combination will meet the needs of the application without exposing personnel or equipment to unsafe or inappropriate working conditions.
This manual is provided to assist the user. Every attempt has been made to ensure that the information provided is accurate and a true reflection of the product's installation requirements. In order to ensure a complete understanding of the operation of the product, the user should read all applicable Schneider
Electric documentation on the operation of the Schneider Electric hardware.
Under no conditions will ProSoft Technology be responsible or liable for indirect or consequential damages resulting from the use or application of the product.
Reproduction of the contents of this manual, in whole or in part, without written permission from ProSoft
Technology is prohibited.
Information in this manual is subject to change without notice and does not represent a commitment on the part of ProSoft Technology Improvements and/or changes in this manual or the product may be made at any time. These changes will be made periodically to correct technical inaccuracies or typographical errors.
1.1 PTQ Installation and Operating Instructions
The statement "power, input and output (I/O) wiring must be in accordance with Class I,
Division 2 wiring methods Article 501-10(b) of the National Electrical Code, NFPA 70 for installations in the U.S., or as specified in section 18-1J2 of the Canadian Electrical
Code for installations within Canada and in accordance with the authority having jurisdiction".
The following or equivalent warnings shall be included:
A
Warning - Explosion Hazard - Substitution of components may Impair Suitability for
Class I, Division 2;
B
Warning - Explosion Hazard - When in Hazardous Locations, Turn off Power before replacing Wiring Modules, and
C
Warning - Explosion Hazard - Do not Disconnect Equipment unless Power has been switched Off or the Area is known to be Nonhazardous.
D
Caution: The Cell used in this Device may Present a Fire or Chemical Burn Hazard if
Mistreated. Do not Disassemble, Heat above 100°C (212°F) or Incinerate.
Important Notice:
CAUTION: THE CELL USED IN THIS DEVICE MAY PRESENT A FIRE
OR CHEMICAL BURN HAZARD IF MISTREATED. DO NOT
DISASSEMBLE, HEAT ABOVE 100°C (212°F) OR INCINERATE.
Maximum battery load = 200 µA.
Maximum battery charge voltage = 3.4 VDC.
Maximum battery charge current = 500 µA.
Maximum battery discharge current = 30 µA.
Contents
Start Here
Your Feedback Please
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
We always want you to feel that you made the right decision to use our products. If you have suggestions, comments, compliments or complaints about the product, documentation or support, please write or call us.
ProSoft Technology
1675 Chester Avenue, Fourth Floor
Bakersfield, CA 93301
+1 (661) 716-5100
+1 (661) 716-5101 (Fax) http://www.prosoft-technology.com
Copyright © ProSoft Technology, Inc. 2000 - 2008. All Rights Reserved.
PTQ-DNPS Application Reference Guide
April 22, 2008
PSFT.DNPS.PTQ.UM.08.04.22
ProSoft Technology ®, ProLinx ®, inRAx ®, ProTalk® and RadioLinx ® are Registered Trademarks of
ProSoft Technology, Inc.
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Contents
Distributed Network Protocol Interface Module
Contents
ProSoft Technology, Inc.
April 22, 2008
Page 5 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Contents
Page 6 of 153 ProSoft Technology, Inc.
April 22, 2008
Distributed Network Protocol Interface Module
Master Port DNPS Slave Configuration Values (DNPS Master Slave List)............................125
ProSoft Technology, Inc.
April 22, 2008
Page 7 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Contents
Page 8 of 153 ProSoft Technology, Inc.
April 22, 2008
Start Here PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Guide to the PTQ-DNPS Application
Reference Guide
Function
Introduction
(Must Do)
Verify Communication,
Diagnostic and
Troubleshooting
→
Reference
Product Specifications
Functional Overview
Glossary
→
Support, Service, and
Warranty
Index
→
→
Section to Read Details
Start Here (page
This Section introduces the customer to the module. Included are: package contents, system requirements, hardware installation, and basic configuration.
Verifying
Communication
Diagnostics and
Troubleshooting
Reference (page
Functional
Product
Specifications
Support, Service and Warranty
This section describes how to verify communications with the network. Diagnostic and Troubleshooting procedures.
These sections contain general references associated with this product, Specifications, and the Functional Overview.
This section contains Support, Service and
Warranty information.
Index of chapters.
ProSoft Technology, Inc.
April 22, 2008
Page 9 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Start Here
Page 10 of 153 ProSoft Technology, Inc.
April 22, 2008
Start Here PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
In This Chapter
Hardware Software Requirements ................................................. 11
Install ProSoft Configuration Builder Software....................................... 13
This guide is intended to guide you through the ProTalk module setup process, from removing the module from the box to exchanging data with the processor. In doing this, you will learn how to:
Set up the processor environment for the PTQ module
View how the PTQ module exchanges data with the processor
Edit and download configuration files from your PC to the PTQ module
Monitor the operation of the PTQ module
2.1 Hardware and Software Requirements
2.1.1 ProTalk Module Carton Contents
ProTalk Module Null Modem Serial Cable
ProSoft Technology, Inc.
April 22, 2008
Page 11 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Start Here
1454-9F DB-9 Female to 9 Pos Screw Terminal adapter (Serial protocol modules only)
ProSoft Solutions CD
Note: The DB-9 Female to 5 Pos Screw Terminal adapter is not required on Ethernet modules and is therefore not included in the carton with these types of modules.
2.1.2 Quantum / Unity Hardware
This guide assumes that you are familiar with the installation and setup of the
Quantum / Unity hardware. The following should be installed, configured and powered up before proceeding:
Quantum or Unity Processor
Quantum
Quantum power supply
Quantum Modbus Plus Network Option Module (NOM Module) (optional)
Quantum to PC programming hardware
NOM Ethernet or Serial connection to PC
2.1.3 PC and PC Software
Windows-based PC with at least one COM port
Quantum programming software installed on machine or
Concept™ PLC Programming Software version 2.6 or
ProWORX PLC Programming Software or
UnityPro XL PLC Programming Software
HyperTerminal (used in this guide) This is a communication program that is included with Microsoft Windows. You can normally find it in Start /
Programs / accessories / Communications
.
Note: ProTalk modules are compatible with common Quantum / Unity programming applications, including Concept and UnityPro XL. For all other programming applications, please contact technical support.
Page 12 of 153 ProSoft Technology, Inc.
April 22, 2008
Start Here PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
2.2 Install ProSoft Configuration Builder Software
You must install the ProSoft Configuration Builder (PCB) software in order to configure the PTQ-DNPS module. You can always get the newest version of
ProSoft Configuration Builder from the ProSoft Technology web site.
To install ProSoft Configuration Builder from the ProSoft Web Site
1
Open your web browser and navigate to http://www.prosofttechnology.com/pcb
2
Click the Download Here link to download the latest version of ProSoft
Configuration Builder.
3
Choose "Save" or "Save File" when prompted. The following illustrations show the file download prompt for two of the most common web browsers.
4
Make a note of the location where you saved the file, for example "Desktop", or "My Documents", so you can start the installation program.
5
When the download is complete, locate and open the file, and then follow the instructions on your screen to install the program.
If you do not have access to the Internet, you can install ProSoft Configuration
Builder from the ProSoft Solutions CD-ROM, included in the package with your
PTQ-DNPS module.
To install ProSoft Configuration Builder from the CD-ROM
1
Insert the ProSoft Solutions CD-ROM into the CD drive of your PC. Wait for the startup screen to appear.
2
On the startup screen, click Product Documentation. This action opens an explorer window.
ProSoft Technology, Inc.
April 22, 2008
Page 13 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Start Here
3
Click to open the Utilities folder. This folder contains all of the applications and files you will need to set up and configure your module.
4
Double-click the ProSoft Configuration Builder Setup program and follow the instructions on your screen to install the software on your PC.
Note: Many of the configuration and maintenance procedures use files and other utilities on the
CD-ROM. You may wish to copy the files from the Utilities folder on the CD-ROM to a convenient location on your hard drive.
Page 14 of 153 ProSoft Technology, Inc.
April 22, 2008
Configuring the Processor with Concept PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
3 Configuring the Processor with Concept
In This Chapter
Information Concept Version 2.6 Users............................................ 16
Create a New Project ............................................................................ 17
Add the PTQ Module to the Project....................................................... 20
Set up Data Memory in Project.............................................................. 22
Download the Project to the Processor ................................................. 25
The following steps are designed to ensure that the processor is able to transfer data successfully with the PTQ module. As part of this procedure, you will use
Concept configuration software from Schneider Electric to create a project, add the PTQ module to the project, set up data memory for the project, and then download the project to the processor.
Important Note: Concept software does not report whether the PTQ module is present in the rack, and therefore is not able to report the health status of the module when the module is online with the Quantum processor. Please take this into account when monitoring the status of the PTQ module.
ProSoft Technology, Inc.
April 22, 2008
Page 15 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Configuring the Processor with Concept
3.1 Information for Concept Version 2.6 Users
This guide uses Concept PLC Programming Software version 2.6 to configure the Quantum PLC. The ProTalk installation CD includes MDC module configuration files that help document the PTQ installation. Although not required, these files should be installed before proceeding to the next section.
1
From a PC with Concept 2.6 installed, choose Start / Programs / Concept /
ModConnect Tool
.
This action opens the Concept Module Installation dialog box.
2
Choose File / Open Installation File.
This action opens the Open Installation File dialog box: o o
3
If you are using a Quantum processor, you will need the MDC files. In the
Open Installation File dialog box, navigate to the MDC Files directory on the
ProTalk CD.
4
Choose the MDC file and help file for your version of Concept:
Concept 2.6 users: select PTQ_2_60.mdc and PTQMDC.hlp
Concept 2.5 users: select PTQ_2_50.mdc and PTQMDC.hlp.
Select the files that go with the Concept version you are using, and then click
OK
. This action opens the add New Modules dialog box.
Page 16 of 153 ProSoft Technology, Inc.
April 22, 2008
Configuring the Processor with Concept PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
5
Click the add all button. A series of message boxes may appear during this process. Click Yes or OK for each message that appears.
6
When the process is complete, open the File menu and choose Exit to save your changes.
3.2 Create a New Project
This phase of the setup procedure must be performed on a computer that has the Concept configuration software installed.
1
From your computer, choose Start / Programs / Concept V2.6 XL.EN /
Concept
. This action opens the Concept window.
2
Open the File menu, and then choose New Project. This action opens the
PLC Configuration dialog box.
ProSoft Technology, Inc.
April 22, 2008
Page 17 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Configuring the Processor with Concept
3
In the list of options on the left side of this dialog box, double-click the PLC
Selection
folder. This action opens the PLC Selection dialog box.
4
In the CPU/Executive pane, use the scroll bar to locate and select the PLC to configure.
Page 18 of 153 ProSoft Technology, Inc.
April 22, 2008
Configuring the Processor with Concept PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
5
Click OK. This action opens the PLC Configuration dialog box, populated with the correct values for the PLC you selected.
6
Make a note of the holding registers for the module. You will need this information when you modify your application as outlined in the ProTalk application Reference Guides. The Holding Registers are displayed in the
PLC Memory Partition pane of the PLC Configuration dialog box.
ProSoft Technology, Inc.
April 22, 2008
Page 19 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
3.3 Add the PTQ Module to the Project
Configuring the Processor with Concept
The next step is to add one or more of the PTQ modules to the Project. To add modules:
1
In the list of options on the left side of the PLC Configuration dialog box, double-click I/O Map. This action opens the I/O Map dialog box.
2
Click the Edit button to open the Local Quantum Drop dialog box. This dialog box is where you identify rack and slot locations.
Page 20 of 153 ProSoft Technology, Inc.
April 22, 2008
Configuring the Processor with Concept PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
3
Click the Module button next to the rack/slot position where the ProTalk module will be installed. This action opens the I/O Module Selection dialog box.
4
In the Modules pane, use the scroll bar to locate and select the ProTalk module, and then click OK. This action copies the description of the ProTalk module next to the assigned rack and slot number of the Local Quantum
Drop dialog box.
ProSoft Technology, Inc.
April 22, 2008
Page 21 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Configuring the Processor with Concept
5
Repeat steps 3 through 5 for each ProTalk module you plan to install. When you have finished installing your ProTalk modules, click OK to save your settings. Click Yes to confirm your settings.
Tip: Select a module, and then click the Help on Module button for help pages.
3.4 Set up Data Memory in Project
1
In the list of options on the left side of the PLC Configuration dialog box, double-click Specials.
Page 22 of 153 ProSoft Technology, Inc.
April 22, 2008
Configuring the Processor with Concept
2
This action opens the Specials dialog box.
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Selecting the Time of Day
1
Select (check) the Time of Day box, and then enter the value 00001 as shown in the following example. This value sets the first time of day register to 400001.
2
Click OK to save your settings and close the Specials dialog box.
ProSoft Technology, Inc.
April 22, 2008
Page 23 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Configuring the Processor with Concept
Saving your project
1
In the PLC Configuration dialog box, choose File / Save project as.
2
This action opens the Save Project as dialog box.
3
Name the project, and then click OK to save the project to a file.
Page 24 of 153 ProSoft Technology, Inc.
April 22, 2008
Configuring the Processor with Concept PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
3.5 Download the Project to the Processor
The next step is to download (copy) the project file to the Quantum Processor.
1
Use the null modem cable to connect your PC's serial port to the Quantum processor, as shown in the following illustration.
Note: You can use a Modbus Plus Network Option Module (NOM Module) module in place of the serial port if necessary.
2
Open the PLC menu, and then choose Connect.
ProSoft Technology, Inc.
April 22, 2008
Page 25 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Configuring the Processor with Concept
3
In the PLC Configuration dialog box, open the Online menu, and then choose
Connect. This action opens the Connect to PLC dialog box.
4
Leave the default settings as shown and click OK.
Note: Click OK to dismiss any message boxes that appear during the connection process.
5
In the PLC Configuration window, open the Online menu, and then choose
Download. This action opens the Download Controller dialog box.
Page 26 of 153 ProSoft Technology, Inc.
April 22, 2008
Configuring the Processor with Concept PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
6
Click all, and then click Download. If a message box appears indicating that the controller is running, click Yes to shut down the controller. The Download
Controller dialog box displays the status of the download as shown in the following illustration.
7
When the download is complete, you will be prompted to restart the controller. Click Yes to restart the controller.
ProSoft Technology, Inc.
April 22, 2008
Page 27 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
3.6 Verify Successful Download
Configuring the Processor with Concept
The final step is to verify that the configuration changes you made were received successfully by the module, and to make some adjustments to your settings.
1
In the PLC Configuration window, open the Online menu, and then choose
Online Control Panel. This action opens the Online Control Panel dialog box.
2
Click the Set Clock button to open the Set Controller's Time of Day Clock dialog box.
3
Click the Write Panel button. This action updates the date and time fields in this dialog box. Click OK to close this dialog box and return to the previous window.
Page 28 of 153 ProSoft Technology, Inc.
April 22, 2008
Configuring the Processor with Concept PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
4
Click Close to close the Online Control Panel dialog box.
5
In the PLC Configuration window, open the Online menu, and then choose
Reference Data Editor. This action opens the Reference Data Editor dialog box. On this dialog box, you will add preset values to data registers that will later be monitored in the ProTalk module.
6
Place the cursor over the first address field, as shown in the following illustration.
7
In the PLC Configuration window, open the Templates menu, and then choose Insert addresses. This action opens the Insert addresses dialog box.
8
On the Insert addresses dialog box, enter the values shown in the following illustration, and then click OK.
ProSoft Technology, Inc.
April 22, 2008
Page 29 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Configuring the Processor with Concept
9
Notice that the template populates the address range, as shown in the following illustration. Place your cursor as shown in the first blank address field below the addresses you just entered.
10
Repeat steps 6 through 9, using the values in the following illustration:
Page 30 of 153 ProSoft Technology, Inc.
April 22, 2008
Configuring the Processor with Concept PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
11
In the PLC Configuration window, open the Online menu, and then choose animate. This action opens the RDE Template dialog box, with animated values in the Value field.
12
Verify that values shown are cycling, starting from address 400065 on up.
13
In the PLC Configuration window, open the Templates menu, and then choose Save Template as. Name the template ptqclock, and then click OK to save the template.
14
In the PLC Configuration window, open the Online menu, and then choose
Disconnect. At the disconnect message, click Yes to confirm your choice.
At this point, you have successfully
Created and downloaded a Quantum project to the PLC
Preset values in data registers that will later be monitored in the ProTalk module.
You are now ready to complete the installation and setup of the ProTalk module.
ProSoft Technology, Inc.
April 22, 2008
Page 31 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Configuring the Processor with Concept
Page 32 of 153 ProSoft Technology, Inc.
April 22, 2008
Configuring the Processor with ProWORX PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
4 Configuring the Processor with ProWORX
When you use ProWORX 32 software to configure the processor, use the example SaF file provided on the ProTalk Solutions CD-ROM.
Important Note: Proworx software does not report whether the PTQ module is present in the rack, and therefore is not able to report the health status of the module when the module is online with the Quantum processor. Please take this into account when monitoring the status of the PTQ module.
1
Run the Schneider_alliances.exe application that is installed with the
Proworx 32 software:
2
Click on Import…
ProSoft Technology, Inc.
April 22, 2008
Page 33 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Configuring the Processor with ProWORX
3
Select the .SaF File that is located at the CD-ROM shipped with the PTQ module.
4
After you click on Open you should see the PTQ modules imported (select
I/O series as Quantum):
Page 34 of 153 ProSoft Technology, Inc.
April 22, 2008
Configuring the Processor with ProWORX PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Now you can close the Schneider alliances application and run the Proworx 32 software. At the Traffic Cop section, select the PTQ module to be inserted at the slot:
ProSoft Technology, Inc.
April 22, 2008
Page 35 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Configuring the Processor with ProWORX
Page 36 of 153 ProSoft Technology, Inc.
April 22, 2008
Configuring the Processor with UnityPro XL PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
5 Configuring the Processor with UnityPro XL
In This Chapter
Create a New Project ............................................................................ 37
Add the PTQ Module to the Project....................................................... 39
Connect Your PC to the Processor ....................................................... 42
Download the Project to the Processor ................................................. 44
The following steps are designed to ensure that the processor (Quantum or
Unity) is able to transfer data successfully with the PTQ module. As part of this procedure, you will use UnityPro XL to create a project, add the PTQ module to the project, set up data memory for the project, and then download the project to the processor.
5.1 Create a New Project
The first step is to open UnityPro XL and create a new project.
1
In the New Project dialog box, choose the CPU type. In the following illustration, the CPU is 140 CPU 651 60. Choose the processor type that matches your own hardware configuration, if it differs from the example. Click
OK to continue.
ProSoft Technology, Inc.
April 22, 2008
Page 37 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Configuring the Processor with UnityPro XL
2
The next step is to add a power supply to the project. In the Project Browser, expand the Configuration folder, and then double-click the 1:LocalBus icon.
This action opens a graphical window showing the arrangement of devices in your Quantum rack.
3
Select the rack position for the power supply, and then click the right mouse button to open a shortcut menu. On the shortcut menu, choose New Device..
Page 38 of 153 ProSoft Technology, Inc.
April 22, 2008
Configuring the Processor with UnityPro XL PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
4
Expand the Supply folder, and then select your power supply from the list.
Click OK to continue.
5
Repeat these steps to add any additional devices to your Quantum Rack.
5.2 Add the PTQ Module to the Project
The next step is to add the PTQ module.
1
Expand the Communication tree, and select GEN NOM. This module type provides extended communication capabilities for the Quantum system, and allows communication between the PLC and the PTQ module without requiring additional programming.
ProSoft Technology, Inc.
April 22, 2008
Page 39 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Configuring the Processor with UnityPro XL
2
Next, enter the module personality value. The correct value for ProTalk modules is 1060 decimal (0424 hex).
3
Before you can save the project in UnityProXL, you must validate the modifications. Open the Edit menu, and then choose Validate. If no errors are reported, you can save the project.
4
Save the project.
Page 40 of 153 ProSoft Technology, Inc.
April 22, 2008
Configuring the Processor with UnityPro XL PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Whenever you update the configuration of your PTQ module or the processor, you must import the changed configuration from the module, and then build
(compile) the project before downloading it to the processor.
Note: The following steps show you how to build the project in Unity Pro XL. This is not intended to provide detailed information on using Unity Pro XL, or debugging your programs. Refer to the documentation for your processor and for Unity Pro XL for specialized information.
To build (compile) the project:
1
Review the elements of the project in the Project Browser.
2
When you are satisfied that you are ready to download the project, open the
Build menu, and then choose Rebuild all Project. This action builds
(compiles) the project into a form that the processor can use to execute the instructions in the project file. This task may take several minutes, depending on the complexity of the project and the resources available on your PC.
3
As the project is built, Unity Pro XL reports its process in a Progress dialog box, with details appearing in a pane at the bottom of the window. The following illustration shows the build process under way.
After the build process is completed successfully, the next step is to download the compiled project to the processor.
ProSoft Technology, Inc.
April 22, 2008
Page 41 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
5.4 Connect Your PC to the Processor
Configuring the Processor with UnityPro XL
The next step is to connect to the processor so that you can download the project file. The processor uses this project file to communicate over the backplane to modules identified in the project file.
Note: If you have never connected from the PC to your processor before, you must verify that the necessary port drivers are installed and available to UnityPro XL.
To verify address and driver settings in UnityPro XL:
1
Open the PLC menu, and choose Standard Mode. This action turns off the
PLC Simulator, and allows you to communicate directly with the Quantum or
Unity hardware.
2
Open the PLC menu, and choose Set address... This action opens the Set address dialog box. Open the Media dropdown list and choose the connection type to use (TCPIP or USB).
Page 42 of 153 ProSoft Technology, Inc.
April 22, 2008
Configuring the Processor with UnityPro XL PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
3
If the Media dropdown list does not contain the connection method you wish to use, click the Communication Parameters button in the PLC area of the dialog box. This action opens the PLC Communication Parameters dialog box.
4
Click the Driver Settings button to open the SCHNEIDER Drivers management Properties dialog box.
5
Click the Install/update button to specify the location of the Setup.exe file containing the drivers to use. You will need your UnityPro XL installation disks for this step.
6
Click the Browse button to locate the Setup.exe file to execute, and then execute the setup program. After the installation, restart your PC if you are prompted to do so. Refer to your Schneider Electric documentation for more information on installing drivers for UnityPro XL.
5.4.1 Connecting to the Processor with TCPIP
The next step is to download (copy) the project file to the processor. The following steps demonstrate how to use an Ethernet cable connected from the
Processor to your PC through an Ethernet hub or switch. Other connection methods may also be available, depending on the hardware configuration of your processor, and the communication drivers installed in UnityPro XL.
ProSoft Technology, Inc.
April 22, 2008
Page 43 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Configuring the Processor with UnityPro XL
1
If you have not already done so, connect your PC and the processor to an
Ethernet hub.
2
Open the PLC menu, and then choose Set address.
Important: Notice that the Set address dialog box is divided into two areas. Enter the address and media type in the PLC area of the dialog box, not the Simulator area.
3
Enter the IP address in the address field. In the Media dropdown list, choose
TCPIP.
4
Click the Test Connection button to verify that your settings are correct.
The next step is to download the Project to the Processor.
5.5 Download the Project to the Processor
1
Open the PLC menu and then choose Connect. This action opens a connection between the Unity Pro XL software and the processor, using the address and media type settings you configured in the previous step.
2
On the PLC menu, choose Transfer Project to PLC. This action opens the
Transfer Project to PLC dialog box. If you would like the PLC to go to "Run" mode immediately after the transfer is complete, select (check) the PLC Run after Transfer check box.
3
Click the Transfer button to download the project to the processor. As the project is transferred, Unity Pro XL reports its process in a Progress dialog box, with details appearing in a pane at the bottom of the window.
When the transfer is complete, place the processor in Run mode.
Page 44 of 153 ProSoft Technology, Inc.
April 22, 2008
Setting Up the ProTalk Module PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
6 Setting Up the ProTalk Module
In This Chapter
Install the ProTalk Module in the Quantum Rack .................................. 45
Collision (DNP modules only) .............................................. 51
Connect the PC to the ProTalk Configuration/Debug Port .................... 51
After you complete the following procedures, the ProTalk module will actively be transferring data bi-directionally with the processor.
6.1 Install the ProTalk Module in the Quantum Rack
6.1.1 Verify Jumper Settings
ProTalk modules are configured for RS-232 serial communications by default. To use RS-422 or RS-485, you must change the jumpers.
The jumpers are located on the back of the module as shown in the following illustration:
ProSoft Technology, Inc.
April 22, 2008
Do not move this jumper unless instructed to do so by
ProSoft Technical Support
Page 45 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
6.1.2 Inserting the 1454-9F connector
Setting Up the ProTalk Module
Insert the 1454-9F connector as shown. Wiring locations are shown in the table:
6.1.3 Install the ProTalk Module in the Quantum Rack
1
Place the Module in the Quantum Rack. The ProTalk module must be placed in the same rack as the processor.
2
Tilt the module at a 45
° angle and align the pegs at the top of the module with slots on the backplane.
Page 46 of 153 ProSoft Technology, Inc.
April 22, 2008
Setting Up the ProTalk Module PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
3
Push the module into place until it seats firmly in the backplane.
CaUTION: The PTQ module is hot-swappable, meaning that you can install and remove it while the rack is powered up. You should not assume that this is the case for all types of modules unless the user manual for the product explicitly states that the module is hot-swappable. Failure to observe this precaution could result in damage to the module and any equipment connected to it.
The application ports on the PTQ-DNPS module support RS-232, RS-422, and
RS-485 interfaces. Please inspect the module to ensure that the jumpers are set correctly to correspond with the type of interface you are using.
Note: When using RS-232 with radio modem applications, some radios or modems require hardware handshaking (control and monitoring of modem signal lines). Enable this in the configuration of the module by setting the UseCTS parameter to 1.
6.2.1 RS-232 Configuration/Debug Port
This port is physically a DB-9 connection. This port permits a PC based terminal emulation program to view configuration and status data in the module and to control the module. The cable for communications on this port is shown in the following diagram:
ProSoft Technology, Inc.
April 22, 2008
Page 47 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
The Ethernet port on this module (if present) is inactive.
Setting Up the ProTalk Module
6.2.2 RS-232
When the RS-232 interface is selected, the use of hardware handshaking
(control and monitoring of modem signal lines) is user definable. If no hardware handshaking will be used, the cable to connect to the port is as shown below:
RS-232: Modem Connection
This type of connection is required between the module and a modem or other communication device.
The "Use CTS Line" parameter for the port configuration should be set to 'Y' for most modem applications.
Page 48 of 153 ProSoft Technology, Inc.
April 22, 2008
Setting Up the ProTalk Module PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
RS-232: Null Modem Connection (Hardware Handshaking)
This type of connection is used when the device connected to the module requires hardware handshaking (control and monitoring of modem signal lines).
RS-232: Null Modem Connection (No Hardware Handshaking)
This type of connection can be used to connect the module to a computer or field device communication port.
Note: If the port is configured with the "Use CTS Line" set to 'Y', then a jumper is required between the RTS and the CTS line on the module connection.
ProSoft Technology, Inc.
April 22, 2008
Page 49 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
6.2.3 RS-485
Setting Up the ProTalk Module
The RS-485 interface requires a single two or three wire cable. The Common connection is optional and dependent on the RS-485 network. The cable required for this interface is shown below:
Note: Terminating resistors are generally not required on the RS-485 network, unless you are experiencing communication problems that can be attributed to signal echoes or reflections. In this case, install a 120 ohm terminating resistor on the RS-485 line.
6.2.4 RS-422
RS-485 and RS-422 Tip
If communication in the RS-422/RS-485 mode does not work at first, despite all attempts, try switching termination polarities. Some manufacturers interpret +/- and A/B polarities differently.
Page 50 of 153 ProSoft Technology, Inc.
April 22, 2008
Setting Up the ProTalk Module PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
6.3 Collision Avoidance (DNP modules only)
The RTS line is controlled by the RTS on and off parameters set for the port. If the CTS line is used (usually only required for half-duplex modems and not defined for use in the DNPS specification), the RTS and CTS lines must either be connected together or connected to the modem. The following illustration shows the cable required when connecting the port to a modem.
If collision avoidance is used in a point-to-point connection on the RS-232 interface, the following cable should be used.
6.4 Connect the PC to the ProTalk Configuration/Debug Port
Make sure you have exited the Quantum programming software before performing these steps. This action will avoid serial port conflict.
ProSoft Technology, Inc.
April 22, 2008
Page 51 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Setting Up the ProTalk Module
Using the supplied Null Modem cable, connect your PC or Laptop to the
Configuration/Debug port on the ProTalk module as shown
To connect to the module's Configuration/Debug serial port:
1
Start PCB program with the application file to be tested. Right click over the module icon.
2
On the shortcut menu, choose Diagnostics.
Page 52 of 153 ProSoft Technology, Inc.
April 22, 2008
Setting Up the ProTalk Module PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
3
This action opens the Diagnostics dialog box. Press "?" to display the Main
Menu.
Important: The illustrations of configuration/debug menus in this section are intended as a general guide, and may not exactly match the configuration/debug menus in your own module.
If there is no response from the module, follow these steps:
1
Verify that the null modem cable is connected properly between your computer's serial port and the module. A regular serial cable will not work.
2
On computers with more than one serial port, verify that your communication program is connected to the same port that is connected to the module.
3
If you are still not able to establish a connection, contact ProSoft Technology for assistance.
ProSoft Technology, Inc.
April 22, 2008
Page 53 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Setting Up the ProTalk Module
Page 54 of 153 ProSoft Technology, Inc.
April 22, 2008
Modifying the Configuration File PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
7 Modifying the Configuration File
In This Chapter
[DNP Database] .......................................................................... 68
[DNP Slave Binary Inputs] ..................................................................... 70
[DNP Slave Analog Inputs] .................................................................... 70
[DNP Slave Float Inputs] ....................................................................... 71
Verification Troubleshooting ........................................................... 74
7.1 ProSoft Configuration Builder
ProSoft Configuration Builder (PCB) provides a quick and easy way to manage module configuration files customized to meet your application needs. PCB is not only a powerful solution for new configuration files, but also allows you to import information from previously installed (known working) configurations to new projects.
ProSoft Technology, Inc.
April 22, 2008
Page 55 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
7.1.1 Set Up the Project
Modifying the Configuration File
To begin, start ProSoft Configuration Builder. If you have used other Windows configuration tools before, you will find the screen layout familiar. ProSoft
Configuration Builder's window consists of a tree view on the left, an information pane and a configuration pane on the right side of the window. When you first start ProSoft Configuration Builder, the tree view consists of folders for Default
Project and Default Location, with a Default Module in the Default Location folder. The following illustration shows the ProSoft Configuration Builder window with a new project.
Your first task is to add the PTQ-DNPS module to the project.
1
Use the mouse to select "Default Module" in the tree view, and then click the right mouse button to open a shortcut menu.
Page 56 of 153 ProSoft Technology, Inc.
April 22, 2008
Modifying the Configuration File PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
2
On the shortcut menu, choose "Choose Module Type". This action opens the
Choose Module Type dialog box.
3
In the Product Line Filter area of the dialog box, select PTQ. In the Select
Module Type dropdown list, select PTQ-DNPS, and then click OK to save your settings and return to the ProSoft Configuration Builder window.
The next task is to set the module parameters.
Adding a Project
To add a project to an existing project file:
1
Select the Default Project icon.
2
Choose Project from the Project menu, then choose Add Project. A new project folder appears.
Adding a Module
To add a module to your project:
1
Double-click the Default Module icon to open the Choose Module Type dialog box.
2
On the Choose Module Type dialog box, select the module type. or
1
Open the Project menu and choose Location
ProSoft Technology, Inc.
April 22, 2008
Page 57 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
2
On the Location menu, choose Add Module.
Modifying the Configuration File
To add a module to a different location:
1
Right-click the Location folder and choose Add Module. A new module icon appears. or
Select the Location icon.
2
From the Project menu, select Location, then select Add Module.
Notice that the contents of the information pane and the configuration pane changed when you added the PTQ-DNPS module to the project.
At this time, you may wish to rename the "Default Project" and "Default Location" folders in the tree view.
To rename an object:
1
Select the object, and then click the right mouse button to open a shortcut menu. From the shortcut menu, choose Rename.
2
Type the name to assign to the object.
3
Click away from the object to save the new name.
Page 58 of 153 ProSoft Technology, Inc.
April 22, 2008
Modifying the Configuration File
Module Entries
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
To configure module parameters
1
Click on the plus sign next to the icon information.
to expand module
2
Double-click the icon to open the Edit dialog box.
3
To edit a parameter, select the parameter in the left pane and make your changes in the right pane.
4
Click OK to save your changes.
Comment Entries
To add comments to your configuration file:
1
Click the plus sign to the left of the
Comments.
2
Double-click the appears.
icon to expand the Module
icon. The Edit - Module Comment dialog
3
Enter your comment and click OK to save your changes.
Printing a Configuration File
To print a configuration file:
1
Select the Module icon, and then click the right mouse button to open a shortcut menu.
2
On the shortcut menu, choose View Configuration. This action opens the
View Configuration window.
3
On the View Configuration window, open the File menu, and choose Print.
This action opens the Print dialog box.
ProSoft Technology, Inc.
April 22, 2008
Page 59 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Modifying the Configuration File
4
On the Print dialog box, choose the printer to use from the dropdown list, select printing options, and then click OK.
7.2 [Module]
This section defines the module name for the Module.
0 to 80 characters
This parameter assigns a name to the module that can be viewed using the configuration/debug port. Use this parameter to identify the module and the configuration file.
This section designates database addresses for input and output on the module and on the processor.
The following example shows a sample [PTQ Backplane] section:
# This section defines the state RAM areas in the processor the module
# will interface.
[PTQ BACKPLANE]
3x Register Start: 1 #3x start register where data moved from module to
#processor (1-n)
4x Register Start: 1 #4x start register where data moved from processor to
#module (1-n)
7.3.1 3x Register Start
1 to n
This parameter sets the first register in the processor where the data transferred from the module to the processor will be placed.
7.3.2 4x Register Start
1 to n
This parameter sets the first register in the processor where the data transferred from the processor to the module is present.
This section provides information required to configure a slave application with the module. Most entries contained within this section are self explanatory.
Page 60 of 153 ProSoft Technology, Inc.
April 22, 2008
Modifying the Configuration File PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Note: A limitation of the DNP slave driver is that all points defined in the module slave database must fit within one Class 0 poll. The maximum packet size for a Class 0 poll is 2048 bytes. A DNP
Message Size Calculator is available on the ProSoft Technology web site. This calculator will help you ensure that the packet size fits within this requirement.
The following example shows a sample [DNP Slave] section:
# This section defines the configuration for the Module.
# port. This port will receive requests from a remote DNP master unit.
#
[DNP Slave]
Internal Slave ID : 32 #0-65534 slave identification code for this
# unit
# DNP slave communication port configuration
Baud Rate : 19200 #Baud rate for port 110-115200
RTS On : 0 #0-65535 milliseconds before message
RTS Off : 0 #0-65535 milliseconds after message
Min Response Delay : 0 #0-65535 milliseconds before response sent from
# slave
# DNP slave modem configuration
Modem : No #Use a dial-up modem on this port (Yes or
# No)
Connect Timeout : 20000 #0-65535 milliseconds before connect timeout
First Character Delay : 1000 #0-65535 milliseconds before 1st char after connect
Redial Delay Time : 100 #0-65535 1/10 seconds min before redial
# attempt
Redial Random Delay : 150 #0-65535 1/10 seconds random before redial
# attempt
Idle Timeout : 200 #0-65535 1/10 seconds inactive timeout
Phone Number : ATDT18001234567
# Collision Avoidance parameters
Collision Avoidance : No #Use Collision Avoidance (Yes or No)
CD Idle Time : 10 #0-32000 mSec min idle time before transmit
CD Random Time : 15 #0-32000 mSec random idle time before
# transmit
CD Time Before Receive : 5 #0-65535 milliseconds before receive
#Default Class Settings
BI Class : 2 #Default class for binary input events
# (0=disable, else 1-3)
AI Class : 3 #Default class for analog input events
# (0=disable, else 1-3)
Float Class : 0 #Default class for float input events
# (0=disable, else 1-3)
# DNP specific parameters
AI Deadband : 1 #0-32767 analog deadband value for events
Float Deadband : 1000.0 #Single float deadband
Select/Operate Arm Time: 2000 #1-65535 milliseconds arm timeout for select/op
# outputs
Write Time Interval : 60 #0-1440 minutes for time sync from master
Data Link Confirm Mode : Never #DL confirm mode (N=Never, S=Sometimes,
ProSoft Technology, Inc.
April 22, 2008
Page 61 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Modifying the Configuration File
# A=Always)
Data Link Confirm Tout : 1000 #1-65535 milliseconds DL confirm timeout
Data Link Max Retry : 2 #0-255 maximum DL confirm retry count
App Layer Confirm Tout : 2000 #1-65535 milliseconds App Layer confirm timeout
Unsolicited Response : No #Generate Unsolicited responses (Yes or No)
Class 1 Unsol Resp Min : 10 #1-255 min number of events before send
Class 2 Unsol Resp Min : 10 #1-255 min number of events before send
Class 3 Unsol Resp Min : 10 #1-255 min number of events before send
Unsol Resp Delay : 2000 #0-65535 milliseconds before events sent
UResp Master Address : 1 #DNP address of master to send UResp data
UResp Retry Count : 0 #0-255 Number of retries before switching
# ports
BI with flag : Yes #return BI data with flag data
BI Events without time : Yes #return BI events without time/date
BO without flag : Yes #return BO data without flag data (packed)
Counter with flag : Yes #return counters with flag byte
Frozen counter with flag: Yes #return frozen counters with flag byte
AI with flag : Yes #return AI with flag byte
AI Events with time : Yes #timestamp AI Event data default (Yes or
# No)
Time Sync Before Events: No #timesync module before events gen (Yes or
# No)
Initialize DNP Database: Yes #Initialize the DNP Slave output database
# areas (Y/N)
7.4.1 Internal Slave ID
0 to 65534
This is the DNP address for the module. All messages with this address from the master will be processed by the module.
Baud rate value
DNP Port Baud Rate: 300, 600, 1200, 2400, 4800, 9600, 19200, 384 (38400) ,
576 (57600), 115 (115200)
0 to 65535 milliseconds
This value represents the number of 1 ms increments to be inserted between asserting the RTS modem line and the actual transmission of the data.
0 to 65535 milliseconds
Page 62 of 153 ProSoft Technology, Inc.
April 22, 2008
Modifying the Configuration File PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
This value represents the number of 1 ms increments to be inserted after the last character of data is transmitted before the RTS modem line is dropped.
7.4.5 Min Response Delay
0 to 65535 milliseconds
Minimum time between receiving a request and transmitting a response. Allows master time to disable transmitter on an RS-485 network.
7.4.6 Modem
Y or N
This parameter defines if a dial-up modem is used on the secondary DNP slave port. A modem cannot be used if the port is configured as a master.
0 to 65535
Defines the number of milliseconds to wait for the CD signal to be set high. The
CD signal indicates a connection is made using a dial-up modem.
7.4.8 First Character Delay
0 to 65535
Defines the number of milliseconds to wait before sending the first message after the connection is first made. This delay only applies to the first packet sent to the modem.
7.4.9 Redial Delay Time
0 to 32000
Defines the minimum number of milliseconds to wait before a redial attempt is made by the slave.
7.4.10 Redial Random Delay
0 to 32000
Defines a random millisecond time range to be added to the redial delay time before the modem is accessed.
7.4.11 Idle Timeout
0 to 65535
Defines the number of milliseconds the modem is inactive before it will disconnect.
ProSoft Technology, Inc.
April 22, 2008
Page 63 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
7.4.12 Phone Number
Modifying the Configuration File
ASCII String Data
This field contain a null-terminated, ASCII character string used by the dial-up modem. The string must contain all characters required by the modem. An example string is ATDT1800222333. Maximum length is 34 bytes including the terminating 0.
7.4.13 Collision Avoidance
Y or N
This parameter defines if collision avoidance will be utilized on the primary DNP slave port.
7.4.14 CD Idle Time
0 to 32000
Defines the minimum number of milliseconds to wait before transmitting a message after the CD signal is recognized as low.
7.4.15 CD Random Time
0 to 32000
Defines the range of random time to be added to the CD Idle Time before a message will be transmitted from the slave.
7.4.16 CD Time Before Receive
0 to 65535
Defines the number of milliseconds to wait before receiving characters after the
CD signal is recognized as high.
7.4.17 BI Class
0 to 3
This parameter specifies the default class to be utilized for all the binary input points in the DNP database that are not defined in the override list section.
7.4.18 AI Class
0 to 3
This parameter specifies the default class to be utilized for all the analog input points in the DNP database that are not defined in the override list section.
Page 64 of 153 ProSoft Technology, Inc.
April 22, 2008
Modifying the Configuration File
7.4.19 Float Class
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
0 to 3
This parameter specifies the default class to be utilized for all the floating-point input points in the DNP database that are not defined in the override list section.
7.4.20 AI Deadband
0 to 32767
This parameter specifies the default deadband value assigned to all points not defined in the override list for the analog input point type in the DNP database.
7.4.21 Float Deadband
0 to maximum float value
This parameter specifies the default deadband value assigned to all points not defined in the override list for the floating-point input point type in the DNP database.
7.4.22 Select/Operate Arm Time
1 to 65535 milliseconds
Time period after select command received in which operate command will be performed. Once the select command is received, the operate command will only be honored if it arrives within this period of time.
7.4.23 Write Time Interval
0 to 1440 minutes
Time interval to set the need time IIN bit (0=never), which will cause the master to write the time. Stored in milliseconds in the module memory.
7.4.24 Data Link Confirm Mode
Coded Value (N=Never, S=Sometimes, A=Always)
IED can request acknowledgement from master station when sending data. The codes are as follows: 0=Never, 1=Sometimes, 2=Always
7.4.25 Data Link Confirm Tout
1 to 65535 milliseconds
Time period to wait for Master Data Link confirmation of last frame sent. This time is in milliseconds. This parameter is only used if the frame is sent with confirmation requested.
ProSoft Technology, Inc.
April 22, 2008
Page 65 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
7.4.26 Data Link Max Retry
Modifying the Configuration File
0 to 255 retries
Maximum number of retries at the Data Link level to obtain a confirmation. If this value is set to 0, retries are disabled at the data link level of the protocol. This parameter is only used if the frame is sent with confirmation requested.
7.4.27 App Layer Confirm Tout
1 to 65535 milliseconds
Event data contained in the last response may be sent again if not confirmed within the millisecond time period set. If application layer confirms are used with data link confirms, ensure that the application layer confirm timeout is set long enough.
7.4.28 Unsolicited Response
Y or N
Set if the slave unit will send unsolicited response messages. If set to N, the slave will not send unsolicited responses. If set to Y, the slave will send unsolicited responses.
7.4.29 Class 1 Unsol Resp Min
1 to 255 events
Minimum number of events in Class 1 required before an unsolicited response will be generated.
7.4.30 Class 2 Unsol Resp Min
1 to 255 events
Minimum number of events in Class 2 required before an unsolicited response will be generated.
7.4.31 Class 3 Unsol Resp Min
1 to 255 events
Minimum number of events in Class 3 required before an unsolicited response will be generated.
7.4.32 Unsol Resp Delay
0 to 65535 milliseconds
Maximum number of 1 millisecond intervals to wait after an event occurs before sending an unsolicited response message. If set to 0, only use minimum number of events.
Page 66 of 153 ProSoft Technology, Inc.
April 22, 2008
Modifying the Configuration File
7.4.33 Uresp Master Address
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
0 to 65534
DNP destination address where unsolicited response messages are sent.
7.4.34 Uresp Retry Count
0 to 255 retries
Determines the number of unsolicited message retries sent on primary DNP port before changing to secondary port. If the value is 0, port switching will be disabled.
7.4.35 BI with Flag
Y or N
This parameter determines which variation will be returned for object 1 when the master requests variation 0. If the parameter is set to N, variation 1 will be returned. If the parameter is set to Y, variation 2 will be returned.
7.4.36 BI Events without time
Y or N
This parameter determines which variation will be returned for object 2 when the master requests variation 0. If the parameter is set to N, variation 2 will be returned. If the parameter is set to Y, variation 1 will be returned.
7.4.37 BO without flag
Y or N
This parameter determines which variation will be returned for object 10 when the master requests variation 0. If the parameter is set to N, variation 2 will be returned. If the parameter is set to Y, variation 1 will be returned.
7.4.38 Counter with flag
Y or N
This parameter determines which variation will be returned for object 20 when the master requests variation 0. If the parameter is set to N, variation 5 will be returned. If the parameter is set to Y, variation 1 will be returned.
7.4.39 Frozen counter with flag
Y or N
This parameter determines which variation will be returned for object 21 when the master requests variation 0. If the parameter is set to N, variation 9 will be returned. If the parameter is set to Y, variation 1 will be returned.
ProSoft Technology, Inc.
April 22, 2008
Page 67 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
7.4.40 AI with flag
Modifying the Configuration File
Y or N
This parameter determines which variation will be returned for object 30 when the master requests variation 0. If the parameter is set to N, variation 4 will be returned. If the parameter is set to Y, variation 2 will be returned.
7.4.41 AI Events with time
Y or N
This parameter determines if the analog input events generated by the module will include the date and time of the event. If the parameter is set to N, the default is set to no time data. If the parameter is set to Y, the default object will include the time of the event.
7.4.42 Time Sync Before Events
Y or N
This parameter determines if events are to be generated by the module before the time synchronization from the master unit. If the parameter is set to N, no events will be generated until the module's time has been synchronized. If the parameter is set to Y, events will always be generated.
7.4.43 Initialize DNP Database
Y or N
This parameter determines if the module will request data from the processor to initialize the DNP database output data areas. If this option is utilized, ladder logic is required to send the requested block from the processor to the module.
7.5 [DNP Slave Database]
The [DNP SLAVE DATABASE] section contains the information to size the database to be used to interface with the remote master. The values entered in this section define the blocks to be transferred between the module and the processor over the backplane and the data to be interfaced with the remote DNP master device. The parameters defined in this section are shown in the configuration form.
[DNP Slave Database]
Binary Inputs : 512 #0-512 point count to hold BI data
Analog Inputs : 50 #0-512 points of analog input data
Float Inputs : 5 #0-128 points of floating-point format data
Counters : 20 #0-128 points of counter data
Binary Outputs : 160 #0-512 point count to hold BO data
Analog Outputs : 28 #0-512 points of analog output data
Float Outputs : 4 #0-128 points of floating-point format data
Page 68 of 153 ProSoft Technology, Inc.
April 22, 2008
Modifying the Configuration File PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
0 to 512 points
Number of digital input points to configure in the DNP slave device. Each point will be stored as a single word in the module memory.
0 to 512 points
Number of analog input points to configure in the DNP slave device. Each point will occupy a two word area in the module memory.
0 to 128 points
Number of floating-point input points to configure in the DNP slave device. Each point will occupy a three word area in the module memory.
7.5.4 Counters
0 to 128 points
Number of counter points to configure in the DNP slave device. Each point will occupy a three word area in the module memory. This number corresponds to the number of frozen counters. The application maps the counters to the frozen counters directly.
0 to 512 points
Number of digital output points to configure in the DNP slave device. Each point will be stored as a single word in the module memory.
0 to 512 points
Number of analog output points to configure in the DNP slave device. Each point will occupy a two word area in the module memory.
0 to 128 points
Number of floating-point output points to configure in the DNP slave device. Each point will occupy a three word area in the module memory.
ProSoft Technology, Inc.
April 22, 2008
Page 69 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
7.6 [DNP Slave Binary Inputs]
Modifying the Configuration File
This area is to override the class (2) binary input database points.
#
# Point# Class
Start
# 0 1
# 1 2
# 2 3
# 3 0 #Events will never be generated for this point
End
This is the information object address of the point.
7.6.2 Class
Class 1 - Highest priority
Class 2 - Middle priority
Class 3 - Lowest priority
0 - Disable.
7.7 [DNP Slave Analog Inputs]
This area is to override the class (3) and deadband for the integer analog input database. The point # is the offset from the start of the analog input database.
#
# Point# Class Deadband
Start
# 6 1 2000 #points 0-5=class 1, deadband = 1000
# 7 1 2000
# 8 2 1000
End
[Section]/Item
[DNP Slave Analog
Inputs]
Description
DNP database analog input override values
This is the information object address of the point.
7.7.2 Class
Class 1 - Highest priority
Class 2 - Middle priority
Class 3 - Lowest priority
Page 70 of 153 ProSoft Technology, Inc.
April 22, 2008
Modifying the Configuration File
0 - Disable.
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
7.7.3 Deadband
A range of values within which the module will avoid generating events.
7.8 [DNP Slave Float Inputs]
This area is to override the class (3) and debased for the single float database.
The point # is not the address in the analog database, but is the offset from the start of the single floating-point database.
#
# Point# Class Deadband
Start
0 1 100.
1 2 12.34
3 0 13.45 #Events will never be generated for this point
4 2 3000.0 #points 5 to 11=class 1, deadband = 1000.00
End
This is the information object address of the point.
7.8.2 Class
Class 1 - Highest priority
Class 2 - Middle priority
Class 3 - Lowest priority
0 - Disable.
7.8.3 Deadband
A range of values within which the module will avoid generating events.
[Secondary Port]
Type : S #' '=Disabled, S=Backup Slave
Baud Rate : 19200 #Baud rate for port 110-115200
RTS On : 10 #0-65535 milliseconds before message
RTS Off : 0 #0-65535 milliseconds after message
Min Response Delay : 0 #0-65535 milliseconds before response sent from slave
# Collision Avoidance parameters
Collision Avoidance : No #Use Collision Avoidance (N=No, Y=Yes)
CD Idle Time : 10 #0-32000 mSec min idle time before transmit
CD Random Time : 20 #0-32000 mSec random idle time before transmit
CD Time Before Receive : 6 #0-65535 milliseconds before receive
ProSoft Technology, Inc.
April 22, 2008
Page 71 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Modifying the Configuration File
[Secondary Port]
Type:
Baud Rate:
RTS On:
RTS Off:
Min Response Delay:
Collision Avoidance:
CD Idle Time:
CD Random Time:
CD Time Before
Receive:
Definitions for secondary port on module
S or blank This parameter defines the functionality of the secondary port on the module.
S = back-up DNP slave port to the primary port.
Any other value will disable the port.
Baud rate value
0 to 65535 millisecond s
Secondary DNP Port Baud Rate: 300,
600, 1200, 2400, 4800, 9600, 19200,
384 (38400) , 576 (57600), 115
(115200)
This value represents the number of 1 ms increments to be inserted between asserting the RTS modem line and the actual transmission of the data.
0 to 65535 millisecond s
0 to 65535 millisecond s
This value represents the number of 1 ms increments to be inserted after the last character of data is transmitted before the RTS modem line is dropped.
Minimum time between receiving a request and transmitting a response.
Allows master time to disable transmitter on an RS-485 network.
Y or N This parameter defines if collision avoidance will be utilized on the primary
DNP slave port.
0 to 32000 Defines the minimum number of milliseconds to wait before transmitting a message after the CD signal is recognized as low.
0 to 32000 Defines the range of random time to be added to the CD Idle Time before a message will be transmitted from the slave.
0 to 65535 Defines the number of milliseconds to wait before receiving characters after the CD signal is recognized as high.
7.9.1 Type
S or blank
This parameter defines the functionality of the secondary port on the module.
S = back-up DNP slave port to the primary port.
Any other value will disable the port.
Baud rate value
Page 72 of 153 ProSoft Technology, Inc.
April 22, 2008
Modifying the Configuration File PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
DNP Port Baud Rate: 300, 600, 1200, 2400, 4800, 9600, 19200, 384 (38400) ,
576 (57600), 115 (115200)
0 to 65535 milliseconds
This value represents the number of 1 ms increments to be inserted between asserting the RTS modem line and the actual transmission of the data.
0 to 65535 milliseconds
This value represents the number of 1 ms increments to be inserted after the last character of data is transmitted before the RTS modem line is dropped.
7.9.5 Min Response Delay
0 to 65535 milliseconds
Minimum time between receiving a request and transmitting a response. Allows master time to disable transmitter on an RS-485 network.
Y or N
This parameter defines if collision avoidance will be utilized on the primary DNP slave port.
7.9.7 CD Idle Time
0 to 32000
Defines the minimum number of milliseconds to wait before transmitting a message after the CD signal is recognized as low.
7.9.8 CD Random Time
0 to 32000
Defines the range of random time to be added to the CD Idle Time before a message will be transmitted from the slave.
7.9.9 CD Time Before Receive
0 to 65535
Defines the number of milliseconds to wait before receiving characters after the
CD signal is recognized as high.
ProSoft Technology, Inc.
April 22, 2008
Page 73 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
7.10 Download the Project to the Module
Modifying the Configuration File
In order for the module to use the settings you configured, you must download
(copy) the updated Project file from your PC to the module.
To Download the Project File
1
In the tree view in ProSoft Configuration Builder, click once to select the PTQ-
DNPS module.
2
Open the Project menu, and then choose Module / Download. The program will scan your PC for a valid com port (this may take a few seconds). When
PCB has found a valid com port, the following dialog box will open.
3
Choose the com port to use from the dropdown list, and then click the
Download button.
The module will perform a platform check to read and load its new settings.
When the platform check is complete, the status bar in ProSoft Configuration
Builder will be updated with the message "Module Running".
7.11 Verification and Troubleshooting
You can now verify that the module is configured properly by viewing parameters that you specified in the configuration file. This is done using the module's Main
Menu. If you are not already at the Main menu, press [Shift][/].
Use the database menu to verify that data appears in registers that you've
mapped. Refer to Diagnostics and Troubleshooting (page 77) for information on
accessing information on the operation of the module.
Page 74 of 153 ProSoft Technology, Inc.
April 22, 2008
Modifying the Configuration File PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Use the DNP Statistics screen to view the communication status. Refer to
Viewing DNP Communication Status for more information.
ProSoft Technology, Inc.
April 22, 2008
Page 75 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Modifying the Configuration File
Page 76 of 153 ProSoft Technology, Inc.
April 22, 2008
Diagnostics and Troubleshooting PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
In This Chapter
Reading Status Data from the Module .................................................. 77
LED Indicators............................................................................ 87
The module provides information on diagnostics and troubleshooting in the following forms:
Status data values are transferred from the module to the processor.
Data contained in the module can be viewed through the
Configuration/Debug port attached to a terminal emulator.
LED status indicators on the front of the module provide information on the module's status.
8.1 Reading Status Data from the Module
The PTQ-DNPS module returns a Status Data block that can be used to determine the module's operating status. This data is located in the module's database status database and error status list. This data is transferred to the
Quantum / Unity processor read blocks with an identification code of 100. For a complete listing of the status data object, refer to the Installing and Configuring the Module section.
You can connect directly from your computer's serial port to the serial port on the module to view configuration information, perform maintenance, and send
(upload) or receive (download) configuration files.
ProSoft Technology recommends the following minimum hardware to connect your computer to the module:
80486 based processor (Pentium preferred)
1 megabyte of memory
At least one UART hardware-based serial communications port available.
USB-based virtual UART systems (USB to serial port adapters) often do not function reliably, especially during binary file transfers, such as when uploading/downloading configuration files or module firmware upgrades.
A null modem serial cable.
ProSoft Technology, Inc.
April 22, 2008
Page 77 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Diagnostics and Troubleshooting
The Configuration and Debug menu for this module is arranged as a tree structure, with the Main Menu at the top of the tree, and one or more sub-menus for each menu command. The first menu you see when you connect to the module is the Main menu.
Because this is a text-based menu system, you enter commands by typing the command letter from your computer keyboard in the diagnostic window in
ProSoft Configuration Builder (PCB). The module does not respond to mouse movements or clicks. The command executes as soon as you press the command letter — you do not need to press [Enter]. When you type a command letter, a new screen will be displayed in your terminal application.
Using the Diagnostic Window in ProSoft Configuration Builder
To connect to the module's Configuration/Debug serial port:
1
Start PCB program with the application file to be tested. Right click over the module icon.
2
On the shortcut menu, choose Diagnostics.
Page 78 of 153 ProSoft Technology, Inc.
April 22, 2008
Diagnostics and Troubleshooting PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
3
This action opens the Diagnostics dialog box. Press "?" to display the Main
Menu.
Important: The illustrations of configuration/debug menus in this section are intended as a general guide, and may not exactly match the configuration/debug menus in your own module.
If there is no response from the module, follow these steps:
1
Verify that the null modem cable is connected properly between your computer's serial port and the module. A regular serial cable will not work.
2
On computers with more than one serial port, verify that your communication program is connected to the same port that is connected to the module.
If you are still not able to establish a connection, contact ProSoft Technology for assistance.
Navigation
All of the sub-menus for this module contain commands to redisplay the menu or return to the previous menu. You can always return from a sub-menu to the next higher menu by pressing [M] on your keyboard.
ProSoft Technology, Inc.
April 22, 2008
Page 79 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Diagnostics and Troubleshooting
The organization of the menu structure is represented in simplified form in the following illustration:
The remainder of this section shows you the menus available for this module, and briefly discusses the commands available to you.
Keystrokes
The keyboard commands on these menus are almost always non-case sensitive.
You can enter most commands in lower case or capital letters.
The menus use a few special characters ([?], [-], [+], [@]) that must be entered exactly as shown. Some of these characters will require you to use the [Shift],
[Ctrl]
or [Alt] keys to enter them correctly. For example, on US English keyboards, enter the [?] command as [Shift][/].
Also, take care to distinguish capital letter [I] from lower case letter [l] (L) and number [1]; likewise for capital letter [O] and number [0]. Although these characters look nearly the same on the screen, they perform different actions on the module.
When you first connect to the module from your computer, your terminal screen will be blank. To activate the main menu, press the [?] key on your computer's keyboard. If the module is connected properly, the following menu will appear on your terminal screen:
Page 80 of 153 ProSoft Technology, Inc.
April 22, 2008
Diagnostics and Troubleshooting PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Caution: Some of the commands available to you from this menu are designed for advanced debugging and system testing only, and can cause the module to stop communicating with the processor or with other devices, resulting in potential data loss or other failures. Only use these commands if you are specifically directed to do so by ProSoft Technology Technical Support staff.
Some of these command keys are not listed on the menu, but are active nevertheless. Please be careful when pressing keys so that you do not accidentally execute an unwanted command.
8
9
A
4
5
6
C
D
E
0
1
2
Setting the Debug Level
You can increase or decrease the level of debug messages sent from the module to the Debug Menu. The following table shows the type of debugging information for each key [0] to [9], [A] to [F]
Key None
X
X
Messages
X
DPA Level
Messages
X
X
X
X
X
X
X
X
X
X
X
X
Viewing the Error List
Press [L] to display the last 60 errors for the DNP slave port. Refer to the error list section of the user manual to interpret each error recorded by the module.
If there are no errors present for the module, the message "NO ERRORS FOR
SYSTEM!" is displayed.
Viewing DNP Set Up & Pointers
Press [P] to display the memory allocation and the database setup parameters.
Viewing Operating Parameters
Press [O] to view the DNP Protocol setup information (Operating Parameters) for the module.
ProSoft Technology, Inc.
April 22, 2008
Page 81 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Warm Booting the Module
Diagnostics and Troubleshooting
Caution: Some of the commands available to you from this menu are designed for advanced debugging and system testing only, and can cause the module to stop communicating with the processor or with other devices, resulting in potential data loss or other failures. Only use these commands if you are specifically directed to do so by ProSoft Technology Technical Support staff.
Some of these command keys are not listed on the menu, but are active nevertheless. Please be careful when pressing keys so that you do not accidentally execute an unwanted command.
Press [R] from the Main Menu to warm boot (restart) the module. This command will cause the program to exit and reload, refreshing configuration parameters that must be set on program initialization. Only use this command if you must force the module to re-boot.
Viewing Comm Stats
Press [S] to view the communication status for the DNP port.
Clearing the Error List
Press [W] to clear the error list. Use this command after viewing the error list
(page 81) to delete the current list of errors and start a new list.
Viewing COM States
Press [V] to view the current state of the DNP application port and the port configuration information.
Viewing Version Information
Press [G] to view Version information for the module.
Use this command to view the current version of the software for the module, as well as other important values. You may be asked to provide this information when calling for technical support on the product.
Values at the bottom of the display are important in determining module operation. The Program Scan Counter value is incremented each time a module's program cycle is complete.
Tip: Repeat this command at one-second intervals to determine the frequency of program execution.
Opening the Class Assignment Menu
Press [Y] to view the class and deadband override values for the binary, analog, float and double input DNP database.
Opening the DNP Database View Menu
Press [U] to open the DNP Database View Menu. This menu allows you to view all data associated with the DNP Server driver. For more information about the
commands on this menu, refer to DNP Database View Menu (page 84).
Page 82 of 153 ProSoft Technology, Inc.
April 22, 2008
Diagnostics and Troubleshooting PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Receiving the Configuration File
Press [<] (Shift Comma) to download (receive) the current configuration file from the module. For more information on receiving and sending configuration files, please see Uploading and Downloading the Configuration File.
Sending the Configuration File
Press [>] (Shift Period) to upload (send) an updated configuration file to the module. For more information on receiving and sending configuration files, please see Uploading and Downloading the Configuration File.
Viewing Block Transfer Statistics
Press [N] from the Main Menu to view the Block Transfer Statistics screen.
Use this command to display the configuration and statistics of the backplane data transfer operations between the module and the processor. The information on this screen can help determine if there are communication problems between the processor and the module.
Tip: Repeat this command at one-second intervals to determine the number of blocks transferred each second.
Viewing DNP Server Data
Press [I] to view all data associated with the DNP server driver.
ProSoft Technology, Inc.
April 22, 2008
Page 83 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
8.1.4 DNP Database View Menu
Diagnostics and Troubleshooting
Use this menu command to view the current contents of the selected database.
Press [?] to view a list of commands available on this menu.
M = Main Menu
D = Database Menu
? = Display Menu
0 – 5 = Pages 0 to 5000
S = Show Again
– = Back 5 Pages
P = Previous Page
+ = Skip 5 Pages
N = Next Page
D = Decimal Display
H = Hexadecimal Display
F = Float Display
A = ASCII Display
M = Main Menu
Redisplays (refreshes) this menu
Selects page 0, 1000, 2000 or 3000
Redisplays last selected page of data
Goes back five pages of data
Goes back one page of data
Goes forward five pages of data
Goes forward one page of data
Displays data in decimal format
Displays data in hex format
Displays data in floating point format
Displays data in text format
Goes up one level to main menu
Page 84 of 153 ProSoft Technology, Inc.
April 22, 2008
Diagnostics and Troubleshooting PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Viewing Data Type Databases
Press [D] from the DNP menu, then hold down the [Shift] key and press the / key.
Use the number keys 1 to 6 to select the display of the data type you wish to view. For example, if the '1' key is pressed, the following is displayed:
Viewing Register Pages
To view sets of register pages, use the keys described below:
Command Description
[0]
[1]
[2]
Display registers 0 to 99
Display registers 1000 to 1099
Display registers 2000 to 2099
And so on. The total number of register pages available to view depends on your module's configuration.
Displaying the Current Page of Registers Again
This screen displays the current page of 100 registers in the database.
ProSoft Technology, Inc.
April 22, 2008
Page 85 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Diagnostics and Troubleshooting
Moving Back Through 5 Pages of Registers
Press [-] from the Database View menu to skip back to the previous 500 registers of data.
Viewing the Previous 100 Registers of Data
Press [P] from the Database View menu to display the previous 100 registers of data.
Skipping 500 Registers of Data
Hold down [Shift] and press [=] to skip forward to the next 500 registers of data.
Viewing the Next 100 Registers of Data
Press [N] from the Database View menu to select and display the next 100 registers of data.
Viewing Data in Decimal Format
Press [D] to display the data on the current page in decimal format.
Viewing Data in Hexadecimal Format
Press [H] to display the data on the current page in hexadecimal format.
Viewing Data in Floating Point Format
Press [F] from the Database View menu. Use this command to display the data on the current page in floating point format. The program assumes that the values are aligned on even register boundaries. If floating-point values are not aligned as such, they are not displayed properly.
Viewing Data in ASCII (Text) Format
Press [A] to display the data on the current page in ASCII format. This is useful for regions of the database that contain ASCII data.
Viewing Data in Double Word Decimal Format
Press [L] to display the data on the current page in Double Word Decimal format.
This is useful for regions of the database that contain Double Word Decimal data.
Viewing Data in Double Word Decimal Format
Press [X] to display the data on the current page in Double Word Hexadecimal format. This is useful for regions of the database that contain Double Word
Hexadecimal data.
Viewing DNP Binary Inputs
Press [1] to view a list of DNP Binary Inputs.
Page 86 of 153 ProSoft Technology, Inc.
April 22, 2008
Diagnostics and Troubleshooting
Viewing DNP Binary Outputs
Press [2] to view a list of DNP Binary Outputs.
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Viewing DNP Counters
Press [3] to view a list of DNP Counters.
Viewing DNP Analog Inputs
Press [4] to view a list of DNP Analog Inputs.
Viewing DNP Analog Outputs
Press [5] to view a list of DNP Analog Outputs.
Viewing DNP Frozen Counters
Press [6] to view a list of DNP Frozen Counters.
Viewing DNP Float Inputs
Press [7] to view a list of DNP Float Inputs.
Viewing DNP Float Outputs
Press [9] to view a list of DNP Float Outputs.
Returning to the Main Menu
Press [M] to return to the Main Menu.
8.2 LED Status Indicators
The LEDs indicate the module's operating status as follows:
ProSoft
Module
Color Status Indication
Off
Off
Off
On
Data is being transferred between the module and a remote terminal using the Configuration/Debug port.
No data is being transferred on the Configuration/Debug port.
Data is being transferred between the module and the DNPS network on its DNPS Primary slave port.
No data is being transferred on the port.
Data is being transferred between the module and the DNPS network on its Port 3. This may either be configured as a
DNPS master or backup slave port.
No data is being transferred on the port.
The PTQ-DNPS is working normally.
The PTQ-DNPS module program has recognized a communication error on one of its DNPS ports.
ProSoft Technology, Inc.
April 22, 2008
Page 87 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Diagnostics and Troubleshooting
ProSoft
Module
BP ACT
Color Status Indication
Amber
Green
On
Off
Green
Red
On
The LED is on when the module is performing a write operation on the backplane.
The LED is off when the module is performing a read operation on the backplane. Under normal operation, the
LED should blink rapidly on and off.
The card is not receiving any power and is not securely plugged into the rack.
The module is operating normally.
The program has detected an error or is being configured. If the LED remains red for over 10 seconds, the program has probably halted. Remove the card from the rack and re-insert the card to restart the module's program.
The battery voltage is OK and functioning.
The battery voltage is low or battery is not present. Allow battery to charge by keeping module plugged into rack for 24 hours. If BAT LED still does not go off, contact ProSoft
Technology, as this is not a user serviceable item.
If the APP, BP ACT and OK LEDs blink at a rate of every one-second, this indicates a serious problem with the module. Call ProSoft Technology support to arrange for repairs.
8.2.1 Clearing a Fault Condition
Typically, if the OK LED on the front of the module turns red for more than ten seconds, a hardware problem has been detected in the module, or the program has exited.
To clear the condition, follow these steps:
1
Turn off power to the rack
2
Remove the card from the rack
3
Verify that all jumpers are set correctly
4
If the module requires a Compact Flash card, verify that the card is installed correctly
5
Re-insert the card in the rack and turn the power back on
6
Verify the configuration data being transferred to the module from the
Quantum / Unity processor.
If the module's OK LED does not turn green, verify that the module is inserted completely into the rack. If this does not cure the problem, contact ProSoft
Technology Support.
8.2.2 Troubleshooting
Use the following troubleshooting steps if you encounter problems when the module is powered up. If these steps do not resolve your problem, please contact
ProSoft Technology Technical Support.
Page 88 of 153 ProSoft Technology, Inc.
April 22, 2008
Diagnostics and Troubleshooting
Processor Errors
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Problem Description Steps to take
Processor Fault Verify that the module is plugged into the slot that has been configured for the module.
Verify that the slot in the rack configuration has been set up correctly in the ladder logic.
Processor I/O LED flashes
This indicates a problem with backplane communications. Verify that all modules in the rack are configured in the ladder logic.
Module Errors
Problem Description Steps to take
BP ACT LED remains off or blinks slowly
This indicates that backplane transfer operations are failing. Connect to the module's Configuration/Debug port to check this.
To establish backplane communications, verify the following items:
The processor is in Run mode.
The backplane driver is loaded in the module.
The module is configured for read and write block data transfer.
OK LED remains red
The ladder logic handles all read and write block situations.
The module is configured in the processor.
The program has halted or a critical error has occurred. Connect to the
Configuration/Debug port to see if the module is running. If the program has halted, turn off power to the rack, remove the card from the rack and re-insert the card in the rack, and then restore power to the rack.
ProSoft Technology, Inc.
April 22, 2008
Page 89 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Diagnostics and Troubleshooting
Page 90 of 153 ProSoft Technology, Inc.
April 22, 2008
Distributed Network Protocol Interface Module
9 Reference
In This Chapter
Master Port DNPS Slave Configuration Values (DNPS Master Slave List)
Command
Entry Form................................................................... 126
DNP Definition......................................................................... 129
The ProTalk DNPS 3.0 Slave Communication Module (PTQ-DNPS) is a
Quantum backplane compatible module that allows Quantum processors to interface easily with DNP 3.0 compatible devices and hosts. Devices commonly supporting the protocol include relays, breakers, sub-station
Communication Modules and other serial devices most commonly associated with power monitoring.
9.1.1 Features and Benefits
The module supports DNP Subset Level 2 features and some of the Level 3 features allowing the many SCADA and field devices supporting the DNP protocol to be integrated into the Quantum platform. The module acts as an input/output module between the DNP network and the Modicon backplane. The data transfer from the Quantum processor is asynchronous from the actions on the DNP network. Databases are user defined and stored in the module to hold the data required by the protocol.
The PTQ-DNPS module is a powerful communication interface for Quantum platform processors. Developed under license from Schneider Electric, the module incorporates proprietary backplane technology that enables powerful data access to the Quantum processor.
Single Slot - Quantum backplane compatible
ProSoft Technology, Inc.
April 22, 2008
Page 91 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Reference
The module is recognized as an Options module and has access to PLC memory for data transfer
Configuration data is stored in non-volatile memory in the ProTalk module
Configuration software for Microsoft Windows XP, 2000 and NT is included with the module.
Up to six modules can be placed in a rack
Local rack - The module must be placed in the same rack as processor.
Compatible with common Quantum / Unity programming tools. o o o
UnityPro XL
Concept
ProWORX
Quantum data types supported: 3x, 4x
High speed data transfer across backplane provides quick data update times.
Sample ladder file available.
Specification Value
Backplane Current
Load
800 mA @ 5 V
Operating
Temperature
0 to 60°C (32 to 140°F)
Storage Temperature -40 to 85°C (-40 to 185°F)
Relative Humidity 5% to 95% (non-condensing)
Vibration
Shock
LED Indicators
Sine vibration 4-100 Hz in each of the 3 orthogonal axes
30G, 11 mSec. in each of the 3 orthogonal axes
Module Status
Configuration Serial
Port (PRT1)
Backplane Transfer Status
Serial Port Activity LED
Serial Activity and Error LED Status
DB-9M PC Compatible
Application Serial
Ports
RS-232 only
No hardware handshaking
(PRT2, PRT3)
DB-9M PC Compatible
RS-232/422/485 jumper selectable
RS-422/485 screw termination included
RS-232 handshaking configurable
500V Optical isolation from backplane
Page 92 of 153 ProSoft Technology, Inc.
April 22, 2008
Distributed Network Protocol Interface Module
The PTQ-DNPS module supports the DNP 3.0 protocol with a minimum of Level
2 functionality. DNP protocol Subset Definitions for the Slave drivers are available in the module's User Manual.
The module has two DNP protocol ports that can be user configured to operate in a Slave/Slave redundant port configuration.
The module has 4000 words of user defined internal register space that are accessible to the protocol driver and to the Quantum processor memory.
Redundant Slave Port Operation
When configured in the Slave/Slave port configuration, the module's slave ports operate in a primary and secondary fashion. In this mode, a single host polls the module via redundant physical layer connections. Several methods are supported to automatically switch between the primary and secondary slave ports.
DNP 3.0 Slave Protocol Specifications
The DNP Slave port(s) accepts DNP commands to control and monitor data stored in the module's DNP Slave databases.
Report-by-Exception data is logged to the module's database
Supports unsolicited messaging
Each DNP point type is user configurable by point
Total point counts must be configured so that Class 0 responses do not exceed 2048 bytes in size
Class assignments are completely user-definable on a Type and point basis
(BI, AI, FI, DI point types)
The analog inputs are class and deadband configurable on a point basis for all formats (integer, float, double float)
Supports clock synchronization from a master or from the Quantum
Support for four octet-strings are supported (object type 110) in the slave driver to return version and other module information
Up to 400 events are stored for Floats, Binary In, Analog In and Double
Inputs
In addition to the module generated events, AI and BI events can be generated in the Quantum and transferred to the module (useful with external timestamping hardware)
Configurable event buffer transmission threshold based on count and/or time since last event transmission
Collision avoidance algorithm per DNP organization for redundant port switching (redundant slave mode)
Special modem AT command string and timing support for dialing out on redundant port (redundant slave mode)
ProSoft Technology, Inc.
April 22, 2008
Page 93 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Reference
This section provides an overview of how the PTQ-DNPS module transfers data using the DNPS protocol. You should understand the important concepts in this chapter before you begin installing and configuring the module.
The following discussion explains several concepts that are important for understanding the operation of the PTQ-DNPS module.
Module Power Up
On power up the module begins performing the following logical functions:
1
Initialize hardware components o o o
Initialize Quantum / Unity backplane driver
Test and clear all RAM
Initialize the serial communication ports
2
Read configuration file from Random Access Memory
3
Enable Slave Driver
After the module has received the configuration, the module will begin communicating with other nodes on the network, depending on the configuration.
Main Logic Loop
Upon completing the power up configuration process, the module enters an infinite loop that performs the functions shown in the following diagram.
From Power Up Logic
Call I/O Handler
Call I/O Handler
Transfers data between the module and processor
(user, status, etc.)
Call CFG/DEBUG Port
Driver
Call Serial Port Driver
Rx and Tx buffer routines are interrupt driven. Call to serial port routines check to see if there is any data in the buffer, and depending on the value, will either service the buffer or wait for more characters.
Call Network Server
Drivers
Call Network Server Drivers
Respond to messages received.
Page 94 of 153 ProSoft Technology, Inc.
April 22, 2008
Distributed Network Protocol Interface Module
Backplane Data Transfer
The current version of the PTQ-DNPS backplane driver (version 2.0) uses a
Large I/O model, which differs from previous versions of the backplane driver in that it transfers all of the data in the input and output databases between the module and the processor on every scan.
The [Backplane Configuration] section of the configuration file defines the starting register for input and output. The typical configuration is 5000 words read (3x/ %
IW) and 5000 words write (4x / % MW).
The following parameters control how much database content will be transferred between the Processor and the Module:
Binary Inputs
Analog Inputs
Float Inputs
Counters
Binary Outputs
Analog Outputs
Float Outputs
Example 1 (Sample Default Values)
Binary Inputs : 100 #0-512 point count to hold BI data
Analog Inputs : 100 #0-512 points of analog input data
Float Inputs : 10 #0-128 points of floating-point format data
Counters : 10 #0-128 points of counter data
Binary Outputs : 100 #0-512 point count to hold BO data
Analog Outputs : 100 #0-512 points of analog output data
Float Outputs : 10 #0-128 points of floating-point format data
ProSoft Technology, Inc.
April 22, 2008
Page 95 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Reference
The following illustration shows the data transfer between processor and Module using the configuration values in Example 1:
Processor
Holding Registers
400001
Control
Words
0 - 64
400064
Binary
Inputs
65 - 164
Analog
Inputs
165 - 364
Float Inputs
365 - 394
Counters
395 - 424
400424
Module
Special
Blocks
0 - 64 word
300001
300064
Binary Inputs points
0 - 99
Analog
Inputs
0 - 99
Float Inputs
0 - 9
Counters
0 - 9
Input Registers
400425
Binary
Outputs
425 - 524
400524
Analog
Outputs
525 - 724
Float
Outputs
725-754
400754
Binary
Outputs
0 - 99
Analog
Outputs
0 - 99
Float
Outputs
0 - 9
Input Registers
300065
Binary
Outputs
65-164
300164
Analog
Outputs
165-364
Float
Outputs
365-664
300664
Binary
Outputs
Data & Flags
0-99
Analog
Outputs
Data & Flags
0-99
Float
Outputs
Data & Flags
0-9
Example 2
Binary Inputs : 160 #0-512 point count to hold BI data
Page 96 of 153 ProSoft Technology, Inc.
April 22, 2008
Distributed Network Protocol Interface Module
Analog Inputs : 100 #0-512 points of analog input data
Float Inputs : 20 #0-128 points of floating-point format data
Counters : 20 #0-128 points of counter data
Binary Outputs : 160 #0-512 point count to hold BO data
Analog Outputs : 50 #0-512 points of analog output data
Float Outputs : 10 #0-128 points of floating-point format data
ProSoft Technology, Inc.
April 22, 2008
Page 97 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Reference
The following illustration shows the data transfer between processor and Module using the configuration values in Example 2:
Processor
Holding Registers
400001
Control
Words
0 - 64
400064
400065
Binary
Inputs
65 - 224
400224
Analog
Inputs
225 - 424
Float
Inputs
425 - 484
Counters
485 - 544
400544
Module
Special
Blocks
0 - 64
Word
Binary
Inputs
Points
0 - 159
Analog
Inputs
0 - 99
Float
Inputs
0 - 19
Counters
0 - 19
Input Registers
300544
Binary
Outputs
545 - 704
300704
Analog
Outputs
705 - 804
Float
Outputs
805 - 834
300834
Binary
Outputs
0 - 159
Analog
Outputs
0 - 49
Float
Outputs
0 - 9
Input Registers
300065
Binary
Outputs
65-224
300224
Analog
Outputs
225-324
Float
Outputs
325-354
300354
Binary
Outputs
Data & Flag
0-159
Analog
Outputs
Data & Flag
0-49
Float
Outputs
Data & Flag
0-9
Page 98 of 153 ProSoft Technology, Inc.
April 22, 2008
ProSoft Technology, Inc.
April 22, 2008
Distributed Network Protocol Interface Module
9.2.2 Input and Output Data Blocks
1
2
3
4
Status Block 9250
Block 9250 identification code requests the module's status data. The module supports a buffer queue of 99 events per data type. The application can verify the status of the queue (free space in the queue) through the module's status data
(Block 9250). When the queue is full, the module will delete the older event in the queue if a new event is received.
There are two ways to request status data:
Read the data in the database, starting at word 4000. Refer to Error Status
Table for detailed information.
Request the entire status block with a block 9250 block request.
The module responds to a valid block 9250 request with a block containing the requested status data. The status data area for the module starts at address
4000 in the database.
Block Format for Read
The format of this block is shown in the following table:
Word Offset Variable Name Description
5
6
7
8
Status request block
Current DNP Slave Port status
DNP Slave Port last transmitted error code
DNP Slave Port total number of message frames received by slave
DNP Slave Port total number of response message frames sent from slave
DNP Slave Port total number of message frames seen by slave
DNP Slave synchronization error count (Physical Layer
Error)
DNP Slave overrun error count (Physical
Layer Error) handled.
This word will contain the value of 9250 when the operation is complete.
This value represents the current value of the error code for the port. This value will only be valid if the port is configured as a slave. The possible values are described in the application documentation.
This value represents the last error code transmitted to the master by this slave port.
This value represents the total number of message frames that have matched this slaves address on this port. This count includes message frames which the slave may or may not be able to parse and respond.
This value represents the number of good (non-error) responses that the slave has sent to the master on this port. The presumption is that if the slave is responding, the message was good. Note: This is a frame count.
This value represents the total number of message frames received by the slave, regardless of the slave address.
This value counts the number of times a sync error occurs. The error occurs when extra bytes are received before the start bytes (0x05 and 0x64) are received.
This value counts the number of times the overrun error occurs. This error occurs when the mainline Data
Link Layer routine cannot read the data received on the communication port before it is overwritten.
Page 99 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Reference
Word Offset
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
Variable Name
DNP Slave length error count (Physical Layer
Error)
DNP Slave bad CRC error (Data Link Layer
Error)
DNP Slave user data overflow error
(Transport Layer Error)
DNP Slave sequence error (Transport Layer
Error)
DNP Slave address error (Transport Layer
Error)
DNP Slave Binary Input
Event count
DNP Slave Binary Input
Event count in buffer
DNP Slave Analog Input
Event count
DNP Slave Analog Input
Event count in buffer
DNP Slave bad function code error (Application
Layer Error)
DNP Slave object unknown error
(Application Layer
Error)
DNP Slave out of range error (Application Layer
Error)
DNP Slave message overflow error
(Application Layer
Error)
Description
This value counts the number of times an invalid length byte is received. If the length of the message does not match the length value in the message, this error occurs.
This value counts the number of times a bad CRC value is received in a message.
This value counts the number of times the application layer receives a message fragment buffer which is too small.
This value counts the number of times the sequence numbers of multi-frame request fragments do not increment correctly.
This value counts the number of times the source addresses contained in a multi-frame request fragments do not match.
This value contains the total number of binary input events which have occurred.
This value represents the number of binary input events which are waiting to be sent to the master.
This value contains the total number of analog input events which have occurred.
This value represents the number of analog input events which are waiting to be sent to the master.
This value counts the number of times a bad function code for a selected object/variation is received by the slave device.
This value counts the number of times a request for an unsupported object is received by the slave device.
This value counts the number of times a parameter in the qualifier, range or data field is not valid or out of range.
This value counts the number of times an application response message from the slave is too long to transmit.
DNP Slave multi-frame message from DNP
Master error
(Application Layer
Error)
This value counts the number of times the slave receives a multi-frame message from the master. The application does not support multi-frame master messages.
Total blocks transferred Total BTR/BTW or side-connect interface transfers attempted by the module.
Successful blocks transferred
This value represents the total number of transfer operations between the PLC and module that are successful.
Total errors in block transfer
Total BTR or write errors
Total number of transfers that resulted in an error condition.
Total number of BTR or write transfers that resulted in an error.
Page 100 of 153 ProSoft Technology, Inc.
April 22, 2008
Distributed Network Protocol Interface Module
Word Offset Variable Name
27 Total BTW or read errors
29
30
Description
Total number of BTW or read transfers that resulted in an error.
Number of BTW requests that resulted in an incorrect
BTW identification code.
Continuous block error counter
Count of sequential data transfer errors. When this value exceeds that specified for the data transfer operation, the error flag below will be set.
Block transfer error flag This flag indicates that data is not being successfully transferred between the PLC and the module. This flag corresponds to the Device Trouble IIN bit.
32 to 33
34 to 35
36 to 37
38 to 39
40
42 the module. The codes are as follows: 0=Single Slave
Configuration or 1=Dual Slave Configuration with one slave active while other is backup.
Product Name (ASCII) These two words contain the product name of the module in ASCII format.
Revision (ASCII) These two words contain the product revision level of the firmware in ASCII format.
Operating System
Revision (ASCII)
Production Run Number
(ASCII)
These two words contain the module's internal operating system revision level in ASCII format.
These two words contain the production 'batch' number for the particular chip in the module in ASCII format.
Scan Counter LSB Program scan counter
Counter
Free Memory LSB Free memory in module
44
45
46
48
49
DNP Slave Port
Transmit State
Value of the DNP Slave state machine for transmit.
DNP Float Event Count Total number of events generated for analog floatingpoint input data points.
DNP Double Event
Count
Total number of events generated for analog double, floating-point input data points.
I/O parameters set
Hot-Standby status word processor is in run mode and 0 if it is not.
This status register contains a value of 0 if the I/O sizes have been read from the processor and 1 if not.
This status register contains the hot-standby status word.
Status Block 9251
Block 9251 identification code requests the module's error list data. The module supports a buffer queue of 99 events per data type.
The module responds to a valid block 9251 request with a block containing the requested error list data.
Block Format for Write
The format of this block is shown in the following table:
ProSoft Technology, Inc.
April 22, 2008
Page 101 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Reference
Word Offset Variable Name Description
This field contains a new value each time the block is handled.
1 Status Request Control
Word
This word will contain the value of 9251 when the operation is complete.
2 Error_List[0] First value in error list
3 Error_List[1] Second value in error list
- -
61 Error_List[59]
-
Last value in error list
Block Format for Read
Word Offset in Block
Data Field(s)
2 to 63
Description
This field contains a new value each time the block is handled.
ID This field contains the value of 9250 identifying the block type to the module.
Not Used Not Used
Block 9970 - Set Quantum / Unity Processor Time using Module Time
This block transfers the module's time to the Quantum / Unity processor. Ladder logic must be used to set the processor's clock using the data received. The format of the block sent from the Quantum / Unity processor has the following format:
Word Offset in Block
Data Field(s) Description
This field contains the value of 9970 identifying the block type to the module.
The module responds to the request with a read block 9970 with the following format:
Word Offset in Block
Data Field(s) Description
1 Block Write ID
2 Year
3 Month
4 Day
5 Hour
6 Minute
This is the next block requested by the module.
This field contains the four-digit year to be used with the new time value.
This field contains the month value for the new time.
Valid entry for this field is in the range of 1 to 12.
This field contains the day value for the new time. Valid entry for this field is in the range of 1 to 31.
This field contains the hour value for the new time.
Valid entry for this field is in the range of 0 to 23.
This field contains the minute value for the new time.
Valid entry for this field is in the range of 0 to 59.
Page 102 of 153 ProSoft Technology, Inc.
April 22, 2008
Distributed Network Protocol Interface Module
Word Offset in Block
Data Field(s) Description
7 Seconds
This field contains the second value for the new time.
Valid entry for this field is in the range of 0 to 59.
9
Remote Time
Synchronization
This field informs the PLC if the date and time passed has been synchronized with a remote DNPS master device on the module's slave port.
Block 9971 - Set Module's Time using the Quantum / Unity Processor Time
This block sets the clock in the module to match the clock in the Quantum / Unity processor. If the Quantum / Unity processor sends a block 9971, the module will set its time using the data contained the block. The format of the block is shown in the following table:
Block Format from Processor
Word Offset in Block
Data Field(s) Description
2 Year
3 Month
4 Day
5 Hour
6 Minute
7 Seconds
This field contains the block identification code of 9971 for the block.
This field contains the four-digit year to be used with the new time value.
This field contains the month value for the new time.
Valid entry for this field is in the range of 1 to 12.
This field contains the day value for the new time. Valid entry for this field is in the range of 1 to 31.
This field contains the hour value for the new time.
Valid entry for this field is in the range of 0 to 23.
This field contains the minute value for the new time.
Valid entry for this field is in the range of 0 to 59.
This field contains the second value for the new time.
Valid entry for this field is in the range of 0 to 59.
Block Format from Module
Word Offset in Block
Data Field(s) Description
handled.
This field contains the block identification code of 9971 for the block.
Block 9958 - Send Binary Input Events
Block 9958 identification code is used by the PLC to send a set of binary input events to the module.
ProSoft Technology, Inc.
April 22, 2008
Page 103 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Reference
Block Format from Processor
Word Offset in Block
Data Field(s) Description
This field contains a new value each time the block is handled.
This field contains the value of 9958 identifying the event block to the module.
Count This field contains the number of events contained in the block. Valid values for this field are 1 to 10.
4 DNP Binary Input Data point block transfer. This synchronizes and confirms receipt of the block by the module.
This is the data point in the DNP binary input database represented by the event. event. Only the LSB byte portion of the word is valid for the DNP protocol.
6 Month/Day Formatted: bits 0 to 4 = Day, bits 8 to 11 = Month. All other bits are ignored.
7 Hour/Minute Formatted: bits 0 to 5 = Minutes, bits 8 to 12 = Hour. All other bits are ignored.
9
10 to 15
16 to 21
22 to 27
28 to 33
34 to 39
40 to 45
46 to 51
52 to 57
58 to 63
Year
Seconds.
This is the four digit year for the event.
Six words of data for Event #2.
Six words of data for Event #3.
Six words of data for Event #4.
Six words of data for Event #5.
Six words of data for Event #6.
Six words of data for Event #7.
Six words of data for Event #8.
Six words of data for Event #9.
Six words of data for Event #10.
To insure the receipt of this block of information, the module returns a block 9958 with the sequence counter set to the value of the last successful block 9958 received.
Block Format from Module
Word Offset in Block
Data Field(s) Description
This field contains a new value each time the block is handled.
ID This field contains the value of 9958 identifying the event block to the module. the module. successful block 9958 received.
Page 104 of 153 ProSoft Technology, Inc.
April 22, 2008
Distributed Network Protocol Interface Module
Block 9959 - Send Analog Input Events
Block 9959 identification code is used by the PLC to send a set of analog input events to the module.
Block Format from Processor
Word Offset in Block
Data Field(s) Description
handled.
This field contains the value of 9959 identifying the event block to the module.
4
5 block. Valid values for this field are 1 to 10.
This field holds the sequence counter for each 9959 block transfer. This synchronizes and confirms receipt of the block by the module.
DNP Analog Input Data point
Analog Input Value
This is the data point in the DNP analog input database represented by the event.
This is the new analog input value represented in the event.
6 Month/Day Formatted: bits 0 to 4 = Day, bits 8 to 11 = Month. All other bits are ignored.
7 Hour/Minute Formatted: bits 0 to 5 = Minutes, bits 8 to 12 = Hour. All other bits are ignored.
9
10 to 15
16 to 21
22 to 27
28 to 33
34 to 39
40 to 45
46 to 51
52 to 57
58 to 63
Year
Seconds.
Four digit year value for event.
Six words of data for Event #2.
Six words of data for Event #3.
Six words of data for Event #4.
Six words of data for Event #5.
Six words of data for Event #6.
Six words of data for Event #7.
Six words of data for Event #8.
Six words of data for Event #9.
Six words of data for Event #10.
To ensure the receipt of this block of information, the module returns a BTR block
9959 with the sequence counter set to the value of the last successful block 9959 received.
Block Format from Module
Word Offset in Block
Data Field(s) Description
This field contains a new value each time the block is handled.
Block identification code for request from PLC by the module.
ProSoft Technology, Inc.
April 22, 2008
Page 105 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Word Offset in Block
Data Field(s) Description
Reference
Count This field contains the number of events processed by the module. successful block 9959 received.
This documentation describes the PTQ-DNPS module configuration and setup as it applies to application design. The design of the entire system must be complete before you attempt to implement this module with a DNP network. This includes:
definition of all the data types and point counts required for each type,
all communication parameters required for the network including media type and
the use of advanced features such as unsolicited messaging.
These must be defined for all master and slave devices on the network.
Additionally, the DNP Device Profiles and DNP Subset Definition documents for each device must be reviewed to make sure all the devices will interact on the network as expected. Failure to fully understand these important documents for all devices on the network will usually lead to many problems when implementing the design.
It is important to fully understand the DNP specification as outlined in the Basic
Four Documents. These are available to users of the DNP users group. It is recommended that all users of the module have access to these important documents as they define the DNP data types, functions and variations. It will be very difficult to implement the module without an understanding of the protocol and the rules that are defined in the specification. Additionally, potential users should review the DNP Subset and Conformance Test documents and the document that discusses DNP protocol support. These documents provide auxiliary information on the protocol. All of these documents are available to members of the DNP User Group at http://www.dnp.org (http://www.dnp.org).
Please check this site for other important information regarding the DNP protocol.
Design
In order to implement a solution using the module, the Quantum processor must be set up using predefined user data structures. This program will interact with the module by sending and receiving data and issuing special control commands.
An internal database in the Quantum processor contains the data to be used by the module and the configuration information is stored in the text file,
DNPSPTQ.CFG, stored on the module's non volatile memory. Before you generate the program or layout the data files, you must first design your system.
Time spent doing system design at the outset of the project will greatly enhance the success and ease of development of the project.
Page 106 of 153 ProSoft Technology, Inc.
April 22, 2008
Distributed Network Protocol Interface Module
Designing the system
System design defines the data requirements of the system, communication parameters, and module functionality. The application developer should refer to the person responsible for the DNP master and slave device configurations to verify that the functionality and data types required for the whole system are consistent. Review the DNP Device Profile and DNP Subset documentation for a definition of the level of DNP support offered by the module.
The following topics describe each element of system design.
Data Requirements
This phase of design defines what data elements are to be interfaced in the
Quantum processor with the DNP master. The module provides the following data types:
Digital
Digital
Counter
Floating
Analog Input
Analog
All communications between the DNP master and the PLC is through these data types. Therefore, all data to be used by the system must be contained and configured in one of these data types.
The following illustration shows the databases maintained by the module for the
DNP data.
DATA AREA
DNP DATA BINARY INPUTS
ANALOG INPUTS
FLOAT INPUTS
COUNTER DATA
BINARY OUTPUTS
ANALOG OUTPUTS
The module is responsible for maintaining the databases using data acquired from the PLC and DNP master attached network port.
The following illustration shows the interaction of the binary and analog input points with the databases.
ProSoft Technology, Inc.
April 22, 2008
Page 107 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Reference
All data for these data types is derived from the processor and is passed to the module over the backplane. The module will constantly monitor for changes in this data and generate event messages when point values change. For binary input points, events will be generated on any state change. For analog input points, events will be generated for points that have a current value outside of the user-set deadband based on the last value used for an event.
The following illustration shows the interaction of the counter points with the databases.
Counter Databases
PLC
Files
PLC
Data
Data
Max Points
0
DNP DB
PLC
Data
Frozen
DNP DB
PLC
Data
This data is constantly sourced from the processor and placed in the module's internal database. This information is available to the remote master for monitoring. When the module receives a freeze command from the master unit, it will copy the current counter values into the frozen counter database area. The remote master can then monitor this information. If the module receives a counter freeze with reset command, the current counter values will be passed to the frozen counter database and only the module's values will be set to 0.
Note: This data is not sent to the controller, and the zero data be overwritten by the counter data contained in the controller. Therefore, the freeze with reset should not be used with this module.
The results will not be as expected. There is no way to guarantee that counts will not be lost during the reset step in the module and controller. As a result, this feature was not implemented in the module.
The following illustration shows the interaction of the binary and analog output points with the databases.
Binary and Analog Output Databases
PLC
Files
PLC
Data
Max Points
0
DNP DB
PLC
Data
Output data is sourced from the controlling master station and passed to the processor over backplane from the module. These data are used in the ladder logic to control operations and I/O in the processor.
Page 108 of 153 ProSoft Technology, Inc.
April 22, 2008
Distributed Network Protocol Interface Module
Data Transfer Interface
The following figure displays the direction of movement of the DNP database data between the module and the processor.
DNP MEMORY
WRITE BLOCK FROM
PROCESSOR
WRITE BLOCK FROM
PROCESSOR
READ BLOCK FROM
MODULE
READ BLOCK FROM
MODULE
READ BLOCK FROM
MODULE
READ BLOCK FROM
MODULE
DIGITAL INPUT DATA
ANALOG INPUT DATA
COUNTER DATA
BINARY OUTPUT DATA
ANALOG OUTPUT DATA
FROZEN COUNTER,
LAST VALUE AND
EVENT DATA
It is important to understand the relationship of the block identifications and the data in the module.
The Reference chapter contains forms to aid in designing your system. They can be used to document the relationship between the point assignments, block identification numbers and the PLC file and offset values and to define the program configuration. Use these forms during your design phase.
ProSoft Technology, Inc.
April 22, 2008
Page 109 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Data Transfer Interface
The following figure displays the direction of movement of the DNP database data between the module and the processor.
Reference
It is important to understand the relationship of the block identifications and the data in the module.
The Reference chapter contains forms to aid in designing your system. They can be used to document the relationship between the point assignments, block identification numbers and the PLC file and offset values and to define the program configuration. Use these forms during your design phase.
DNP Digital Input Data
This data type stores the binary value of 1 or 0. The size of this data area is determined from the configuration parameter Binary Inputs (number of words, each containing 1 binary input point). These data are transferred to the module from the PLC using the read operation. Therefore, these data are read-only for the module and the DNP master unit communicating with the module. When the module receives a new block of this data from the PLC, it compares the new values to those currently in the database. If there is a change in any of the data, the module will generate an event message for the points that change.
Page 110 of 153 ProSoft Technology, Inc.
April 22, 2008
Distributed Network Protocol Interface Module
The remote DNP master unit can read the current status data and the event data from the module. Event messages generated by the module can be retrieved using a poll for Class 2 data, as all digital input events are considered a Class 2 data type. If unsolicited message generation is enabled in the application, the events will automatically be sent by the module to the DNP master unit when the maximum event count for Class 2 data is reached or when the timeout for unsolicited messages is exceeded. A data flow diagram for the digital input data is shown in the following figure.
ProSoft Technology, Inc.
April 22, 2008
Page 111 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Reference
DNP Digital Output Data
This data type stores digital control and command state data received from the
DNP master unit with a value of 1 or 0. The size of this data area is determined from the configuration parameter Binary Outputs (defines number of words, each containing 1 binary output point). These data are transferred from the module to the PLC using the write operation. Therefore, these data are read-only for the
PLC, as the PLC cannot directly alter these values in module. It is the responsibility of the DNP master unit to maintain this data. For example, if the
DNP master sets a digital point on, it will remain on until the master resets the point. A data flow diagram for the digital output data is shown in the following figure.
Page 112 of 153 ProSoft Technology, Inc.
April 22, 2008
Distributed Network Protocol Interface Module
DNP Counter Data
This data type stores accumulated count data. These data are stored in the module in a double word value and have a data range of 0 to 4,294,967,296. The size of this data area is determined from the configuration parameter Counters.
The PLC transfers data of this type to the module using the read operation. The module maintains two values for each counter point: a current running value and a frozen value. The DNP master must send the freeze command to the module in order to transfer the current running values to the frozen area.
Note: The freeze-reset command is not supported in the data transfer operation. There is no way to guarantee counts will not be lost using the freeze-reset operation, therefore, this feature is not implemented.
A data flow diagram for the counter data is shown in the following figure.
ProSoft Technology, Inc.
April 22, 2008
Page 113 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Reference
DNP Analog Input Data
This data type stores analog data with a data range of 0 to 65535 or -32768 to
32767. The size of this data area is determined from the configuration parameter
Analog Inputs. These data are transferred to the module from the PLC using the read operation. Therefore, these data are read-only for the module and the DNP master unit. When the module receives a new block of this data from the PLC, it compares the new values to those currently in the database. If there is a change in any of the data, the module will generate an event message for the points that change. The dead-band parameter configured for the module determines the variance required for the event message.
The DNP master unit can read the current value data and the event data from the module. Event messages generated by the module can be retrieved using a poll for Class 3 data, as all analog input events are considered a Class 3 data type. If unsolicited message generation is enabled in the application, the events will automatically be sent by the module to the DNP master unit when the maximum event count for Class 3 data is reached or when the timeout for unsolicited messages is exceeded. A data flow diagram for the analog input data is shown in the following figure.
Page 114 of 153 ProSoft Technology, Inc.
April 22, 2008
Distributed Network Protocol Interface Module
DNP Analog Output Data
This data type stores analog values sent from the DNP master unit to the module and PLC with a data range of 0 to 65535 or -32768 to 32767. The size of this data area is determined from the configuration parameter Analog Outputs. These data are transferred from the module to the PLC using the write operation.
Therefore, these data are read-only for the PLC, as the PLC cannot directly alter these values in the module. It is the responsibility of the DNP master unit to maintain this data. For example, if the DNP master sends a value of 3405 to the module for a specific point, the value will be stored in the module until changed by the master. A data flow diagram for the analog output data is shown in the following figure.
Functionality
This phase of design defines the features of the DNP Level 2 Subset supported by the module and to be utilized in the specific application. For example, will the unit use unsolicited messaging? Coordination with the DNP master developer is required to verify that the host will support the functionality you select. The features that must be defined in this design step are as follows:
ProSoft Technology, Inc.
April 22, 2008
Page 115 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Will analog events be returned with or without a time value?
Will events be logged before time synchronization has occurred?
Will the module start with database values initialized by the processor?
For a complete description of the module configuration, refer to the Module
Setup
section.
Reference
Data Transfer at Startup
The module can be configured to have the internal databases initialized with data contained in the processor. This feature requires ladder logic. Data to be initialized are as follows: Binary and Analog Output data. This feature can be used to bring the module to a known state (last state set in controller) when the module is first initialized. For example, in order to have the module startup using the last set of binary output values and setpoint values (analog outputs), enable this feature.
Module Operation
After the system has been designed and the system is set up, the module will be ready to operate. When the module is first initialized, it will read the configuration file After the file is processed, the module will use the data to set up the data structures of the application. If any errors are encountered during the initialization process, the default value for the parameter will be assigned and used.
The module will next check if the output initialization feature is utilized. The option permits the PLC to set these read-only data at startup. There is no static memory available on the module to remember the last values for these data types. In order to prevent a "shock" to the system at boot time, this option can be used to set the module's database to the last transferred set of data.
If the module is configured for unsolicited messaging, the module will immediately send an unsolicited response once the remote master connects to the module, informing the master of a module restart. The module will not log events or process any data read operations from the master until the master clears the restart IIN data bit. The master must also synchronize the time with the module before events will be generated if the module is so configured. The master is also responsible for enabling the unsolicited message facility in the module by sending the Enable Unsolicited Messaging command to the module.
If the module is not configured for unsolicited messaging, the DNP master must clear the restart IIN bit before the module will start logging events. The master must also synchronize the time with the module before events will be generated if the module is so configured.
Additionally, the program will listen on Port 1 for requests. This is the debug port for the module and transfers module information to an attached terminal. Refer to
Diagnostics and Troubleshooting
(page 77) for a complete discussion on the
use of this important feature.
Page 116 of 153 ProSoft Technology, Inc.
April 22, 2008
9.3 Module Error Codes
Distributed Network Protocol Interface Module
If the module's program encounters an error during execution, it will log the error to the error list. This list is transferred to the Quantum / Unity processor using block identification code 100 (see section above) in at offsets 62 to 119. This data is also available for viewing on the debug monitor port. The following tables list the error codes generated by the program with their associated description.
Use the errors to help define where problems exist in the system.
0
3
4
1
2
0x0001
0x0002
0x0004
0x0008
0x0010
Invalid baud rate selected
Invalid address assigned (0 to 65534)
Database defined will not fit into memory
Invalid binary input point count
Invalid binary output point count
5
6
7
0x0020
0x0040
0x0080
Invalid counter point count
Invalid analog or float input point count
Invalid analog or float output point count
8 0x0100
9 0x0200
10 0x0400
11 0x0800
12 0x1000
13 0x2000
14 0x4000
15 0x8000
9.3.2 Slave Port Communication Errors
Error
Code
Name Description
0 OK
10 DNP synchronization error (Physical Layer
Error)
The module is operating correctly and there are no errors.
Extra bytes are received before the start bytes (0x05 and 0x64).
11
12
13
14
DNP overrun error (Physical Layer Error) Mainline Data Link Layer routine could not read data received on DNP port before it was overwritten.
DNP length error (Physical Layer Error)
DNP bad CRC error (Data Link Layer
Error)
Length of message does not match length value in message.
Computed CRC value for message does not match that received in message.
DNP user data overflow error (Transport
Layer Error)
Application layer received a message fragment buffer which is too small.
ProSoft Technology, Inc.
April 22, 2008
Page 117 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Error
Code
15
Reference
Name Description
16
17
18
19
20
21
DNP sequence error (Transport Layer
Error)
Sequence numbers of multi-frame request fragments do not increment correctly.
DNP address error (Transport Layer Error) Source addresses contained in multiframe request fragments do not match.
DNP bad function code error (Application
Layer Error)
DNP object unknown error (Application
Layer Error)
DNP out of range error (Application Layer
Error)
Function code received from DNP master is not supported for selected object/variation.
Slave does not have the specified objects or there are no objects assigned to the requested class.
Qualifier, range or data fields are not valid or out of range for the selected object/variation.
DNP message overflow error (Application
Layer Error)
DNP master multi-frame message error
(Application Layer Error)
Application response buffer overflow condition. The response message from the slave is too long to transmit.
Received a multi-frame message from the DNP master. This application does not support multi-frame messages from the master.
9.3.3 System Configuration Errors
Name Description Error
Code
100
101
102
103
104
107
108
123
334
Too many binary input points
Too many binary output points
Too many binary input points are configured for the module. Maximum value is 512.
Too many binary output points are configured for the module. Maximum value is 512.
Too many counter points Too many counter points are configured for the module.
Maximum value is 128.
Too many analog input points
Too many analog input points are configured for the module. Maximum value is 512.
Too many analog output points
Invalid analog input deadband
Not enough memory
Too many analog output points are configured for the module. Maximum value is 512.
Deadband value for analog input events is out of range.
Value must be in the range of 0 to 32767.
There is not enough memory in the module to configure the module as specified.
Too many float input or output points
Baud rate of secondary port
Too many float input or output points are configured for the module. Maximum value is 128 for each type.
The baud rate configured for the secondary slave port is invalid.
Page 118 of 153 ProSoft Technology, Inc.
April 22, 2008
Distributed Network Protocol Interface Module
9.3.4 DNP Port Configuration Errors
Name Description Error
Code
212
213
219
220
222
223
224
225
226
227
228
230
Invalid DNP address
Invalid DNP port baud rate
The DNP address specified in the configuration is not valid (0 to 65534).
The baud rate code specified in the configuration is not valid.
Invalid DNP data link layer confirm mode The data link confirmation mode code is not valid in the configuration.
Invalid DNP data link confirm time-out
Invalid DNP select/operate arm time duration
Invalid DNP application layer confirm timeout
The data link time-out period specified in the configuration is 0. It must be an integer in the range of 1 to 65535.
The select/operate arm timer is set to 0.
It must be an integer in the range of 1 to
65535.
The application layer confirm time-out value is set to 0. It must be an integer in the range of 1 to 65535.
Invalid DNP write time interval
Invalid DNP unsolicited response mode
Invalid DNP unsolicited response minimum quantity for Class 1
Invalid DNP unsolicited response minimum quantity for Class 2
Invalid DNP unsolicited response minimum quantity for Class 3
Invalid DNP unsolicited response destination address
The write time interval is not in the data range in the configuration. The value must be in the range of 0 to 1440.
The unsolicited response mode code is not valid in the configuration.
The unsolicited response minimum quantity for Class 1 is not valid in the configuration. Value must be an integer in the range of 1 to 255.
The unsolicited response minimum quantity for Class 2 is not valid in the configuration. Value must be an integer in the range of 1 to 255.
The unsolicited response minimum quantity for Class 3 is not valid in the configuration. Value must be an integer in the range of 1 to 255.
The unsolicited response destination address is not valid in the configuration.
Value must be in the range of 1 to
65534.
9.3.5 Error Status Table
The program maintains an error/status table. This table of data is available to the
Quantum / Unity processor automatically through block 100. Ladder logic should be programmed to accept this block of data and place it in the module's controller tag. You can use the error/status data to determine the "health" of the module.
The data in the block is structured as shown in the following table:
ProSoft Technology, Inc.
April 22, 2008
Page 119 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Reference
Word Block
Offset
Variable Name
0 2 Current DNPS Slave Port status
1 3 DNPS Slave Port last transmitted error code
Description
This value represents the current value of the error code for the port. This value will only be valid if the port is configured as a slave. The possible values are described in the application documentation.
This value represents the last error code transmitted to the master by this slave port.
2 4 DNPS Slave Port total number of message frames
This value represents the total number of message frames that have matched this slaves received by slave address on this port. This count includes message frames which the slave may or may not be able to parse and respond.
3 5 DNPS Slave Port total number of response message frames sent from slave
This value represents the number of good (nonerror) responses that the slave has sent to the master on this port. The presumption is that if the slave is responding, the message was good.
Note: This is a frame count.
4 6 DNPS Slave Port total This value represents the total number of number of message frames seen by slave message frames received by the slave, regardless of the slave address.
5 7 DNPS Slave synchronization error count
(Physical Layer Error)
This value counts the number of times a sync error occurs. The error occurs when extra bytes are received before the start bytes (0x05 and
0x64) are received.
6 8 DNPS Slave overrun error count (Physical Layer Error)
This value counts the number of times the overrun error occurs. This error occurs when the mainline
Data Link Layer routine cannot read the data received on the communication port before it is overwritten.
7 9 DNPS Slave length error count (Physical Layer Error)
This value counts the number of times an invalid length byte is received. If the length of the message does not match the length value in the message, this error occurs.
8 10 DNPS Slave bad CRC error
(Data Link Layer Error)
This value counts the number of times a bad CRC value is received in a message.
9 11 DNPS Slave user data overflow error (Transport
Layer Error)
10 12 DNPS Slave sequence error (Transport Layer
Error)
This value counts the number of times the application layer receives a message fragment buffer which is too small.
This value counts the number of times the sequence numbers of multi-frame request fragments do not increment correctly.
11 13 DNPS Slave address error
(Transport Layer Error)
This value counts the number of times the source addresses contained in a multi-frame request fragments do not match.
12 14 DNPS Slave Binary Input
Event count
13 15 DNPS Slave Binary Input
Event count in buffer
This value contains the total number of binary input events which have occurred.
This value represents the number of binary input events which are waiting to be sent to the master.
14 16 DNPS Slave Analog Input
Event count
15 17 DNPS Slave Analog Input
Event count in buffer
This value contains the total number of analog input events which have occurred.
This value represents the number of analog input events which are waiting to be sent to the master.
Page 120 of 153 ProSoft Technology, Inc.
April 22, 2008
Distributed Network Protocol Interface Module
Word Block
Offset
Variable Name Description
16 18 DNPS Slave bad function code error (Application
Layer Error)
This value counts the number of times a bad function code for a selected object/variation is received by the slave device.
17 19 DNPS Slave object unknown error (Application
Layer Error)
This value counts the number of times a request for an unsupported object is received by the slave device.
18 20 DNPS Slave out of range error (Application Layer
Error)
19 21 DNPS Slave message overflow error (Application
Layer Error)
This value counts the number of times a parameter in the qualifier, range or data field is not valid or out of range.
This value counts the number of times an application response message from the slave is too long to transmit.
20 22 DNPS Slave multi-frame message from DNPS
Master error (Application
Layer Error)
This value counts the number of times the slave receives a multi-frame message from the master.
The application does not support multi-frame master messages.
Total BTR/BTW or side-connect interface transfers attempted by the module.
22 24 Successful blocks transferred
This value represents the total number of transfer operations between the Quantum / Unity processor and module that are successful.
23 25 Total errors in block transferTotal number of transfers that resulted in an error condition.
24
25
26
27
Total BTR or write errors Total number of BTR or write transfers that resulted in an error.
Total BTW or read errors Total number of BTW or read transfers that resulted in an error.
26 28 Block error Number of BTW requests that resulted in an incorrect BTW identification code.
27 29 Continuous block error counter
Count of sequential data transfer errors. When this value exceeds that specified for the data transfer operation, the error flag below will be set.
28 30 Reserved
Type This is a coded field that defines the configuration of the module. The codes are as follows:
0=Single Slave Configuration, 1=Dual Slave
Configuration, 2=Slave/Master Configuration
30 to 31 32 to 33 Product Name (ASCII)
32 to 33 34 to 35 Revision (ASCII)
These two words contain the product name of the module in ASCII format.
These two words contain the product revision level of the firmware in ASCII format.
34 to 35 36 to 37 Operating System Revision
(ASCII)
These two words contain the module's internal operating system revision level in ASCII format.
36 to 37 38 to 39 Production Run Number
(ASCII)
38 40 DNPS Master Port Slave
Count
These two words contain the production 'batch' number for the particular chip in the module in
ASCII format.
This is the total number of slaves configured for the DNPS Master port. This may not represent the number of active slaves as it includes slaves that are not enabled.
ProSoft Technology, Inc.
April 22, 2008
Page 121 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Reference
Word Block
Offset
Variable Name
39 41 DNPS Master Port
Command Count
40 42 DNPS Master Port Device
Memory Block Count
Description
This is the total number of commands configured for the DNPS Master port. This may not represent the number of active commands as it includes commands that are disabled.
This value represents the number of memory allocation blocks for slave devices. This number should be one greater than the number of slave devices. The extra device is held for the broadcast device.
41 43 DNPS Master Port Frame
Block Count
42 44 DNPS Master Port Data
Link Receive Block Count
This value represents the number of physical layer frame memory allocation blocks used by the program.
This value represents the number of receive data link layer memory blocks allocated.
43 45 DNPS Master Port Data
Link Transmit Block Count
This value represents the number of transmit data link layer memory blocks allocated.
44 46 DNPS Master Port
Application Layer Receive
Block Count
This value represents the number of application layer receive memory blocks allocated.
45 47 DNPS Master Port
Application Layer Receive
Block Count
46 48 DNPS Master Port Device
Memory Allocation Error
Count
This value represents the number of application layer transmit memory blocks allocated.
This value represents the number of memory allocation errors for device blocks.
47 49 DNPS Master Port Physical
Layer Memory Allocation
This value represents the number of memory allocation errors for physical layer frame blocks.
Error Count
48 50 DNPS Master Port Data
Link Layer Receive Memory
This value represents the number of memory allocation errors for data link layer receive blocks.
Allocation Error Count
This value represents the number of memory allocation errors for data link layer transmit blocks.
49 51 DNPS Master Port Data
Link Layer Transmit
Memory Allocation Error
Count
50 52 DNPS Master Port
Application Layer Receive
Memory Allocation Error
Count
This value represents the number of memory allocation errors for application layer receive blocks.
51 53 DNPS Master Port
Application Layer Transmit
Memory Allocation Error
Count
This value represents the number of memory allocation errors for application layer transmit blocks.
52 54 DNPS Master
Synchronization Error
Count (Physical Layer
Error)
This value counts the number of times a sync error occurs. The error occurs when extra bytes are received before the start bytes (0x05 and
0x64) are received.
53 55 DNPS Master Length Error
Count (Physical Layer
Error)
This value counts the number of times an invalid length byte is received. If the length of the message does not match the length value in the message, this error occurs.
Page 122 of 153 ProSoft Technology, Inc.
April 22, 2008
ProSoft Technology, Inc.
April 22, 2008
Distributed Network Protocol Interface Module
Word Block
Offset
Variable Name Description
54 56 DNPS Master Bad CRC
Error Count (Physical Layer
This value counts the number of times a bad CRC value is received in a message.
Error)
55 57 Scan Counter LSB Program scan counter
57 59 Free Memory LSB Free memory in module
59 61 DNPS Slave Port Transmit
State
Value of the DNPS Slave state machine for transmit.
60 62 DNPS Float Event Count Total number of events generated for analog floating-point input data points.
61 63 DNPS Double Event Count Total number of events generated for analog double, floating-point input data points.
62 64 Event Message Queue
Count
Number of event messages waiting to send to processor.
63 65 Event Message Queue
Overflow
64 to 77 66 to 79 Reserved
78 80 Error_List[0]
Flag to indicate if the event message queue has overflowed. If more than 200 event messages are received on the master port and they are not sent to the processor, this flag will be set (1). The flag will clear after the messages are sent to the processor.
Future Use
First value in error list
79 81 Error_List[1]
- - -
137 139 Error_List[59]
Second value in error list
-
Last value in error list
9.3.6 Command Error Codes
General Command Errors
Error Code Name
-1 (65535) Current command being issued on the port
0 OK
1 Device not defined
2
3
Invalid command
Object not supported
Description
Command has been issued out the port, and the module is waiting for the slave to respond.
The command was issued and responded to correctly.
The IED slave address referenced in the command is not defined in the module. Check to make sure there is an entry in the slave table for each slave device referenced in the command list.
This command is not valid. Check to make sure the slave address parameter is greater than or equal to zero and that the point count is not set to zero.
The data object in the command is not supported by the module. Refer to the DNPS subset for the
Master Port.
Page 123 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Reference
Error Code
4
10
11
20
30
31
40
50
51
60
61
70
80
Name
Command function not supported
Description
The function specified in the command is not supported for the object type selected. Refer to the DNPS subset for the Master Port.
This binary input object command is not valid. Invalid binary input poll command
Invalid binary input event poll command
Invalid binary output command function
This binary input event object poll command is not valid.
This binary output function command is not valid.
Invalid counter poll command function
The counter object poll command contains an invalid function code.
Invalid counter poll command This counter object poll command is not valid.
Invalid frozen counter poll command
This frozen counter object poll command is not valid.
This analog input poll command is not valid. Invalid analog input poll command
Invalid analog input event poll command
Invalid analog output poll function command
Invalid analog output poll command
This analog input event poll command is not valid.
This analog output poll command contains an invalid function code.
This analog output poll command is not valid.
Invalid time/date poll command
Invalid event poll command
This time/date object poll command is not valid.
This event poll command is not valid.
Application Layer Errors
Error Code Name
1000 Device index invalid
1001
1002
Duplicate request in application layer queue
COM port device removed from system
1003
1004
1005
Page 124 of 153
Sequence number error
Response to select before operate does not match
Response does not contain date/time object
Description
The device index in the request or response message is not found in the slave list.
The newly submitted message to the application layer already exists in the queue. The message is ignored.
The communication port for the message has been uninstalled on the system. This error should never occur as the communication ports are only uninstalled when the module's program is terminated.
The application sequence number in the response message does not match that based on the last request message. This indicates application layer messages are received out of order.
The select response message received from the slave module is not that expected from the last select request. This indicates a synchronization problem between the master and slave devices.
The response message from the slave device does not contain a date/time object. The master expects this object for the response message.
ProSoft Technology, Inc.
April 22, 2008
Distributed Network Protocol Interface Module
Error Code
1006
1007
1008
1009
1010
Name
Time-out condition on response
Function code in application layer message not supported
Read operation not supported for object/variation
Operate function not supported for the object/variation
Write operation not supported for the object/variation
Description
The slave device did not respond to the last request message from the master within the time-out set for the IED device. The application layer time-out value is specified for each IED unit in the slave configuration table in the module. This table is established each time the module performs the restart operation.
The function code returned in the response message is not valid for the application layer or not supported by the module.
The application layer response message contains an object that does not support the read function.
The application layer response message contains an object that does not support the operate function.
The application layer response message contains an object that does not support the write function.
9.4 Master Port DNPS Slave Configuration Values (DNPS Master Slave
List)
Column Variable
1
2
3
4
Name
DNPS Slave
Address
Data Link
Confirm Mode
Data Link
Confirm Timeout
Maximum
Retries for
Data Link
Confirm
Data Range Description IF
Error
Config.
Value
Ignore 0 to 65534
Coded Value
(0=Never,
1=Sometimes,
2=Always)
This is the slave address for the unit to override the default values.
This value specifies if data link frames sent to the remote device require a data link confirm. This value should always be set to zero for almost all applications.
1 to 65535 milliseconds
This parameter specifies the time to wait for a data link confirm from the remote device before a retry is attempted.
0 to 255 retries Maximum number of retries at the Data Link level to obtain a confirmation. If this value is set to 0, retries are disabled at the data link level of the protocol. This parameter is only used if the frame is sent with confirmation requested.
0
300
3
ProSoft Technology, Inc.
April 22, 2008
Page 125 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Column Variable
Name
5
Application
Layer
Response
Time-out
6 Slave Mode
Data Range
1 to 65535 milliseconds
Coded Value
(Bit 0=Enable,
Bit 1=Unsol
Msg, Bit
2=Use DM, Bit
3=Auto Time
Sync)
Description
Time-out period the master will wait for each response message fragment. If data link confirms are enabled, make sure the time-out period is set long enough to permit all data confirm retries.
This word contains bits that define the slave mode. The slave mode defines the functionality of the slave device and can be combined in any combination. The fields have the following definition:
Enable-- determines if this slave will be used. Unsol Msg-
- causes an enabled unsolicited response message to be sent to the slave when its RESTART IIN bit is set.
This parameter is also required for unsolicited message reporting by the IED unit.Use DM--uses delay measurement. Auto Time
Sync--time synchronization used when NEED TIME IIN bit set.
Reference
IF
Error
Config.
Value
5000
5
10
11
12
13
8
9
6
7
4
5
2
3
0
1
9.5 Command List Entry Form
0
# Port/
Flags
1
Slave
Add.
2 3 4 5 6
Pnt
Coun t
7
DNP
DB
Page 126 of 153
8 9
IED DB Poll
Interval
ProSoft Technology, Inc.
April 22, 2008
0
# Port/
Flags
1
Slave
Add.
2
43
44
45
46
39
40
41
42
47
48
49
35
36
37
38
31
32
33
34
26
27
28
29
30
22
23
24
25
18
19
20
21
14
15
16
17
3 4
Distributed Network Protocol Interface Module
5 8 9
IED DB Poll
Interval
6
Coun t
7
DNP
DB
ProSoft Technology, Inc.
April 22, 2008
Page 127 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Reference
Digital input
0 Port/Flags
1 Slave Address
2 1
3 0, 1 or 2
4 1*
5 Address in Slave
6 # of Points
7 DNPS DB Address
8 IED DB Address
9 Poll Interval
Frozen Counter
Digital input Events Digital Output
Port/Flags
Slave Address
2
Port/Flags
Slave Address
12
0, 1, 2 or 3
1*
Address in Slave
# of Points
Poll Interval
1*
3, [4], 5 or 6
Address in Slave
# of Points
DNPS DB Address
IED DB Address
Poll Interval
Analog Input
0 Port/Flags
1 Slave Address
2 21
3 0, 9 or 10
4 1*
5 Address in Slave
Port/Flags
Slave Address
30
0, 1, 2, 3 or 4
1*
Address in Slave
6 # of Points # of Points
7 DNPS DB Address DNPS DB Address
8 IED DB Address
9 Poll Interval
IED DB Address
Poll Interval
Time and Date
0 Port/Flags
1 Slave Address
2 50
3 1*
4 2*
5
6 1
7
8
9 Poll Interval
Class 0
Port/Flags
Slave Address
60
1
1
Poll Interval
Class 3
0 Port/Flags
1 Slave Address
Cls 1, 2 & 3
Port/Flags
Slave Address
Analog Input
Events
Port/Flags
Slave Address
32
0, 1, 2, 3 or 4
1*
Address in Slave
# of Points
Poll Interval
Class 1
Port/Flags
Slave Address
60
2
1
Poll Interval
Cls 0, 1, 2 & 3
Port/Flags
Slave Address
Page 128 of 153
Counter
Port/Flags
Slave Address
20
0, 5 or 6
1, 7, 8, 9 or 10
Address in Slave
# of Points
DNPS DB Address
IED DB Address
Poll Interval
Analog Output
Port/Flags
Slave Address
41
2*
3, [4], 5 or 6
Address in Slave
# of Points
DNPS DB Address
IED DB Address
Poll Interval
Class 2
Port/Flags
Slave Address
60
3
1
Poll Interval
[Clear Restart Bit]
Port/Flags
Slave Address
ProSoft Technology, Inc.
April 22, 2008
Class 3
2 60
3 4
Cls 1, 2 & 3
60
5
Distributed Network Protocol Interface Module
Cls 0, 1, 2 & 3
60
6
[Clear Restart Bit]
80
1
6 1
7
8
9 Poll Interval
Cold Restart
0 Port/Flags
1 Slave Address
2 0
3
4 13
5
6 1
7
8
9
1
Poll Interval
Warm Restart
Port/Flags
Slave Address
0
14
1
1
Poll Interval
1
Enable Unsol. Msg Disable Unsol. Msg
Port/Flags
Slave Address
0
Port/Flags
Slave Address
0
20 21
1 1
9.7 DNP Subset Definition
Note: Objects that we support that are not required within the Level II specification are grayed out.
Refer to the associated notes to determine our response to the message.
OBJECT
Obj Va r
1 0 Binary Input - All
Variations
REQUEST
Code s
1
Codes
(hex)
06
RESPONSE
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
NOTES
1 Binary Input
2 Binary Input with
Status
Input
Change - All
Variations
1 Binary Input
Change Without
Time
2 Binary Input
Change With Time
1
1
06 129, 1
130
06 129, 8
130
1 06,
08
1 06, 129,
08 130
1 06, 129,
08 130
17, 28
17, 28
8
56
Slave will return variation 1 data (user can override and have variation 2 returned)
Slave will return this variation
Slave will return this variation
Slave will return variation 2 data (user can override and have variation 1 returned)
Slave will return this variation
Slave will return this variation
ProSoft Technology, Inc.
April 22, 2008
Page 129 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
OBJECT
Obj Va r
10
3 Binary Input
Change With
Relative Time
0 Binary Output - All
Variations
REQUEST RESPONSE
Func
Codes Code s
Codes
(hex)
1 06,
08
129,
130
Qual
Codes
(hex)
17, 28 24
Data
Size
(bits)
1 00, 06
12
20
21
1
2 Binary Output
Status
0 Control Block - All
Variations
1 Control Relay
Output Block
2 Pattern Control
Block
3 Pattern Mask
0 Binary Counter -
All Variations
1
2
Binary Output
32-Bit Binary
Counter
16-Bit Binary
Counter
3 32-Bit Delta
Counter
4 16-Bit Delta
Counter
5
6
32-Bit Binary
Counter Without
Flag
16-Bit Binary
Counter Without
Flag
7 32-Bit Delta
Counter Without
Flag
8 16-Bit Delta
Counter Without
Flag
0 Frozen Counter -
All Variations
1
1
3, 4,
5, 6
1, 7,
8, 9,
10
1, 7,
8, 9,
10
1, 7,
8, 9,
10
1, 7,
8, 9,
10
1, 7,
8, 9,
10
1
00, 06
00, 06 129,
130
17, 28 129
06
06
129,
130
129,
130
00, 01 8
Echo of request
1
88
88
88
16
06 129,
130
00, 01 40
06 129,
130
00, 01 24
129,
130
129,
130
00, 01
00, 01
40
24
06 129,
130
00, 01 32
06 129,
130
00, 01 16
00, 01 32
00, 01 16
NOTES
Slave will return this variation (counter upper 16bits removed)
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Reference
Slave will parse this message and return no data
Slave will return variation 2 data (user can override and have variation 1 returned)
Slave will return this variation
Slave will return this variation
Slave will use variation 1 control
Slave will respond correctly to this variation
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return variation 5 data (user can override and have variation 1 returned)
Slave will return this variation
Slave will return this variation (counter upper 16bits removed)
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return this variation
1
Page 130 of 153
32-Bit Frozen
Counter
1 06 129,
130
00, 01 40
Slave will return variation 9 data (user can override and have variation 1 returned)
Slave will return this variation
ProSoft Technology, Inc.
April 22, 2008
Distributed Network Protocol Interface Module
OBJECT
Obj Va r
2 16-Bit Frozen
Counter
3 32-Bit Frozen
Delta Counter
4
5
6
16-Bit Frozen
Delta Counter
32-Bit Frozen
Counter With
Time Of Freeze
16-Bit Frozen
Counter With
Time Of Freeze
7
8
32-Bit Frozen
Delta Counter
With Time Of
Freeze
16-Bit Frozen
Delta Counter
With Time Of
Freeze
9 32-Bit Frozen
Counter Without
Flag
10 16-Bit Frozen
Counter Without
Flag
11 32-Bit Frozen
Delta Counter
Without Flag
12 16-Bit Frozen
Delta Counter
Without Flag
1
2
3
Event - All
Variations
32-Bit Counter
Change Event
Without Time
16-Bit Counter
Change Event
Without Time
32-Bit Delta
Counter Change
Event Without
Time
REQUEST
Code s
1
Codes
(hex)
RESPONSE
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
06 129,
130
00, 01 24
NOTES
40
24
88
Slave will return this variation (counter upper 16bits removed)
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
72 Slave will return Unknown
Object to this request
88 Slave will return Unknown
Object to this request
1
1
130
130
1 06,
08
129,
130
129,
130
17, 28
17, 28
72
06 129, 32
06 129, 16
32
16
40
24
40
Slave will return Unknown
Object to this request
Slave will return this variation
Slave will return this variation (counter upper 16bits removed)
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will parse this request and return no data
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
ProSoft Technology, Inc.
April 22, 2008
Page 131 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
OBJECT
Obj Va r
4
REQUEST
Code s
Codes
(hex)
RESPONSE
Func
Codes
Qual
Codes
(hex)
5
6
7
8
16-Bit Delta
Counter Change
Event Without
Time
32-Bit Counter
Change Event
With Time
16-Bit Counter
Change Event
With Time
32-Bit Delta
Counter Change
Event With Time
16-Bit Delta
Counter Change
Event With Time
30
1
2
3
Event - All
Variations
32-Bit Frozen
Counter Event
Without Time
16-Bit Frozen
Counter Event
Without Time
32-Bit Frozen
Delta Counter
Event Without
Time
4
5
16-Bit Frozen
Delta Counter
Event Without
Time
32-Bit Frozen
Counter Event
With Time
6
7
16-Bit Frozen
Counter Event
With Time
32-Bit Frozen
Delta Counter
Event With Time
8 16-Bit Frozen
Delta Counter
Event With Time
0 Analog Input - All
Variations
1 06
88
72
88
72
40
24
40
24
88
72
88
72
Data
Size
(bits)
24
NOTES
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Reference
Slave will respond with variation 4 data (user can override and have variation
2 returned)
Page 132 of 153 ProSoft Technology, Inc.
April 22, 2008
Distributed Network Protocol Interface Module
OBJECT
Obj Va r
1
2
3
32-Bit Analog
Input
16-Bit Analog
Input
32-Bit Analog
Input Without Flag
1
1
4
5
16-Bit Analog
Input Without Flag
Short Floating
Point Analog Input
1
1
6
1
Long Floating
Point Analog Input
Analog
Input - All
Variations
1
2
32-Bit Frozen
Analog Input
16-Bit Frozen
Analog Input
3
4
5
6
32-Bit Frozen
Analog Input With
Time To Freeze
16-Bit Frozen
Analog Input With
Time To Freeze
32-Bit Frozen
Analog Input
Without Flag
16-Bit Frozen
Analog Input
Without Flag
REQUEST
Code s
1
Codes
(hex)
RESPONSE
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
06 129,
130
00, 01 40
NOTES
06 129,
06
06
130
06 129,
130
06 129,
130
129,
130
129,
130
7
8
Short Floating
Point Frozen
Analog Input
Long Floating
Point Frozen
Analog Input
Change
Event - All
Variations
1 06,
08
1
2
32-Bit Analog
Change Event
Without Time
16-Bit Analog
Change Event
Without Time
1
1
06, 07,
08
06, 07,
08
129,
130
129,
130
17, 28
17, 28
24
32
16
00, 01 40
00, 01 72
40
24
88
72
32
16
40
72
40
24
Slave will return this variation (Note: Data will only be 16-bit)
Slave will return this variation
Slave will return this variation (Note: Data will only be 16-bit)
Slave will return this variation
Slave will return this variation
Slave will return this variation
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return variation 2 data (user can override and have variation 4 returned)
Slave will return this variation (Note: Data only
16-bit)
Slave will return this variation
ProSoft Technology, Inc.
April 22, 2008
Page 133 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
OBJECT
Obj Va r
REQUEST
3
4
5
6
32-Bit Analog
Change Event
With Time
16-Bit Analog
Change Event
With Time
Short Floating
Point Analog
Change Event
Long Floating
Point Analog
Change Event
1
1
1
7 Short Floating
Point Analog
Change Event
With Time
1
Analog
Event - All
Variations
8
1
Long Floating
Point Analog
Change Event
With Time
32-Bit Frozen
Analog Event
Without Time
1
2 16-Bit Frozen
Analog Event
Without Time
3
4
5
6
7
8
32-Bit Frozen
Analog Event With
Time
16-Bit Frozen
Analog Event With
Time
Short Floating
Point Frozen
Analog Event
Long Floating
Point Frozen
Analog Event
Short Floating
Point Frozen
Analog Event With
Time
Long Floating
Point Frozen
Analog Event With
Time
Code s
1
Codes
(hex)
06, 07,
08
06, 07,
08
06, 07,
08
06, 07,
08
06, 07,
08
06, 07,
08
RESPONSE
Func
Codes
Qual
Codes
(hex)
129,
130
17, 28 88
Data
Size
(bits)
129,
130
129,
130
129,
130
129,
130
129,
130
17, 28 72
17, 28 40
17, 28 72
17, 28 88
17, 28 120
40
24
88
72
40
72
88
120
NOTES
Slave will return this variation (Note: Data only
16-bit)
Slave will return this variation
Slave will return this variation
Slave will return this variation
Slave will return this variation
Slave will return this variation
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Reference
Page 134 of 153 ProSoft Technology, Inc.
April 22, 2008
Distributed Network Protocol Interface Module
OBJECT
Obj Va r
REQUEST
Output
Status - All
Variations
1 32-Bit Analog
Output Status
1
Code s
1
06
Codes
(hex)
06
RESPONSE
Func
Codes
Qual
Codes
(hex)
129,13
0
00,01
Data
Size
(bits)
24
NOTES
Slave will return variation 2 data
40
2
3
4
16-Bit Analog
Output Status
Short Floating
Point Analog
Output Status
Long Floating
Point Analog
Output Status
1
1
1
06 129,
06
06
130
129,
130
129,
130
00, 01
00, 01
24
40
72
Slave will return this variation but data only 16-bit accuracy
Slave will return this variation
Slave will return this variation
Slave will return this variation
1
2
Block - All
Variations
32-Bit Analog
Output Block
16-Bit Analog
Output Block
3, 4,
5, 6
3, 4,
5, 6
24 Slave will respond to this request using variation 2 data
Slave will respond to this request but data only 16-bit
Slave will respond to this request
50
51
3 Short Floating
Point Analog
Output Block
4 Long Floating
Point Analog
Output Block
0 Time and Date -
All Variations
1 Time and Date
2 Time and Date
With Interval
0 Time and Date
CTO - All
Variations
1 Time and Date
CTO
3, 4,
5, 6
3, 4,
5, 6
2
2
17, 28 129,13
0
17, 28 129
00,01
17, 28
17, 28
129
129
40
Echo of
Reques t
Echo of
Reques t
Echo of
Reques t
24
40
72
48 07, With
Quant=
1
07, With
Quant=
1
48
80
129,
130
Slave will respond to this request
Slave will respond to this request
Slave will use variation 1
Slave will respond to this variation
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
Slave will return Unknown
Object to this request
52
2 Unsynchronized
Time and Date
CTO
0 Time Delay - All
Variations
129,
130
07, With
Quant=
1
07, With
Quant=
1
48
48 Slave will return Unknown
Object to this request
ProSoft Technology, Inc.
April 22, 2008
Page 135 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
OBJECT
Obj Va r
60
1 Time Delay
Coarse
0 Not Defined
1 Class 0 Data
REQUEST
1
Code s
2 Time Delay Fine
Codes
(hex)
06
RESPONSE
Func
Codes
Qual
Codes
(hex)
129
129
07, With
Quant=
1
07, With
Quant=
1
16
Data
Size
(bits)
16
70
2
3
4
Page 136 of 153
Class 1 Data
Class 2 Data
Class 3 Data
0 Not Defined
1 File Identifier
80
81
82
0 Not Defined
1 Internal
Indications
0
1
Not Defined
Storage Object
0 Not Defined
1 Device Profile
83 0 Not Defined
1 Private
Registration
Object
2 Private
Registration
Objection
Descriptor
90 0 Not Defined
1 Application
Identifier
100 0
1 Short Floating
Point
2
3
Long Floating
Point
Extended Floating
Point
1
1
1
06, 07,
08
06, 07,
08
06, 07,
08
2 00,
Index=7
24
48
80
88
NOTES
Not Defined in DNP
Reference
Slave will never return this variation
Slave will return this variation to functions 0D,
0E, and 17
Not Defined in DNP
Slave will respond to this variation with all static data
Slave will respond to this variation (No class 1 data defined in application)
Slave will respond to this variation with all class 2 data (binary input events)
Slave will respond to this variation with all class 3 data (analog input events)
Not Defined in DNP
Slave will return Unknown
Object to this request
Not Defined in DNP
Slave will respond to this variation
Not Defined in DNP
Not Defined in DNP
Not Defined in DNP
ProSoft Technology, Inc.
April 22, 2008
OBJECT
Obj Va r
101 0
1 Small Packed
Binary-Coded
Decimal
2 Medium Packed
Binary-Coded
Decimal
3 Large Packed
Binary-Coded
Decimal
110 0 Not Defined
Octet String 1 to
10
0
No Object
1
13
14
20
21
23
Distributed Network Protocol Interface Module
Data
Size
(bits)
16
NOTES
32
64
00, 01,
06, 07,
08, 17,
28
129,
130
00, 01,
07, 08,
17, 28
8 *
Var #
Not Defined as the variation determines the string length
The module will return this variation for the points defined in the module. The variation determines the returned string length.
Slave supports the Cold
Restart Function and will return Obj 52, Var 2, Qual 7,
Cnt 1
Slave supports the Warm
Restart Function and will return Obj 52, Var 2, Qual 7,
Cnt 1
Slave supports the Enable
Unsolicited Function
Slave supports the Disable
Unsolicited Function
Slave supports the Delay
Measurement & Time
Synchronization Function and will return Obj 52, Var
2, Qual 7, Cnt 1
First Byte
Bit Description
0
All stations message received. Set when a request is received with the destination address set to 0xffff. Cleared after next response. Used to let master station know broadcast received.
1
2
Class 1 data available. Set when class 1 data is ready to be sent from the slave to the master. Master should request class 1 data when this bit is set.
Class 2 data available. Set when class 2 data is ready to be sent from the slave to the master. Master should request class 2 data when this bit is set.
ProSoft Technology, Inc.
April 22, 2008
Page 137 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Reference
Bit Description
3
Class 3 data available. Set when class 3 data is ready to be sent from the slave to the master. Master should request class 3 data when this bit is set.
4
5
Time synchronization required from master. The master should write the date and time when this bit is set. After receiving the write command the bit will be cleared.
Slave digital outputs are in local control. This bit is not used in this application.
7
Device restart. This bit is set when the slave either warm or cold boots. It is cleared after a master writes a 0 to the bit.
Second Byte
Bit Description
0
Bad function code. The function code contained in the master request is not supported for the specified object/variation.
1
2
Requested object(s) unknown. Object requested by master is not supported by the application.
Parameters in the qualifier, range or data fields are not valid or out of range for the slave.
3
4
5
Event buffer(s) or other application buffers have overflowed. This bit is also set if the slave receives a multi-frame message from the master.
Request understood but requested operation is already executing. The slave will never set this bit.
Bad configuration. The slave configuration is invalid and should be re-configured. If the configuration is invalid, the slave will set the invalid parameters to default values and continue to run. Check error log using debug port.
How fast do the "Backplane Data Exchange" commands run?
The "Backplane Data Exchange" commands will execute one at a time during the
I/O service interval of the PLC. What this means is that if you had a list of 10 commands at the end of every PLC scan one command would execute. This would mean that it would take 10 PLC scans to execute the 10 commands contained within the "Backplane Data Exchange" section of the configuration file.
What is the maximum number of words I can transfer with a "Backplane
Data Exchange" command?
For command types 1 & 2 you may move up to 130 words with each command.
Function 3 is somewhat different in that it provides only 64 words of data movement BUT since it is intended to solve very specialized operations its size must be restricted.
Do I need to use "Backplane Data Exchange" function 3?
Page 138 of 153 ProSoft Technology, Inc.
April 22, 2008
Distributed Network Protocol Interface Module
The only time you should need it is if you are using the DNPS, DNP or one of the
IEC protocols. If you are using one of these protocols then you can find sample structured text examples included in the manual for these protocols. In all other instances you should not need to use this function.
How much data can I transfer between the PLC and the Module.
You can enter up to 100 commands in the [BACKPLANE DATA EXCHANGE] section of the configuration file. The limit for any single execution of a Function 1 or 2 is 130 words but you may enter multiple commands to transfer more data.
How do I configure the module?
The ProTalk requires a simple text based configuration file to make it operational.
For a really quick tutorial on the modules communications with the PLC you should review the [QUICK START GUIDE] or for more in depth information the chapter on "Backplane Data Exchange" should answer most questions.
What software application is required for my Ladder Logic?
The design of the module should be software independent and for many installations minimal or possibly no ladder will be required. The section on
"Backplane Data Exchange" offers to samples to help in the few instances where ladder is required.
What kind of data transfer rates can I expect between the PLC and the module?
Data transfer rates between the PLC and the module depend on a number of variables, among them the number of words being transferred per command, the amount of other network traffic at the time data is being transferred, and overall processor scan times.
Is a .MDC available for configuration of the Module?
Yes. The CD-ROM that ships with the module should have a version for both
Concept 2.5 and 2.6 in the ProTalk directory.
Does the module work in a remote rack?
The module is designed to be located in the chassis with the PLC and will not operate in a remote chassis. If your application requires remote placement of the communication device you should investigate the other members of the ProLinx family such as the 4202-MNET-DFCM. (if you require DF1 connectivity for instance although many others are available) This module for example would allow you to communicate with DF1 devices and allow you to map the contents of its memory using Modbus TCP/IP.
Can I use the ProTalk module in a hot backup system?
Support for Hot Backup is not currently implemented in the module. We are currently investigating the addition of this functionality but until this development can be finalized it may be possible to use one of the 4000 series of ProLinx
Communication products. Please call our technical support technicians when considering this application.
ProSoft Technology, Inc.
April 22, 2008
Page 139 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Reference
What does "Initialize Output Data" in the configuration file mean?
The default of this user parameter is NO. When the module reboots it will reset all of its internal registers to a zero value. In some applications this will cause a problem as the master wishes to see what he/she believes he/she put in that register during the last access. If this is true you should set this parameter to
YES, which will cause the module to convert the writes (command function 2) in the [BACKPLANE DATA EXCHANGE] section to reads for one scan and one scan only. This will reload the registers in the module with the information contained within the PLC.
Where do the individual data types actually exist in the modules memory?
The placement of the individual data types is in a pre-defined order, which is the same as they are placed in the configuration file for easy reference. They will be placed in memory sequentially as follows:
Binary
Analog
Counter
Binary
Analog
When you describe the database in the DNPS configuration file you should create sufficient data size for your application plus any anticipated growth. If for instance you describe 10 Binary Inputs today and later increase the size to 20, you will have effectively changed the location of your Analog Inputs, Counter
Data, Binary Outputs and Analog Outputs by 10 locations.
If you choose not to do this then you should enter one or more commands for each data transfer. In this instance you could change the data AND change the
[BACKPLANE DATA EXCHANGE] commands to maintain your mapping in the
PLC.
Page 140 of 153 ProSoft Technology, Inc.
April 22, 2008
Support, Service & Warranty PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
10 Support, Service & Warranty
In This Chapter
How to Contact Us: Sales and Support ............................................... 142
Return Material Authorization (RMA) Policies and Conditions............. 142
Procedures for Return of Units Under Warranty.................................. 143
Procedures for Return of Units Out of Warranty.................................. 144
Be sure and read the full Warranty that can be found on our web site at
www.prosoft-technology.com
for details and other terms and conditions. The content in this summary is subject to change without notice. The content is current at date of publication.
ProSoft Technology, Inc. strives to provide meaningful support to its customers.
Should any questions or problems arise, please feel free to contact us at:
Internet
Web Site: http://www.prosoft-technology.com/support
E-mail address: [email protected]
Those of us at ProSoft Technology, Inc. want to provide the best and quickest support possible, so before calling please have the following information available. You may wish to fax this information to us prior to calling.
1
Product Version Number
2
System architecture
3
Network details
In the case of hardware, we will also need the following information:
1
Module configuration and contents of file
2
Module Operation
3
Configuration/Debug status information
4
LED patterns
5
Information about the processor and user data files as viewed through the development software and LED patterns on the processor
6
Details about the networked devices interfaced, if any
For technical support calls within the United States, an after-hours answering system allows pager access to one of our qualified technical and/or application support engineers at any time to answer your questions.
ProSoft Technology, Inc.
April 22, 2008
Page 141 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
10.1 How to Contact Us: Sales and Support
Support, Service & Warranty
All ProSoft Technology Products are backed with full technical support. Contact our worldwide Technical Support team and Customer Service representatives directly by phone or email:
USA / Latin America (excluding Brasil) (Office in California)
+1(661) 716-5100
+1(661) 716-5101 (Fax)
1675 Chester Avenue, 4th Floor
Bakersfield, California 93301
U.S.A.
+1.661.716.5100, [email protected]
Languages spoken include: English, Spanish
Asia Pacific Sales (office in Malaysia)
+603.7724.2080
+603.7724.2090 (Fax)
C210, Damansara Intan,
1 Jalan SS20/27, 47400 Petaling Jaya
Selangor, Malaysia
+603.7724.2080, [email protected]
Languages spoken include: Chinese, Japanese, English
Asia Pacific Support (office in China)
+86.21.64518356 x 8011
+86.21.64756957 (Fax)
4/F, No. 16 Hongcao Road
Shanghai, China 200233
China
+86.21.64518356 x 8011, [email protected]
Languages spoken include: Chinese, English
Europe / Middle East / Africa (office in Toulouse, France)
+33 (0) 5.34.36.87.20
+33 (0) 5.61.78.40.52 (Fax)
Zone d'activité de Font Grasse
17, rue des Briquetiers
F-31700 Blagnac
France
+33 (0) 5.34.36.87.20. [email protected]
Languages spoken include: French, English
Brasil (office in Sao Paulo)
+55-11-5084-5178
+55-11-5083-3776 (Fax)
Rua Vergueiro, 2949 - sala 182 - Edifício Vergueiro Work Center
Vila Mariana - São Paulo
Cep: 04101-300 - Brasil
+55-11-5084-5178, [email protected]
Languages spoken include: Portuguese, English
The following RMA Policies and Conditions apply to any returned product. These
RMA Policies are subject to change by ProSoft without notice. For warranty information, see Section C below entitled "Limited Warranty". In the event of any inconsistency between the RMA Policies and the Warranty, the Warranty shall govern.
Page 142 of 153 ProSoft Technology, Inc.
April 22, 2008
Support, Service & Warranty PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
10.2.1 All Product Returns
1
In order to return a Product for repair, exchange or otherwise, the Customer must obtain a Returned Material Authorization (RMA) number from ProSoft and comply with ProSoft shipping instructions.
2
In the event that the Customer experiences a problem with the Product for any reason, Customer should contact ProSoft Technical Support at one of the telephone numbers listed above in Section A. A Technical Support Engineer will request several tests in an attempt to isolate the problem. If after these tests are completed, the Product is found to be the source of the problem,
ProSoft will issue an RMA.
3
All returned Products must be shipped freight prepaid, in the original shipping container or equivalent, to the location specified by ProSoft, and be accompanied by proof of purchase. The RMA number is to be prominently marked on the outside of the shipping box. Customer agrees to insure the
Product or assume the risk of loss or damage in transit. Products shipped to
ProSoft without an RMA number will be returned to the Customer, freight collect. Contact ProSoft Technical Support for further information.
4
Out of warranty returns are not allowed on RadioLinx accessories such as antennas, cables, and brackets.
The following policy applies for Non-Warranty Credit Returns:
A
10% Restocking Fee if Factory Seal is not broken
B
20% Restocking Fee if Factory Seal is broken
ProSoft retains the right, in its absolute and sole discretion, to reject any nonwarranty returns for credit if the return is not requested within three (3) months after shipment of the Product to Customer, if the Customer fails to comply with
ProSoft's shipping instructions, or if the Customer fails to return the Product to
ProSoft within six (6) months after Product was originally shipped.
10.3 Procedures for Return of Units Under Warranty
1
A Technical Support Engineer must pre-approve all product returns.
2
Module is repaired or replaced after a Return Material Authorization Number is entered and a replacement order is generated.
3
Credit for the warranted item is issued within 10 business days after receipt of product and evaluation of the defect has been performed by ProSoft. The credit will only be issued provided the product is returned with a valid Return
Material Authorization Number and in accordance with ProSoft's shipping instructions.
ProSoft Technology, Inc.
April 22, 2008
Page 143 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Support, Service & Warranty a) If no defect is found, a credit is issued. b) If a defect is found and is determined to be customer generated or if the defect is otherwise not covered by ProSoft's Warranty, or if the module is not repairable, a credit is not issued and payment of the replacement module is due.
10.4 Procedures for Return of Units Out of Warranty
1
Customer sends unit in for evaluation.
2
If no defect is found, Customer will be charged the equivalent of US $100 plus shipping, duties and taxes that may apply. A new Purchase Order will be required for this evaluation fee.
If the unit is repaired the charge to the Customer will be 30%* of the list price plus any shipping, duties and taxes that may apply. A new Purchase Order will be required for a product repair.
3
For an immediate exchange, a new module may be purchased and sent to
Customer while repair work is being performed. Credit for purchase of the new module will be issued when the new module is returned in accordance with ProSoft's shipping instructions and subject to ProSoft's policy on nonwarranty returns. This is in addition to charges for repair of the old module and any associated charges to Customer.
4
If, upon contacting ProSoft Customer Service, the Customer is informed that unit is believed to be unrepairable, the Customer may choose to send unit in for evaluation to determine if the repair can be made. Customer will pay shipping, duties and taxes that may apply. If unit cannot be repaired, the
Customer may purchase a new unit.
10.4.1 Un-repairable Units
3150-All
3750
3600-All
3700
3170-All
3250
1560 can be repaired, if defect is the power supply
1550 can be repaired, if defect is the power supply
3350
3300
1500-All
* 30% of list price is an estimated repair cost only. The actual cost of repairs will be determined when the module is received by ProSoft and evaluated for needed repairs.
Page 144 of 153 ProSoft Technology, Inc.
April 22, 2008
Support, Service & Warranty PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Purchasing Warranty Extension
As detailed below in ProSoft's Warranty, the standard Warranty Period is one year (or in the case of RadioLinx modules, three years) from the date of delivery.
The Warranty Period may be extended for an additional charge, as follows:
Additional 1 year = 10% of list price
Additional 2 years = 20% of list price
Additional 3 years = 30% of list price
This Limited Warranty ("Warranty") governs all sales of hardware, software and other products (collectively, "Product") manufactured and/or offered for sale by
ProSoft, and all related services provided by ProSoft, including maintenance, repair, warranty exchange, and service programs (collectively, "Services"). By purchasing or using the Product or Services, the individual or entity purchasing or using the Product or Services ("Customer") agrees to all of the terms and provisions (collectively, the "Terms") of this Limited Warranty. All sales of software or other intellectual property are, in addition, subject to any license agreement accompanying such software or other intellectual property.
10.5.1 What Is Covered By This Warranty
A Warranty On New Products
: ProSoft warrants, to the original purchaser only, that the Product that is the subject of the sale will (1) conform to and perform in accordance with published specifications prepared, approved, and issued by ProSoft, and (2) will be free from defects in material or workmanship; provided these warranties only cover Product that is sold as new. This
Warranty expires one year (or in the case of RadioLinx modules, three years) from the date of shipment (the "Warranty Period"). If the Customer discovers within the Warranty Period a failure of the Product to conform to specifications, or a defect in material or workmanship of the Product, the
Customer must promptly notify ProSoft by fax, email or telephone. In no event may that notification be received by ProSoft later than 15 months (or in the case of RadioLinx modules, 39 months) from the date of delivery. Within a reasonable time after notification, ProSoft will correct any failure of the
Product to conform to specifications or any defect in material or workmanship of the Product, with either new or used replacement parts. Such repair, including both parts and labor, will be performed at ProSoft's expense. All warranty service will be performed at service centers designated by ProSoft.
If ProSoft is unable to repair the Product to conform to this Warranty after a reasonable number of attempts, ProSoft will provide, at its option, one of the following: a replacement product, a full refund of the purchase price or a credit in the amount of the purchase price. All replaced product and parts become the property of ProSoft. These remedies are the Customer's only remedies for breach of warranty.
ProSoft Technology, Inc.
April 22, 2008
Page 145 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Support, Service & Warranty
B Warranty On Services
: Material and labor used by ProSoft to repair a verified malfunction or defect are warranted on the terms specified above for new
Product, provided said warranty will be for the period remaining on the original new equipment warranty or, if the original warranty is no longer in effect, for a period of 90 days from the date of repair.
C
The Warranty Period for RadioLinx accessories (such as antennas, cables, brackets, etc.) are the same as for RadioLinx modules, that is, three years from the date of shipment.
10.5.2 What Is Not Covered By This Warranty
A
ProSoft makes no representation or warranty, expressed or implied, that the operation of software purchased from ProSoft will be uninterrupted or error free or that the functions contained in the software will meet or satisfy the purchaser's intended use or requirements; the Customer assumes complete responsibility for decisions made or actions taken based on information obtained using ProSoft software.
B
With the exception of RadioLinx accessories referenced in paragraph 1(c) this Warranty does not cover any product, components, or parts not manufactured by ProSoft.
C
This Warranty also does not cover the failure of the Product to perform specified functions, or any other non-conformance, defects, losses or damages caused by or attributable to any of the following: (i) shipping; (ii) improper installation or other failure of Customer to adhere to ProSoft's specifications or instructions; (iii) unauthorized repair or maintenance; (iv) attachments, equipment, options, parts, software, or user-created programming (including, but not limited to, programs developed with any IEC
61131-3 programming languages, or "C") not furnished by ProSoft; (v) use of the Product for purposes other than those for which it was designed; (vi) any other abuse, misapplication, neglect or misuse by the Customer; (vii) accident, improper testing or causes external to the Product such as, but not limited to, exposure to extremes of temperature or humidity, power failure or power surges outside of the limits indicated on the product specifications; or
(viii) disasters such as fire, flood, earthquake, wind or lightning.
D
The information in this Agreement is subject to change without notice.
ProSoft shall not be liable for technical or editorial errors or omissions made herein; nor for incidental or consequential damages resulting from the furnishing, performance or use of this material. The user guides included with your original product purchased by you from ProSoft, contains information protected by copyright. No part of the guide may be duplicated or reproduced in any form without prior written consent from ProSoft.
Page 146 of 153 ProSoft Technology, Inc.
April 22, 2008
Support, Service & Warranty PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
10.5.3 DISCLAIMER REGARDING HIGH RISK ACTIVITIES
PRODUCT MANUFACTURED OR SUPPLIED BY PROSOFT IS NOT FAULT
TOLERANT AND IS NOT DESIGNED, MANUFACTURED OR INTENDED FOR
USE IN HAZARDOUS ENVIRONMENTS REQUIRING FAIL-SAFE
PERFORMANCE (INCLUDING, WITHOUT LIMITATION, THE OPERATION OF
NUCLEAR FACILITIES, AIRCRAFT NAVIGATION OF COMMUNICATION
SYSTEMS, AIR TRAFFIC CONTROL, DIRECT LIFE SUPPORT MACHINES
OR WEAPONS SYSTEMS), IN WHICH THE FAILURE OF THE PRODUCT
COULD LEAD DIRECTLY OR INDIRECTLY TO DEATH, PERSONAL INJURY,
OR SEVERE PHYSICAL OR ENVIRONMENTAL DAMAGE (COLLECTIVELY,
"HIGH RISK ACTIVITIES"). PROSOFT SPECIFICALLY DISCLAIMS ANY
EXPRESS OR IMPLIED WARRANTY OF FITNESS FOR HIGH RISK
ACTIVITIES.
10.5.4 DISCLAIMER OF ALL OTHER WARRANTIES
THE WARRANTIES SET FORTH IN PARAGRAPH 1 ABOVE ARE IN LIEU OF
ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT
LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PURPOSE.
10.5.5 LIMITATION OF REMEDIES**
IN NO EVENT WILL PROSOFT (OR ITS DEALER) BE LIABLE FOR ANY
SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES BASED ON
BREACH OF WARRANTY, BREACH OF CONTRACT, NEGLIGENCE, STRICT
TORT, OR ANY OTHER LEGAL THEORY. DAMAGES THAT PROSOFT AND
ITS DEALER WILL NOT BE RESPONSIBLE FOR INCLUDE, BUT ARE NOT
LIMITED TO: LOSS OF PROFITS; LOSS OF SAVINGS OR REVENUE; LOSS
OF USE OF THE PRODUCT OR ANY ASSOCIATED EQUIPMENT; LOSS OF
DATA; COST OF CAPITAL; COST OF ANY SUBSTITUTE EQUIPMENT,
FACILITIES, OR SERVICES; DOWNTIME; THE CLAIMS OF THIRD PARTIES,
INCLUDING CUSTOMERS OF THE PURCHASER; AND INJURY TO
PROPERTY.
** Some areas do not allow time limitations on an implied warranty, or allow the exclusion or limitation of incidental or consequential damages. In such areas the above limitations may not apply. This Warranty gives you specific legal rights, and you may also have other rights which vary from place to place.
10.5.6 Time Limit for Bringing Suit
Any action for breach of warranty must be commenced within 15 months (or in the case of RadioLinx modules, 39 months) following shipment of the Product.
ProSoft Technology, Inc.
April 22, 2008
Page 147 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
10.5.7 No Other Warranties
Support, Service & Warranty
Unless modified in writing and signed by both parties, this Warranty is understood to be the complete and exclusive agreement between the parties, suspending all oral or written prior agreements and all other communications between the parties relating to the subject matter of this Warranty, including statements made by salesperson. No employee of ProSoft or any other party is authorized to make any warranty in addition to those made in this Warranty. The
Customer is warned, therefore, to check this Warranty carefully to see that it correctly reflects those terms that are important to the Customer.
10.5.8 Intellectual Property
A
Any documentation included with Product purchased from ProSoft is protected by copyright and may not be photocopied or reproduced in any form without prior written consent from ProSoft.
B
ProSoft's technical specifications and documentation that are included with the Product are subject to editing and modification without notice.
C
Transfer of title shall not operate to convey to Customer any right to make, or have made, any Product supplied by ProSoft.
D
Customer is granted no right or license to use any software or other intellectual property in any manner or for any purpose not expressly permitted by any license agreement accompanying such software or other intellectual property.
E
Customer agrees that it shall not, and shall not authorize others to, copy software provided by ProSoft (except as expressly permitted in any license agreement accompanying such software); transfer software to a third party separately from the Product; modify, alter, translate, decode, decompile, disassemble, reverse-engineer or otherwise attempt to derive the source code of the software or create derivative works based on the software; export the software or underlying technology in contravention of applicable US and international export laws and regulations; or use the software other than as authorized in connection with use of Product.
10.5.9 Additional Restrictions Relating To Software And Other
Intellectual Property
In addition to complying with the Terms of this Warranty, Customers purchasing software or other intellectual property shall comply with any license agreement accompanying such software or other intellectual property. Failure to do so may void this Warranty with respect to such software and/or other intellectual property.
This Warranty allocates the risk of product failure between ProSoft and the
Customer. This allocation is recognized by both parties and is reflected in the price of the goods. The Customer acknowledges that it has read this Warranty, understands it, and is bound by its Terms.
Page 148 of 153 ProSoft Technology, Inc.
April 22, 2008
Support, Service & Warranty
10.5.11
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Controlling Law and Severability
This Warranty shall be governed by and construed in accordance with the laws of the United States and the domestic laws of the State of California, without reference to its conflicts of law provisions. If for any reason a court of competent jurisdiction finds any provisions of this Warranty, or a portion thereof, to be unenforceable, that provision shall be enforced to the maximum extent permissible and the remainder of this Warranty shall remain in full force and effect. Any cause of action with respect to the Product or Services must be instituted in a court of competent jurisdiction in the State of California.
ProSoft Technology, Inc.
April 22, 2008
Page 149 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
Support, Service & Warranty
Page 150 of 153 ProSoft Technology, Inc.
April 22, 2008
Index
[
[DNP Slave Analog Inputs] • 70
[DNP Slave Binary Inputs] • 70
[DNP Slave Database] • 68
[DNP Slave Float Inputs] • 71
[DNP Slave] • 60
[Module] • 60
[PTQ BACKPLANE] • 60
[Secondary Port] • 71
3
3x Register Start • 60
4
4x Register Start • 60
A
Add the PTQ Module to the Project • 20, 39
Adding a Module • 57
Adding a Project • 57
Additional Restrictions Relating To Software And Other
Intellectual Property • 148
AI Class • 64
AI Deadband • 65
AI Events with time • 68
AI with flag • 68
All Product Returns • 143
Allocation of risks • 148
Analog Inputs • 69
Analog Outputs • 69
App Layer Confirm Tout • 66
Application Layer Errors • 124
B
Backplane Data Transfer • 95
Baud Rate • 62, 72
BI Class • 64
BI Events without time • 67
BI with Flag • 67
Binary Inputs • 69
Binary Outputs • 69
Block 9958 - Send Binary Input Events • 103
Block 9959 - Send Analog Input Events • 105
Block 9970 - Set Quantum / Unity Processor Time using Module Time • 102
Block 9971 - Set Module's Time using the Quantum /
Unity Processor Time • 103
Block Format for Read • 99, 102
Block Format for Write • 101
Block Format from Module • 103, 104, 105
Block Format from Processor • 103, 104, 105
BO without flag • 67
ProSoft Technology, Inc.
April 22, 2008
Distributed Network Protocol Interface Module
Build the Project • 41
C
Cable Connections • 47
CD Idle Time • 64, 73
CD Random Time • 64, 73
CD Time Before Receive • 64, 73
Class • 70, 71
Class 1 Unsol Resp Min • 66
Class 2 Unsol Resp Min • 66
Class 3 Unsol Resp Min • 66
Clearing a Fault Condition • 88
Clearing the Error List • 82
Collision Avoidance • 64, 73
Collision Avoidance (DNP modules only) • 51
Command Error Codes • 123
Command List • 128
Command List Entry Form • 126
Comment Entries • 59
Configuration Error Word • 117
Configuring the Processor with Concept • 15
Configuring the Processor with ProWORX • 33
Configuring the Processor with UnityPro XL • 37
Connect the PC to the ProTalk Configuration/Debug
Port • 51
Connect Timeout • 63
Connect Your PC to the Processor • 42
Connecting to the Processor with TCPIP • 43
Controlling Law and Severability • 149
Counter with flag • 67
Counters • 69
Create a New Project • 17, 37
D
Data Link Confirm Mode • 65
Data Link Confirm Tout • 65
Data Link Max Retry • 66
Data Requirements • 107
Data Transfer at Startup • 116
Data Transfer Interface • 109, 110
Deadband • 71
Design • 106
Designing the system • 107
Diagnostics and Troubleshooting • 9, 74, 77, 116
DISCLAIMER OF ALL OTHER WARRANTIES • 147
DISCLAIMER REGARDING HIGH RISK ACTIVITIES •
147
Displaying the Current Page of Registers Again • 85
DNP Analog Input Data • 114
DNP Analog Output Data • 115
DNP Counter Data • 113
DNP Database View Menu • 82, 84
DNP Digital Input Data • 110
DNP Digital Output Data • 112
DNP Port Configuration Errors • 119
DNP Subset Definition • 129
DNPS Specific Questions • 140
Download the Project to the Module • 74
Download the Project to the Processor • 25, 44
Page 151 of 153
PTQ-DNPS ♦ Quantum / Unity Platform
Distributed Network Protocol Interface Module
E
Error Codes • 117, 123
Error Status Table • 119
F
Features and Benefits • 91
First Character Delay • 63
Float Class • 65
Float Deadband • 65
Float Inputs • 69
Float Outputs • 69
Frequently Asked Questions • 138
Frozen counter with flag • 67
Functional Overview • 9, 94
Functional Specifications • 93
Functionality • 115
G
General Command Errors • 123
General Concepts • 94
General Specifications • 91
Guide to the PTQ-DNPS Application Reference Guide
• 9
H
Hardware and Software Requirements • 11
Hardware Specifications • 92
How to Contact Us
Sales and Support • 142
I
Idle Timeout • 63
Information for Concept Version 2.6 Users • 16
Initialize DNP Database • 68
Input and Output Data Blocks • 99
Inserting the 1454-9F connector • 46
Install ProSoft Configuration Builder Software • 13
Install the ProTalk Module in the Quantum Rack • 45,
46
Installing MDC Configuration Files • 16
Intellectual Property • 148
Internal Indication Word • 137
Internal Slave ID • 62
K
Keystrokes • 80
L
LED Status Indicators • 9, 87
LIMITATION OF REMEDIES** • 147
LIMITED WARRANTY • 145
M
Main Logic Loop • 94
Main Menu • 80
Master Port DNPS Slave Configuration Values (DNPS
Master Slave List) • 125
Min Response Delay • 63, 73
Page 152 of 153
Modem • 63
Modifying the Configuration File • 55
Module Entries • 59
Module Error Codes • 117
Module Name • 60
Module Operation • 116
Module Power Up • 94
Moving Back Through 5 Pages of Registers • 86
Navigation • 79
No Other Warranties • 148
N
O
Opening the Class Assignment Menu • 82
Opening the DNP Database View Menu • 82
P
PC and PC Software • 12
Phone Number • 64
Please Read This Notice • 2
Point # • 70, 71
Printing a Configuration File • 59
Procedures for Return of Units Out of Warranty • 144
Procedures for Return of Units Under Warranty • 143
Product Specifications • 9, 91
ProSoft Configuration Builder • 55
ProTalk Module Carton Contents • 11
PTQ Installation and Operating Instructions • 2
PTQ-DNPS Application Design • 106
Purchasing Warranty Extension • 145
Q
Quantum / Unity Hardware • 12
R
Reading Status Data from the Module • 77
Receiving the Configuration File • 83
Redial Delay Time • 63
Redial Random Delay • 63
Reference • 9, 91
Required Hardware • 77
Return Material Authorization (RMA) Policies and
Conditions • 142
Returning to the Main Menu • 87
RS-232 • 48
Modem Connection • 48
Null Modem Connection (Hardware Handshaking)
• 49
Null Modem Connection (No Hardware
Handshaking) • 49
RS-232 Configuration/Debug Port • 47
RS-422 • 50
RS-485 • 50
RS-485 and RS-422 Tip • 50
RTS Off • 62, 73
RTS On • 62, 73
Index
ProSoft Technology, Inc.
April 22, 2008
S
Select/Operate Arm Time • 65
Sending the Configuration File • 83
Set Module Parameters • 58
Set up Data Memory in Project • 22
Set Up the Project • 56
Setting the Debug Level • 81
Setting Up the ProTalk Module • 45
Skipping 500 Registers of Data • 86
Slave Port Communication Errors • 117
Start Here • 9, 11
Status Block 9250 • 99
Status Block 9251 • 101
Support, Service & Warranty • 9, 141
System Configuration Errors • 118
T
The Configuration/Debug Menu • 78
Time Limit for Bringing Suit • 147
Time Sync Before Events • 68
Troubleshooting • 88
Type • 72
U
Un-repairable Units • 144
Unsol Resp Delay • 66
Unsolicited Response • 66
Uresp Master Address • 67
Uresp Retry Count • 67
Using the Diagnostic Window in ProSoft Configuration
Builder • 78
V
Verification and Troubleshooting • 74
Verify Jumper Settings • 45
Verify Successful Download • 28
Viewing Block Transfer Statistics • 83
Viewing COM States • 82
Viewing Comm Stats • 82
Viewing Data in ASCII (Text) Format • 86
Viewing Data in Decimal Format • 86
Viewing Data in Double Word Decimal Format • 86
Viewing Data in Floating Point Format • 86
Viewing Data in Hexadecimal Format • 86
Viewing Data Type Databases • 85
Viewing DNP Analog Inputs • 87
Viewing DNP Analog Outputs • 87
Viewing DNP Binary Inputs • 86
Viewing DNP Binary Outputs • 87
Viewing DNP Counters • 87
Viewing DNP Float Inputs • 87
Viewing DNP Float Outputs • 87
Viewing DNP Frozen Counters • 87
Viewing DNP Server Data • 83
Viewing DNP Set Up & Pointers • 81
Viewing Operating Parameters • 81
Viewing Register Pages • 85
Viewing the Error List • 81, 82
Viewing the Next 100 Registers of Data • 86
ProSoft Technology, Inc.
April 22, 2008
Distributed Network Protocol Interface Module
Viewing the Previous 100 Registers of Data • 86
Viewing Version Information • 82
W
Warm Booting the Module • 82
What Is Covered By This Warranty • 145
What Is Not Covered By This Warranty • 146
Write Time Interval • 65
Your Feedback Please • 3
Y
Page 153 of 153
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 2 PLEASE READ THIS NOTICE
- 2 PTQ Installation and Operating Instructions
- 2 Important Notice
- 3 Your Feedback Please
- 9 GUIDE TO THE PTQ-DNPS APPLICATION REFERENCE GUIDE
- 11 START HERE
- 11 Hardware and Software Requirements
- 11 ProTalk Module Carton Contents
- 12 Quantum / Unity Hardware
- 12 PC and PC Software
- 13 Install ProSoft Configuration Builder Software
- 15 CONFIGURING THE PROCESSOR WITH CONCEPT
- 16 Information for Concept Version 2.6 Users
- 16 Installing MDC Configuration Files
- 17 Create a New Project
- 20 Add the PTQ Module to the Project
- 22 Set up Data Memory in Project
- 25 Download the Project to the Processor
- 28 Verify Successful Download
- 33 CONFIGURING THE PROCESSOR WITH PROWORX
- 37 CONFIGURING THE PROCESSOR WITH UNITYPRO XL
- 37 Create a New Project
- 39 Add the PTQ Module to the Project
- 41 Build the Project
- 42 Connect Your PC to the Processor
- 43 Connecting to the Processor with TCPIP
- 44 Download the Project to the Processor
- 45 SETTING UP THE PROTALK MODULE
- 45 Install the ProTalk Module in the Quantum Rack
- 45 Verify Jumper Settings
- 46 Inserting the 1454-9F connector
- 46 Install the ProTalk Module in the Quantum Rack
- 47 Cable Connections
- 47 RS-232 Configuration/Debug Port
- 51 Collision Avoidance (DNP modules only)
- 51 Connect the PC to the ProTalk Configuration/Debug Port
- 55 MODIFYING THE CONFIGURATION FILE
- 55 ProSoft Configuration Builder
- 56 Set Up the Project
- 58 Set Module Parameters
- 60 [Module]
- 60 Module Name
- 60 [PTQ BACKPLANE]
- 60 3x Register Start
- 60 4x Register Start
- 60 [DNP Slave]
- 62 Internal Slave ID
- 62 Baud Rate
- 62 RTS On
- 62 RTS Off
- 63 Min Response Delay
- 63 Modem
- 63 Connect Timeout
- 63 First Character Delay
- 63 Redial Delay Time
- 63 Redial Random Delay
- 63 Idle Timeout
- 64 Phone Number
- 64 Collision Avoidance
- 64 CD Idle Time
- 64 CD Random Time
- 64 CD Time Before Receive
- 64 BI Class
- 64 AI Class
- 65 Float Class
- 65 AI Deadband
- 65 Float Deadband
- 65 Select/Operate Arm Time
- 65 Write Time Interval
- 65 Data Link Confirm Mode
- 65 Data Link Confirm Tout
- 66 Data Link Max Retry
- 66 App Layer Confirm Tout
- 66 Unsolicited Response
- 66 Class 1 Unsol Resp Min
- 66 Class 2 Unsol Resp Min
- 66 Class 3 Unsol Resp Min
- 66 Unsol Resp Delay
- 67 Uresp Master Address
- 67 Uresp Retry Count
- 67 BI with Flag
- 67 BI Events without time
- 67 BO without flag
- 67 Counter with flag
- 67 Frozen counter with flag
- 68 AI with flag
- 68 AI Events with time
- 68 Time Sync Before Events
- 68 Initialize DNP Database
- 68 [DNP Slave Database]
- 69 Binary Inputs
- 69 Analog Inputs
- 69 Float Inputs
- 69 Counters
- 69 Binary Outputs
- 69 Analog Outputs
- 69 Float Outputs
- 70 [DNP Slave Binary Inputs]
- 70 Point
- 70 Class
- 70 [DNP Slave Analog Inputs]
- 70 Point
- 70 Class
- 71 Deadband
- 71 [DNP Slave Float Inputs]
- 71 Point
- 71 Class
- 71 Deadband
- 71 [Secondary Port]
- 72 Baud Rate
- 73 RTS On
- 73 RTS Off
- 73 Min Response Delay
- 73 Collision Avoidance
- 73 CD Idle Time
- 73 CD Random Time
- 73 CD Time Before Receive
- 74 Download the Project to the Module
- 74 Verification and Troubleshooting
- 77 DIAGNOSTICS AND TROUBLESHOOTING
- 77 Reading Status Data from the Module
- 77 Required Hardware
- 78 The Configuration/Debug Menu
- 80 Main Menu
- 84 DNP Database View Menu
- 87 LED Status Indicators
- 88 Clearing a Fault Condition
- 88 Troubleshooting
- 91 REFERENCE
- 91 Product Specifications
- 91 Features and Benefits
- 91 General Specifications
- 92 Hardware Specifications
- 93 Functional Specifications
- 94 Functional Overview
- 94 General Concepts
- 99 Input and Output Data Blocks
- 106 PTQ-DNPS Application Design
- 117 Module Error Codes
- 117 Configuration Error Word
- 117 Slave Port Communication Errors
- 118 System Configuration Errors
- 119 DNP Port Configuration Errors
- 119 Error Status Table
- 123 Command Error Codes
- 125 Master Port DNPS Slave Configuration Values (DNPS Master Slave List)
- 126 Command List Entry Form
- 128 Command List
- 129 DNP Subset Definition
- 137 Internal Indication Word
- 138 Frequently Asked Questions
- 140 DNPS Specific Questions
- 141 SUPPORT, SERVICE & WARRANTY
- 142 How to Contact Us: Sales and Support
- 142 Return Material Authorization (RMA) Policies and Conditions
- 143 All Product Returns
- 143 Procedures for Return of Units Under Warranty
- 144 Procedures for Return of Units Out of Warranty
- 144 Un-repairable Units
- 145 LIMITED WARRANTY
- 145 What Is Covered By This Warranty
- 146 What Is Not Covered By This Warranty
- 151 DISCLAIMER REGARDING HIGH RISK ACTIVITIES