C HAPTER 3 _______________________________________________________________ INSTALLATION
Connection to an AC supply
The DMP248 transmitter can also be connected to an AC supply without an external rectifier. However, when more than one transmitter is connected for example to one 24 VAC transformer, a common loop is formed and there is an increased risk of a shortcircuit. To avoid this, always use separate floating supply for each transmitter (see F IGURE 3-18 A). However, if several transmitters have to share one transformer, the phase (
∼
) must always be connected to + connector in each transmitter (see F IGURE 3-18 B).
A) NO COMMON LOOP FORMED - RECOMMENDED
DMP248 transmitter Controller
24 VAC
24 VAC
B) COMMON LOOP FORMED - NOT RECOMMENDED!
DMP248 transmitter
Controller
24 VAC
DMP248 transmitter shared common line
F IGURE 3-18
DMP248 transmitter
Connecting the transmitter to an AC supply.
V AISALA _________________________________________________________________________ 23
advertisement
Related manuals
advertisement
Table of contents
- 5 CHAPTER 1 GENERAL INFORMATION
- 7 CHAPTER 2 PRODUCT DESCRIPTION
- 10 Use in high pressure
- 11 CHAPTER 3 INSTALLATION
- 13 Mounting; overview
- 14 Mounting the probe directly to the process
- 15 Installing the probe through the ball valve assembly
- 21 Mounting the probe with a quick connect
- 22 Sample cell
- 24 Grounding
- 26 Connections
- 27 Connection to an AC supply
- 29 CHAPTER 4 COMMISSIONING
- 37 CHAPTER 5 COMMANDS
- 59 CHAPTER 6 CALIBRATION AND ADJUSTMENT
- 60 Two-point calibration and adjustment adjustment procedure
- 60 Using serial commands
- 61 Using display/keypad commands
- 62 Using LED commands
- 63 Humidity calibration table
- 63 One point offset correction
- 63 Using serial commands
- 64 Using display/keypad commands
- 64 Using LED commands
- 65 Two-point temperature calibration and adjustement
- 65 Using serial commands
- 66 Using display/keypad commands
- 66 Using LED commands
- 67 Using serial commands
- 67 Using display/keypad commands
- 68 Using LED commands
- 71 CHAPTER 7 MAINTENANCE
- 76 CHAPTER 8 TECHNICAL DATA
- 80 CHAPTER 9 OPTIONS
- 81 CHAPTER 10 SPARE PARTS AND ACCESSORIES
- 83 APPENDIX 1 SERIAL COMMANDS
- 105 APPENDIX 2 POWER SUPPLY MODULE
- 109 APPENDIX 3 INSTALLING AND USING THE RS 485/422 SERIAL PORT MODULE
- 119 APPENDIX 4 INSTALLING AND USING THE CURRENT LOOP MODULE
- 129 APPENDIX 5 ERROR MESSAGES
- 133 APPENDIX 6 WIRING DIAGRAM
- 135 APPENDIX 7 ALARM OUTPUT UNIT
- 141 APPENDIX 8 PRESSURE CONVERSION CHART
- 141 Multiplication factors