INSTALLATION
This chapter introduces the installation and connection of NetSure 801 CAA series power supply system (power supply system for short).
Cabinet Installation
Cabinet Placement
Before installing and connecting the power system, make sure the layout of each cabinet in the power system, especially the placement of DC cabinet and rectifier cabinet. Different placement may directly impact the selection and installation of the parallel connection copper bars, there are mainly two placement modes:
Rectifier cabinet – DC cabinet spaced placement
The NetSure 801 CAA power supply system can be expanded up to 6000A. As the max current carrying capacity of single parallel connection bar is 2000A, when the system capacity exceeds
2000A, the system cabinets should be arranged in the way that the max current carrying capacity of one parallel connection bar does not exceed 2000A.
It is recommended to place the cabinets in the way of “Rectifier cabinet - DC cabinet- Rectifier cabinet- DC cabinet”. For a system composed of Rack1000-A rectifier cabinet, place one rectifier cabinet or two rectifier cabinets as a unit. For a system composed of Rack2000-A, Rack1500-A rectifier cabinet, place one rectifier cabinet as a unit.
Recommended arrangement of 6000A system using Rack1000-A rectifier cabinet.
Recommended arrangement of 6000A system using Rack2000-A, Rack1500-A rectifier cabinet:
Rectifier cabinet - Rectifier cabinet and DC cabinet - DC cabinet parallel placement
If the installation site does not permit the cabinet arrangement shown above, it is suggested to use two parallel connection copper bars so that the current carrying capacity of single connection bar does not exceed 2000A.
If ‘ Rectifier cabinet - Rectifier cabinet and DC cabinet - DC cabinet parallel placement ’ is adopted, the cabinet placement on the customer site must be stated or a schematic arrangement of the cabinets must be provided when pre-purchasing the power system.
Vertiv | NetSure 801 CAA Series Power Supply System Instruction Manual 42
advertisement
Related manuals
advertisement
Table of contents
- 5 Safety Precautions
- 5 Electrical Safety
- 6 Battery
- 7 Others
- 8 OVERVIEW
- 8 Model Information
- 8 Overview
- 9 Components
- 9 Rectifier
- 11 Controller
- 11 AC Distribution Cabinet
- 16 DC Distribution Cabinet
- 24 Rectifier Cabinet
- 29 installation preparation
- 29 Installation Requirements
- 29 Environmental Requirements
- 29 Layout Requirements of The Equipment Room
- 32 Power Supply
- 33 Safety Protection
- 34 Equipment Running Environment Checklist
- 36 Storage Conditions
- 36 Installation Preparation
- 40 Unpacking Inspection
- 42 Installation
- 42 Cabinet Installation
- 42 Cabinet Placement
- 43 Mounting Large Side Door And Small Side Door
- 43 Installation on The Floor
- 45 Installation on Supporting Rack
- 46 Parallel Connection Between Cabinets
- 46 Parallel Connection with Copper Bars
- 49 Connecting Power Cables
- 50 Connecting Earth Cable
- 52 Distribution Cabinet
- 55 Connecting AC Input Cables
- 57 Connecting DC Emergency Lighting Cables (Optional)
- 58 Connecting DC Load Cables
- 59 Connecting Battery Cables
- 60 Installation Checklist
- 61 Installing Rectifier and Controller
- 61 Installing Rectifier
- 62 Installing Controller
- 63 Board
- 66 Cable
- 66 Connecting Rectifier Cabinet Communication Cable
- 68 Cabinet
- 69 Connecting Communication Cable of Distribution Cabinet
- 71 Installing Options
- 71 Installing Temperature Sensor
- 73 Testing
- 73 Note on Testing
- 73 Power-on
- 75 Setting Basic Parameters
- 75 Setting DIP Switch
- 76 Setting Basic Parameters for Controller
- 82 Checking Alarm and Operation Status
- 82 Testing Controller
- 84 Testing AC Distribution
- 85 Testing DC Distribution
- 86 Access Controller Through Web
- 94 Operation
- 94 Power Distribution LCD Operation
- 96 Controller Operation of Rectifier Cabinet
- 96 System Alarm and Status
- 96 Distribution Parameters Setting
- 96 Setting the Position Number of The Rectifier Manually
- 100 Adding Load
- 100 Adding Rectifier
- 101 Maintenance
- 101 Maintenance Requirements
- 101 General
- 101 Maintenance Tools and Equipment
- 102 Reference Technical Specification for Maintenance
- 104 Routine Maintenance Items
- 107 Routine Maintenance
- 108 Basic Inspection
- 108 Handling Controller Fault
- 108 Handling Rectifier Fault
- 110 Replacing Rectifier
- 111 Emergency Treatment
- 113 Appendix 1 Technical Parameters
- 116 Appendix 2 Alarm list
- 122 Appendix 3 ENGINEERING DESIGN DIAGRAM
- 138 APPENDIX 4 WIRING DIAGRAM
- 156 Appendix 5 SPARE PARTS