Figure 32: Earth terminal of the DC distribution cabinet (left view)

Earth terminal

3. Connect one end of the earth cable to the user earth bar, and the other end to the earth bar in the AC distribution cabinet (See Figure 31 and Figure 32 ).

4. Lead out the DC earth cable from the positive busbar of the DC distribution cabinet, and connect it to the copper earth bar in the equipment room. The sectional area of the DC earth cable increases with system capacity, and should be at least 95mm 2 .

Connecting Cables Between Rectifier Cabinet and AC Distribution Cabinet

For Rack1000-A rectifier cabinet, choose one 160A MCB as AC input switch of the rectifier cabinet.

For Rack1500-A and Rack2000-A rectifier cabinets, choose two 160A MCBs as AC input switches of the rectifier cabinet.

Follow the steps below to install the AC input cables of the rectifier cabinet.

1. If the AC input cables of the rectifier cabinet are routed inside the cabinets, users can use the accessory cables as the AC input cables. Otherwise users need to prepare armored cables by themselves. If the system capacity exceeds 2000A, users need to prepare extra cables. The cable specification cannot greater than 50mm 2 . The wiring is shown in Figure 33 .

Vertiv | NetSure 801 CAA Series Power Supply System Instruction Manual 52

Figure 33: Connection of AC input cables of rectifier cabinet in AC distribution cabinet (front view)

2. Connect one end of the cable to the output terminal of the selected MCB in the AC distribution cabinet (do not connect the neutral line). The AC input cable wiring is shown in Figure 34 and Figure

35 .

Figure 34: AC input cable wiring (manually switch AC distribution cabinet, rear view)

Front view Right view

Vertiv | NetSure 801 CAA Series Power Supply System Instruction Manual

Top view

Input cable wiring area

Output cable wiring area one

Output cable wiring area two

53

Figure 35: AC input cable wiring (automatically switch AC distribution cabinet, rear view)

Top view

Output cable wiring area

Input cable wiring area

Right view Front view

3. Connect the other end of the cable to the AC input terminal of the rectifier cabinet. The connection of AC input cables in rectifier cabinet is shown in Figure 36 .

Vertiv | NetSure 801 CAA Series Power Supply System Instruction Manual 54