Table 14: Setting DIP switches of DC distribution cabinet
BIT 1 BIT 2 BIT 3 BIT 4
1
0
1
0
1
1
0
1
0
1
0
1
0
0
1
0
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
NOTE!
Address of the AC distribution cabinet default setting from factory is 72, if there are multiple AC screens, set the cabinets address to 72, 73 ,… ,87.
CORRESPONDING
ADDRESS IN THE
CONTROLLER
83
84
85
86
87
79
80
81
82
72
73
74
75
76
77
78
The setting explanation of bits 5 to 8 is given in Table 15 .
Table 15: Setting list of DIP switch
BIT
5
6
7
8
DEFINITION
Reserved
Reserved
Reserved
Reserved
SETTING EXPLANATION
Default: OFF
Default: OFF
Default: OFF
Default: OFF
Setting Basic Parameters for Controller
To put the system into service, system setting must be done through the controller, battery group number, battery nominal capacity, charge current limit and other function requirements according to the actual system configuration. Otherwise, the system information display and output control cannot function normally.
1. At the default LCD screen (if stay in other screen, press ESC will exit to the default screen) of the controller in AC distribution cabinet, press ESC to enter the product information screen, as shown in
Figure 61 .
2. check whether the ‘ Address ’ is within the range of 64 ~ 71. If the address is out of the range or there are two or above AC screens set to the same address, then press and simultaneously at the first screen to enter the parameter setting screen and reset the address, and press Enter to confirm.
Figure 61: AC screen address
Vertiv | NetSure 801 CAA Series Power Supply System Instruction Manual 76
Model:
CommAddr:
SW Ver:
AEM02
64
V1.00
2. At the default LCD screen of DC distribution cabinet, press ESC to enter the product information screen. Check whether the ‘ Address ’ is within the range of Table 16 . If the address is out of the range in Table 16 or there are two or above DC screens set to the same address, then reset the address according to Setting DIP Switch .
Figure 62: DC screen address
Model: HDUL
Syetem Type: X3
CommAddr: 72
SW Ver: 1.001
3. At the controller MAINMENU screen in DC cabinet, press ENT to enter the ‘Settings’ screen
(password: 1), enter ‘ DC Settings ’ --> ’Total Load Brh:’ --> ’Total Load Curr’, set the b ranch number
(that is load branch number of the first layer in DC screen, the branches of the second layer and third layer are not calculated) and the sampling component type of the total load current.
Figure 63: Setting load sampling type
Tot alL oadBr h:
Tot alL oadCur r :
8
Hall
Table 16: DC screen setting
PARAMETER NAME
DESCRIPTION
Total Load Brh Total Load Curr
8
8
8
8
8
Hall
Hall
Hall
Hall
Hall
For PD48/2500DF-A-Y1
For PD48/2500DF-A-Y2
For PD48/2500DF-A-Y3
For PD48/1600DF-A-Y1
For PD48/1600DF-A-Y2
At the controller first screen in DC cabinet, press ENT to enter the ‘Settings’ screen (password: 1), enter ‘ Batt. Settings ’ --> ’ Shunt Qty :’, ‘Shunt Coef’ --> ’ Current ’, set the battery shunt quantity and battery shunt coefficient of the DC cabinet.
Figure 64: Setting battery shunt
Vertiv | NetSure 801 CAA Series Power Supply System Instruction Manual 77
Batt. String Qty: 2
Shunt Coef:
--Current: 1250A
Table 17: Battery shunt setting
Shunt Qty
4
4
4
2
2
PARAMETER NAME
Shunt Coef-Curr
1250A
1250A
1250A
1250A
1250A
For PD48/2500DF-A-Y1
For PD48/2500DF-A-Y2
For PD48/2500DF-A-Y3
For PD48/1600DF-A-Y1
For PD48/1600DF-A-Y2
DESCRIPTION
NOTE!
Except the above four parameters, other parameters of the DC distribution cabinet should be set in the M831D interface.
4. At the first screen of DC distribution cabinet, press ENT to enter ‘Settings’ --> ’System Parameters’ menu (password: 1), and confirm that the syst em type is ‘X3’.
Figure 65: Setting system type
ComDownLoad: N
LVD Enable: N
Syetem Type:
X3
5. At the controller MAINMENU screen in rectifier cabinet, press or to move the cursor to the setting icon
. Click the setting icon and input user name ( ‘ admin ’ ) and password ( ‘ 1 ’ ) to enter the setting screen.
6. Enter ‘ AC Settings ’ --> ’ AC Distrib 1 ’…… ’ AC Distrib n ’ , check the PD380/400AFH&PD380/630AFH
AC coefficients of transformer, the corresponding coefficient of PD380/630AFH would be 160, the corresponding coefficient of PD380/400AFH would be 100. If any inconsistencies exist, set the parameters as above.
Figure 66: AC settings
AC Distrib1
Curr Trans Coef:
160
Input Type:
3-Phase
Input Number:
2
AC Distrib1
Input Number:
2
Cur Measurement:
3-Phase
Output Number:
0
Vertiv | NetSure 801 CAA Series Power Supply System Instruction Manual 78
Table 18: AC transformer setting
PARAMETER NAME
DEFAULT
SETTING
DESCRIPTION
AC Transformer
Coefficient
160
100
Used for PD380/630AFH, the corresponding coefficient is 800/5
Used for PD380/400AFH, the corresponding coefficient is 500/5
Current Measure Ty Single phase
Set according to actual current transformer number, the default setting is single phase
7. Back to the setting screen, enter ‘ DC Settings ’ --> ’ DC Distrib 1 ’…… ’ DC Distrib n ’ , check whether the ‘ Hall Coefficient ’ is consistent with Table 19 . If any inconsistencies exist, reset the parameters according to Table 19 .
Vertiv | NetSure 801 CAA Series Power Supply System Instruction Manual 79
Figure 67: Load hall coefficient
DC Distrib1
Sensor Coeff:
4000
Num of Battery:
2
Temp Number:
1
Table 19: Setting DC hall sensor
Parameter name
Default setting Description
3000 Used for PD48/2500DF-A-Y1/Y2/Y3
Hall Coefficient
1500 Used for PD48/1600DF-A-Y1/Y2
8. Enter ‘ DC Settings ’ --> ’ DC Distrib 1 ’…… ’ DC Distrib n ’ , set the ‘Branch Curr Coeff’ and ‘Curr Output
Num’ according to actual situation .
Figure 68: Setting branch current coefficient and current output number
DC Distrib1
Temp Number:
1
Branch Curr Coeff:
500
Curr Output Num:
0
Table 20: Setting branch current coefficient and current output number in DC screen
Parameter name Default setting Description
Branch Curr Coeff 500
8
4
8
Used for PD48/1600DF and PD48/2500DF
Used for PD48/1600DF-A-Y1
Used for PD48/1600DF-A-Y2
Used for PD48/2500DF-A-Y1 Curr Output Num
6 Used for PD48/2500DF-A-Y2
12 Used for PD48/2500DF-A-Y3
9. Enter ‘ DC Settings ’ --> ’ DC Distrib 1 ’…… ’ DC Distrib n ’ , set the ‘Num of Output’, the default value is
64. If the number of output is less than 64, then there is no need to set the ‘Num of Output’.
Figure 69: Setting number of output
DC Distrib1
Branch Curr Coeff :
500
Curr Output Num:
0
Numof Output:
64
Vertiv | NetSure 801 CAA Series Power Supply System Instruction Manual 80
10. Back to ‘ DC Settings ’ --> ’ DC Distrib 1 ’…… ’ DC Distrib n ’ , set the ‘ Num of Battery ’ of each DC distribution screen according to actual connected battery strings.
Figure 70: Setting number of battery
DC Distrib1
Sensor Coeff:
4000
Num of Battery:
2
Temp Number:
1
11. Set battery parameters as follows:
Back to ‘ Settings ’ screen, enter ‘ Batt Settings ’ ->’ Charge ’ , set the actual connected battery string capacity, then click ‘ Reset Batt Cap ’ , select ‘ Yes ’ and press ENT to confirm. Back to the ‘ Batt
Settings ’ screen, enter the ‘ LargeDU ’ screen to set the battery current sampling coefficient. (The battery string index is related with the connected DC cabinet address and battery string number, if the DIP of DC Distrib 1 is set to 72, and the the DIP of DC Distrib 2 is set to 73, and the battery string number is set to 2, then the battery current coefficient of battery string1 and battery string 2 is the shunt coefficient of two battery ports in DC Distrib 1, and the current coefficient of battery string 3 and battery string 4 is the shunt coefficient of two battery ports in DC Distrib 2.)
Figure 71: Setting battery nominal capacity
Auto EQ:
Yes
Rated Capacity:
500Ah
Reset Batt Cap:
Yes
Charge
Figure 72: Setting battery string sampling coefficient
Batt Settings
Charge >
Battery Test >
Temp Comp >
LargeDU Batt1 >
LargeDU Batt2 >
Batt Settings
Charge >
Battery Test >
Temp Comp >
LargeDU Batt1 >
LargeDU Batt2 >
Back to ‘ Batt Settings ’ screen, enter ‘ Temp Comp ’ screen, set the ‘ Temp Comp Coeff ’ according to battery factory requirement. The default value is 72mV/°C (If no temperature sensor is configured, ignore this item), and set the ‘ TempComp Sensor ’ to ‘Ldu1 Temp1’ , as shown in Figure 73 . (If no temperature sensor is configured or the temperature compensation function needs to be canceled, then set the ‘ TempComp Sensor ’ to ‘ None ’ ). Meanwhile, set ‘ DC Settings ’ ’ DC Distrib 1 ’ Temp
Number ’ to 1 ~ 2 (if no temperature sensor is configured or the temperature compensation function needs to be canceled, then set the ‘ Temp Number ’ to ‘ 0 ’ ), as shown in Figure 74 .
Vertiv | NetSure 801 CAA Series Power Supply System Instruction Manual 81
advertisement
Related manuals
advertisement
Table of contents
- 5 Safety Precautions
- 5 Electrical Safety
- 6 Battery
- 7 Others
- 8 OVERVIEW
- 8 Model Information
- 8 Overview
- 9 Components
- 9 Rectifier
- 11 Controller
- 11 AC Distribution Cabinet
- 16 DC Distribution Cabinet
- 24 Rectifier Cabinet
- 29 installation preparation
- 29 Installation Requirements
- 29 Environmental Requirements
- 29 Layout Requirements of The Equipment Room
- 32 Power Supply
- 33 Safety Protection
- 34 Equipment Running Environment Checklist
- 36 Storage Conditions
- 36 Installation Preparation
- 40 Unpacking Inspection
- 42 Installation
- 42 Cabinet Installation
- 42 Cabinet Placement
- 43 Mounting Large Side Door And Small Side Door
- 43 Installation on The Floor
- 45 Installation on Supporting Rack
- 46 Parallel Connection Between Cabinets
- 46 Parallel Connection with Copper Bars
- 49 Connecting Power Cables
- 50 Connecting Earth Cable
- 52 Distribution Cabinet
- 55 Connecting AC Input Cables
- 57 Connecting DC Emergency Lighting Cables (Optional)
- 58 Connecting DC Load Cables
- 59 Connecting Battery Cables
- 60 Installation Checklist
- 61 Installing Rectifier and Controller
- 61 Installing Rectifier
- 62 Installing Controller
- 63 Board
- 66 Cable
- 66 Connecting Rectifier Cabinet Communication Cable
- 68 Cabinet
- 69 Connecting Communication Cable of Distribution Cabinet
- 71 Installing Options
- 71 Installing Temperature Sensor
- 73 Testing
- 73 Note on Testing
- 73 Power-on
- 75 Setting Basic Parameters
- 75 Setting DIP Switch
- 76 Setting Basic Parameters for Controller
- 82 Checking Alarm and Operation Status
- 82 Testing Controller
- 84 Testing AC Distribution
- 85 Testing DC Distribution
- 86 Access Controller Through Web
- 94 Operation
- 94 Power Distribution LCD Operation
- 96 Controller Operation of Rectifier Cabinet
- 96 System Alarm and Status
- 96 Distribution Parameters Setting
- 96 Setting the Position Number of The Rectifier Manually
- 100 Adding Load
- 100 Adding Rectifier
- 101 Maintenance
- 101 Maintenance Requirements
- 101 General
- 101 Maintenance Tools and Equipment
- 102 Reference Technical Specification for Maintenance
- 104 Routine Maintenance Items
- 107 Routine Maintenance
- 108 Basic Inspection
- 108 Handling Controller Fault
- 108 Handling Rectifier Fault
- 110 Replacing Rectifier
- 111 Emergency Treatment
- 113 Appendix 1 Technical Parameters
- 116 Appendix 2 Alarm list
- 122 Appendix 3 ENGINEERING DESIGN DIAGRAM
- 138 APPENDIX 4 WIRING DIAGRAM
- 156 Appendix 5 SPARE PARTS