Setting Basic Parameters for Controller. Vertiv NetSure 801 CAA

Add to My manuals
158 Pages

advertisement

Setting Basic Parameters for Controller. Vertiv NetSure 801 CAA | Manualzz

Table 14: Setting DIP switches of DC distribution cabinet

BIT 1 BIT 2 BIT 3 BIT 4

1

0

1

0

1

1

0

1

0

1

0

1

0

0

1

0

0

0

1

1

0

0

1

1

0

0

1

1

0

0

1

1

0

0

0

0

1

1

1

1

0

0

0

0

1

1

1

1

0

0

0

0

0

0

0

0

1

1

1

1

1

1

1

1

NOTE!

Address of the AC distribution cabinet default setting from factory is 72, if there are multiple AC screens, set the cabinets address to 72, 73 ,… ,87.

CORRESPONDING

ADDRESS IN THE

CONTROLLER

83

84

85

86

87

79

80

81

82

72

73

74

75

76

77

78

The setting explanation of bits 5 to 8 is given in Table 15 .

Table 15: Setting list of DIP switch

BIT

5

6

7

8

DEFINITION

Reserved

Reserved

Reserved

Reserved

SETTING EXPLANATION

Default: OFF

Default: OFF

Default: OFF

Default: OFF

Setting Basic Parameters for Controller

To put the system into service, system setting must be done through the controller, battery group number, battery nominal capacity, charge current limit and other function requirements according to the actual system configuration. Otherwise, the system information display and output control cannot function normally.

1. At the default LCD screen (if stay in other screen, press ESC will exit to the default screen) of the controller in AC distribution cabinet, press ESC to enter the product information screen, as shown in

Figure 61 .

2. check whether the ‘ Address ’ is within the range of 64 ~ 71. If the address is out of the range or there are two or above AC screens set to the same address, then press and simultaneously at the first screen to enter the parameter setting screen and reset the address, and press Enter to confirm.

Figure 61: AC screen address

Vertiv | NetSure 801 CAA Series Power Supply System Instruction Manual 76

Model:

CommAddr:

SW Ver:

AEM02

64

V1.00

2. At the default LCD screen of DC distribution cabinet, press ESC to enter the product information screen. Check whether the ‘ Address ’ is within the range of Table 16 . If the address is out of the range in Table 16 or there are two or above DC screens set to the same address, then reset the address according to Setting DIP Switch .

Figure 62: DC screen address

Model: HDUL

Syetem Type: X3

CommAddr: 72

SW Ver: 1.001

3. At the controller MAINMENU screen in DC cabinet, press ENT to enter the ‘Settings’ screen

(password: 1), enter ‘ DC Settings ’ --> ’Total Load Brh:’ --> ’Total Load Curr’, set the b ranch number

(that is load branch number of the first layer in DC screen, the branches of the second layer and third layer are not calculated) and the sampling component type of the total load current.

Figure 63: Setting load sampling type

Tot alL oadBr h:

Tot alL oadCur r :

8

Hall

Table 16: DC screen setting

PARAMETER NAME

DESCRIPTION

Total Load Brh Total Load Curr

8

8

8

8

8

Hall

Hall

Hall

Hall

Hall

For PD48/2500DF-A-Y1

For PD48/2500DF-A-Y2

For PD48/2500DF-A-Y3

For PD48/1600DF-A-Y1

For PD48/1600DF-A-Y2

At the controller first screen in DC cabinet, press ENT to enter the ‘Settings’ screen (password: 1), enter ‘ Batt. Settings ’ --> ’ Shunt Qty :’, ‘Shunt Coef’ --> ’ Current ’, set the battery shunt quantity and battery shunt coefficient of the DC cabinet.

Figure 64: Setting battery shunt

Vertiv | NetSure 801 CAA Series Power Supply System Instruction Manual 77

Batt. String Qty: 2

Shunt Coef:

--Current: 1250A

Table 17: Battery shunt setting

Shunt Qty

4

4

4

2

2

PARAMETER NAME

Shunt Coef-Curr

1250A

1250A

1250A

1250A

1250A

For PD48/2500DF-A-Y1

For PD48/2500DF-A-Y2

For PD48/2500DF-A-Y3

For PD48/1600DF-A-Y1

For PD48/1600DF-A-Y2

DESCRIPTION

NOTE!

Except the above four parameters, other parameters of the DC distribution cabinet should be set in the M831D interface.

4. At the first screen of DC distribution cabinet, press ENT to enter ‘Settings’ --> ’System Parameters’ menu (password: 1), and confirm that the syst em type is ‘X3’.

Figure 65: Setting system type

ComDownLoad: N

LVD Enable: N

Syetem Type:

X3

5. At the controller MAINMENU screen in rectifier cabinet, press or to move the cursor to the setting icon

. Click the setting icon and input user name ( ‘ admin ’ ) and password ( ‘ 1 ’ ) to enter the setting screen.

6. Enter ‘ AC Settings ’ --> ’ AC Distrib 1 ’…… ’ AC Distrib n ’ , check the PD380/400AFH&PD380/630AFH

AC coefficients of transformer, the corresponding coefficient of PD380/630AFH would be 160, the corresponding coefficient of PD380/400AFH would be 100. If any inconsistencies exist, set the parameters as above.

Figure 66: AC settings

AC Distrib1

Curr Trans Coef:

160

Input Type:

3-Phase

Input Number:

2

AC Distrib1

Input Number:

2

Cur Measurement:

3-Phase

Output Number:

0

Vertiv | NetSure 801 CAA Series Power Supply System Instruction Manual 78

Table 18: AC transformer setting

PARAMETER NAME

DEFAULT

SETTING

DESCRIPTION

AC Transformer

Coefficient

160

100

Used for PD380/630AFH, the corresponding coefficient is 800/5

Used for PD380/400AFH, the corresponding coefficient is 500/5

Current Measure Ty Single phase

Set according to actual current transformer number, the default setting is single phase

7. Back to the setting screen, enter ‘ DC Settings ’ --> ’ DC Distrib 1 ’…… ’ DC Distrib n ’ , check whether the ‘ Hall Coefficient ’ is consistent with Table 19 . If any inconsistencies exist, reset the parameters according to Table 19 .

Vertiv | NetSure 801 CAA Series Power Supply System Instruction Manual 79

Figure 67: Load hall coefficient

DC Distrib1

Sensor Coeff:

4000

Num of Battery:

2

Temp Number:

1

Table 19: Setting DC hall sensor

Parameter name

Default setting Description

3000 Used for PD48/2500DF-A-Y1/Y2/Y3

Hall Coefficient

1500 Used for PD48/1600DF-A-Y1/Y2

8. Enter ‘ DC Settings ’ --> ’ DC Distrib 1 ’…… ’ DC Distrib n ’ , set the ‘Branch Curr Coeff’ and ‘Curr Output

Num’ according to actual situation .

Figure 68: Setting branch current coefficient and current output number

DC Distrib1

Temp Number:

1

Branch Curr Coeff:

500

Curr Output Num:

0

Table 20: Setting branch current coefficient and current output number in DC screen

Parameter name Default setting Description

Branch Curr Coeff 500

8

4

8

Used for PD48/1600DF and PD48/2500DF

Used for PD48/1600DF-A-Y1

Used for PD48/1600DF-A-Y2

Used for PD48/2500DF-A-Y1 Curr Output Num

6 Used for PD48/2500DF-A-Y2

12 Used for PD48/2500DF-A-Y3

9. Enter ‘ DC Settings ’ --> ’ DC Distrib 1 ’…… ’ DC Distrib n ’ , set the ‘Num of Output’, the default value is

64. If the number of output is less than 64, then there is no need to set the ‘Num of Output’.

Figure 69: Setting number of output

DC Distrib1

Branch Curr Coeff :

500

Curr Output Num:

0

Numof Output:

64

Vertiv | NetSure 801 CAA Series Power Supply System Instruction Manual 80

10. Back to ‘ DC Settings ’ --> ’ DC Distrib 1 ’…… ’ DC Distrib n ’ , set the ‘ Num of Battery ’ of each DC distribution screen according to actual connected battery strings.

Figure 70: Setting number of battery

DC Distrib1

Sensor Coeff:

4000

Num of Battery:

2

Temp Number:

1

11. Set battery parameters as follows:

Back to ‘ Settings ’ screen, enter ‘ Batt Settings ’ ->’ Charge ’ , set the actual connected battery string capacity, then click ‘ Reset Batt Cap ’ , select ‘ Yes ’ and press ENT to confirm. Back to the ‘ Batt

Settings ’ screen, enter the ‘ LargeDU ’ screen to set the battery current sampling coefficient. (The battery string index is related with the connected DC cabinet address and battery string number, if the DIP of DC Distrib 1 is set to 72, and the the DIP of DC Distrib 2 is set to 73, and the battery string number is set to 2, then the battery current coefficient of battery string1 and battery string 2 is the shunt coefficient of two battery ports in DC Distrib 1, and the current coefficient of battery string 3 and battery string 4 is the shunt coefficient of two battery ports in DC Distrib 2.)

Figure 71: Setting battery nominal capacity

Auto EQ:

Yes

Rated Capacity:

500Ah

Reset Batt Cap:

Yes

Charge

Figure 72: Setting battery string sampling coefficient

Batt Settings

Charge >

Battery Test >

Temp Comp >

LargeDU Batt1 >

LargeDU Batt2 >

Batt Settings

Charge >

Battery Test >

Temp Comp >

LargeDU Batt1 >

LargeDU Batt2 >

Back to ‘ Batt Settings ’ screen, enter ‘ Temp Comp ’ screen, set the ‘ Temp Comp Coeff ’ according to battery factory requirement. The default value is 72mV/°C (If no temperature sensor is configured, ignore this item), and set the ‘ TempComp Sensor ’ to ‘Ldu1 Temp1’ , as shown in Figure 73 . (If no temperature sensor is configured or the temperature compensation function needs to be canceled, then set the ‘ TempComp Sensor ’ to ‘ None ’ ). Meanwhile, set ‘ DC Settings ’  ’ DC Distrib 1  ’ Temp

Number ’ to 1 ~ 2 (if no temperature sensor is configured or the temperature compensation function needs to be canceled, then set the ‘ Temp Number ’ to ‘ 0 ’ ), as shown in Figure 74 .

Vertiv | NetSure 801 CAA Series Power Supply System Instruction Manual 81