Notation convention for describing the table. Schneider Electric XBTF / TXBTF Graphic Terminals
Werbung
Werbung
2. Dialog table content
The number of words in the table depends on the choice of states and commands that are to be processed during the dialog. You may add or delete items as you choose.
Notation convention for describing the table
NOTE
%MWn word of 16 bits with address n.
%MWn, i : bit i of word n.
The address n is taken as the table's start address.
The table comprises a maximum of 135 words.
The description below gives the content of the various dialog table words; refer to the XBT-L1000 software's on-line help for further information on the various words.
The word number is adapted in accordance with the words of the dialogue table used. The words are addressed in the order established in the "available functions".
C
Ex.
PLC <-- XBT: Terminal writes the corresponding word(s) in the PLC.
PLC --> XBT: Terminal reads the corresponding word(s) in the PLC.
PLC <--> XBT: Terminal and the PLC can modify the corrresponding word(s) in the PLC.
Graphic Magelis
C - 9
2. Dialog table content
Select the Configuration/Dialog table menu.
Check the Use dialog table option.
Click Modify to change the address of the beginning of table %MW100.
In the Function selections list, delete or add the functions required by the application by means of the Add Function or Delete Function buttons to obtain the following list:
Once creation is completed, save the application using the File/ Save menu.
C - 10
Graphic Magelis
2. Dialog table content
%MWn+13
%MWn+14
%MWn+15
%MWn+16
%MWn+17
%MWn+18
%MWn+19
%MWn+20
%MWn+21
%MWn+22
Word
%MWn+0
%MWn+1
%MWn+2
%MWn+3
%MWn+4 to
%MWn+7
%MWn+8
%MWn+9
%MWn+10
%MWn+11
%MWn+12
Functions
Image of static function keys
Image of system keys
Image of numeric keys
Communication control
Set PLC clock
Number of displayed page
Number of last field entered
Number of last alarm acknowledged
Last groups of alarms acknowledged
Report
Log filling rate
Graph plottings performed
Application checksum
Number of page to be processed
Number of field to be entered
Print command
Activating graphs plotting
Table write authorization
Recipe transfer not allowed
Clear Log
Exchange Page
PLC <- XBT
PLC <- XBT
PLC <- XBT
PLC <- XBT
PLC <- XBT
PLC <- XBT
PLC <- XBT
PLC <- XBT
PLC <- XBT
PLC <- XBT
PLC <- XBT
PLC <- XBT
PLC <- XBT
PLC<->XBT
PLC<->XBT
PLC<->XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
C
Graphic Magelis
C - 11
2. Dialog table content
Word
%MWn+23
%MWn+24
%MWn+25
Functions
Static function keys LEDs llighting.
Static function keys LEDs flashing.
Dynamic function keys LEDs lighting.
%MWn+26
%MWn+27
Dynamic function keys LEDs flashing.
Static function keys locking
%MWn+28
%MWn+29
%MWn+30 to
%MWn+90
%MWn+91 to
%MWn+94
%MWn+95 to
%MWn+134
System keys locking
Numeric keys locking
Alarm table
Set terminal clock
Free format print table (40 words maxi)
Exchange Page
PLC -> XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
C - 12
Graphic Magelis