Installation
2.2 Mounting the UPS
The UPS can be placed on a shelf with no other parts needed. Any version of the FXM can be rack or wall mounted or secured to a shelf, such as on an outdoor enclosure’s shelf, with the optional mounting brackets as shown in Figure 2.2.1. The brackets and the screws to attach them to the UPS’s case are available from Alpha Technologies (part number 740-697-21).
Terminal block covers and the battery harness restraining bracket MUST be used and are available from Alpha Technologies (part number 740-698-21). If the
UPS end application is mounted inside an enclosure or in an area restricted to authorized personnel, then the covers and bracket may or may not be needed.
NOTE: To meet NEBS Level 1 specifications when you are installing this unit in a rack or frame, you MUST:
1. Before installation, clean all attachment points on the UPS, rack and mounting brackets and bring them to a bright finish. Then coat them with an anti-oxidant (such as Sanchem
Inc.’s No-Ox ID “A-Special Electrical Grade” or equivalent).
2. Attach the mounting brackets with the provided screws insure adequate grounding between the UPS’s chassis and the rack or frame.
Mounting brackets position for rack mounting (rotate to fit either 19-inch or 23-inch racks).
Figure 2.2.1 – Mounting the UPS
For the FXM 1100/2000 units only, the control panel and the power connection panel can be rotated to suit your needs. To rotate either one, unscrew the screws in each corner, remove the panel, rotate it and reinstall the screws.
Use care to avoid damaging or pulling out the wires or the ribbon cables when rotating the panels.
Doc# 017-201-B0 Rev 05/07 13
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 5 1 Introduction
- 6 1.1 Safety Checklists
- 6 1.1.1 UPS Safety Checklist
- 7 1.1.2 Battery Safety Checklist
- 8 1.2 Unpacking and Inspection Checklist
- 9 1.3 The FXM Front Panel
- 15 2 Installation
- 16 2.1 Site Preparation Checklists
- 17 2.2 Mounting the UPS
- 18 2.3 Wiring the External Batteries
- 20 2.4 Wiring the UPS
- 21 2.5 ATS/GTS Option
- 22 3 Operation
- 23 3.1 Operating the Control Panel
- 25 3.2 Turning the UPS On and Off
- 27 3.3 Replacing the Batteries
- 28 3.4 Operating the UPS
- 30 3.5 Making Measurements
- 32 3.6 Troubleshooting the UPS
- 34 3.7 Viewing the 25-Event Log
- 35 4 Communication
- 36 4.1 Wiring the RS-232 Port
- 37 4.2 Using the Main Menu
- 37 4.2.1 Main Menu Screen
- 38 4.2.2 RS-232 Menu Tree
- 39 4.2.3 Line Status
- 39 4.2.4 Output Status
- 40 4.2.5 Fault and Alarm Displays
- 41 4.3 Adjusting and Controlling the UPS
- 42 Clock
- 42 4.4.1 Programming the Dry Contacts
- 43 4.4.2 Setting the Timer Contact
- 43 4.4.3 Setting the Date and Time
- 44 4.5 100-Event Log
- 45 4.6 Novus User Software
- 45 4.6.1 Introduction
- 45 for the .NET Framework
- 46 4.6.3 Installation and Set Up
- 47 4.6.4 Operation
- 50 5 Maintenance
- 51 5.1 Updating the Software
- 53 Specifications
- 55 Index
- 58 Warrant