Operation
3.2 Turning the UPS On and Off
If the UPS constantly switches between Inverter and Line modes due to a noisy line, the
UPS’s input parameters should be broadened from normal to generator (See Section
3.4, “Operating the UPS, Sense Type.” Also See Specifications, “Boost/Buck/Line
Transfer Thresholds”).
In generator mode, the range of acceptable input frequency and voltage is expanded to accept the fluctuations created by a generator .
3.2.1 Turn On
This procedure assumes the line is qualified and the batteries are fully charged. If the UPS does not act as described, do troubleshooting as described in Section 3.6, “Troubleshooting.”
If this is the first turn on after the UPS’s installation or maintenance, do steps 3 and 4, or do a battery test (See Section 3.4 “Operating the UPS, Battery Test”) to confirm the wiring is correct, that the batteries are charged and that the UPS functions correctly.
Before starting, make sure the UPS’s battery and input circuit breakers are off.
Procedure
1. Turn on the battery circuit breaker.
The LCD displays STANDBY and the fan turns on for about a minute.
2. Turn on the input circuit breaker.
The FXM series has autofrequency sensing. When it is first turned on, it senses the line frequency and adjusts its output frequency to match (Also
See Specifications).
The LCD displays RETRAN, then shows
LINE, or BUCK or BOOST. The status
LED turns on.
If there is no line power, the UPS will go to Line mode when the line is qualified.
If you need to provide backup battery power to the load, do a manual start by using the inverter command (See Section
3.4 “Operating the UPS, Inverter”).
Doc# 017-201-B0 Rev 05/07 21
FXM UPS Operator's Manual
3. Turn off the input circuit breaker.
The LCD shows INVERTER, the status
LED starts flashing to show the UPS is running on backup battery power. Make sure the load(s) are receiving power.
4. Turn on the input circuit breaker.
The LCD displays RETRAN, then shows
LINE, or BUCK or BOOST. The status
LED turns on.
Turn On Finished
3.2.2 Turn Off
1. Turn off the input circuit breaker.
2. Turn off the battery circuit breaker.
The status LED is off and the LCD panel is blank.
Turn Off Finished
22 Doc# 017-201-B0 Rev 05/07
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 5 1 Introduction
- 6 1.1 Safety Checklists
- 6 1.1.1 UPS Safety Checklist
- 7 1.1.2 Battery Safety Checklist
- 8 1.2 Unpacking and Inspection Checklist
- 9 1.3 The FXM Front Panel
- 15 2 Installation
- 16 2.1 Site Preparation Checklists
- 17 2.2 Mounting the UPS
- 18 2.3 Wiring the External Batteries
- 20 2.4 Wiring the UPS
- 21 2.5 ATS/GTS Option
- 22 3 Operation
- 23 3.1 Operating the Control Panel
- 25 3.2 Turning the UPS On and Off
- 27 3.3 Replacing the Batteries
- 28 3.4 Operating the UPS
- 30 3.5 Making Measurements
- 32 3.6 Troubleshooting the UPS
- 34 3.7 Viewing the 25-Event Log
- 35 4 Communication
- 36 4.1 Wiring the RS-232 Port
- 37 4.2 Using the Main Menu
- 37 4.2.1 Main Menu Screen
- 38 4.2.2 RS-232 Menu Tree
- 39 4.2.3 Line Status
- 39 4.2.4 Output Status
- 40 4.2.5 Fault and Alarm Displays
- 41 4.3 Adjusting and Controlling the UPS
- 42 Clock
- 42 4.4.1 Programming the Dry Contacts
- 43 4.4.2 Setting the Timer Contact
- 43 4.4.3 Setting the Date and Time
- 44 4.5 100-Event Log
- 45 4.6 Novus User Software
- 45 4.6.1 Introduction
- 45 for the .NET Framework
- 46 4.6.3 Installation and Set Up
- 47 4.6.4 Operation
- 50 5 Maintenance
- 51 5.1 Updating the Software
- 53 Specifications
- 55 Index
- 58 Warrant