Programmable I/O (PIO) NA-9379, Basic setting

KI00341 2014-10

1 Function and area of use

The Programmable I/O (PIO) combines CODESYS control with the opportunity to build control systems to the exact size and specifications for the I/O signals involved.

In this document “PIO” are used for “Programmable I/O” (NA-9379).

2 About this Start Up document

Copyright © Beijer Electronics, 2014

This documentation (below referred to as ‘the material’) is the property of Beijer Electronics. The holder or user has a non-exclusive right to use the material.

The holder is not allowed to distribute the material to anyone outside his/her organization except in cases where the material is part of a system that is supplied by the holder to his/her customer.

The material may only be used with products or software supplied by Beijer Electronics.

Beijer Electronics assumes no responsibility for any defects in the material, or for any consequences that might arise from the use of the material.

It is the responsibility of the holder to ensure that any systems, for whatever applications, which is based on or includes the material (whether in its entirety or in parts), meets the expected properties or functional requirements.

Beijer Electronics has no obligation to supply the holder with updated versions.

This Start Up document should not be considered as a complete manual. It is an aid to be able to start up a normal application quickly and easily.

Use the following software and drivers in order to obtain a stable application:

Programming software

• CODESYS V3.5 SP3 Patch 1 or later , programming the PIO

• Compiler version 3.5.3.10 (CODESYS V3.5 SP3 Patch 1)

• IOGuidePro 1.1.0.8 #0004 or later

Device description, Crevis PIO NA-9379

• PIO_DeviceDescription 20140416.devdesc(.xml) or later, enable PIO in CODESYS

Library manager, CODESYS

• Standard 3.5.2.0 (System)

• IoStandard 3.5.3.0 (System)

• Time and Date 3.5.1.0

• Ethernet 3.4.2.0

• Modbus Master TCP 3.5.3.0 (IoDrvModbusTCP)

• Modbus Slave TCP 3.5.3.0 (IoDrvModbusTCPSlave)

Beijer Electronics Automation AB − a Beijer Electronics Group company

Head Office

Beijer Electronics Automation AB

P.O. Box 426, Stora Varvsgatan 13a

SE-201 24 Malmö, SWEDEN

Telephone +46 40 35 86 00

Fax +46 40 93 23 01

1 (35)

Subsidiaries

Norway, Drammen: Beijer Electronics AS,  +47 32 24 30 00

Finland, Vantaa : Beijer Electronics Oy,  +358 207 46 35 00

Denmark, Roskilde : Beijer Electronics A/S,  +45 75 76 66

Estonia, Tallinn : Beijer Electronics Eesti Oü,  +372 6 518140

Latvia, Riga : Beijer Electronics SIA,  +371 6 7842280

Lithuania, Kaunas : Beijer Electronics UAB,  +370 5 2323101

Reg no. 556701-3965  VAT no SE556701396501  www.beijer.se  [email protected]

Programmable I/O (PIO) NA-9379, Basic setting

KI00341

In this document we have used following hardware and software

• PIO (NA-9379), ST-3424, ST-4422, ST-1218, ST-2328, ST-3702

• CODESYS V3.5 SP3 Patch 1

• IO Guide Pro 1.1.0.8 #4

For further information we refer to

• CODESYS, Manuals and help in the software

• NA-9379 Manual www.beijer.se

NA-9379, User Manual

NA-9379, Specification Preliminary

NA-9379, Quick Guide

• Crevis Manual www.beijer.se

FnIO Configuration Parameter/Memory/Register

Crevis FnIO S-Series All manuals

• Start Up document “Programmable I/O (PIO) NA-9379, Communication”, KI00342

Start Up document “iX TxA/TxB - Programmable I/O (PIO) NA-9379”, KI00343

This document and other Start Up documents can be obtained from our homepage.

Please use the address [email protected] for feedback on our Start Up documents.

2014-10

3 First step!

For best understanding and easy working with Programmable I/ O and CODESYS we recommend:

- Basic knowledge of CODESYS. There is a quick start in CODESYS help file.

- Prepare the computer with the programming tools CODESYS and IOGuidePro.

- Download manuals

Note!

- Always use the correct version of the drivers and software!

In order to obtain the correct functionality of the Programmable IO, always start installing the required CODESYS V3.5 SP3 Patch 1.

This is done to get all libraries and driver versions required of the product.

- When using BootP in IOGuidePro: use Windows XP (windows 7, 64 bit are not supported). www.beijer.se

2 (35)

Programmable I/O (PIO) NA-9379, Basic setting

KI00341 2014-10

4 Table of Contents

1 Function and area of use .................................................................................................................................................. 1

2 About this Start Up document ......................................................................................................................................... 1

3 First step! ........................................................................................................................................................................... 2

4 Table of Contents .............................................................................................................................................................. 3

5 Specification ...................................................................................................................................................................... 4

5.1

Interface, PIO (NA-9379) ........................................................................................................................................ 4

5.2

LED Indicator .......................................................................................................................................................... 5

6 Setup IP address in PIO ................................................................................................................................................... 7

6.1

IP setting (default) ................................................................................................................................................... 7

6.2

Set the IP with BootP server .................................................................................................................................... 7

7 Configuration of CODESYS ............................................................................................................................................ 9

7.1

Add PIO (NA-9379) to CODESYS ........................................................................................................................... 9

8 Configuration of PIO in CODESYS .............................................................................................................................. 11

8.1

Programming and configuration ........................................................................................................................... 11

8.2

How to add a POU ................................................................................................................................................ 12

8.3

How to add a Task ................................................................................................................................................. 13

8.4

How to add a POU to a Task ................................................................................................................................. 13

8.5

PLC setting ............................................................................................................................................................ 14

8.6

Select I/O module ................................................................................................................................................... 15

8.7

Setting Device Parameter and I/O Mapping ......................................................................................................... 16

9 Program example ............................................................................................................................................................ 17

9.1

New project ............................................................................................................................................................ 17

9.2

Add Global Variable and Persistent Variables ..................................................................................................... 17

9.3

I/O Mapping .......................................................................................................................................................... 19

9.4

Write program in “PLC_PRG ............................................................................................................................... 20

9.5

Transfer CODESYS project to PIO ....................................................................................................................... 21

9.6

Monitor .................................................................................................................................................................. 23

10 Project backup ................................................................................................................................................................ 24

10.1

CODESYS, Create backup files ............................................................................................................................. 24

10.2

CODESYS, Project Archive ................................................................................................................................... 24

11 Persistent variables (32 kbyte) ....................................................................................................................................... 25

12 Appendix .......................................................................................................................................................................... 26

12.1

Environment specification ..................................................................................................................................... 26

12.2

Interface Specification ........................................................................................................................................... 27

12.3

Wiring diagram, PIO ............................................................................................................................................. 29

12.4

Dimension .............................................................................................................................................................. 31

12.5

Expansion .............................................................................................................................................................. 31

12.6

Inserting and Removing the Module ...................................................................................................................... 31

12.7

Removable Terminal Block (RTB) ......................................................................................................................... 32

12.8

Method of Wiring ................................................................................................................................................... 32

12.9

Program Memory .................................................................................................................................................. 32

12.10

Boot application .................................................................................................................................................... 32

12.11

Check Compiler, PIO and Library version ............................................................................................................ 33

12.12

Trouble Shooting ................................................................................................................................................... 34

www.beijer.se

3 (35)

Programmable I/O (PIO) NA-9379, Basic setting

KI00341 2014-10

5 Specification

5.1

Interface, PIO (NA-9379)

(1) 2 Ports RJ-45 for Ethernet

PIO has a built-in 10/100Mbps Ethernet Port and switch hub (internally).

Caution!

Do not use two ports connected to the same hub.

(2) RS232 or RS485

- F/W update or Repair.

- Modbus RTU Slave Protocol acts by each two independent ports.

(3) RUN/STOP Switch

RUN : PLC program is running. Monitoring the program and protocol in the CODESYS.

STOP : PLC program is stopped.

(4) Reset Switch

PLC program is initialized, its role is same as the “Reset Cold” in the CODESYS, but login and other communications should be reconnected.

Caution!

Do not turn on the power while pushing the reset switch. www.beijer.se

4 (35)

Programmable I/O (PIO) NA-9379, Basic setting

KI00341 2014-10

5.2

LED Indicator

LED Status when the module is operating normally

• Green ON : MOD, RUN, IO

• Yellow flashing and Green ON : LAN Port LED

LED No.

MOD

NET

RUN

I/O

Field Power

LED Function / Description LED Color

Module Status Green/Red

Not used

Error Status

Expansion Module Status

-

Green/Red

Green/Red

Field Power Enable Green

5.2.1

MOD (Module Status LED)

Status LED is To indicate

Not Powered OFF

Normal, Operational Green

Device in Standby Blinking Green

Not power is supplied to the unit.

The unit is operating in normal condition.

The EEPROM parameter is not initialized yet.

Serial Number is zero value (0x00000000)

IAP Mode

Minor Fault

Flashing Green IAP Mode : Available for firmware download using Firefox.

Blinking Red The unit has occurred recoverable fault in self-testing.

- EEPROM checksum fault.

Unrecoverable Fault Red The unit has occurred unrecoverable fault in self-testing.

- Firmware fault

5.2.2

NET (Network Status LED)

Status

Not Used

LED is

-

To indicate

-

5.2.3

RUN (PLC Run/Stop Status LED)

Status

Not programmed

Run

Stop

Error

LED is

OFF

To indicate

No power is supplied to the unit or Not programmed

ON PLC Run

Blinking Green PLC Stop

Blinking Red Failure of Module Configuration www.beijer.se

5 (35)

Programmable I/O (PIO) NA-9379, Basic setting

KI00341 2014-10

5.2.4

I/O LED (Extension Module Status LED)

Status

Not Powered

No Expansion Module

On-line,

Do not Exchanging I/O

Connection,

Run Exchanging I/O

Connection Fault during exchanging I/O

LED is

OFF

Flashing

Green

Green

Red

To indicate

Device has no expansion module or may not be powered

FnBus is normal but does not exchanging I/O data.

(Passed the expansion module configuration)

Exchanging I/O data

Expansion

Configuration Failed

Flashing

Red

One or more expansion module occurred in fault state.

• Changed expansion module configuration

• Expansions module failure

Failed to initialize expansion module

• Detect invalid expansion module ID

• Overflowed Input/Output size

• Too many expansion modules

• Initial protocol failure

• Mismatch vendor code between adapter and expansion module

5.2.5

Field Power LED (Field Power Status LED)

Status LED is

Not supplied field power OFF

To indicate

Not supplied 24Vdc field power, 5Vdc system power.

Supplied field power Green Supplied 24Vdc field power, 5Vdc system power.

5.2.6

Indicator states and flash rates

LED ON

LED OFF

LED flickering

Constantly ON

Constantly OFF

Equal ON and OFF times with a frequency of approximately 10 Hz:

ON for approximately 50ms and OFF for approximately 50ms.

LED blinking Equal ON and OFF times with a frequency of approximately 2,5Hz:

ON for approximately 200ms followed by OFF for approximately 200ms.

LED single flash One short flash (approximately 200ms) followed by a long OFF phase

(approximately 1000ms)

LED double flash A sequence of two short flashes (approximately 200ms), separated by an OFF phase

(approximately 200ms).

The sequence is finished by a long OFF phase (approximately 1000ms).

LED triple flash A sequence of three short flashes (approximately 200ms), separated by an OFF phase

(approximately 200ms).

The sequence is finished by a long OFF phase (approximately 1000ms). www.beijer.se

6 (35)

Programmable I/O (PIO) NA-9379, Basic setting

6 Setup IP address in PIO

The IP address can be set with Bootp or DHCP server.

Default value are BootP.

KI00341

6.1

IP setting (default)

Default IP

Subnet

Gateway

Update F/W

192.168.100.100

255.255.0.0

192.168.0.1

192.168.100.10

6.2

Set the IP with BootP server

• Install IOGuidePro (in Windows XP)

• Run IOGuidePro and start BootP server from meny “Tools”

• Click “Start Bootp” and Power ON to PIO and the MAC address is shown five times

2014-10 www.beijer.se

7 (35)

Programmable I/O (PIO) NA-9379, Basic setting

• The new IP-adress must be set within this time “one minute”

- Click on “Add New Device”

- Set IP address, Subnet Mask and gateway

- Restart the PIO

- When the MAC address is shown, click on ”OK”

Note!

If you “Add New Device” after “one minute” you have to power OFF/ON. Then the PIO take the new setting.

Note!

Changing the IP can be made in a different way, such as:

- Click on “Start BootP”, Power on the PIO and Double click at the MAC address.

- Write the new IP address and click on OK.

• Check IP address with the “Ping”

Note!

IP address can also be checked via the port for Modbus RTU / Slave.

- Use IOGuidePro and "Protocol Messenger / Modbus"

- Standard RS-232 (straight cable) can be used

Link to Adapter Address

KI00341 2014-10 www.beijer.se

8 (35)

Programmable I/O (PIO) NA-9379, Basic setting

7 Configuration of CODESYS

This installation has to be done once for every computer.

7.1

Add PIO (NA-9379) to CODESYS

• Change “Standard” to “Professional”

• Install PIO and I/O modules (device description file) to CODESYS

(Programmable IO_NA9379.devdesc.xml and ST-xxxx.devdesc.xml)

NOTE!

All “devdesc.xml” files can be installed at once if the file are in same library www.beijer.se

KI00341 2014-10

9 (35)

Programmable I/O (PIO) NA-9379, Basic setting

• The file is installed under “PLCs” and the I/O moduls under “Miscellaneous”

KI00341 2014-10 www.beijer.se

10 (35)

Programmable I/O (PIO) NA-9379, Basic setting

8 Configuration of PIO in CODESYS

8.1

Programming and configuration

• Start “CODESYS”

• Click “File” and Choose “New project”

• In “Templates”, mark “Standard project”

• In “Name”, write the name of the project

• In “Location” write the library to save the project in…

• Click “OK”

• Select Ladder Logic Diagram (LD) www.beijer.se

KI00341 2014-10

11 (35)

Programmable I/O (PIO) NA-9379, Basic setting

8.2

How to add a POU

• Highlight the “Application” option in the “Device” window and right click

• Select “Add Object” and choose “POU”.

Customize the POU according to desired characteristics.

KI00341 2014-10 www.beijer.se

12 (35)

Programmable I/O (PIO) NA-9379, Basic setting

8.3

How to add a Task

When a “Standard project” is selected, it automatically creates a "Main Task"

• Highlight the “Application” option (to make a “Task Configuration”) or highlight the “TaskConfiguration” (to make a “Task”)

• Select “Add Object” and choose “Task Configuration” or “Task”

• Click “Open”, a task named “Task” is automatically created

KI00341

8.4

How to add a POU to a Task

Connect the created POU to the task in order for the IEC code in the POU to get executed.

• Open the “MainTask”

• Under “POUs”, select “Add POU”

• In the “Items” window, under “Application”, highlight desired “POU” and click “OK”

2014-10 www.beijer.se

13 (35)

Programmable I/O (PIO) NA-9379, Basic setting

KI00341 2014-10

8.5

PLC setting

• Interval time for the application (default value 20 ms)

Update the I/O, set the Bus cycle task and Output handle at stop.

• Double click at “Device (NA9379)” and select “PLC setting” and set like picture.

Note!

When test of I/O (hardware wiring) with an empty program or the PIO in STOP, set like picture.

In STOP mode, the digital outputs go to OFF state, even if they are set to ON as default setting. www.beijer.se

14 (35)

Programmable I/O (PIO) NA-9379, Basic setting

KI00341 2014-10

8.6

Select I/O module

• Highlight the “Slot (Slot)” option in the “Device” window and right click at the module place

“Empty”

• Click at “Plug Device”, mark the module and “double click” at module or “Plug Device”

NOTE!

Select the module in order like the user configuration.

Auto scan are not supported. www.beijer.se

15 (35)

Programmable I/O (PIO) NA-9379, Basic setting

KI00341 2014-10

8.7

Setting Device Parameter and I/O Mapping

• Mark the module and “right click” and then “Edit Object” or “double click” at module

8.7.1

Parameter setting (I/O Module)

• Mark the module and “right click” and then “Edit Object” or “double click” at module

Setting value can be read in the manual “FnIO_Configuration_Parameter_Memory_Register”

8.7.2

I/O Mapping

Connect the I/O to a variable

• Click ”Analog or Digital IOs I/O Mapping”

• Dubbel Click in “Variable” and get the variable from “Global Variable list” www.beijer.se

16 (35)

Programmable I/O (PIO) NA-9379, Basic setting

KI00341 2014-10

9 Program example

The folder “ProgExample_PIO_Basic ” contains the program example from this StartUp document.

Can be downloaded from our homepage.

9.1

New project

• Configure the project like

9.2

Add Global Variable and Persistent Variables

The easiest way to edit the variables: use “textual” www.beijer.se

• Global Variables

17 (35)

Programmable I/O (PIO) NA-9379, Basic setting

• Persistent Variables

KI00341 2014-10 www.beijer.se

18 (35)

Programmable I/O (PIO) NA-9379, Basic setting

9.3

I/O Mapping

• Mapping the I/O

Result

• Do the same for all input, output (digital and analog) www.beijer.se

KI00341 2014-10

19 (35)

Programmable I/O (PIO) NA-9379, Basic setting

9.4

Write program in “PLC_PRG

KI00341 2014-10

• Rebuild the program

• If no Error, go to next step!

View error, warning and message with “View \ Messages”

NOTE!

When “Generate code” there can be warning(s). It´s only a warning. The project is working correct. www.beijer.se

20 (35)

Programmable I/O (PIO) NA-9379, Basic setting

KI00341 2014-10

9.5

Transfer CODESYS project to PIO

A gateway needs to be created in order to communicate between the PC and the PIO

• Double click the “Device(NA9379)” option under “Devices”

• Select the “Communication setting” options

• If no gateway present, create one by selecting “Add Gateway” (choose default value)

• Highlight the gateway

• Press “Scan network” and wait until scanning is done

• All CODESYS devices on the network will be listed below the gateway.

The last two numbers (02) in the “id” [0001.C002] are the last group in IP-address

NOTE!

If you don´t find your “CODESYS devices”, try to “Add Device” www.beijer.se

21 (35)

Programmable I/O (PIO) NA-9379, Basic setting

• Select the device that the project will be downloaded to and press “Set active path”.

This device will be highlighted by a bold font.

• Download the project to the device (TxB SoftControl) which was selected above menu “Online” select “Login”.

KI00341 2014-10

• The project will now be downloaded to the device (the RUN led are flickering)

• Set the PIO to RUN with the switch on front at PIO.

RUN/STOP of PIO can also bedone with “F5” or the symbol (if the switch are ON)

• When all are green (see picture), the PIO is running! www.beijer.se

22 (35)

Programmable I/O (PIO) NA-9379, Basic setting

9.6

Monitor

• I/O module

• Global variable

KI00341 2014-10 www.beijer.se

23 (35)

Programmable I/O (PIO) NA-9379, Basic setting

KI00341 2014-10

10 Project backup

10.1

CODESYS, Create backup files

If this option is activated, at each saving the project will not only be saved in <projectname>.project but also copied to a file <projectname>.backup.

If needed you can rename this backup-file and re-open in CODESYS.

Menu \Tools\Options

10.2

CODESYS, Project Archive

The best way to get all components from a CODESYS project is to make a ‘ Save/Send Archive ’.

That will save and pack all files referenced by and used within the currently opened project in to one archive file. The archive file can either be stored or sent as attachment of an email.

The archive file can easily be unpacked by use of ‘ Extract Archive ’

Note!

The archive function is not intended for restoring a project environment.

It is designed for an easy packing of all files belonging to a project! www.beijer.se

24 (35)

Programmable I/O (PIO) NA-9379, Basic setting

KI00341 2014-10

11 Persistent variables (32 kbyte)

Persistent variables (battery powered, 6 days) can ONLY be declared in a special global variables list of object type, which is assigned to an application.

There might be only ONE such list per application.

• Highlight the “Application” entry in “Devices”

• Right click and select “Add Object”

• Choose “Persistent Variables..”

• In next “Pop-up” write the Name “PersistentVars” and click “Open”

• Persistent variables, function.

Programmable I/O (PIO) supports “Persistent variables”. www.beijer.se

25 (35)

Programmable I/O (PIO) NA-9379, Basic setting

12 Appendix

12.1

Environment specification

Environmental specification

Operating Temperature

Storage Temperature

Relative Humidity

Mounting

General specification (TBD)

Shock Operating

Vibration/shock resistance

EMC resistance burst/ESD

Installation Pos. / Protect. Class

Product Certifications

-20 ~ +60 ° C

-40 ~ +85 ° C

5 ~ 90% non-condensing

DIN rail

IEC 60068-2-6

Based on IEC 60068-2-6

Sine Vibration

- 10 ~ 25 Hz : 0.5mm

- 50 ~ 150 Hz : 5g

- 150 ~ 1000 Hz : 2g

- Sweep Rate : 1 Oct/min, 50 cycles

Sine Vibration

- 10 ~ 25 Hz : 0.03 g²/Hz

- 25 ~ 50 Hz : 0.05 g²/Hz

- 50 ~ 150 Hz : 0.15 g²/Hz

- 150 ~ 1000 Hz : 0.01 g²/Hz

- Test time: 5hrs for each test

EN 61000-6-2 : 2005

EN 61000-6-4/ALL : 2011

Variable/IP20

TBD

KI00341 2014-10 www.beijer.se

26 (35)

Programmable I/O (PIO) NA-9379, Basic setting

12.2

Interface Specification

Items

Programmable Specification

Programming

Program Memory

Data Memory

Non-Volatile Memory

Run-Time System

Program Languages

RTC

Max. Task

Max. Cycle Task

Max. Status Task

Process Time

Interface Specification

Adapter Type

Max. Expantsion Module

Max. Input Size

Max. Output Size

Max. Nodes

Baud rate

Interface Connector

Protocol

Max. Socket

Other Serial Port

Serial Configuration (RS232/485)

Indicator

Specification

KI00341

CODESYS V3.5 SP3 Patch 1

512 KBytes

512 KBytes.

Retain Time : 6 days

%IW0~%IW639 (640 word Input and Internal memory)

%QW0~%QW639 (640 word Output and Internal memory)

%MW0~%MW639 (640 word Internal memory)

32 KBytes. Retain Time : 6 days

Register (16bit): 16 KBytes, Flag (1 bit): 16 KBytes

Multiple PLC Task

IEC 61131-3 (LD, IL, ST, FBD, SFC)

Retain Time : 6 days

Accuracy : < 2min/month

2

2

1

3 us (100 Instruction)

2014-10

Master & Slave Node (Modbus TCP)

32 Slots

126 Words (252 Byte)

126 Words (252 Byte)

Limited by Ethernet Specification

10/100Mbps, Auto-negotiation, Full Duplex

RJ-45 socket * 2pcs

Modbus TCP, DHCP, BOOTP, SNMP (ARP not supported)

Max 18 connection.

6 UDP: Is used by CODESYS, BootP, NA-9379 (Network

Variable), etc

12 TCP: Is used by Modbus TCP Master/Slave.

- Example NA-9189/NA-9289 (Modbus TCP Slave).

- Six of this connection are “TCP_LISTEN” used by HMI, etc

RS232/485 for Modbus RTU, Operator Panel or IOGuidePro

Node: 1 (default)

Baud Rate: 38400 (default)

Data bit: 8 (default)

Parity bit: No parity (default)

Stop bit: 1 (default)

RS232: max 10 m

RS485: max 1200 m

4 LEDs (NET LED is Not used)

1 Green/Red, Module Status (MOD)

1 Green/Red, Run Status (RUN)

1 Green/Red, Extension Module Status (I/O)

1 Green, Field Power Status www.beijer.se

27 (35)

Programmable I/O (PIO) NA-9379, Basic setting

General specification

System Power

Power Dissipation

Current for I/O Module

Isolation

Field Power

Max. Current Field Power Contact

Weight

Module Size

Environment Condition

KI00341

Supply voltage: 24Vdc nominal

Supply voltage range: 11 ~ 28.8 Vdc

Protection: Output current limit (Min. 1.5A)

Reverse polarity protection

110 mA typical @ 24Vdc

1.5A @ 5Vdc

System power to internal logic

System power I/O driver

RJ45

RS232/RS485

Non-isolation

Isolation

Isolated with transformator

Non-isolation

Supply voltage: 24Vdc nominal

Supply voltage range: 11~28.8V dc

DC 10A Max

< 165g (TBD)

54 x 99 x 70 mm

Refer to ‘Environment Specification’

2014-10 www.beijer.se

28 (35)

Programmable I/O (PIO) NA-9379, Basic setting

12.3

Wiring diagram, PIO

12.3.1

PIO NA-9379, RTB terminal block

KI00341 2014-10

Pin

0

2

4

Signal Description Signal Description

System Power 0V System Power 0V

F.G

Field Power 0V

FG (Frame Ground)

Field Power 0V

6 Field Power 24V Field Power 24V

• System Power: The power for starting up CPU

• Field Power: The power for input and output line

NOTE!

Do not use an incorrect voltage/frequency!

The use of an incorrect supply voltage or frequency can cause severe damage to the component.

Pin

1

3

5

7

12.3.2

PIO NA-9379, Pin description

Communication between the Network adapter and the expansion module as well as system / field power supply of the bus modules is carried out via the internal bus. It is comprised of 6 data pin and

2 field power pin.

No. Name Description

1 System Vcc System supply voltage (5V dc)

2 System GND System Ground

3 Token Output Token output port of Processor module

4 Serial Output Transmitter output port of Processor module

5 Serial Input

6 Reserved

7 Field GND

8 Field Vcc

Receiver input port of Processor module

Reserved for bypass Token

Field Ground

Field supply voltage (24Vdc)

NOTE!

Do not touch data and field power pins in order to avoid soiling and damage by ESD noise. www.beijer.se

29 (35)

Programmable I/O (PIO) NA-9379, Basic setting

12.3.3

RJ-45 Socket

RJ-45 Signal Name

1

4

5

2

3

6

7

TD +

TD -

RD +

-

-

RD -

-

8

Case

-

Shield

Description

Transmit +

Transmit -

Receive +

Receive -

KI00341

12.3.4

RS232/485 Port for MODBUS/RTU Slave, Operator Panel or IOGuidePro

Pin

1

2

3

4

7

8

5

6

9

Signal Name

-

TXD =>

RXD <=

-

GND

D +

-

D -

-

Description

RS232 TXD =>

RS232 RXD <=

RS232 GND

RS485 D +

RS485 D -

2014-10

12.3.5

Toggle Switch and Push Botton

Toggle Switch

Status

UP

DOWN

Module is Description

RUN

STOP

PLC Run

PLC Stop (Fault Action is performed)

Push Botton Module is Description

Press and release Reset Reset the PLC and then stop

Hold down and reset the power

IAP mode Available for firmware download using

FireFox www.beijer.se

30 (35)

Programmable I/O (PIO) NA-9379, Basic setting

12.4

Dimension

KI00341 2014-10

Unit: mm

12.5

Expansion

The number of module that can be connected is 32. So the maximum length is 426 mm.

Exception, ST-2748 is excepted to calculate maximum length because that is double width module.

12.6

Inserting and Removing the Module

As above figure in order to safeguard the FnIO module from jamming, it should be fixed onto the

DIN rail with locking level. To do so, fold on the upper of the locking lever.

To pull out the FnIO module, unfold the locking lever as below figure.

NOTE!

Before work is done on the components, the voltage supply must be turned off. www.beijer.se

31 (35)

Programmable I/O (PIO) NA-9379, Basic setting

KI00341 2014-10

12.7

Removable Terminal Block (RTB)

12.8

Method of Wiring

Connecting or removing the cable by pushing the terminal button for the relevant points.

NOTE!

The use of an incorrect supply voltage or frequency can cause severe damage to the component.

12.9

Program Memory

Memory Size Function

Program Memory

Data Memory

512 KBytes PLC program (CODESYS)

Data register, Counter, Timer, Auxiliary Relay (memory cell)

512 KBytes Retain Time : 6 days

%IW0~%IW639 (640 word Input and Internal memory)

%QW0~%QW639 (640 word Output and Internal memory)

%MW0~%MW639 (640 word Internal memory)

Non-Volatile Memory 32 KBytes Retain Time : 6 days

Register (16bit): 16 KBytes, Flag (1 bit): 16 KBytes

Battery backup / persistent variables

- 8000 points: Data register/Counter/Timer (16 bit)

- 128 000* points: Auxiliary Relay (memory cell) (1 bit)

*)16k bytes => 16*8bit =128 000

12.10

Boot application

PIO do not use “Boot Application” file to restore the application after a power off/on. www.beijer.se

32 (35)

Programmable I/O (PIO) NA-9379, Basic setting

12.11

Check Compiler, PIO and Library version

• Check ”Compiler” Version

• Check ”NA9379” (PIO) version

• Check ”Library” version www.beijer.se

KI00341 2014-10

33 (35)

Programmable I/O (PIO) NA-9379, Basic setting

12.12

Trouble Shooting

KI00341 2014-10

12.12.1

How to diagnose by LED indicator

LED Status

All LED turns off

Cause

No power

System power is not supplied

MOD LED flashes green Failure of initialization EEPROM parameter

MOD LED flashes red Excess of expansion slot

Excess of IO size

Wrong IO composition

Occurrence of EEPROM check-sum

MOD LED is red error

Wrong address ID

Occurrence critical error in firmware

I/O LED turns off Failure of realization expansion

Module

None expansion Module

I/O LED flashes red

I/O LED is red

Action

Check main power Cable

Contact Sales team and send module for repair

Contact Sales team and send module for repair

Use expansion slot up to 32.

Compose that IO total size is not excess.

Check composition I/O Module

Contact Sales team and send module for repair

Check connector status both NA series and expansion module

Failure of configuration baud rate Check communication cable with Master

Check power for master

Failure of initialization I/O Use expansion slot up to 32

Compose that IO total size is not excess

Failure of exchanging I/O data

NA series notice unidentified expansion module ID.

Check status of expansion module.

Check status of expansion IO connection.

RUN LED flashed red Failure of Module Configuration Check the module hardware and are the same. www.beijer.se

34 (35)

Programmable I/O (PIO) NA-9379, Basic setting

12.12.2

How to diagnose when device couldn’t communicate network

Inspection of wrong or omission cable connection

- Check status of cable connection for each node

- Check that all color matches between connector and cable

- Check wire omission

Terminator resistor

- If terminator resistor is not installed, install terminator resistor

- Check location of terminator resistor

Configuration of Node address

- Check duplication node address

Configuration of Master

- Check configuration of master

- Check whether to do download or don’t

- Check composition is right

Configuration of communication baudrate

I/O size

Configuration of each node

Ground and environment

- Check ground is contacted

- Check environment factor (temperature, humidity, etc.) is in less than regular limit

KI00341 2014-10 www.beijer.se

35 (35)