Programmable I/O (PIO) NA-9379, Basic setting

KI00341 2014-10

5.2

LED Indicator

LED Status when the module is operating normally

• Green ON : MOD, RUN, IO

• Yellow flashing and Green ON : LAN Port LED

LED No.

MOD

NET

RUN

I/O

Field Power

LED Function / Description LED Color

Module Status Green/Red

Not used

Error Status

Expansion Module Status

-

Green/Red

Green/Red

Field Power Enable Green

5.2.1

MOD (Module Status LED)

Status LED is To indicate

Not Powered OFF

Normal, Operational Green

Device in Standby Blinking Green

Not power is supplied to the unit.

The unit is operating in normal condition.

The EEPROM parameter is not initialized yet.

Serial Number is zero value (0x00000000)

IAP Mode

Minor Fault

Flashing Green IAP Mode : Available for firmware download using Firefox.

Blinking Red The unit has occurred recoverable fault in self-testing.

- EEPROM checksum fault.

Unrecoverable Fault Red The unit has occurred unrecoverable fault in self-testing.

- Firmware fault

5.2.2

NET (Network Status LED)

Status

Not Used

LED is

-

To indicate

-

5.2.3

RUN (PLC Run/Stop Status LED)

Status

Not programmed

Run

Stop

Error

LED is

OFF

To indicate

No power is supplied to the unit or Not programmed

ON PLC Run

Blinking Green PLC Stop

Blinking Red Failure of Module Configuration www.beijer.se

5 (35)

Programmable I/O (PIO) NA-9379, Basic setting

KI00341 2014-10

5.2.4

I/O LED (Extension Module Status LED)

Status

Not Powered

No Expansion Module

On-line,

Do not Exchanging I/O

Connection,

Run Exchanging I/O

Connection Fault during exchanging I/O

LED is

OFF

Flashing

Green

Green

Red

To indicate

Device has no expansion module or may not be powered

FnBus is normal but does not exchanging I/O data.

(Passed the expansion module configuration)

Exchanging I/O data

Expansion

Configuration Failed

Flashing

Red

One or more expansion module occurred in fault state.

• Changed expansion module configuration

• Expansions module failure

Failed to initialize expansion module

• Detect invalid expansion module ID

• Overflowed Input/Output size

• Too many expansion modules

• Initial protocol failure

• Mismatch vendor code between adapter and expansion module

5.2.5

Field Power LED (Field Power Status LED)

Status LED is

Not supplied field power OFF

To indicate

Not supplied 24Vdc field power, 5Vdc system power.

Supplied field power Green Supplied 24Vdc field power, 5Vdc system power.

5.2.6

Indicator states and flash rates

LED ON

LED OFF

LED flickering

Constantly ON

Constantly OFF

Equal ON and OFF times with a frequency of approximately 10 Hz:

ON for approximately 50ms and OFF for approximately 50ms.

LED blinking Equal ON and OFF times with a frequency of approximately 2,5Hz:

ON for approximately 200ms followed by OFF for approximately 200ms.

LED single flash One short flash (approximately 200ms) followed by a long OFF phase

(approximately 1000ms)

LED double flash A sequence of two short flashes (approximately 200ms), separated by an OFF phase

(approximately 200ms).

The sequence is finished by a long OFF phase (approximately 1000ms).

LED triple flash A sequence of three short flashes (approximately 200ms), separated by an OFF phase

(approximately 200ms).

The sequence is finished by a long OFF phase (approximately 1000ms). www.beijer.se