Installation
10
At a Glance
Subject of this chapter
What's in this
Chapter?
This Chapter deals with the installation of step-by-step axis command modules.
This chapter contains the following sections:
Section
10.1
10.2
10.3
10.4
Topic
General
Connection of translator signals
Connecting sensors/pre-actuators and supply modules
Electrical characteristics of modules
Page
231
Installation
232
Installation
10.1
General
At a Glance
Subject of this section
What's in this
Section?
This Section introduces general points for installing TSX CFY modules.
This section contains the following topics:
Topic
Necessary basic configuration
Installation procedure
General precautions for wiring
Page
233
Installation
Necessary basic configuration
Introduction
Maximum number of
TSX CFY • 1 modules per station
Step-by-step axis command modules can be installed in any slot of a TSX RKY•• rack. The rack power supply must be chosen according to the number of modules installed.
l l
Each step-by-step command module supports:
1 application-specific channel for TSX CFY 11 module,
2 application-specific channels for TSX CFY 21 module.
Since the maximum number of application-specific channels managed by a PLC station depends of the type of processor installed, the maximum number of l l
TSX CFY •1 modules in a PLC station will therefore depend on: the type of processor installed, the number of application-specific channels already used other than step-by-step command application-specific channels.
You should therefore make a global report at PLC station level to find out the number of application-specific channels already in use and thus define the number of
TSX CFY •1 modules which can be used.
Reminder of number of application-specific channels managed by each type of processor:
Processors
TSX P57 103
TSX P57 153
TSX P57 203 / PCX 57 203 / TSX P57 2•23
TSX P 57 253
TSX P 57 2623 / TSX P 57 2823
TSX P 57 303
TSX P57 353 / PCX 57 353 / TSX P57 3623
TSX P57 453 / TSX P57 4823
24
24
24
32
8
8
Number of "application-specific" channels managed
32
48
234
Installation
Installation procedure
General The module can be installed or removed without cutting the rack power supply, to ensure that a device is available.
CAUTION
Connection and disconnection of connectors
It is not recommended that you connect or disconnect the connectors with the translator power supplies, as some translators cannot cope with this action. The auxiliary input/output connector can be disconnected while switched on without damaging the module.
However, for safety reasons it is recommended that you turn off the auxiliary power supply before any type of disconnection.
Failure to follow this precaution can result in injury or equipment damage.
The module fixing screws and connectors must be correctly screwed in place in order to guarantee effective resistance to electrostatic and electromagnetic interference.
235
Installation
General precautions for wiring
General The power supply to sensors and actuators must be protected against overload or overvoltage by fast-blow fuses.
l l l when wiring use wires of sufficient size to avoid on-line voltage falls and overheating, keep sensor and actuator cables away from any source of radiation resulting from high-power electric circuit switching, all cables connecting the translators must be shielded, the shielding must be good quality and connected to the protective ground both for the module and the translator. Continuity must be ensured throughout connections. Do not transmit any other signals in the cable than those for the translators.
For reasons of performance the auxiliary inputs of the module have a short response time. You must therefore make sure that there is enough self-sufficient supply to these inputs to ensure the module continues to operate correctly in the event of a short power break. It is recommended that you use a regulated supply to ensure more reliable response times from the actuators and sensors. The 0 V supply must be connected to the protective ground nearest to the supply module output.
236
Installation
10.2
Connection of translator signals
At a Glance
Subject of this section
What's in this
Section?
This Section deals with the connection of translator signals.
This section contains the following topics:
Topic
Signal labeling
Connection to a translator with RS 422/485 interface
Connecting to a translator with NPN open collector interface
Page
237
Installation
Signal labeling
Diagram of the principle
This diagram illustrates the principles for labeling:
+ pulses output
- pulses output
(or direction)
Boost output
Enable output translator
Loss of step check
reactivation output
Translator check input
Loss of step check input insulated 0 V insulated 5 V nc: not connected
238
Description
Installation
Each module output signal is RS 485, for each output there is therefore a direct signal (+) and its complement (-). The outputs are TTL type current extraction compatible. The 5 V insulated voltage is only available, if necessary, to supply translator input and output. The 0 V is common to inputs and outputs. 5 V must only be used with translators with open collector outputs and TTL type inputs
(5 V insulated not provided by the translator).
Illustration:
+ output driver
RS 485
- output input
The proposed type of connection is direct wiring by soldering onto the connector: the
TSX CAP S15 (See
Overview of the TSX TAP S15•• wiring accessories, p. 134) kit
comprising a SUB-D connector and its protective cover.
239
Installation
Connection to a translator with RS 422/485 interface
Diagram of the principle
It is recommended that you use a shielded cable containing 7 twisted pairs.
The + and – wires of each module output signal must be connected in the same pair.
This diagram illustrates the principle of connection:
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
12
13
14
5
6
7 NC
0V 8
5V 15 NC
3
4
9
1
2
10
11
+
-
+
-
+
-
+
-
+
-
-
-
-
NC
NC
NC
+ pulses
- pulses (or direction)
Boost,
Translator enable
Reactivation of loss of step check
Translator check
Loss of step check
TRANSLATOR
RS 422/485 input compatible
RS 422/485 outputs
240
Installation
Connecting to a translator with NPN open collector interface
Diagram of the principle
Only one wire is used per input/output signal. If the translator does not provide 5 V insulated voltage do not forget to supply the interface from the insulated 5 V provided by the module.
This diagram illustrates the principle of connection:
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
1
2
9
10
3
4
-
-
-
14
5
6
11
12
13
-
-
7
0V 8
5V 15
NC
0V
+ pulses
- pulses (or direction)
Boost,
Translator enable
Reactivation of loss of step check
Translator check
Loss of step check
TRANSLATOR
TTL/5 V “source” compatible inputs
NPN open collector outputs
241
Installation
10.3
Connecting sensors/pre-actuators and supply modules
At a Glance
Subject of this section
What's in this
Section?
This Section deals with the connection of sensors/pre-actuators and supply modules.
This section contains the following topics:
Topic
Signal labeling
Connections
Connecting auxiliary inputs and outputs to processor.
Principle of connecting I/O channel 0
Connection using a TSX CDP 301/501 pre-wired strand
Connection with TELEFAST pre-wiring system
Availability of signals on TELEFAST
Correspondence between TELEFAST terminals and HE10 connector
Wiring precautions
Page
242
Installation
Signal labeling
Diagram of the principle
This diagram illustrates the principles for labeling signals:
I0 reference point cam
1 2 emergency stop 11
3
5
4
6
I3 event
I4 external stop channel 0 input
I5 limit-
+I2 end limit
I0 reference point cam emergency stop 11
+I2 end limit
7
9
11
8
10
12
I3 event
I4 external stop channel 1 input
I5 limit-
Q0 brake
Q0 brake
13
15
14
16 channel output 0 channel output 1
24V supply sensors/pre-actuators
17 18
19 20
0 V supply sensors/pre-actuators
The 0 V of sensors/pre-actuators is connected in the module to the protective ground by an R/C network with the value: R = 100M
Ω
/ C = 4.7 nF.
243
Installation
Connections
General There are several possible options for connecting the sensors/pre-actuators of the
TSX CFY 11 / 21 module. They can be connected directly by the TSX
CDP 301 / 501 (See
Connection using TSX CDP 301 or 501 strips, p. 199) strip or
via the Discrete TELEFAST pre-wiring system.
244
Installation
Connecting auxiliary inputs and outputs to processor.
General To ensure optimum operation, the event and reference point inputs have a weak immunity. It is recommended that you use contacts without bounce (proximity sensor for example).
245
Installation
Principle of connecting I/O channel 0
Diagram of the principle
This diagram illustrates the principles for connecting I/I channel 0:
TSX CFY 21 event reference point cam external stop emergency stop limitlimit+ idem channel 0 electro brake channel 0
Supply for sensors and pre-actuators
246
Description
Installation
The emergency stop or end limit switch contacts are open.
End limit switch contacts are not contacts which have to be wired in series with the emergency input. End limit switch contacts are used to command movement stop with deceleration. The end limit switch (ELS+) stops movement in the +direction, the end limit switch (ELS-) stops movement in the- direction. It is therefore important to positions them at the correct end of the axis (see diagram below).
Illustration: on-limit on-limit emergency stop
ELRP moving
EVT EL+
247
Installation
Connection using a TSX CDP 301/501 pre-wired strand
General Connection using a pre-wired strand enables direct contact to the actuators, preactuators or any terminal system. This strand comprises 20 gage 22 wires
(0.34 mm
2
) with a connector at one end and free wires at the other end, labeled using a color code.
248
Illustration This diagram shows the color code:
TSX CFY 21 cable: length:
TSX CDP 301 (3 m)
TSX CDP 501 (5 m)
Installation white brown green yellow gray pink blue red black violet gray-pink red-blue white-green brown-green white-yellow yellow-brown white-gray gray-brown white-pink pink-brown reference point cam event emergency stop external stop limit+ limitreference point cam event emergency stop external stop limit+ limitbrake Q0 channel 0 nc brake Q0 channel 1 nc
24 V
0 V
24 V
0 V channel 0 channel 1
249
Installation
Connection with TELEFAST pre-wiring system
Diagram of the principle
This connection is made using a TELEFAST 2 base: ABE-7H16R20.
TSX CDP 053 / 503
24 VDC sensors/pre-actuators supply
+ + - -
+ + - -
ABE-7H16R20
Example of wiring:
IO I1 I2 I3 I4 I5 Q0 IO I1 I2 I3 I4 I5 Q0
200
+
100
202
+
102
204
+
104
201
+
101
203
+
103
205
+
105 112
RI
312
-
206
+
106
208
+
108
210
+
110
207
+
107
209
+
109
211
+
111 114
314
RI
-
200
+
100
202
102
204
+ +
104
201
101
+
203
+
103
205
+
105 112
312
RI
-
206
+
106
208
+
108
210
+
110
207
+
107
209
+
109
211
+
111 114
314
RI
-
NO NC NC NO NO NC NO NC NC NO NO NC
200
+
100
202
102
204
+ +
104
201
+
101
203
+
103
205
+
105 112
312
RI
-
206
+
106
208
+
108
210
+
110
207
107
+
209
+
109
211
+
111 114
RI
314
-
NO NC NC NO NO NC NO NC NC NO NO NC
NO: normally open,
NC: normally conductor.
250
Availability of signals on TELEFAST
Illustration This diagram shows the availability of signals on TELEFAST:
Installation
(1) At the ABE-7H16R20 base, the position of the jumper wire determines the polarity of all terminals from 200 to 215: l l jumper wire in position 1 or 2: terminals 200 to 215 have + polarity, jumper wire in position 3 or 4: terminals 200 to 215 have - polarity,
(2) At the ABE-7H16R20 base, it is possible to add an optional ABE-7BV20 strip to create a second shared sensor (+ or - according to user’s choice).
251
Installation
Correspondence between TELEFAST terminals and HE10 connector
General This table shows the correspondence between TELEFAST terminals and the module’s HE10 connector:
Nature of signal
112
113
114
115
+ 24 VDC
- 0 VDC
+ 24 VDC
- 0 VDC
3
4
1
2
200...215
104
105
106
107
108
109
110
111
TELEFAST screw terminal block
(Terminal No.)
100
101
102
103
300...315
17
18
19
20
13
14
15
16
9
10
11
12
7
8
5
6
3
4
1
2
HE10 20-pin connector
(Pin No.)
I0 cam reference point channel 0
I3 event
I1 emergency stop
I4 external stop
I2 limit
I5 limit
I0 cam reference point channel 1
I3 event
I1 emergency stop
I4 external stop
I2 limit+
I5 limit-
Q0 brake output nc
Q0 brake output nc (1) channel 0 channel 1
Auxiliary input sensor supply
Terminals 200 to 215 at +24 VDC
Terminals 200 to 215 at –0 VDC
Connecting shared sensors to: l l
+24 VDC if terminals 1 and 2 are connected,
- 0 VDC if terminals 3 and 4 are connected
On the optional ABE-7BV20 bar, the terminals that can be used as a shared sensor must be connected by a wire to the shared voltage.
(1) nc = not connected
For a TSX CFY 11 module, the signals corresponding to the channel are not connected.
252
Installation
Wiring precautions
General To ensure the best performance, inputs I0 to I5 are rapid inputs. If the actuator is a dry contact, the inputs must be connected by a twisted pair, or by a shielded cable if the sensor is a two or three-wire proximity detector.
The module includes as standard basic protection against short circuits or voltage inversions. However, the module cannot remain operational for long with an error.
You must therefore ensure that the fuses in series with the supply carry out their protective function. These are 1A maximum fast-blow fuses, the supply energy must be sufficient to ensure their fusion.
Important note: wiring of Q0 static outputs
The actuator connected to the Q0 brake output has its shared pin connected to supply 0 V. If for any reason there is a 0 V outage of the output amplifier supply
(e.g. poor contact or accidental unplugging), when the 0 V of the actuators remains connected to the 0 V supply, there may be enough mA output current from the amplifier to keep low-power actuators triggered.
Illustration:
+ + - -
+ + - -
IO I1 I2 Q0 IO I1 I2 Q0
204
+
104
205
+
105
206
+
106 112
312
208
+
108
209
+
109
210
+
110 114
314
RI RI
253
Installation
Connection via
TELEFAST
This kind of connection is the most guaranteed, on the condition that the shared actuators are connected to the 200 to 215 shared points strip (jumper wire in position
1-2). In this case there can be no outage of the shared module without an outage of the shared actuators.
254
Installation
Connection using a TSX
CDP 301 / 501 pre-wired strand
This kind of connection must be carried out with the greatest care and attention. It is recommended that you take special care in wiring this cable, for example using the cable ferules on screw terminals. It may be necessary to double the connections in order to ensure permanent contacts. When the actuator supply is a long distance away from the modules and close to the shared actuators, there may be an accidental break of the link between the latter and the 0 V terminal of the module(s).
Illustration:
TSX CFY 11/21
Supplying actuators
Critical wire
If there is a break of the supply section between A and B, there is a risk that the RL actuators may not remain operational. You must, if possible, double connections of
0 V supply to the modules.
Connection using a TSX CDP 301 / 501 pre-wired strand:
TSX CFY 11/21
HE10
17 white-pink white-gray
19 white-green
13
15 white-yellow
RL
24 V
0 V
RL
0VDC
18
20 gray-brown pink-brown
0VDC user connection terminal block
255
Installation
10.4
Electrical characteristics of modules
At a Glance
Subject of this section
What's in this
Section?
This Section introduces the different electrical characteristics of TSX CFY modules.
This section contains the following topics:
Topic
General characteristics
Characteristics of translator inputs (SUB-D connector)
Characteristics of translator outputs (SUB-D connector)
Characteristics of auxiliary inputs (HE10 connector)
Characteristics of Q0 brake output
Page
256
General characteristics
Table of characteristics
This table introduces the general characteristics of TSX CFY modules:
Maximum frequency of pulses
Current consumed on internal 5 V
Current consumed by the module on sensor/pre-actuator 24V with no sensor/ pre-actuator current
Power dissipated in the module
Module
TSX CFY 11
TSX CFY 21
TSX CFY 11
TSX CFY 21
187.316 KHz
Value
510 mA
650 mA
50 mA
100 mA
Insulation resistance
Dielectric rigidity between I/O "translator" and protective ground or PLC logic
Operating temperature
Storage temperature
Hygrometry (without condensation)
Operating altitude
TSX CFY 11
TSX CFY 21
3.8 W
5.6 W
> 10 M
Ω
under 500 VDC
1000 Veff 50 / 60 Hz for 1 mn
0 to 60 °C
-25 °C to 70 °C
5% to 95%
< 2000 m
Installation
257
Installation
Characteristics of translator inputs (SUB-D connector)
Diagram These inputs have positive logic current extraction:
Characteristics The following table shows the characteristics of translator inputs:
Characteristics
Nominal current
(Ue = 0 V)
Voltage for ON state
Voltage for OFF state
Immunity of loss of step input
Immunity of translator error input
Symbol
Ie
Uon
Uoff
Value
4,5
2
3,6
15 to 30
3 to 10
Unit mA
V
V
µ s ms
258
Installation
Characteristics of translator outputs (SUB-D connector)
Table of characteristics
These outputs are insulated RS 422/485. There are two complemented outputs per signal.
Characteristics
Differential voltage output on R load
≤
100
Ω
Short-circuit current
Permitted shared mode voltage
Permitted differential voltage
Values
+/- 2
< 150
≤
7
≤
12
Units
V mA
V
V
259
Installation
Characteristics of auxiliary inputs (HE10 connector)
Illustration Diagram:
260
Installation
Characteristics Table of characteristics for auxiliary inputs:
Electrical characteristics
Nominal voltage
Nominal voltage limits
(ripple included)
Nominal current
Input impedance (at Unom)
Voltage for "On" state
Current at Uon (11 V)
Voltage for "Off" state
Current at "Off" state
Input immunity:
Cam reference point input and event
Other inputs
IEC 1131 compatibility with sensors
Compatibility with 2 and 3-wire sensors
Type of input
Logic type
Pre-actuator voltage check
Time of supply detection
Symbol
Un
U1
Utime (1)
In
Re
Uon
Ion
Uoff
Ioff
3,4
≥
11
>6
<5
<2
Value
24
19 to 30
34
7
Unit
V
V mA k
Ω
V mA
V mA supply threshold OK supply threshold error supply OK supply error ton/toff (2) ton/toff
< 250
3 to 10
µ s ms type 2 all proximity sensors supplied at 24 VDC current ducts
Positive (sink)
> 18
< 14
< 30
> 1
V
V ms
ms
(1) Utime: maximum permitted voltage for 1 hour in every 24 hours.
(2) Inputs: reference point cam and events are fast inputs (response time < 250 µ s) compliant with maximum frequency of 187.316 KHz of translator command outputs.
261
Installation
Characteristics of Q0 brake output
Illustration Brake output:
Supply check sensors / pre-actuators
Fault monitoring short-circuit command
+
-
24V
Q0
262
Characteristics
Installation
Table of characteristics:
Electrical characteristics
Nominal voltage
Voltage limits
Temporary voltage
Nominal current
Max voltage fall "On"
Leakage current at "OFF" state
Load impedance
Max current to 30 V and to 34 V
Communication time
Electro unload time
Max switching frequency
(on inductive load)
Compatibility with inductive inputs
Value
24
19 to 30
34 (1)
500
< 1 mA
V
< 0,3 mA
80<Zon<1500
Ω
625
< 250 mA
µ s
< L/R s
F<0.6 / (LI
2
)
Hz
V
V
Unit
V
IEC 1131 compatibility
Protection from overloads and short-circuits
Monitoring short-circuits of each channel
Reset l l via application program automatic
Protection against channel overvoltage
Any input whose Re is less than 15 k
Ω
and has positive logic
Yes by current limiter and circuit breaker thermal, signaling: 1 bit per channel
One bit per module
Protection against polarity inversions
Power of a filament lamp
Pre-actuator voltage check
Reaction time of voltage check
Zener (55 V) between outputs and
+24 V
Using a reverse diode on the supply
8 W
OK if supply >
18 (ascending) not OK if supply
< 14
(decreasing)
V
V
NOK --> OK<30
OK --> NOK>1 ms ms
(1) maximum permitted voltage for 1 hour in every 24 hours of operation.
263
Installation
264