Wiring accessories. Schneider Electric TSX57/PCX57, Hardware PLC Implementation, Counting, Axis Command, Cam, Sercos
Reklama
Reklama
Implementing
7.4
Wiring accessories
At a Glance
Subject of this section
What's in this
Section?
This Section introduces the wiring accessories for the TSX CAY modules.
This section contains the following topics:
Topic
Encoder connection accessories
Information on FRB type 12 pin connectors
TSX TAP S15 05 mounting and dimensions
Connecting absolute encoder // via a TELEFAST with ABE-7CPA11 adaptation
Connecting to a NUM MDLA variable speed controller
Page
182
Implementing
Encoder connection accessories
General A number of accessories are available to facilitate implementation and installation.
These accessories are used to pre-wire the installation. A direct link with the installation can be established using cover kits containing the 15 pin SUB-D connector, TSX CAP S15. To facilitate installation, the TSX TAP S15 05 is used as an interface between the SUB-D and 12 pin DIN connector. Using a fixing hook, this accessory can be mounted on a DIN rail or on a cabinet lead-in with a gasket and adjusting nut. Connection to the module is via a 2.5m long TSX CCP S15 cable.
183
Implementing
Examples Illustration:
Incremental encoder or absolute encoder
Incremental encoder or absolute encoder
Incremental encoder 5 V
RS 422
Incremental encoder 5 V
RS 422
Note: Good signal and shielding continuity can be ensured in difficult conditions thanks to these accessories. Encoder connection cables can generally be obtained from encoder suppliers.
184
Implementing
Information on FRB type 12 pin connectors
General Number labeling of pins in these connectors is performed in two different ways.
Most encoders have a built-in 12 pin base and are labeled anti-clockwise. The
TSX TAP S15 has a 12 pin female base labeled anti-clockwise. All user cables must be equipped with connecting plugs labeled clockwise, so that the pin numbers correspond to one another when wired.
Illustration: coupling connectors
Encoder with connector anti-clockwise
TSX TAP S15 05 user cable base base
M
2
3
1 9
10
11
12
4 5
8
6
7
F
8 9
7
6
12
11
10
4 5
1
3
2 clockwise anti-clockwise
M
7
6
8 9
12
11
10
4 5
1
3
2
F
2
3
1 9
10
11
12
4 5
8
6
7
185
Implementing
Labeling of the
DIN and 15 pin
SUB-D connector of the
TSX TAP S15 05
Table of numbers:
7
8
9
10
11
12
5
6
3
4
1
2
DIN
Pin
Signal nc
0 V nc
5 V
B-
Supp return
Z+
Z-
A+
A- nc
B+
1
2
4
5
SUB_D
Pin
11
13
10
8
15
Shielding should be continuous along the connections which should be linked to the mechanical ground connection on both sides.
186
Implementing
TSX TAP S15 05 mounting and dimensions
Mounting onto a
Telequick board
The TSX TAP S15 05 can be attached to an AM1-PA••• type perforated board or any other support using the bracket supplied.
Mounting through a cabinet
The TSX TAP S15 05 can be mounted through a cabinet as it has a fixing nut. Its joint creates an impervious seal between the interior and exterior. max width=5mm gasket hole = 37 mm in diameter
187
Implementing
Dimensions Illustration:
70,4
Ø5,5
27,4 43
188
Implementing
Connecting absolute encoder // via a TELEFAST with ABE-7CPA11 adaptation
General
Illustration l l l l l l l l the multiplexing function must not be used: each channel uses a base, to which only one absolute encoder with parallel outputs is connected, the encoder frame should be configured as follows: code: binary or Gray (according to the encoder type), header bits: 0, data bits: 24 (irrespective of the number of encoder data bits), status bits: 3, rank of the error bit: 1 (optional), parity: even.
This diagram shows the connection between a TSX CAY and a TELEFAST
ABE-7CPA11:
TSX CAY
TELEFAST
ABE-7CPA11
ON
OFF
Absolute encoder with parallel output inhibiting the outputs of the encoder encoder configuration using base type of encoder connected
189
Implementing
Connecting to a NUM MDLA variable speed controller
General
Illustration
The NUM 400 V controller contains all the elements necessary to functioning.
It offers an output whose signals simulate the functioning of an incremental encoder as a position report. Direct connection is possible using the 2.5 cm or 6m long
TSX CXP 233 / 633 cable accessory.
Connection to a variable speed controller:
J2 signal encoder
0 V
Cable length:
Cable
TSX CXP 213
TSX CXP 633
Length
2.5 cm
6 m
Note: Here, it is not necessary to have an encoder supply.
190
Stiahnuť
Reklama