5.1. Communication Port. Entec ETMFC610


Add to my manuals
372 Pages

advertisement

5.1. Communication Port. Entec ETMFC610 | Manualzz

Multi-Function Control ETMFC610

5.1. Communication Port

http://www.entecene.co.kr

1) RS232 PORT

RS232 has D-SUB 9pin as Male type and all pins are connected except pin number 9, RI(Ring

Indicator).

Table 5-2. RS232-1/RS2332-2 Pin Description

6

7

4

5

8

Pin

1

2

3

Signal

DCD

RXD

TXD

DTR

GND

DSR

RTS

CTS

Description

Data Carrier Detect

Receive Data(IN)

Transmit Data(OUT)

Data Terminal Ready(OUT)

Ground

Data Set Ready(IN)

Request To Send(OUT)

Clear To Send(IN)

Figure 5-2. RS232

9 N/C No Connection

2) RS485 PORT

RS485 has 3pins as in ‘Table 5-3. RS485 Pin Description’ .

Table 5-3.RS485 Pin Description

Pin Description

3 2 1

1

2

3

RS485+

RS485-

SG (Cable Shield)

FG N P

Figure 5-3.RS485

EN HANCED TEC HNOLOGY 35

Multi-Function Control ETMFC610

3) ETHERNET PORT

http://www.entecene.co.kr

Ethernet1 and 2 are RJ-45 that has 8pins as in ‘Table 5-4.Ehternet(TP) Pin Description’ .

Ethernet port can be selected between TP and FX type. If FX type is used, LC type optical communication will be supported.

Ethernet 1 and 2 are composed of duplex switch ports

Table 5-4.Ethernet(TP) Pin Description

Pin

1

2

Wire Color

White/Green

Green

10Base-T Signal

100Base-TX Signal

Transmit+

Transmit- Eth2 Eth1

[ Ethernet TP ]

1L/ACT

1SPEED

2L/ACT

2SPEED

5

6

3

4

White/Orange

Blue

White/Blue

Orange

Receive+

Unused

Unused

Receive-

Eth2 Eth1

[ Ethernet FX ]

1L/ACT

1SPEED

2L/ACT

2SPEED

7

8

White/Brown

Brown

Unused

Unused

Figure 5-4.Ethernet Port

4) IRIG-B Connector - Option

It is a IRIG-B connector for time synchronization function using Time Synchronization module.

Input current : 4 mA at 5 V (typical)

Table 5-5. IRIG-B Pin Description 2 1

Connector Pin Description

IRIG-B

Connector

1

2

POSITIVE

NEGATIVE

- +

Figure 5-5.

IRIG-B

EN HANCED TEC HNOLOGY 36

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Key Features

  • Comprehensive metering and recording capabilities
  • Advanced protection functions for over/under voltage, over/under frequency, over/under current, and more
  • Flexible communication options including RS-485, Ethernet, and Modbus
  • User-friendly interface with a large LCD display and intuitive navigation
  • Compact and rugged design suitable for harsh environments
  • Versatile control capabilities for load shedding, generator control, and more
  • Advanced monitoring functions for voltage, current, power, and energy consumption

Related manuals

Frequently Answers and Questions

What are the input and output capabilities of the ETMFC610?
The ETMFC610 has 4 voltage inputs, 3 current inputs, 8 digital inputs, and 6 relay outputs.
What communication protocols does the ETMFC610 support?
The ETMFC610 supports Modbus RTU and Modbus TCP/IP protocols.
What is the accuracy of the ETMFC610's metering functions?
The ETMFC610's metering functions have an accuracy of 0.5% for voltage and current measurements, and 1% for power and energy measurements.
What is the maximum fault current that the ETMFC610 can withstand?
The ETMFC610 can withstand a maximum fault current of 20kA for 1 second.
What is the operating temperature range of the ETMFC610?
The ETMFC610 has an operating temperature range of -20°C to +70°C.

advertisement

Table of contents