GROUP # / FAULT INDICTION / INRUSH RESTRAINT / INRUSH DURATION T / OTHERS / Make Use ‘I’

Range NO, YES

[OTHERS]

>Make Use ‘I’: NO

[NO/YES]

Default

Set whether or not to use current as decision condition for operating function.

NO Step ~

When it sets to NO, the inrush current restraint interval becomes active the switch is closed (52A) and live line status.

 When it set to YES, when the current increases above 2A, the inrush current restraint interval is active.

8.1.5. FI Auto Reset

ETMFC610 has a function to automatically reset fault indicator target (front panel lamp y communication BI points, etc.) after detecting fault current and when line is restored normally. The configuration as like below;

GROUP # / FAULT INDICTION / FI Auto Reset / Reset Mode

Range OFF/TEMP/PERM/ALL

[FI AUTO RESET]

>Reset Mode: OFF

ResetTime: 10.00

[OFF/TEMP/PERM/ALL]

Default

OFF

OFF

TEMP

Step

: FI Auto Reset is not used.

~

It configures if FI Auto Reset will be used or no.

: Auto Reset is applied when Temporary fault is detected on

‘IV’ FI Type.

 PERM : Auto Reset is applied when Permanent fault is detected on ‘IV’ FI Type.

 ALL : Auto Reset is applied when all the types of fault current are detected on ‘IV’ FI Type and ‘I’ FI Type.

GROUP # / FAULT INDICTION / FI Auto Reset / Reset Time

Range 0.01~600.00:0.01s

[FI AUTO RESET]

> Reset Mode: OFF

>Reset Time: 10.00

[0.01~600.00:0.01s]

Default 10.00 Step

Reset time is applied about FI Auto Reset.

0.01s

After voltage comes back to live line, when the setting value is maintained during setting time, FI will be reset automatically.

EN HANCED TEC HNOLOGY 191

advertisement

Key Features

  • Comprehensive metering and recording capabilities
  • Advanced protection functions for over/under voltage, over/under frequency, over/under current, and more
  • Flexible communication options including RS-485, Ethernet, and Modbus
  • User-friendly interface with a large LCD display and intuitive navigation
  • Compact and rugged design suitable for harsh environments
  • Versatile control capabilities for load shedding, generator control, and more
  • Advanced monitoring functions for voltage, current, power, and energy consumption

Related manuals

Frequently Answers and Questions

What are the input and output capabilities of the ETMFC610?
The ETMFC610 has 4 voltage inputs, 3 current inputs, 8 digital inputs, and 6 relay outputs.
What communication protocols does the ETMFC610 support?
The ETMFC610 supports Modbus RTU and Modbus TCP/IP protocols.
What is the accuracy of the ETMFC610's metering functions?
The ETMFC610's metering functions have an accuracy of 0.5% for voltage and current measurements, and 1% for power and energy measurements.
What is the maximum fault current that the ETMFC610 can withstand?
The ETMFC610 can withstand a maximum fault current of 20kA for 1 second.
What is the operating temperature range of the ETMFC610?
The ETMFC610 has an operating temperature range of -20°C to +70°C.

advertisement

Table of contents