8.3.3. SEF Directional Controls (67SEF). Entec ETMFC610


Add to my manuals
372 Pages

advertisement

8.3.3. SEF Directional Controls (67SEF). Entec ETMFC610 | Manualzz

Multi-Function Control ETMFC610

GROUP # / DIRECTION / GROUND / M.T.A

[GROUND]

Type: NONE

>M.T.A: 135

M.P.V(3V0): 0.30

Block OC: YES

[0~359:1Lead] http://www.entecene.co.kr

Range 0 ~ 359 degree

Default 135 Step 1 degree

Enter the maximum torque angle, The maximum torque angle setting determines the range of current direction for the polarized voltage.

For system with high-resistance grounding or floating neutrals, the ground maximum torque angle will be approximately ∠ 135 degree.

For system with solidly grounded or resistively grounded the maximum torque angle will be approximately ∠ 90 degree.

GROUP # / DIRECTION / GROUND / M.P.V(3V0)

Range 0(OFF), 0.10~0.80 xVT

[GROUND]

Type: NONE

M.T.A: 135

>M.P.V(3V0): 0.30

Block OC: YES

0(OFF),0.10~0.80 xVT

Default 0.30 Step 0.01 xVT

Set Minimum Polarizing Voltage to check ground fault direction.

Voltage shall be higher than this set value to check the direction.

Otherwise, direction check will be blocked. In case of setting 0(OFF), direction checking is disabled.

GROUP # / DIRECTION / GROUND / Block OC

Range NO, YES

[GROUND]

Type: NONE

M.T.A: 135

M.P.V(-3V0): 0.30

>Block OC: YES

[NO/YES]

Default minimum polarizing voltage set.

NO :

YES

Trip on over current element.

Step ~

Select whether to trip when polarizing voltage is dropped below

YES : No trip on over current element.

8.3.3. SEF Directional Controls (67SEF)

The SEF direction control process a very similar method to the GROUND directional control. But the default value of SEF directional element “Type” is ‘NONE’, and default value of “M.T.A(V0) is ‘135°’ .

EN HANCED TEC HNOLOGY 265

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Key Features

  • Comprehensive metering and recording capabilities
  • Advanced protection functions for over/under voltage, over/under frequency, over/under current, and more
  • Flexible communication options including RS-485, Ethernet, and Modbus
  • User-friendly interface with a large LCD display and intuitive navigation
  • Compact and rugged design suitable for harsh environments
  • Versatile control capabilities for load shedding, generator control, and more
  • Advanced monitoring functions for voltage, current, power, and energy consumption

Related manuals

Frequently Answers and Questions

What are the input and output capabilities of the ETMFC610?
The ETMFC610 has 4 voltage inputs, 3 current inputs, 8 digital inputs, and 6 relay outputs.
What communication protocols does the ETMFC610 support?
The ETMFC610 supports Modbus RTU and Modbus TCP/IP protocols.
What is the accuracy of the ETMFC610's metering functions?
The ETMFC610's metering functions have an accuracy of 0.5% for voltage and current measurements, and 1% for power and energy measurements.
What is the maximum fault current that the ETMFC610 can withstand?
The ETMFC610 can withstand a maximum fault current of 20kA for 1 second.
What is the operating temperature range of the ETMFC610?
The ETMFC610 has an operating temperature range of -20°C to +70°C.

advertisement

Table of contents