8.1.4. Inrush Restraint. Entec ETMFC610


Add to my manuals
372 Pages

advertisement

8.1.4. Inrush Restraint. Entec ETMFC610 | Manualzz

Multi-Function Control ETMFC610

8.1.4. Inrush Restraint

http://www.entecene.co.kr

ETMFC610 has inrush restraint function to prevent the malfunction by inrush current produced at the restoration of load supply. Inrush restraint function setting can be set separately in phase, ground, sensitive earth fault and negative sequence during the inrush time after the restoration of load supply, FI(fault indicator) about phase, ground, sensitive earth fault and negative sequence is not detected.

According to setting of “Make use ‘I’” , the condition to decide the restoration of load supply will be changed. If “YES” is set, the decision is made when the load current becomes over 0.2% of the rated current. If “NO” is set, the decision is made when the switch is closed (52A) and live line status.

8.1.4.1. Inrush Restraint Setup

‘INRUSH RESTRAINT’ menu is sub-divided as follow;

[INRUSH RESTRAINT]

>1.INRUSH DURATION T

2.OTHERS

1) Inrush Duration Time

GROUP # / FAULT INDICTION / INRUSH RESTRAINT / INRUSH DURATION T / Phase

Range 0.00~600.00 sec

[INRUSH DURATION T]

>Phase: 2.00

Ground: 2.00

SEF: 2.00

Neg Seq’: 2.00

[0.00~600.00:0.01s]

Default 2.00 of load supply.

Step

Set the block time for inrush current of phase.

0.01sec

Phase fault is not detected during this setting time after the restoration

*. NOTE ) Setting for Ground, SEF and Neg Seq’ are same as Phase setting above.

EN HANCED TEC HNOLOGY 190

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Key Features

  • Comprehensive metering and recording capabilities
  • Advanced protection functions for over/under voltage, over/under frequency, over/under current, and more
  • Flexible communication options including RS-485, Ethernet, and Modbus
  • User-friendly interface with a large LCD display and intuitive navigation
  • Compact and rugged design suitable for harsh environments
  • Versatile control capabilities for load shedding, generator control, and more
  • Advanced monitoring functions for voltage, current, power, and energy consumption

Related manuals

Frequently Answers and Questions

What are the input and output capabilities of the ETMFC610?
The ETMFC610 has 4 voltage inputs, 3 current inputs, 8 digital inputs, and 6 relay outputs.
What communication protocols does the ETMFC610 support?
The ETMFC610 supports Modbus RTU and Modbus TCP/IP protocols.
What is the accuracy of the ETMFC610's metering functions?
The ETMFC610's metering functions have an accuracy of 0.5% for voltage and current measurements, and 1% for power and energy measurements.
What is the maximum fault current that the ETMFC610 can withstand?
The ETMFC610 can withstand a maximum fault current of 20kA for 1 second.
What is the operating temperature range of the ETMFC610?
The ETMFC610 has an operating temperature range of -20°C to +70°C.