Below you will find brief information for Programmable Terminal NT NT20, Programmable Terminal NT NT20S, Programmable Terminal NT NT20M. The NT20 is a programmable terminal used to display and transmit information in an FA site. It can be easily installed and used. NT20, NT20S and NT20M support features and functionality to display, receive data from a host and send data to a host. It also gives the operation examples and characteristics of the NT20.
Advertisement
Advertisement
SECTION 2
Hardware Settings and Connections
This section describes the settings of the NT20, connections to a Host, and other hardware settings.
2-1-1 Description of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-2 Operation Status DIP Switch Settings . . . . . . . . . . . . . . . . . . . . . . .
2-2-1 Installation Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2-2 Installation to the Operation Panel . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2-3 Power Supply Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3 Connecting Link Adapters and RS-422A Converters . . . . . . . . . . . . . . . . . . .
2-3-1 Connecting an CJ1W-CIF11 RS-422A Converter . . . . . . . . . . . . . .
2-3-2 Connecting an NT-AL001 Link Adapter . . . . . . . . . . . . . . . . . . . . .
2-5-1 Installation Method. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-6 Connecting to the RS-232C Port at the Host . . . . . . . . . . . . . . . . . . . . . . . . .
2-6-1 Host Types and Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-6-2 Connecting Directly between RS-232C Ports . . . . . . . . . . . . . . . . .
2-7 Communicating with the PLC Using C200H Direct Communications . . . . .
2-7-1 Applicable PLC Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-7-2 Connection Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Turning the Power ON/OFF When Using C200H Direct
Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-8 Host Connections by RS-232C (NT20-ST128) . . . . . . . . . . . . . . . . . . . . . . .
2-8-1 Host Computer Communications Settings . . . . . . . . . . . . . . . . . . . .
2-8-2 Connector Pin Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
17
Description of Parts and Settings
Note
Section 2-1
On unpacking the NT20 and peripheral devices, check their external appearance and confirm that there is no damage. Also confirm that there is no abnormal noise when you shake the PT lightly.
2-1 Description of Parts and Settings
Before getting to the operation, confirm the names and functions of parts.
Also set the DIP switches on the NT20.
2-1-1 Description of Parts
Front View
Rear View
Note
RUN indicator
• Lit green while the PT is in
RUN mode.
Touch switches can be created in the desired locations on the display and used as lamps, input switches, and other functional objects.
The NT20 comes in two body colors.
• NT20-ST121-E: Ivory
• NT20-ST121B-E: Black
• NT20-ST128: Ivory
• NT20-ST128B: Black
Expansion interface connector
When using an Expansion Interface Unit such as a Memory Unit, connect it here.
Battery cover
There is a battery holder beneath this cover. The Battery is not installed when the
PT is shipped.
Type name
Contrast control
Use a fine flat-blade screwdriver.
Reset switch
DIP switch
Power input terminals
Connect the power to the NT20 at these terminals
Serial port B connector
Connect this connector to communicate with a host. An RS-232C 9-pin connector is required. A
CJ1W-CIF11 RS-422A Converter can be connected directly.
Serial port A connector
Connect this connector to a host or to a computer running Support Software.
An RS-232C 9-pin connector is required. A CJ1W-CIF11 RS-422A
Converter can be connected directly.
18
Description of Parts and Settings
Section 2-1
2-1-2 Operation Status DIP Switch Settings
Set the NT20 operation status with the DIP switches located in the bottom right corner on the rear of the body.
Switch #
SW2-1
SW2-2
SW2-3
SW2-4
SW2-5
SW2-6
Function
Screen data forced initialize effective/ineffective
Note When this switch is ON, SW2-4, SW2-5 and SW2-6 must be OFF.
ON The NT20 will start in a special RUN mode in which the screen data memory is initialized. When it is started, the memory initialization menu will be displayed. For the initialization procedure, refer to
Section 3-4 Initializing Memory.
[OFF] The NT20 will start in normal RUN mode.
Screen display language mode. DIP SW2-2 is used to indicate language selection. If it is turned ON, then display language will use English and the language parameter in memory SW is not selectable (User can't choose other language than English.) But if it is turned OFF, then user can choose other language through language parameter in memory SW.
[ON]
OFF
Messages are displayed in English.
Language can be selected.
Switching to the System Menu enabled/disabled
ON The System Menu cannot be displayed. If an error occurs during a start-up, the System Menu will be automatically displayed. However, “transfer mode” cannot be entered.
[OFF] The System Menu can be displayed.
Unused (Reserved for system use)
System resource initialize
Note When this switch is ON, SW2-1, SW2-4 and SW2-6 must be OFF.
ON Effective
[OFF] Invalid
System program initialize
Note When this switch is ON, SW2-1, SW2-4 and SW2-5 must be OFF.
ON Effective
[OFF] Invalid
[ ] indicates factory setting.
!Caution If the DIP switch settings have been changed when the NT20 is powered, reset the power to the NT20. The changes with the DIP switches become effective only after the power supply is reset.
Note
(1) ln addition to the DIP switches, set also the “communications type”, “host link baud rate”, etc. at the memory switches when host link/NT link is used.
For these settings, refer to Section 3-5 Setting the Conditions of Commu-
nications with the Host by Using the Memory Switches (page 91).
(2) It may be necessary to change the DIP switch settings after installing the
NT20 in an operation panel. Bear this in mind when deciding the installa-
19
Description of Parts and Settings
Section 2-1
tion position.
During work at the panel, take care to ensure that no metal scraps enter the unit.
20
Installation
Section 2-2
2-2 Installation
Install the NT20 to the operation panel and connect the power to the NT20 as described below.
2-2-1 Installation Environment
Observe the following points when installing the PT in an operation panel.
!Caution Do not install the NT20 at sites subject to the following conditions.
Otherwise, the product may malfunction.
• Severe temperature variations
• Temperatures or humidities outside the ranges stated in the specifications
• High humidity, condensation
• Splashing chemical agents
• Severe oil splashing
• Corrosive or flammable gases
• Strong vibrations or shocks
• Direct exposure to wind and rain (outdoor sites)
• Strong ultra-violet irradiation
Take adequate measures to ensure shielding if the NT20 is used at a location subject to any of the following conditions.
• Static electricity, or noise from other equipment
• Strong electric or magnetic fields
• Nearby power cables
• Potential exposure to radioactivity
!Caution Do not perform a withstand voltage test. Performing with stand voltage tests may result in malfunction.
21
Installation
Section 2-2
2-2-2 Installation to the Operation Panel
The NT20 can be flush mounted to an operation panel.
Use the panel fittings and tools included in the product package and follow the procedure below.
!Caution During work at the panel, take care to ensure that no metal scraps enter the unit. Otherwise, the product may malfunction.
Note
The thickness of applicable operation panel is 1.6 mm to 4.8 mm. All fittings must be tightened uniformly to a torque of at least 0.5 to 0.6 N·cm in order to ensure water- and dust-resistance. The panel must not be soiled or warped, and must be able to support an installation that will remain secure and strong.
1.
Open a hole, shown below, in the panel and install the NT20 from the front of the panel.
98.5
+0.5 mm
0 mm
178.5
+0.5 mm
0 mm
2.
Attach the panel fittings at four positions, shown below, on the rear of the
NT20.
Fit the hook of the fitting in the square hole in the body and tighten the screw with a Phillips head screwdriver while lightly pulling the fitting.
Note
In order to ensure adequate water and dustproof performance, tighten the four panel fittings uniformly and make sure there are no gaps between the fittings and the NT20 panel.
22
Installation
Section 2-2
2-2-3 Power Supply Connection
Connect a 24 VDC power supply to the power input terminals.
!Caution Carefully check the wiring before turning ON the power.
!Caution Do not connect AC power to the DC terminals. Incorrect wiring may result in burning.
Note
(1) Depending on how the power is turned ON/OFF, the entire system may stop. Follow the correct procedure when turning the power ON/OFF. Otherwise the system may operate unpredictably.
(2) Use DC power supplies with low voltage fluctuation. An incorrect power supply may result in malfunctions.
(3) Do not perform a dielectric strength test. Otherwise, the product may malfunction.
(4) If complying with EC directives (low voltage directives), use a power supply with reinforced insulation (compliance with EC directives is planned for June 1998).
NC
24 V
DC
Circuit breaker
Note
24 VDC power supply
Power Supply
The applicable power supply specifications are as follows.
Item Value
Power supply 24 VDC
Allowable power supply voltage fluctuation range 20.4 VDC to 27.6 VDC
(24 VDC
−15%, +15%)
Power supply voltage capacity 10 W or more
Parts Used for Connection
For the connection to the power supply terminal block, use stranded wire of
2 mm
2
or greater cross sectional Area (14 AWG stranded wire) and M3.5 size crimp terminals.
Tighten the screws on the terminal block to a torque of 0.8 N
⋅m.
Otherwise the product may malfunction.
Fork type Round type
7 mm or less 7 mm or less
Recommended Terminals
Maker
Japan Solderless Terminal MFG
Fuji Terminal
Nichifu Terminal
Fork type Round type Stranded wire size
2-YS3A
2-YAS3.5
2Y-3.5
2-3.5
V2-S3.5
2-3.5
2.0 to 2.63 mm
2
(14 to 13 AWG)
23
Connecting Link Adapters and RS-422A Converters
Section 2-3
2-3 Connecting Link Adapters and RS-422A Converters
This section describes the installation of the NT-AL001 Link Adapter and
CJ1W-CIF11 RS-422A Converter, including the external dimensions, procedure for mounting and removal, and specifications. Refer to this information when designing the control panel. For further details, refer to the Instruction
Sheet supplied with the NT-AL001 or CJ1W-CIF11.
2-3-1 Connecting an CJ1W-CIF11 RS-422A Converter
The CJ1W-CIF11 RS-422A Converter connects directly to the NT20’s serial port A or B and converts RS-232C communications to RS-422A or RS-485.
The NT20 supplies power to the RS-422A Converter through pin 6 of the RS-
232C connector, so an external power supply is not required.
Note
1.
The RS-232C connector is not insulated from the RS-422A/RS-485 connector within the CJ1W-CIF11 RS-422A Converter. If there are concerns about differences in ground potential or noise, we recommend using the
NT-AL001 Link Adapter.
2.
Always turn OFF the NT20’s power supply before installing/removing a RS-
422A Converter or connecting/disconnecting cables.
3.
Always discharge any static electricity by touching a grounded object before installing the RS-422A Converter or connecting cables.
Specifications
General Specifications
Dimensions
Item
Weight
Ambient operating temperature
Ambient storage temperature
Ambient operating humidity
Rated power supply voltage
Current consumption
Operating atmosphere
Vibration resistance
18.2
× 34.0 × 38.8 mm (W × H × D)
Specification
20 g max.
0 to 55
°C
–20 to 75
°C
10% to 90% (with no condensation)
5 V
40 mA max.
No corrosive gases
Same as NT20 Series.
(Supplied from pin 6 of the RS-232C connector.)
Shock resistance
Isolation method
Same as NT20 Series.
Not isolated
Maximum communications distance 50 m (Use the NT-AL001 if the total communications distance exceeds 50 m.)
RS-232C Connector
Connector Pin Arrangement for
RS-232C Port
Pin number
1
2
3
4
5
6
7, 8
9
Hood
FG
RD
SD
CS
RS
+5V
NC
SG
NC
Signal
24
Connecting Link Adapters and RS-422A Converters
Note
Section 2-3
The hood will have the same electrical potential as the connector on the other end of the cable.
RS-422A/485 Terminal
Block
Signal
RDA–
RDB+
SDA–
SDB+
FG
Block Diagram
SD
RS
CS
SW.6
SW.3
SW.2
SW.1
SDB(+)
SDA( -)
SW.5
RD
RDB(+)
RDA(-)
ER
DR
SV
SG
FG FG
DIP Switch Settings
Pin number
1
Function
Terminating resistance
2
3
4
5
6
ON OFF
With (at both ends of the communications path)
Two-wire method
Without
Four-wire method Two-wire/four-wire method selection (See note 1.)
Two-wire/four-wire method selection (See note 1.)
Not used.
Selection of RS control for RD
(See note 2.)
Selection of RS control for SD
(See note 3.)
Two-wire method
---
With RS control
With RS control
Four-wire method
---
Without RS control (always ready to receive)
Without RS control (always ready to send)
Note
(1) Set pins 2 and 3 to the same setting. (ON for the two-wire method or OFF for the four-wire method.)
(2) To prohibit echoback, set pin 5 to ON (with RS control).
25
Connecting Link Adapters and RS-422A Converters
Section 2-3
(3) When connecting to several devices using the four-wire method in a 1:N connection, set pin 6 to ON (with RS control). When connecting using the two-wire method, set pin 6 to ON (with RS control).
Dimensions
5.8
38.8
18.2
DIP Switch Settings,
Wiring, and Installation
The DIP switch settings must be changed to perform communications according to settings other than the default settings.
1.
Remove the DIP switch cover using a flat-bladed screwdriver in the way shown below.
Wiring the RS-422A/485
Terminal Block
Note
Press the cover gently while removing it to prevent it from popping out suddenly.
2.
Using a fine pair of tweezers or other tool with a fine point, change the settings of the DIP switch pins to match the desired communications conditions.
3.
Be sure to remount the cover after finishing the DIP switch settings.
O
N
3
4
1
2
5
6
O
N
All the pins are factory-set to OFF.
• Use either two-wire or four-wire shielded cable.
Recommended cable: CO-HC-ESV-3P
×7/0.2 (Hirakawa Hewtech)
26
Connecting Link Adapters and RS-422A Converters
Section 2-3
• Connect the shield wire at both ends of the cable carrying RS-422A/485 signals to ground, and ground the ground terminal on the Power Supply
Unit of the CPU or Expansion Rack to 100
Ω max.
1.
Taking care not to damage the shield, strip between 30 and 80 mm of sheath off the end of the cable.
30 to 80 mm
2.
Carefully twist the shield mesh together to form a single wire, and carefully cut off the material surrounding the signal wires and any unnecessary signal wires.
3.
Strip the sheath off the signal wires to a length sufficient to attach crimp terminals. Apply vinyl tape or heat–shrinking tube to the sheathes and stripped parts of communications lines.
4.
Attach stick-type crimp terminals to ends of the signal lines and crimp them using a crimp tool.
• Recommend crimp terminals:
Phoenix Contact
AI Series
AI-0.5-8WH-B (serial number: 3201369)
• Recommended crimp tool:
Phoenix Contact ZA3
With four-wire cables, insert two signal lines into each crimp terminal together before crimping.
• Recommend crimp terminals:
Phoenix Contact
AI Series
AI-TWIN2
×0.5-8WH (serial number: 3200933)
• Recommended crimp tool:
Phoenix Contact
UD6 (serial number: 1204436)
5.
Connect the signal lines and the shield line to the RS-422A/485 terminal block.
27
Connecting Link Adapters and RS-422A Converters
Section 2-3
RS-422A/485 Cable Shield
Connections
When using the CJ1W-CIF11 (with or without the NT-AL001), connect the signal lines, shields, and grounds as shown in the following diagram.
CPU Rack
CPU Unit or Communications
Unit
Power
Supply
Unit
LG
GR
RS-422A/485 shield connected at both ends
Signal line
PT
CJ1W-CIF11
PT
CJ1W-CIF11
PT
CJ1W-CIF11
2-3-2 Connecting an NT-AL001 Link Adapter
The NS-AL001 Link Adapter connects to serial port A or B of the NT20 with an
RS-232C cable and converts the RS-232C communications to RS-422A or
RS-485. (Serial ports A and B cannot be used simultaneously.)
The NT20 supplies +5 V power (150 mA max.) to the Link Adapter through pin
6 of the RS-232C connector, so an external power supply is not required.
Note
1.
The RS-232C connector is insulated from the RS-422A/RS-485 connector within the NT-AL001 Link Adapter.
2.
Always turn OFF the NT20’s power supply before installing/removing a
Link Adapter or connecting/disconnecting cables.
28
Connecting Link Adapters and RS-422A Converters
Dimensions
Section 2-3
The following diagram shows the dimensions of the NT-AL001 Link Adapter.
All dimensions are in mm.
53.5
(2.11)
110 (4.33)
4 (0.16)
74.5 (2.93)
100.2 (3.94)
105 (4.13) max.
NT-AL001-E
(30)
(1.18)
45 (1.77)
30 (1.18)
Installation and Removal
Units: mm (inch)
Dimensions with RS-422A Terminal Block Cover Closed
30
× 114 × 100.2 mm (W × H × D)
Dimensions with RS-422A Terminal Block Cover Open
30
× 114 × 119.5 mm (W × H × D)
The NT-AL001 Link Adapter can be mounted on a DIN Track or in a control panel. The Link Adapter’s RS-422A terminal block can be removed easily.
Mounting to a DIN Track
Latch the hook (a) on the rear of the Link Adapter onto the top edge of the DIN
Track, and pivot the Link Adapter downwards (b) as shown in the diagram below.
Next, fit End Plates at the right and left of the Link Adapter to secure it so that it cannot shift laterally.
(a)
(b)
29
Connecting Link Adapters and RS-422A Converters
Section 2-3
Removal from a DIN Track
Remove the End Plates from the right and left of the Link Adapter, insert a flat blade screwdriver into the catch at the bottom of the Link Adapter, and pull it down to release the catch.
Mounting to a Control Panel
The control panel must be at least 2 mm (5/64 inch) thick. Drill two mounting screw holes in a control panel and secure the Link Adapter with screws.
30
(1.18)
100
(3.94)
110
(4.33)
Specifications
Note
21
(0.83)
2-M4 holes
Units: mm (inch)
The control panel must be at least 2 mm (5/64 inch) thick for a secure and strong mount.
The following tables list the NT-AL001 Link Adapter’s general and communications specifications.
General Specifications
Item Specification
Dimensions
Weight
Ambient temperature
With RS-422A terminal block cover closed:
30
× 114 × 100.2 mm (W × H × D)
With RS-422A terminal block cover open:
30
× 114 × 119.5 mm (W × H × D)
200 g max.
Operating 0 to 55
°C
Storage –20 to 75
°C
Operating ambient humidity 10% to 90% (with no condensation)
Rated power supply voltage +5 V
± 10%
(through pin 6 of the RS-232C connector)
Rated power supply current 150 mA max.
Inrush current
Insulation resistance
0.8 A max.
20 M
Ω min., measured between the RS-422A terminal signal lines and FG terminal (at 500 VDC)
30
Connecting Link Adapters and RS-422A Converters
Section 2-3
Item
Dielectric strength
Operating environment
Vibration resistance
Shock resistance
Specification
1,500 VAC for 1 minute between the RS-422A terminal signal lines and the FG terminal
Leakage current: 10 mA max.
No corrosive gases
Conforms to JIS C0911, 60 minutes each in X, Y, and
Z directions
Conforms to JIS C0912, 147 m/s
2
, 3 times each in X,
Y, and Z directions
Communications Specifications (RS-232C Interface)
Item
Baud rate
Transmission distance
Connector
Specification
115.2k bps max.
2 m max.
9-pin D-SUB connector (female)
Communications Specifications (RS-422A/485 Interface)
Baud rate
Item
500 m max.
Specification
115.2k bps max. (depends on the RS-232C baud rate)
Transmission distance
Terminal block configuration 8-terminal detachable terminal block, M3.0
31
Connecting Link Adapters and RS-422A Converters
DIP Switch Settings
Section 2-3
The NT-AL001 Link Adapter has a 6-pin DIP switch that sets the RS-422A/
RS-485 communications conditions. Set the DIP switch before connecting the communications cable.
Note
ON
1 2 3 4 5 6
(Factory settings)
NT-AL001-E
SW1-1: Not used (always ON)
SW1-2: Built-in terminator setting
- OFF Terminator not set
- ON Terminator set
SW1-3 and SW1-4: 2-wire/4-wire
SW1-3 SW1-4
OFF
2-wire (RS-485)
ON
SW1-3 SW1-4
OFF
ON
4-wire (RS-422A)
SW1-5 and SW1-6: RS-422A send mode
SW1-5 SW1-6
OFF
ON
No RS/CS control
SW1-5 SW1-6
OFF
ON
RS-232C CS control (high)
(Data sent at CS high)
SW1-5 SW1-6
OFF
ON
RS-232C CS control (low)
(Data sent at CS low)
When using Host Link or 1:1 NT Link communications, set the RS-422A send mode to “no RS/CS control” by turn OFF both SW1-5 and SW1-6.
When using 1:N NT Link communications (standard or high-speed), set the communications mode to “RS/CS control” by turning ON either pin SW1-5 or
SW1-6.
1.
Do not turn ON both SW1-5 and SW1-6 at the same time. This may damage internal circuits.
2.
The power supply to the device supplying +5 V must be turned OFF before starting wiring work.
3.
Before connecting the RS-232C cable and turning ON the power to an RS-
232C device such as a PT (i.e., turning ON the power to the Link Adapter), check that the cable is wired correctly and that the DIP switch settings are correct. If the power is turned ON and there is a wiring fault, the internal circuits of the Link Adapter or the RS-232C device may be damaged.
32
Connecting Link Adapters and RS-422A Converters
Terminal Pin Allocation
7
5
3
1
3
4
1
2
5
8
6
4
2
6
7
8
9
Section 2-3
4.
When the Link Adapter is connected to a C200HX/HG/HE (-ZE), CQM1H,
CS1G/H, CS1G/H-H, or CJ1G model of OMRON PLC as an RS-422A device, set pins SW1-5 and SW1-6 as indicated below.
SW1-5
OFF
SW1-6
ON
5 6
The NT-AL001 Link Adapter has a terminal block for an RS-422A/485 interface connection and a connector for an RS-232C interface connection.
The pin allocations for the RS-422A/485 terminal block and the RS-232C connector are as follows.
RS-422A/485 Terminal Block
The CSB and CSA signals are for specialized applications.
8
5
4
7
6
3
2
1
Pin Signal name
Request to send (–)
Request to send (+)
Receive data (–)
Receive data (+)
Send data (–)
Send data (+)
Signal ground
Functional ground
Code
CSA
CSB
RDA
RDB
SDA
SDB
Signal direction
(Link Adapter
⇔ Device)
Link Adapter
→ RS-422A/485 Device
Link Adapter
→ RS-422A/485 Device
Link Adapter
← RS-422A/485 Device
Link Adapter
← RS-422A/485 Device
Link Adapter
→ RS-422A/485 Device
Link Adapter
→ RS-422A/485 Device
SG (GND) ---
---
Compatible Crimp Terminals
Use crimp terminals for M3 screws.
Fork terminal Round terminal
6.2 mm max.
6.2 mm max.
Manufacturer Style
J.S.T. Mfg Co., Ltd.
Fork
Round
Molex Fork
Round
Model Compatible wire
V1.25-N3A
V1.25-MS3
AWG22 to AWG16
(0.25 to 1.65 mm
2
)
VSY1.25-3.5L
AWG22 to AWG16
RAV1.25-3
(0.3 to 1.65 mm
2
)
1
2
3
4
RS-232C Connector
The connector hood is connected to the RS-422A terminal block’s frame ground terminal.
5
6
7
Pin Signal name
Not used
Send data
Receive data
Request to send
(shorted to CS internally)
Clear to send
(shorted to RS internally)
+5 V (150 mA) input for Link
Adapter
Data set ready
(shorted to ER internally)
Code
---
SD
RD
RS
CS
+5 V
DR
Signal direction
(RS-232C Device
⇔ Link Adapter)
---
RS-232C Device
← Link Adapter
RS-232C Device
→ Link Adapter
RS-232C Device
← Link Adapter
RS-232C Device
→ Link Adapter
RS-232C Device
→ Link Adapter
RS-232C Device
→ Link Adapter
33
Connecting Link Adapters and RS-422A Converters
Section 2-3
Block Diagram
RS-232C side
D-SUB 9-pin Case
+5 V
SG
6
Fuse
9
R
Pin Signal name Code
ER
Signal direction
(RS-232C Device
⇔ Link Adapter)
RS-232C Device
← Link Adapter
8 Data terminal ready
(shorted to DR internally)
Signal ground 9 SG ---
The following diagram shows the internal block diagram of the NT-AL001 Link
Adapter. Refer to this diagram only when wiring custom cables or connecting devices with special interfaces.
POWER
Indicator
RS-422A/485 Dr/Rec
DC-DC
Converter
IS_5 V
L L REG
IS_0 V
RS-422A/485 side
8 terminal block
1
FG
2
SG
RD
3
2
SD
RS
4
CS
DR
5
7
8
ER
RS-232C
Dr/Rec
R
Photocoupler
R R R
SW1-6
SW1-5
SW1-3
Terminating resistance
RS-422A Dr
R
SW1-2
3
4
2-wire/
4-wire
SW1-4
SDB
SDA
5
6
RDB
RDA
7
8
CSB
CSA
RS-422A/485 Cable Shield
Connections
When using RS-422A or RS-485 cables for long-distance communications, do not ground the shield at both ends of the communications line because large currents can flow through the shield due to the difference in potential at the two grounding points. We recommend grounding the shield at one end, as shown in the following diagram.
Signal lines
NT-AL001
RS-232C
NT20
Host
RS-422A/485 shield
Connect to the terminal block's
FG terminal.
RS-232C
NT20
RS-232C
NT20
34
Connecting the NT Support Tool
Section 2-4
2-4 Connecting the NT Support Tool
In order to install the system program in the NT20, or to transmit screen data created with the NT Support Tool to the NT20, the NT20 must be connected to a personal computer with an RS-232C cable.
The NT20 connects with the RS-232C cable from a personal computer at serial port A. When the host is connected at serial port B, the connection with the host can be maintained as it is while the NT20 is connected to the RS-
232C cable from a personal computer.
Serial port A
(RS-232C, 9-pin)
Communications Conditions
The communications conditions are automatically set when the system installer and NT Support Tool are started.
Recommended Connector Cable
Use the cable indicated below.
• CV500-CN228 (length: 2 m), made by OMRON
(D-SUB 9-pin, male
⇔ D-SUB 25-pin, male)
• XW2Z-S001 (conversion cable), made by OMRON
(D-SUB 25-pin, female
⇔ half pitch 14-pin, male)
• XW2Z-S002 (length: 2 m), made by OMRON
(D-SUB 9-pin, male
⇔ D-SUB 9-pin, female)
For details on making a connector cable, refer to Appendix E Making the
Cable for Connecting a Personal Computer on page 267.
35
Using a Memory Unit
Section 2-5
2-5 Using a Memory Unit
This section explains how to use a Memory Unit with the NT20. By installing a
Memory Unit (NT-MF261) on the NT20, the system program or the screen data in the NT20 can be recorded (backed up) in the Memory Unit.
In addition, the system program or the screen data in the Memory Unit can be automatically read into the NT20 when it starts up. This means that system program and screen data can be changed easily at the operation site without connecting to the NT Support Tool.
The data in the Memory Unit is retained without backup by a battery or other means.
In systems where there are frequent setup changes, by preparing a number of
Memory Units in advance and recording screen data in them according to the control performed in each case, the NT20 screen data can be changed simply by installing the Memory Unit, without connecting to the NT Support Tool.
Even if NT20 is replaced, the previous status can be maintained simply by installing the Memory Unit that retains the system program and screen data of the previous NT20.
By using the following combinations, data can be stored (backed up) to a
Memory Unit.
• Screen data for two PTs.
• System program for two PTs.
• System program and screen data for one PT.
One Memory Unit can store the screen data for two PTs.
Note
(1) Make sure that the power supply to the PT is OFF before connecting or disconnecting a Memory Unit. After mounting a Memory Unit, be sure to tighten its two screws. Otherwise the product may malfunction.
(2) During data transmission, do not turn OFF the power supply to the NT20.
(3) Do not touch the PCB (printed circuit board) with bare hands. Also, discharge any static electricity by touching a grounded object before connecting or disconnecting a Memory Unit. Static electricity may cause the components to malfunction.
(4) Be sure that the combination of the system program and screen data is correct in the NT20 before transferring data from the Memory Unit to the
NT20. If the system program and screen data are not combined correctly, unexpected operation may result.
Reference:
• When a Memory Unit is mounted, the NT20 cannot be set to the operating status. On completion of data transmission with a Memory Unit, always disconnect the Memory Unit from the NT20 before starting NT20 operation.
• One Memory Unit can store a system program for up to two PTs of different models. In order to transmit a system program from the Memory Unit to the NT20, the system program must be compatible to the target PT model.
• The status of memory switch settings can be recorded to the Memory Unit besides screen data. When the data in the Memory Unit is written into the
NT20, make sure that these settings can be adapted to the NT20 used before transmission.
36
Using a Memory Unit
Section 2-5
2-5-1 Installation Method
Install the Memory Unit (NT-MF261) at the expansion interface connector at the rear of the NT20 as shown in the figure below.
Mounting screws
Screw hole
2-5-2 Method of Use
As shown in the figure below, a Memory Unit has 2 four-pin DIP switches, and the operation is determined by the DIP switch settings at startup.
1 2 3 4 1 2 3 4
DIP Switch Functions
Note
Factory setting is turned all to OFF .
OFF
SW1
OFF
SW2
Always confirm that the power to the NT20 is OFF before setting the DIP switches.
The functions of the DIP switches on the Memory Unit are indicated in the table below.
SW1
Pin Function
SW1-1 Automatic transmission (writing from the Memory Unit to the PT)
SW1-2 Automatic transmission (writing from the PT to the Memory Unit)
SW1-3 Manual transmission (Direction of transmission and bank used selected at the PT touch panel)
SW1-4 Data type to transfer
OFF: Not executed
ON: Executed
OFF: Not executed
ON: Executed
OFF: Not executed
ON: Executed
OFF: Screen data
ON: System program
SW2
Pin
SW2-1
SW2-2
Disable/enable writing to PT
Function
SW2-3 Area (bank) selection of automatic transmission
(See note.)
SW2-4
Disable/enable writing to the Memory Unit
System/Screen simultaneous transmission
OFF: Disable
ON: Enable
OFF: Disable
ON: Enabled
OFF: Bank 0
ON: Bank 1
OFF: Disable
ON: Enable
37
Using a Memory Unit
Section 2-5
Writing Screen Data to a
Memory Unit Using
Automatic Transmission
(PT to Memory Unit)
Note
The Memory Unit stores system program or screen data for one PT in each of Areas (bank 0, bank 1). (The total data storage is for two
PTs.) SW2-3 sets which of these two banks is used for automatic transmission.
Reference:
• In the following cases, a mode setting error occurs.
• More than one of the SW1-1 to SW1-3 switches are set to ON.
• None of the SW1-1 to SW1-3 switches are set to ON.
• In the following case, a protect setting error occurs.
Transmitting to the write destination has been disabled by the setting for
SW2-1 or SW2-2.
• In the following cases, a data transmission error occurs.
• An attempt is made to transmit data other than the system program to
PT System Program Area.
• An attempt is made to transmit the system program to PT Screen Data
Area.
• For details on mode setting errors and protect setting errors, refer to
Errors When Using a Memory Unit (page 42).
In this mode, system program or the screen data in the NT20 is forcibly written to the Memory Unit irrespective of the setting status of the NT20.
This mode is convenient if the touch panel is broken and touch switch operation is not possible, or if someone unfamiliar with touch switch operation at the operation site is using the system.
Reference:
When screen data is written to the Memory Unit, the data that has been stored in the specified Area up until that point is lost (if the data is written into only one Bank, the other Bank will not be affected).
■
Method of Execution
Use the following procedure to write the system program or screen data in the
NT20 to the Memory Unit by automatic transmission.
1,2,3...
1.
Check that the power supply to the NT20 is OFF, then set the DIP switches of the Memory Unit as follows after installing Memory Unit to NT20.
ON
ON
1 2 3 4
1 2 3 4
SW1
SW2
SW2-4 ON: System/Screen transmitted simultaneously
OFF: System/Screen not transmitted simultaneously
SW1-4 ON: System program
OFF: Screen data
SW2-3 ON: Bank 1
OFF: Bank 0
It is not strictly necessary to set SW2-1 to OFF (to disable writing to the
PT), but it is recommended to do so to avoid loss of data in the event of operating errors.
Reference:
• Setting SW2-4 to ON (System/Screen transmitted simultaneously) disables the setting of SW1-4.
• Setting SW2-4 to ON (System/Screen transmitted simultaneously) disables the setting of SW2-3, writes the system program into bank 0, and the screen data into bank 1 at all times.
38
Using a Memory Unit
Section 2-5
2.
Turn the NT20 power ON.
The screen data is automatically written into the Memory Unit. The screen data in the NT20 is preserved.
The messages Preparing, Transmitting, Verifying, and Finished are displayed on the screen according to the progress of data writing.
At the same time, the progress of the data writing status is displayed by the means of the number of bytes and blocks (1 bank = 16 block = 1024k byte).
RUN Indicator operates as follows according to the processing status.
Preparing: flashes at intervals of 1 second
Transmitting: flashes at intervals of 0.5 second
Verifying: flashes at intervals of 0.5 second
Finished: lights up
3.
Turn the NT20 power OFF, remove the Memory Unit.
To operate NT20 continuously, turn the NT20 power back ON.
Writing Screen Data to the
PT Using Automatic
Transmission (Memory
Unit to PT)
In this mode, the system program or screen data in the Memory Unit is forcibly written to NT20 irrespective of the setting status of the NT20.
Since data transmission by this method is faster than when the NT Support
Tool or system installer is used, it can save a lot of time. When transmitting the same system program or screen data to multiple NT20, this mode becomes convenient.
Reference:
When data is written to the NT20, the data that has been stored up until that point is lost. When the system program is changed, the operation of NT20 also changes.
■
Method of Execution
Use the following procedure to write the screen data in Memory Unit to the
NT20 by automatic transmission.
1,2,3...
1.
Check that the NT20 power is OFF, then set the DIP switches on the Memory Unit as follows after installing Memory Unit to NT20.
ON
ON
1 2 3 4
1 2 3 4
SW1
SW2
SW2-4 ON: System/Screen transmitted simultaneously
OFF: System/Screen not transmitted simultaneously
SW1-4 ON: System program
OFF: Screen data
SW2-3 ON: Bank 1
OFF: Bank 0
It is not strictly necessary to set SW2-2 to OFF (to disable writing to the
Memory Unit), but it is recommended to do so to avoid loss of data in the event of operating errors.
39
Using a Memory Unit
Section 2-5
Reference:
• Setting SW2-4 to ON (System/Screen transmitted simultaneously) disables the setting of SW1-4.
• Setting SW2-4 to ON (System/Screen transmitted simultaneously) disables the setting of SW2-3. In this case, the data transmission becomes possible only if the data inside Memory Unit is in either of following combinations.
Bank 0: system program, Bank 1: other than system program
Bank 0: other than system program, Bank 1: system program
If the combination is not as listed above, a data transmitting error occurs.
• When writing the system program into the NT20, the type of system program inside Memory Unit and the PT model must correspond.
2.
Turn the NT20 power ON.
The screen data is automatically written into the PT.
The messages Preparing, Transmitting, Verifying and Finished are displayed on the screen according to the progress of data writing.
At the same time, the progress of data writing status is displayed by the means of the number of bytes and blocks (1 bank = 16 block = 1024k byte).
The RUN Indicator operates as follows according to the processing status.
Preparing: flashes at intervals of 1 second
Transmitting: flashes at intervals of 0.5 second
Verifying: flashes at intervals of 0.5 second
Finished: lights up
3.
Turn the NT20 power OFF, remove the Memory Unit.
To operate NT20 continuously, turn the NT20 power back ON.
Reading and Writing Data by Manual Transmission
In this method, the direction of transmission and Area of the Memory Unit used are set by touch switch operations at the NT20. Transmission can be executed while checking the settings.
Reference:
When data is written to the NT20 or Memory Unit, the data that has been stored up until that point is lost.
■
Method of Execution
Use the following procedure to write screen data using manual transmission.
1,2,3...
1.
Check that the NT20 power is OFF, then set the DIP switches on the Memory Unit as follows.
ON
ON
1 2
SW1
3 4
1
SW2
2 3 4
Setting of SW2-4 not relevant
Setting of SW1-4 not relevant Setting of SW2-3 not relevant
In order to avoid loss of data in the event of operating errors, it is advisable to set SW2-1 and SW2-2 so as to disable writing to the Unit from which the data is to be read.
2.
Turn the NT20 power ON.
Display language select screen appears.
40
Using a Memory Unit
Section 2-5
3.
Press the Japanese or English touch switches to select the display language.
The screen shown below is displayed.
Current PT Screen Data, System
The first line: System program name and version for the system program inside the PT.
The second line: Resource name and version for the resource inside the
PT.
Current PT Screen Data, Screen
The comment for the screen data in the NT20 is displayed here.
Current Memory Unit Screen Data
• System Program:
The first line: System program name and version for the system program inside the Memory Unit.
The second line: Resource name and version for the resource inside the
Memory Unit.
• Screen Data:
The comment for the screen data in the NT20 is displayed here.
The available transmitting destinations are altered depending on the settings of the source of transmitting as described in the table below
Source
[PT]screen
[PT]system
Description
[Memory Unit] Bank 0
[Memory Unit] Bank 1
[PT]system/screen
[Memory Unit] Bank 0
[Memory Unit] Bank 1
[Memory Unit] Bank 0/1 (fixed)
• If system program is selected
[PT]system (fixed)
• If screen data is selected
[PT]screen (fixed)
[Memory Unit] Bank 0/1 [PT]system/screen (fixed)
Reference:
• When transmitting the system program and screen data simultaneously from the PT to the Memory Unit, the setting of banks is Bank 0: system program, Bank 1: screen data, and when transmitting them from the
Memory Unit to the PT, either of the following combinations must be used.
Bank 0: system program, Bank 1: other than system program
Bank 0: other than system program, Bank 1: system program
• When writing the system program into the NT20, the type of system program inside Memory Unit and the PT model must correspond.
41
Using a Memory Unit
Errors When Using a
Memory Unit
Section 2-5
4.
Press Execute.
The messages Preparing, Transmitting, Verifying, and Finished are displayed according to the progress of data transmission. At the same time, the progress of data transmitting status is displayed by the means of the number of bytes and blocks (1 bank = 16 block = 1024k byte).
When the data transmission is operated manually, RUN Indicator remains
OFF.
5.
Turn the NT20 power OFF, remove the Memory Unit, then turn the NT20 power back ON.
If an error occurs when using the Memory Unit, the NT20 operates as follows
• Details on the error and remedial action are displayed on the screen.
Each screen has touch switches to change the display language from one to the other. When the manual data transmission is operating, the content of error and remedial action are shown with selected language. When the automatic transmission is operating, it is displayed in Japanese.
• The continuous buzzer sounds.
• The RUN Indicator flashes.
If a protect setting error occurs when executing manual transmission, it is possible to return to the Memory Unit manual transmission screen by pressing the OK touch switch, but in the case of other errors, the status described above remains in effect until the NT20 power is turned OFF or reset.
When an error occurs, take remedial action by referring to the table below.
Error
Mode setting error
Protect setting error
(automatic transmission)
Protect setting error
(manual transmission)
Probable Cause
DIP Switch pins SW1-1 to
SW1-3 are all OFF, or more than one is ON.
Writing to the data write destination has been prohibited by the setting of SW2-1 or SW2-
2.
Writing to the data write destination has been prohibited by the setting of SW2-1 or SW2-
2.
Remedial Action
Turn the NT20 power OFF, set the Memory Unit DIP switches correctly, then turn the NT20 power back ON.
Turn the NT20 power OFF, set the Memory Unit DIP switches correctly, then turn the NT20 power back ON.
Perform either of the following procedures.
• Press the OK touch switch to return to the Memory Unit manual transmission screen, make the correct settings, then try again.
• Turn the NT20 power OFF, correct the DIP switches settings of the Memory Unit, then turn the power back
ON.
Flash memory error An error occurred during initialization of the NT20 or
Memory Unit flash memory, or during write processing.
Turn the NT20 power OFF, then back ON. If the error recurs, the flash memory at the write destination may be faulty. In this case, replace the
Unit.
42
Using a Memory Unit
Section 2-5
Error
Verify error
Transmitting data error (The automatic transmission only)
Probable Cause
An error occurred during verification processing at the flash memory of the NT20 or the
Memory Unit.
An attempt is made to transmit data other than a system program or the system program of a different PT model into the NT20 as the system program.An attempt is made to write a system program into the NT20 as screen data.
Remedial Action
Turn the NT20 power OFF, then back ON. If the error recurs, the flash memory at the write destination may be faulty. In this case, replace the
Unit.
Perform either of the following procedures.
• Turn the NT20 power OFF, correct the DIP switch settings of the Memory Unit, and then turn the power back ON.
• Turn the NT20 power OFF, set the DIP switch settings to the manual transmission, and then check the data inside the Memory Unit.
43
Connecting to the RS-232C Port at the Host
Section 2-6
2-6 Connecting to the RS-232C Port at the Host
The method for connecting directly between the RS-232C port of the PT and the RS-232C port of the host is as follows.
The following discussion is focused on the connection method to OMRON
PLCs.
Direct Connection between RS-232C Ports with RS-232C Cable
This is the easiest connection method. Depending on the host to which the connection is to be made, it may be possible to use OMRON cables with connectors.
NT20 Host
RS-232C cable (15 m max.)
Note
The CS/CJ-series CPU Unit cannot be connected with the 1:1 NT link method. Use the 1:N NT link method instead of making a 1:1 connection. For
details, refer to Using the 1:N NT Link on page 60 or Using the High-speed
2-6-1 Host Types and Settings
The types of host that can be connected to a PT by using the RS-232C ports of both devices, and the settings to be made at the host, are described here.
Using the Host Link Method
Compatible Hosts
Some models and series of OMRON PLCs have the Host Link function built in.
In the CS-series (including the CS1-H PLCs), CJ-series, and CQM1H PLCs, the Host Link method can be used by installing a Serial Communications
Board or Unit. In addition, some C200HX/HG/HE(-Z)E have an integral CPU
Unit that can be connected in the Host Link method by installing a Communications Board.
Check the model and series of the PLC, the type of installed Serial Communications Board, Serial Communications Unit, or Host Link Unit before making a connection.
The hosts that can be connected to the NT20 by the Host Link method using the RS-232C ports of both Units are indicated in the table below.
PLC
Series
Units with Built-in Host Link
Function
CS Series CS1G-CPU42/43/44/45-EV1
CS1H-CPU63/64/65/66/67-EV1
CS1G-CPU42H/43H/44H/45H
CS1H-CPU63H/64H/65H/66H/
67H
CJ Series CJ1G-CPU44/45
CPU Units Connectable with
Host Link Units or Expansion
Communications Board
CS1G-CPU42/43/44/45-EV1
CS1H-CPU63/64/65/66/67-EV1
CS1G-CPU42H/43H/44H/45H
CS1H-CPU63H/64H/65H/66H/
67H
CJ1G-CPU44/45
Host Link Unit/
Communications
Board
CS1W-SCU21
CS1W-SCB21
CS1W-SCB41
CJ1W-SCU41
Connectable to
CS1G
CS1H
CS1G-H
CS1H-H
CJ1G
44
Connecting to the RS-232C Port at the Host
Section 2-6
3.)
PLC
Series
C Series
CVM1
Series
(See note
Compo-
Bus/S
Master
Unit
Units with Built-in Host Link
---
Function
C200HS-CPU21/23/31/33-E
C200HE-CPU42-E
C20HE-CPU42-ZE
C200HG-CPU43/63-E
C200HG-CPU43/63-ZE
C200HX-CPU44/64-E
C200HX-CPU44/64/65/85-ZE
CPU Units Connectable with
Host Link Units or Expansion
Communications Board
C200HS-CPU01/03/21/23/31/
33-E
C200HE-CPU11/32/42-E
C200HE-CPU11/32/42-ZE
C200HG-CPU33/43/53/63-E
C200HG-CPU33/43/53/63-ZE
C200HX-CPU34/44/54/64-E
C200HX-CPU34/44/54/64/65/
85-ZE
---
C200HE-CPU32/42-E
C200HE-CPU32/42-ZE
C200HG-CPU33/43/53/63-E
C200HG-CPU33/43/53/63-ZE
C200HX-CPU34/44/54/64-E
C200HX-CPU34/44/54/64/65/
85-ZE
---
Host Link Unit/
Communications
Board
C200H-LK201-EV1
---
C200HW-COM02/04/
05/06-EV1
--CPM1-10/20/30CDR-
@
+CPM1-CIF01
CPM1A-10/20/30/40CD @-@
+CPM1-CIF01
CPM2A-30/40/60CD @@-@
+CPM1-CIF01
(Peripheral port connection)
CPM2C-10/20 @@@@@@-@
(See note 1.)
CQM1-CPU21-E
CQM1-CPU41/42/43/44-EV1
CQM1H-CPU11/21/51/61 (See note 2.)
CVM1-CPU01-EV2
CVM1-CPU11-EV2
CVM1-CPU21-EV2
---
---
---
---
CQM1H-CPU51/61
CVM1-CPU01-EV2
CVM1-CPU11-EV2
CVM1-CPU21-EV2
SRM1-C02-V1 ---
---
---
---
---
CQM1H-SCB41
CV500-LK201
---
Note
Connectable to
C200HS
C200HE
C200HE-Z
C200HG
C200HG-Z
C200HX
C200HX-Z
C200HS
C200HE
C200HE-Z
C200HG
C200HG-Z
C200HX
C200HX-Z
CPM1
CPM2A
CPM2C
CQM1
CQM1H
CVM1
SRM1
(1) Use a CPM2C-CN111 or CS1W-CN114/118 Connecting Cable, CPM1-
CIF01 RS-232C Adapter, or CPM1-CIF11 RS-422A Adapter to connect.
(2) The CQM1H-CPU11 does not have a built-in RS-232C port, so connect to the PT at the peripheral port with a CS1W-CN118 Connecting Cable.
(3) CPU Units of CVM1/CV-series PLCs without the suffix -EV @ cannot be connected.
45
Connecting to the RS-232C Port at the Host
Settings at the Host
Note
Section 2-6
When using the Host Link method, the settings shown below must be made at the host (depending on the Unit, some of these settings may not be necessary, or settings not shown here may be necessary).
Item
I/O port
Baud rate
Transfer code
Parity
1-to-1/1-to-N
Switch Setting
RS-232C
Set the same baud rate as for the NT20. (See note 1.)
ASCII, 7 data bits, 2 stop bits
Even
Command level
Unit #
1-to-N (See note 2.)
Level 1, 2, 3
00
(1) Set the Host Link baud rate up to 115,200 bps with the memory switch at the NT20.
(2) The 1-to-N setting enables BCC (Block Check Character). It is not actually possible to connect more than one NT20 in a single Host Link.
Connecting to a C-series
Host Link Unit
The setting methods for each Unit are described below.
C200H, C200HS, and C200HE/HG/HX (-Z)E Rack-mounted Unit:
C200H-LK201-V1
Setting the Front Switches
Set each switch with a flat blade screwdriver so that the values or symbols in the setting value window agree with the following.
LK201
RUN
RCV
XMT
ERROR
• Unit # (SW1, SW2)
Set these switches to 0.
SW1
0
0
SW2
SW3
5 2
SW4
• Command level, parity, and transfer code (SW4)
Set this switch to 2.
• Baud rate (SW3)
Set this switch to 5 to select 9,600 bps.
Set this switch to 6 to select 19,200 bps.
Setting the Rear Switches
• 1-to-1/1-to-N selection (DIP switch)
Set pin 3 to ON.
CTS selector switch
External
0 V (ON)
ON
1
2
3
4
• CTS selection (selector switch)
Set this always to 0V (ON).
46
Connecting to the RS-232C Port at the Host
Connecting to a CVM1/CVseries Host Link Unit
Note
Section 2-6
CVM1/CV-series Rack-mounted Unit: CV500-LK201
A CVM1/CV-series Host Link Unit (CV500-LK201) has two connectors (communications ports 1 and 2). Either of these ports can be used for connection to an NT20 by the RS-232C method. However, since the connectors at these ports are of different types, a cable that matches the connector must be prepared.
• Communications Port 1
Communications port 1 is a 25-pin connector for RS-232C use only.
• Communications Port 2
Communications port 2 is a 9-pin connector that allows selection of the
RS-232C or RS-422A method. When this port is used with the RS-232C method, the I/O port selector switch on the front of the Unit must be set to
RS-232C (the upper position).
CPU Bus Unit Settings
When connecting to a CVM1/CV-series Host Link Unit, set the following communications conditions for the CPU Bus Unit settings.
Item
Baud rate
Transfer code
Parity
1-to-1, 1-to-N
Setting at Host
Set the same baud rate as set at the NT20 (See note 1.)
ASCII, 7 data bits, 2 stop bits
Even
Command level
1-to-N (See note 2.)
Level 1, 2, 3
(1) Set the Host Link baud rate at 9,600 bps or 19,200 bps with the memory switch at the NT20.
(2) The 1-to-N setting enables BCC (Block Check Character). It is not actually possible to connect more than one NT20 in a single Host Link.
Set the CPU Bus Unit settings directly from a Programming Device (e.g.,
SYSMAC Support Software).
For details on the CPU Bus Unit settings, refer to the SYSMAC CVM1/CV-
series Host Link Unit Operation Manual (W205-E1@).
47
Connecting to the RS-232C Port at the Host
Setting the Front Switches
Section 2-6
Connecting to a CS/CJseries Serial
Communications Unit
Communications port 1
(RS-232C)
Communications port 2
(RS-232C/RS-422A)
I/O port selector switch
RS-232C
RS-422A
• Unit # (SW3, SW4)
When using communications port 2, set these switches to 0.
• I/O port selection (selector switch)
Set this to RS-232C.
• CTS selection (Pins 2 and 3)
Set pin 2 or 3 to ON. (Set this always to 0V.)
To use communications port 1, turn ON pin 2.
To use communications port 2, turn ON pin 3.
• Communications condition setting (Pin 1)
Set this pin to OFF.
Communications are executed in accordance with the CPU Bus Unit system settings made at the PLC.
The initial values for the system settings are as
- Baud rate: 9,600 bps
- Parity: Even
- Xon/Xoff control: Not executed
- Communications method: Full duplex
- Stop bits: 2 stop bits
- Data length: 7 bits
CS/CJ-series Rack-mounted Unit: CS1W-SCU21CJ-series: CJ1W-SCU41
(Port 2 is an RS-232C Port.)
Setting the Front Switches
Set the unit number of the Serial Communications Unit by using the rotary switch located on the front panel. Set each switch with a flat blade screwdriver so that the values or symbols in the setting value window agree with the following.
CS1W-SCU21
SCU21
RUN
ERC
SD1
RD1
UNIT
10
5
6
FE
C
7 8 9
A
RDY
ERH
SD2
RD2
Set the unit number to 0 through F so that it will not duplicate the numbers used in other Units.
CJ1W-SCU41
Set the unit number to 0 through F so that it will not duplicate the numbers used in other Units.
Allocation DM Area Settings for CPU Unit
Settings are written from the Programming Device (a Programming Console or CX-Programmer) directly into the allocated DM Area (PLC Setup) of the
CPU Unit. After the settings are written, they become effective by turning the power ON, restarting the Unit, restarting the communications port, or execution of the STUP instruction.
48
Connecting to the RS-232C Port at the Host
Connecting to a CPU Unit
Note
Section 2-6
The following table shows the words allocated in the DM Area and the settings.
m = DM30000 + 100
× unit number
Value Settings Allocated DM word
Port 1 Port 2
m m+10 8000 m+1 m+2 m+3 m+11 m+12 m+13
0000
0007
0008
0009
000A
0000
0000
Host Link mode, 2 stop bits, even parity, data length 7 bits
Baud rate: 9,600 bps.
Baud rate: 19,200 bps.
Baud rate: 38,400 bps.
Baud rate: 57,600 bps.
Baud rate: 115,200 bps.
Transmit delay time 0 ms.
No CTS control Unit No.0 for Host Link
CV-series and CVM1/CV-series (-EV @) CPU Units
CVM1-CPU01-EV2/CVM1-CPU11-EV2/CVM1-CPU21-EV2
PLC Setup
When connecting to a CVM1/CV-series CPU Unit, set the following communications conditions for the PLC Setup.
Baud rate
Stop bits
Parity
Data length
Unit #
Item Setting at Host
Set the same baud rate as set at the NT20 (See note.)
2 stop bits
Even
ASCII 7 bits
00
Set the Host Link baud rate at 9,600 bps or 19,200 bps with the memory switch at the NT20.
Either set PLC Setup directly from a Programming Device (e.g., SYSMAC
Support Software), or transmit the PLC Setup made at a Programming Device to the CPU Unit.
For details on the PLC Setup, refer to the SYSMAC CVM1/CV500/1000/2000
Operation Manual: Ladder Diagrams (W202-E1@).
49
Connecting to the RS-232C Port at the Host
Setting the Front Switches
Section 2-6
I/O port selector switch
RS-232C
RS-422A
• Host Link Communications method
(selector switch)
Set this to RS-232C.
• System setting (Pin 4)
To effect the existing DIP switch settings, set SW4 to ON.
To effect the existing PLC Setup, set pin 4 to OFF.
Note
For CPU Units manufactured before or during June 1995 (lot No. jj65), the existing DIP switch settings differ from the existing PLC Setup as follows.
- DIP switch settings:
2,400 bps, 1 stop bit, even parity, 7 bit data length
- PLC Setup:
9,600 bps, 2 stop bits, even parity, 7 bit data length
For CPU Units manufactured from July
1995 onward (lot No.
@@75), the stipulated values in the DIP switch settings also are 9,600 bps and 2 stop bits.
C-series C200HS, C200HX/HG/HE(-Z)E, CPM1, CPM2A, CPM2C, CQM1,
CQM1H CPU Units and SRM1
The connection method depends upon the model of PLC being used, as shown in the following table.
PLC model
C200HS, CQM1
Connection method
Connect to the CPU Unit’s built-in RS-232C port.
C200HX/HG/HE(-Z)E • Connect to the CPU Unit’s built-in RS-232C port.
• Connect to one of the RS-232C ports (port A or port B) on a Serial Communications Board.
CQM1H • Connect to the CPU Unit’s built-in RS-232C port.
• Connect to the peripheral port through a CS1W-CN118
Connecting Cable.
• Connect to the RS-232C port (port 1) on a Serial Communications Board.
CPM1
CPM2A, SRM1
CPM2C
Connect to the peripheral port through a CPM1-CIF01 RS-
232C Adapter.
• Connect to the CPU Unit’s built-in RS-232C port.
• Connect to the peripheral port through a CPM1-CIF01 RS-
232C Adapter.
Connect to the CPU Unit’s RS-232C port or the peripheral port through a Connecting Cable (CPM2C-CN111, CS1W-
CN118, or CS1W-CN114).
(The CPM2C-CN111 splits the Unit’s Communications Port into a RS-232C port and a peripheral port. A CPM1-CIF01
RS-232C Adapter is also required to connect to this peripheral port.)
50
Connecting to the RS-232C Port at the Host
Note
Section 2-6
PLC Setup Settings
When connecting to a C200HS, C200HX/HG/HE(-Z)E, CPM1, CPM2A,
CPM2C, CQM1, or CQM1H CPU Unit, or SRM1, set the following communications conditions for the PLC Setup.
Item
Communications mode
Baud rate
Stop bits
Parity
Data length
Unit #
Setting at Host
Host Link mode
Set the same speed as set at the NT20 (See note.)
2 stop bits
Even
ASCII 7 bits
00
Set the Host Link baud rate at 9,600 bps or 19,200 bps with the memory switch at the NT20.
Set the PLC Setup settings directly from a Programming Device (e.g., the CX-
Programmer Support Software).
For details on operations relating to the PLC Setup, refer to the manual for the
PLC which is used.
The PLC Setup area word addresses and settings to be made depending on the Unit and port to which the connection is made are shown below.
CPM2A, CPM2C, CQM1H, or SRM1: Peripheral Port Connection
Word Writing Value
DM6650 0001
DM6651 0303
0304
DM6653 0000
Settings
Host Link mode, no CTS control
Communications conditions set by the contents of DM
Data length 7 bits, 2 stop bits, even parity, baud rate:
9,600 bps
Data length 7 bits, 2 stop bits, even parity, baud rate:
19,200 bps
Unit # 00
C200HS, C200HX/HG/HE(-Z)E, CPM2A, CPM2C, CQM1, CQM1H (other than the CPU11), or SRM1: Built-in RS-232C Port Connection
Word Writing Value
DM6645 0001
DM6646 0303
0304
DM6648 0000
Settings
Host Link mode, no CTS control
Communications conditions set by the contents of DM
Data length 7 bits, 2 stop bits, even parity, baud rate:
9,600 bps
Data length 7 bits, 2 stop bits, even parity, baud rate:
19,200 bps
Unit # 00
C200HX/HG/HE(-Z)E: Serial Communications Board Port A
CQM1H: Serial Communications Board Port 1
Word Writing Value
DM6555 0001
DM6556 0303
0304
DM6558 0000
Settings
Host Link mode, no CTS control
Communications conditions set by the contents of DM
Data length 7 bits, 2 stop bits, even parity, baud rate:
9,600 bps
Data length 7 bits, 2 stop bits, even parity, baud rate:
19,200 bps
Unit # 00
51
Connecting to the RS-232C Port at the Host
Section 2-6
C200HX/HG/HE(-Z)E: Serial Communications Board Port B
Word Writing Value
DM6550 0001
DM6551 0303
0304
DM6553 0000
Settings
Host Link mode, no CTS control
Communications conditions set by the contents of DM
Data length 7 bits, 2 stop bits, even parity, baud rate:
9,600 bps
Data length 7 bits, 2 stop bits, even parity, baud rate:
19,200 bps
Unit # 00
CPM1: Peripheral Port Connection through a CPM1-CIF01 RS-232C Adapter
Word Writing Value
DM6650 0001
DM6651 0303
0304
DM6653 0000
Settings
Host Link mode
Communications conditions set by the contents of DM
Data length 7 bits, 2 stop bits, even parity, baud rate:
9,600 bps
Data length 7 bits, 2 stop bits, even parity, baud rate:
19,200 bps
Unit # 00
Connecting to a CPM2C
The CPM2C PLCs do not have the same kind of port connectors found on
CS1-series PLCs. The CPM2C’s communications port handles both RS-232C and peripheral port connections, which are divided internally. Therefore, when using the CPM2C, it is necessary to select RS-232C or peripheral port connections, according to the kind of cable and port (on the cable) used, as shown in the following table. Refer to the CPM2C Operation Manual for more details.
Port connecting to PT PLC Setup
RS-232C port (D-Sub 9-pin) of CPM2C-CN111 Built-in RS-232C port settings
Peripheral port of CPM2C-CN111
RS-232C port (D-Sub 9-pin) of CS1W-CN118
Peripheral port of CS1W-CN114
Peripheral port settings
Built-in RS-232C port settings
Peripheral port settings
Peripheral port
CPM2C-CN111
CPM2C
CS1W-CN118
CPM2C
CS1W-CN114
CPM2C
RS-232C port
(D-Sub 9-pin, female)
RS-232C port
(D-Sub 9-pin, female)
Peripheral port
Setting the DIP Switches of a C200HX/HG/HE(-Z)E, CQM1, or CQM1H
When using a C200HX/HG/HE(-Z)E, CQM1, or CQM1H, the DIP switches on the front panel must be set as shown below in order to make the settings in the PLC Setup (in the DM Area) effective.
52
Connecting to the RS-232C Port at the Host
C200HX/HG/HE(-Z)E
CQM1 CQM1H
Section 2-6
RS-232C port communications condition setting
Set pin 5 to OFF to make the settings made in
PLC Setup effective.
When using the CQM1H’s built-in peripheral port, turn ON SW7.
Setting the Switches of a CPM2A
When using a CPM2A, the switches on the front panel must be set as shown below in order to make the PLC Setup settings effective.
Set the Communications switch to OFF (down position).
Setting the Switches of a CPM2C
When using a CPM2C, the switches on the front panel must be set as shown below in order to make the PLC Setup settings effective.
The settings for SW1 and SW2 depend upon the usage of the peripheral port and RS-232C port.
• Connecting PT to peripheral port
• Connecting PT to built-in RS-232C port
(A device that requires non-standard communications settings is connected to the peripheral port.)
SW1: OFF
SW2: ON
• Connecting PT to built-in RS-232C port
(A Programming Console is connected to the peripheral port.)
SW1: OFF
SW2: OFF
Setting the Switches on an RS-232C Adapter
When using a CPM1-CIF01 RS-232C Adapter, set the mode switch as shown in the following diagram.
CPM1-
CIF01
CPM1
Set the mode setting switch to HOST (upper position).
53
Connecting to the RS-232C Port at the Host
Note
Section 2-6
CS/CJ-series CPU Units: CS1G/H-CPU @@-E (-V1)
CS1G/H-CPU @@H
CJ1G-CPU @@
Connect to the built-in RS-232C port of the CPU Unit, or the RS-232C port of the Communications Board. Note that the connection to a peripheral port must be made via an RS-232C Adapter (CS1W-CN118) specially designed for connecting to a peripheral port.
PLC Setup
When connecting to a CS/CJ-series CPU Unit, set the following communications conditions for the PLC Setup. Since the settings shown below are the
PLC default settings for the CPU Unit, no change to the PLC Setup is necessary as long as the baud rate is maintained at 9,600 bps.
Item
Baud rate
Stop bits
Parity
Data length
Unit No. for the Host Link
Setting at Host
Set the same speed as set at the NT20 (See note.)
2 stop bits
Even
ASCII 7 bits
00
Set the Host Link baud rate up to 115,200 bps with the memory switch at the
NT20. When the baud rate is set to 19,200 bps, the PLC Setup of the CPU
Unit need to be changed.
Either set the PLC Setup directly from a Programming Device (Programming
Console), or transmit the PLC Setup made at a Programming Device (CX-
Programmer) to the CPU Unit.
For details on PLC Setup, refer to the SYSMAC CS Series Operation Manual
(W339-E1-
@) or SYSMAC CJ Series Operation Manual (W393-E1-@).
When using the built-in RS-232C port of a CS1G/H, CS1G/H-H, or CJ1G
Word address
CIO 160
CIO 161
CIO 166
8000
Writing Value
0000
0007
0008
0009
000A
0000
Settings
Host Link mode, data length 7 bits,
2 stop bits, even parity
Baud rate: 9,600 bps.
Baud rate: 19,200 bps.
Baud rate: 38,400 bps.
Baud rate: 57,600 bps.
Baud rate: 115,200 bps.
Unit #00
When using the peripheral port of a CS1G/H, CS1G/H-H, or CJ1G
Word address
CIO 144
CIO 145
CIO 150
8000
Writing Value
0000
0007
0008
0009
000A
0000
Settings
Host Link mode, data length 7 bits,
2 stop bits, even parity
Baud rate: 9,600 bps.
Baud rate: 19,200 bps.
Baud rate 38,400 bps.
Baud rate 57,600 bps.
Baud rate 115,200 bps.
Unit #00
54
Connecting to the RS-232C Port at the Host
Peripheral port
This is used mainly for connection to the
Programming Device.
(This also supports the
RS-232C Unit connection.)
Section 2-6
Setting the Front Switches
Set pins 4 and 5 of the CPU Unit DIP switch according to the port that the
NT20 is connected to.
CS1G/H, CS1G/H-H
RUN
ERR/ALM
INH
PRPHL/COMM
SYSMAC CS1G
PROGRAMMABLE CONTROLLER
CPU42
MCPWR
OPEN
OPEN
BUSY
DIP switches (inside the battery storage)
• Set pin 4 to ON (establishing communications in accordance with PLC Setup) when connecting the
NT20 to the peripheral port.
• Set pin 5 to OFF (establishing communications in accordance with PLC Setup) when connecting the
NT20 to the RS-232C port.
PERIPHERAL
RS-232C port
This is used mainly for connection to the RS-
232C Unit. (This also supports a CX-
Programmer connection.)
PORT
CJ1G
DIP switches (inside the battery storage)
• Set pin 4 to ON (establishing communications in accordance with PLC Setup) when connecting the
NT20 to the peripheral port.
• Set pin 5 to OFF (establishing communications in accordance with PLC Setup) when connecting the
NT20 to the RS-232C port.
Peripheral port
This is used mainly for connection to the Programming Device.
(This also supports the RS-232C
Unit connection.)
RS-232 port
This is used mainly for connection to the RS-232C
Unit. (This also supports a CX-Programmer connection.)
Connecting to CS-series Serial Communications Board
Serial Communications Board equipped with a RS-232C port for CS-series
CPU Units: CS1W-SCB41/21
Allocation DM Area Settings for CPU Unit
Settings are written from the Programming Device (a Programming Console or CX-Programmer) directly into the allocated DM Area (PLC Setup) of the
CPU Unit. After the settings are written, they become effective by turning the power ON, restarting the Unit, restarting the communications port, or execution of the STUP instruction.
55
Connecting to the RS-232C Port at the Host
Section 2-6
The following table shows the words allocated in the DM Area and the settings.
Value Settings Allocated DM word
Port 1 Port 2
DM32000 DM32010 8000
DM32001
DM32002
DM32003
DM32011
DM32012
DM32013
0000
0007
0008
0009
000A
0000
0000
Host Link mode, 2 stop bits, even parity, data length 7 bits
Baud rate 9,600 bps.
Baud rate 19,200 bps.
Baud rate 38,400 bps.
Baud rate 57,600 bps.
Baud rate 115,200 bps.
Transmit delay time 0 ms.
No CTS control Unit No.0 for Host Link
Using the 1:1 NT Link Compatible Host Units
Some models and series of OMRON PLCs have the 1:1 NT Link function built in. With CQM1H PLCs, a Serial Communications Board can be added to provide 1:1 NT Link communications. Some C200HX/HG/HE(-Z)E CPU Units can be connected by the 1:1 NT Link by installing a Communications Board.
Check the model and series of the PLC against the model of CPU Unit before making the connections.
56
Connecting to the RS-232C Port at the Host
Section 2-6
The hosts that can be connected to the NT20 by the 1:1 NT Link using the
RS-232C ports of both Units are indicated in the table below.
PLC Series CPU Units with Built-in
NT Link Function
---
CPU Units Connectable with Expansion
Communications Board
(See note 1.)
Connectable to
C Series C200HS-CPU21-E, -EC
C200HS-CPU23-E
C200HS-CPU31-E
C200HS-CPU33-E
C200HE-CPU42-(Z)E
C200HG-CPU43-(Z)E
C200HG-CPU63-(Z)E
C200HX-CPU44-(Z)E
C200HX-CPU64-(Z)E
C200HX-CPU65-ZE
C200HX-CPU85-ZE
CPM1-10CDR@ (See note 2.)
CPM1-20CDR@ (See note 2.)
CPM1-30CDR@ (See note 2.)
CPM1A-10CD @-@ (See note 2.)
CPM1A-20CD @-@ (See note 2.)
CPM1A-30CD @-@ (See note 2.)
CPM1A-40CD @-@ (See note 2.)
CPM2A-30CD @@-@
CPM2A-40CD
@@-@
CPM2A-60CD @@-@
CPM2C-10
@@@@@@-@ (See note 3.)
CPM2C-20 @@@@@@-@ (See note 3.)
CQM1-CPU41-EV1
CQM1-CPU42-EV1
CQM1-CPU43-EV1
CQM1-CPU44-EV1
CQM1-CPU45-EV1
CQM1H-CPU21-E
CQM1H-CPU51-E
CQM1H-CPU61-E
CVM1 Series
(See note 5.)
CVM1-CPU01-EV2
CVM1-CPU11-EV2
CVM1-CPU21-EV2
CompoBus/S
Master Unit
SRM1-C02-V2
C200HE-CPU32-(Z)E
C200HE-CPU42-(Z)E
C200HG-CPU33-(Z)E
C200HG-CPU43-(Z)E
C200HG-CPU53-(Z)E
C200HG-CPU63-(Z)E
C200HX-CPU34-(Z)E
C200HX-CPU44-(Z)E
C200HX-CPU54-(Z)E
C200HX-CPU64-(Z)E
C200HX-CPU65-ZE
C200HX-CPU85-ZE
---
---
---
---
CQM1H-CPU51 (See note 4.)
CQM1H-CPU61 (See note 4.)
---
---
C200HS
C200HE (-Z)E
C200HG (-Z)E
C200HX (-Z)E
CPM1
CPM2A
CPM2C
CQM1
CQM1H
CVM1
SRM1
Note
Note
(1) One of the following Communications Boards is required: C200HW-
COM02/COM04/COM05/COM06-EV1.
(2) A CPM1-CIF01 adapter is required.
(3) Use a CPM2C-CN111 or CS1W-CN114/118 Connecting Cable, CPM1-
CIF01 RS-232C Adapter, or CPM1-CIF11 RS-422A Adapter to connect.
(4) A CQM1H-SCB41 Serial Communications Board is required.
(5) CPU Units of CVM1/CV-series PLCs without the suffix -EV
@ cannot be connected.
CS/CJ-series CPU Unit cannot be connected with the 1:1 connection NT link method. Use the 1:N connection NT link method (standard or high-speed)
instead of making the 1:1 connection. For details, refer to Using the 1:N NT
Link (page 60) or Using the High-speed 1:N NT Links (page 65).
57
Connecting to the RS-232C Port at the Host
Note
Section 2-6
Settings at the Host
The setting methods for each Unit are as follows:
Connecting to a C-series C200HS, C200HX/HG/HE(-Z)E, CPM1, CPM2A,
CPM2C, CQM1, CQM1H, or SRM1
PLC Setup Settings
Write the PLC Setup (in the DM Area) settings directly from a Programming
Device (e.g., SYSMAC Support Software) according to the host model and port.
Host Model
RS-232C port of C200HS, C200HX/
HG/HE(-Z)E, CPM2A, CPM2C,
CQM1, CQM1H, SRM1
Port A of C200HX/HG/HE(-Z)E (See note 1.)
Port 1 of CQM1H (See note 2.)
Port B of C200HX/HG/HE(-Z)E (See note 1.
CPM1
Word
DM6645
DM6555
DM6550
DM6650
Writing Value
4000
Setting
Use 1:1 NT
Link
(1) RS-232C port of the Communications Board
(2) RS-232C port of the Serial Communications Board
For details on operations relating to the PLC Setup, refer to the manual for the
PLC that is used.
Connecting to a CPM2C
The CPM2C PLCs do not have the same kind of port connectors found on CS/
CJ-series PLCs. The CPM2C’s communications port handles both RS-232C and peripheral port connections, which are divided internally. Therefore, when using the CPM2C, it is necessary to select RS-232C or peripheral port connections, according to the kind of cable and port (on the cable) used, as shown in the following table. Refer to the CPM2C Operation Manual for more details.
Port connecting to PT PLC Setup
RS-232C port (D-Sub 9-pin) of CPM2C-CN111 Built-in RS-232C port settings
Peripheral port of CPM2C-CN111
RS-232C port (D-Sub 9-pin) of CS1W-CN118
Peripheral port of CS1W-CN114
Peripheral port settings
Built-in RS-232C port settings
Peripheral port settings
Peripheral port
CPM2C-CN111
CPM2C
CS1W-CN118
CPM2C
CS1W-CN114
CPM2C
RS-232C port
(D-Sub 9-pin, female)
RS-232C port
(D-Sub 9-pin, female)
Peripheral port
Setting the DIP Switches on the Front of a C200HX/HG/HE(-Z)E, CQM1,
CQM1H
When using a C200HX/HG/HE(-Z)E, CQM1, or CQM1H, the DIP switches on the front panel must be set as shown below in order to make the settings in the PLC Setup (data memory) effective.
58
Connecting to the RS-232C Port at the Host
C200HX/HG/HE(-Z)E
CQM1 CQM1H
Section 2-6
RS-232C port communications condition setting
Set pin 5 to OFF to make the settings made in
PLC Setup effective.
Setting the Switches of a CPM2A
When using a CPM2A, the switches on the front panel must be set as shown below in order to make the PLC Setup settings effective.
Set the Communications switch to OFF (down position).
Setting the Switches of a CPM2C
When using a CPM2C, the switches on the front panel must be set as shown below in order to make the PLC Setup settings effective.
The settings for SW1 and SW2 depend upon the usage of the peripheral port and RS-232C port.
• Connecting PT to peripheral port
• Connecting PT to built-in RS-232C port
(A device that requires non-standard communications settings is connected to the peripheral port.)
SW1: OFF
SW2: ON
• Connecting PT to built-in RS-232C port
(A Programming Console is connected to the peripheral port.)
SW1: OFF
SW2: OFF
Setting the Switches on an RS-232C Adapter
When using a CPM1-CIF01 RS-232C Adapter, set the mode switch as shown in the following diagram.
CPM1-
CIF01
Set the mode setting switch to NT (lower position).
59
Connecting to the RS-232C Port at the Host
Connecting to a CVM1/CV (-EV @)
Set the DIP switch on the front panel as follows:
Section 2-6
I/O port selection (selector switch)
Set this to RS-232C.
DIP switch setting (Pin 3)
2
1
4
3
6
5
ON
OFF
↔ ON
Set Pin 3 to use NT Link
(ON, right side).
Using the 1:N NT Link
PLC Series
CS Series
CJ Series
When using a CVM1/CV-series PLC, CPU Unit execution processing (execution control 2) in the PLC Setup must be set to Simultaneous processing.
Compatible Host Units
The OMRON PLCs that can be connected using the 1:N NT Link are the CSseries (CS1G/H or CS1G/H-H), CJ-series CJ1G, C-series C200HX/HG/HE(-
Z)E, CQM1H, and SRM1 only. With the CS/CJ-series PLCs, it is possible to connect a 1:N NT Link using a CS1W-SCU21 or CJ1W-SCU41 Serial Communications Unit.
Check the model and series of the PLC as well as the model of Serial Communications Board or Unit being used before making the connections.
The hosts that can be connected to the NT20 by the 1:N NT Link using the
RS-232C ports of both Units are indicated in the table below.
CPU Units with Built-in
NT Link Function
CS1G-CPU42/43/44/45-EV1
CS1H-CPU63/64/65/66/67-EV1
CS1G-CPU42H/43H/44H/45H
CS1H-CPU63H/64H/65H/66H/67H
CJ1G-CPU44/45
CPU Units Connectable with
Communications Board or Unit
(See note 1.)
CS1G-CPU42/43/44/45-EV1
CS1H-CPU63/64/65/66/67-EV1
CS1G-CPU42H/43H/44H/45H (See note 1.)
CS1H-CPU63H/64H/65H/66H/67H
(See note 1.)
CJ1G-CPU44/45 (See note 2.)
Connectable to
CS1G
CS1H
CS1G-H
CS1H-H
CJ1G
60
Connecting to the RS-232C Port at the Host
Section 2-6
PLC Series
C Series
CPU Units with Built-in
NT Link Function
C200HE-CPU42-(Z)E
C200HG-CPU43-(Z)E
C200HG-CPU63-(Z)E
C200HX-CPU44-(Z)E
C200HX-CPU64-(Z)E
C200HX-CPU65-ZE
C200HX-CPU85-ZE
---
CPU Units Connectable with
Communications Board or Unit
(See note 1.)
C200HE-CPU32-(Z)E (See note 3.)
C200HE-CPU42-(Z)E (See note 3.)
C200HG-CPU33-(Z)E (See note 3.)
C200HG-CPU43-(Z)E (See note 3.)
C200HG-CPU53-(Z)E (See note 3.)
C200HG-CPU63-(Z)E (See note 3.)
C200HX-CPU34-(Z)E (See note 3.)
C200HX-CPU44-(Z)E (See note 3.)
C200HX-CPU54-(Z)E (See note 3.)
C200HX-CPU64-(Z)E (See note 3.)
C200HX-CPU65-ZE (See note 3.)
C200HX-CPU85-ZE (See note 3.)
CQM1H-CPU51 (See note 4.)
CQM1H-CPU61 (See note 4.)
---
Connectable to
C200HE (-Z)E
C200HG (-Z)E
C200HX (-Z)E
CQM1H
SRM1 CompoBus/S
Master Control
Unit
SRM1-C02-V2
Note
(1) A CS1W-SCB21 or CS1W-SCB41 Serial Communications Board or
CS1W-SCU21 Serial Communications Unit is required.
(2) A CJ1W-SCU41 Serial Communications Unit is required.
(3) One of the following Communications Boards is required:
C200HW-COM02/COM04/COM05/COM06 (-EV1)
(4) A CQM1H-SCB41 Serial Communications Board is required.
(5) The -V1 versions of CS-series PLCs and CJ-series PLCs support the high-speed 1:N NT Link as well as the standard 1:N NT Link. Furthermore, the high-speed 1:N NT Link can be used in earlier versions of CSseries PLCs by installing a new version of Serial Communications Board
or Unit. For details, refer to Using the High-speed 1:N NT Links
Settings at the Host
The Settings required for each Unit are described below.
Connecting a C200HX/HG/HE(-Z)E, CQM1H, or SRM1
PLC Setup Settings
Write the PLC Setup (in the DM Area) settings directly from a Programming
Device (e.g., SYSMAC Support Software) according to the host model and port.
Connection to
C200HX/HG/HE(-Z)E, SRM1
Built-in RS-232C port
C200HX/HG/HE(-Z)E
Communications Board port A
(See note 1.)
CQM1H port 1 (See note 2.)
C200HX/HG/HE(-Z)E
Communications Board port B
(See note 1.)
Word Writing
Value
DM6645 5 @00
DM6555
Setting
Use 1:N NT Link
@ = largest unit number of the connected PTs (1 to 7)
(See note 3.)
DM6550
Note
(1) RS-232C port on the Communications Board
(2) RS-232C port on the Serial Communications Board
61
Connecting to the RS-232C Port at the Host
Section 2-6
(3) When using a C200HE (-Z)E, the maximum PT unit number is 3.
Refer to the PLC’s operation manual for details on changing PLC Setup settings.
Setting the DIP Switches of a C200HX/HG/HE(-Z)E
When using a C200HX/HG/HE(-Z)E, the DIP switches on the front panel must be set as shown below in order to make the settings in the PLC Setup (in the
DM Area) effective.
RS-232C port communications condition setting
Set pin 5 to OFF to make the settings made in
PLC Setup effective.
Note
Connecting to CS/CJ-series CPU Units
CS-series CPU Unit: CS1G/H-CPU @@-E(V1), CS1G/H-CPU@@H
CJ-series CPU Unit: CJ1G-CPU @@
PLC Setup
When connecting to a CS/CJ-series CPU Unit, set the following communications conditions for the PLC Setup, according to the communications port to be used.
When using the built-in RS-232C port of a CS1G/H, CS1G/H-H, or CJ1G
Word
CIO 160
CIO 161
CIO 166
Value
8200
0000 to 0009 (See note.)
000
@
Settings
1:N NT Link mode
Communications baud rate (standard)
@ = The largest model number of the connected PT (0 – 7)
Set any value between 0000 and 0009 Hex for the communications baud rate.
The same baud rate will be used regardless of the value as long as it is between 0000 and 0009 Hex.
Note
When using the peripheral port of a CS1G/H, CS1G/H-H, or CJ1G
Word
CIO 144
CIO 145
CIO 150
Value
8200
0000 to 0009 (See note.)
000 @
Settings
1:N NT Link mode
Communications baud rate (standard)
@ = The largest model number of the connected PT (0 – 7)
Set any value between 0000 and 0009 Hex for the communications baud rate.
The same baud rate will be used regardless of the value as long as it is between 0000 and 0009 Hex.
When connecting PTs with model numbers 0 and 2 to 5 to the built-in RS-
232C port, for example, set CIO 160 to 8200 Hex, CIO 161 to 0000 Hex and set CIO166 to 0005 Hex.
62
Connecting to the RS-232C Port at the Host
Section 2-6
Peripheral port
This is used mainly for connection to the
Programming Device.
(This also supports the
RS-232C Unit connection.)
RS-232C port
This is used mainly for connection to the RS-
232C Unit.
(This also supports a
CX-Programmer connection.)
Either set PLC Setup directly from a Programming Device (Programming Console), or transmit the PLC Setup made at a Programming Device (CX-Programmer) to the CPU Unit. For details on PLC Setup ,refer to the SYSMAC
CS Series Operation Manual (W339-E1@) or SYSMAC CJ Series Operation
Manual (W393-E1@).
Setting the Front Switches
Set pins 4 and 5 of the CPU Unit DIP switch according to the port that the
NT20 is connected to.
CS1G/H, CS1G/H-H
RUN
ERR/ALM
INH
PRPHL/COMM
SYSMAC CS1G
PROGRAMMABLE CONTROLLER
CPU42
MCPWR
OPEN
OPEN
BUSY
DIP switches (inside the battery storage)
• Set pin 4 to ON (establishing communications in accordance with PLC Setup) when connecting the NT20 to the peripheral port.
• Set pin 5 to OFF (establishing communications in accordance with PLC Setup) when connecting the NT20 to the RS-232C port.
PERIPHERAL
PORT
CJ1G
DIP switches (inside the battery storage)
• Set pin 4 to ON (establishing communications in accordance with PLC Setup) when connecting the
NT20 to the peripheral port.
• Set pin 5 to OFF (establishing communications in accordance with PLC Setup) when connecting the
NT20 to the RS-232C port.
Peripheral port
This is used mainly for connection to the
Programming Device.
(This also supports the
RS-232C Unit connection.)
RS-232C port
This is used mainly for connection to the RS-232C
Unit. (This also supports a CX-Programmer connection.)
Connecting to CS-series Serial Communications Board
Serial Communications Board equipped with a RS-232C port for CS-series
CPU Units: CS1W-SCB41/21
63
Connecting to the RS-232C Port at the Host
Note
Section 2-6
CPU Unit Allocation DM Area Settings
Setting is written from the Programming Device (a Programming Console or
CX-Programmer) directly into the allocated DM Area (PLC Setup) of the CPU
Unit. After the setting is written, it becomes effective by turning the power ON, restarting the Unit, restarting the communications port, or execution of the
STUP instruction.
The following table shows the words allocated in the DM Area and the settings.
Allocated DM word
Port 1 Port 2
DM32000
DM32001
DM32010
DM32011
DM32006 DM32016
Value Settings
8200
0000 to 0009 (See note.)
000
@
1:N NT Link mode
Communications baud rate (standard)
@ = The largest model number of the connected PT (0 - 7)
Set any value between 0000 and 0009 Hex for the communications baud rate.
The same baud rate will be used regardless of the value as long as it is between 0000 and 0009 Hex.
For example, when connecting PTs with model numbers 3, 4, 5, and 6 to port
1, set DM 32000 to 8200 Hex, DM 32001 to 0000 Hex, and DM 32006 to 0006
Hex.
Connecting to CS/CJ-series Serial Communications Unit
A CS-series Rack-mounted Unit: CS1W-SCU21
CJ-series: CJ1W-SCU41 (Port 2 is an RS-232C port.)
Setting the Front Switches
Set the unit number of the Serial Communications Unit by using the rotary switch located on the front panel. Set each switch with a flat blade screwdriver so that the values or symbols in the setting value window agree with the following.
CS1W-SCU21
SCU21
RUN
ERC
SD1
RD1
UNIT
No.
32
10
5
6
7 8
FE
C
9
A
RDY
ERH
SD2
RD2
Set the unit number to 0 through F so that it will not duplicate the numbers used in other Units.
CJ1W-SCU41
Set the unit number to 0 through F so that it will not duplicate the numbers used in other Units.
64
Connecting to the RS-232C Port at the Host
Section 2-6
Allocation DM Area Settings for CPU Unit
Setting is written from the Programming Device (a Programming Console or
CX-Programmer) directly into the allocated DM Area (PLC Setup) of the CPU
Unit. After the setting is written, it becomes effective by turning the power ON, restarting the Unit, restarting the communications port, or execution of the
STUP instruction.
The following table shows the words allocated in the DM Area and the settings.
m = DM30000 + (100
× unit number)
Value Settings
m m+1
Allocated DM word
Port 1 Port 2
m+10 m+11 m+6 m+16
8200
0000 to 0009 (See note.)
000
@
1:N NT Link mode
Communications baud rate (standard)
@ = The largest model number of the connected PT (0 - 7)
Using the High-speed 1:N
NT Links
Note
Set any value between 0000 and 0009 Hex for the communications baud rate.
The same baud rate will be used regardless of the value as long as it is between 0000 and 0009 Hex.
Compatible Host Units
Only the -V1 versions of the CS1-series CS1G/H, CS1-H-series CS1G/H-H, and CJ-series CJ1G PLCs support the high-speed 1:N NT Links directly.
Other CS/CJ-series PLCs can use the high-speed 1:N NT Links indirectly through a CS1W-SCU21 or CJ1W-SCU41 Serial Communications Unit. (If a
Serial Communications Unit is used, even CS1-series Units without the “-V1” suffix can be connected via high-speed 1:N NT Links.)
Be sure to check the model number of the PLC and Serial Communications
Board/Unit before trying to establish the high-speed 1:N NT Links.
The following table shows which CS1-series PLCs can be connected to an
NT20 with the high-speed 1:N NT Links.
PLC model
CS Series
CJ Series
CPU Units with Built-in
NT Link Function
CS1G-CPU42/43/44/45-EV1 (See note 1.)
CS1H-CPU63/64/65/66/67-EV1 (See note 1.)
CS1G-CPU42H/43H/44H/45H (See note 1.)
CS1H-CPU63H/64H/65H/66H/67H (See note
1.)
CJ1G-CPU44/45
CPU Units Connectable only through a
Serial Communications Board or Unit
CS1G-CPU42/43/44/45-E(V1) (See note
2.)
CS1H-CPU63/64/65/66/67-E(V1) (See note 2.)
CS1G-CPU42H/43H/44H/45H (See note
2.)
CS1H-CPU63H/64H/65H/66H/67H (See note 2.)
Connectable models
CS1G
CS1H
CS1G-H
CS1H-H
CJ1G-CPU44/45 (See note 3.)
CJ1G
Note
(1) The direct high-speed 1:N NT Link connection is not supported by CS1series CPU Units without the -V1 suffix.
(2) A CS1W-SCB21 or CS1W-SCB41 Serial Communications Board or
CS1W-SCU21 Serial Communications Unit is required.
(3) A CJ1W-SCU41 Serial Communications Unit is required.
Settings at the Host
The Settings required for each Unit are described below.
65
Connecting to the RS-232C Port at the Host
Note
Section 2-6
Connecting CS/CJ-series CPU Units
CS-series CPU Unit model: CS1G/H-CPU @@-EV1, CS1G/H-CPU@@H
CJ-series CPU Unit model: CJ1G-CPU @@
PLC Setup
When connecting to a CS/CJ-series CPU Unit, set the following communications conditions for the PLC Setup, according to the communications port to be used.
When using the built-in RS-232C port of a CS1G/H, CS1G/H-H, or CJ1G
160
161
166
Word
8200
000A
000 @
Value Settings
1:N NT Link mode
Communications baud rate (high-speed)
@ = The largest model number of the connected PT (0 - 7)
When using the peripheral port of a CS1G/H, CS1G/H-H, or CJ1G
144
145
150
Word
8200
000A
000 @
Value Settings
1:N NT Link mode
Communications baud rate (high-speed)
@ = The largest model number of the connected PT (0 - 7)
When connecting PTs with model numbers 0, 2, 3, 4, and 5 to the built-in RS-
232C port, for example, set CIO 160 to 8200 Hex, CIO 161 to 000A Hex, and
CIO166 to 0005 Hex.
Either set PLC Setup directly from a Programming Device (Programming Console), or transmit the PLC Setup made at a Programming Device (CX-Programmer) to the CPU Unit.
For details on PLC Setup, refer to the SYSMAC CS Series Operation Manual
(W339-E1@) or SYSMAC CJ Series Operation Manual (W393-E1-@).
When using the CX-Programmer to set the high-speed 1:N NT Link, set the communications baud rate to 115,200 bps.
Setting the Front Switches
Set pins 4 and 5 of the CPU Unit DIP switch according to the port that the
NT20 is connected to.
66
Connecting to the RS-232C Port at the Host
Section 2-6
Peripheral port
This is used mainly for connection to the
Programming Device.
(This also supports connection of RS-232C devices.)
RS-232C port
This is used mainly for connection of RS-232C devices.
(This also supports the connection of CX-
Programmer.)
CS1G/H, CS1G/H-H
RUN
ERR/ALM
INH
PRPHL/COMM
SYSMAC CS1G
PROGRAMMABLE CONTROLLER
CPU42
MCPWR
OPEN
OPEN
BUSY
PERIPHERAL
PORT
DIP switches (inside the battery storage)
• Set pin 4 to ON (establishing communications in accordance with PLC Setup) when connecting the
NT20 to the peripheral port.
• Set pin 5 to OFF (establishing communications in accordance with PLC Setup) when connecting the
NT20 to the RS-232C port.
CJ1G
DIP switches (inside the battery storage)
• Set pin 4 to ON (establishing communications in accordance with PLC Setup) when connecting the NT20 to the peripheral port.
• Set pin 5 to OFF (establishing communications in accordance with PLC Setup) when connecting the NT20 to the RS-232C port.
Peripheral port
This is used mainly for connection to the
Programming Device.
(This also supports connection of RS-232C devices.)
RS-232C port
This is used mainly for connection of
RS-232C devices. (This also supports the connection of CX-Programmer.)
Note
Connecting to a CS-series Serial Communications Board
Serial Communications Board equipped with a RS-232C port for CS-series
CPU Units: CS1W-SCB41/21
Serial Communications Boards and Serial Communications Units with lot number 991220 (12/20/99) and later support the high-speed 1:N NT Link.
Boards and Units with earlier lot numbers cannot be used.
CPU Unit Allocation DM Area Settings
Setting is written from the Programming Device (a Programming Console or
CX-Programmer) directly into the allocated DM Area (PLC Setup) of the CPU
Unit. After the setting is written, it becomes effective by turning the power ON, restarting the Unit, restarting the communications port, or execution of the
STUP instruction.
67
Connecting to the RS-232C Port at the Host
Note
Section 2-6
The following table shows the words allocated in the DM Area and the settings.
Value Settings Allocated DM word
Port 1 Port 2
DM32000
DM32001
DM32006
DM32010
DM32011
DM32016
8200
000A
000 @
1:N NT Link mode
Communications baud rate (high-speed)
@ = The largest model number of the connected PT (0 - 7)
For example, when connecting PTs with model numbers 3, 4, 5, and 6 to port
1, set DM 32000 to 8200 Hex, DM 32001 to 000A Hex, and DM 32006 to 0006
Hex.
Connecting to a CS/CJ-series Serial Communications Unit
A CS-series Rack-mounted Unit: CS1W-SCU21
CJ-series: CJ1W-SCU41 (Port 2 is an RS-232C port.)
Serial Communications Boards and Serial Communications Units with lot number 991220 (12/20/99) and later support the high-speed 1:N NT Link.
Boards and Units with earlier lot numbers cannot be used.
Setting the Front Switches
Set the unit number of the Serial Communications Unit by using the rotary switch located on the front panel. Set each switch with a flat blade screwdriver so that the values or symbols in the setting value window agree with the following.
CS1W-SCU21
SCU21
RUN
ERC
SD1
RD1
UNIT
No.
32
10
5
6
7 8
FE
C
9
A
RDY
ERH
SD2
RD2
Set the unit number to 0 through F so that it will not duplicate the numbers used in other Units.
CJ1W-SCU41
Set the unit number to 0 through F so that it will not duplicate the numbers used in other Units.
Allocation DM Area Settings for CPU Unit
Setting is written from the Programming Device (a Programming Console or
CX-Programmer) directly into the allocated DM Area (PLC Setup) of the CPU
Unit. After the setting is written, it becomes effective by turning the power ON, restarting the Unit, restarting the communications port, or execution of the
STUP instruction.
The following table shows the words allocated in the DM Area and the settings.
Word m = DM30000 + 100
× unit number
Value Settings
m
Allocated DM word
Port 1 Port 2
m+10 8200 1:N NT Link mode
68
Connecting to the RS-232C Port at the Host
Section 2-6
m+1 m+6
Allocated DM word
Port 1 Port 2
m+11 m+16
Value
000A
000 @
Settings
Communications baud rate (high-speed)
@ = The largest model number of the connected PT (0 - 7)
2-6-2 Connecting Directly between RS-232C Ports
The method for connection between the RS-232C ports of the NT20 and the host is described here.
Recommended Connector Cable
When making the connector cable, as far as possible use the recommended connectors, connector hoods, and cables indicated in the table below. Some
Units come supplied with one connector and one connector hood.
Check the required components and prepare them in advance.
Name Model
Connector XM2A-0901
XM24-2501
Connector hood
XM2S-0911
Remarks
9-pin
Made by OMRON
25-pin
Made by OMRON
9-pin
Made by OMRON
XM2S-0913 9-pin
Made by OMRON
XM2S-0911-E 9-pin
Made by OMRON
Delivered with
CS-series CS1G/CS1H,
CS1G-H/CS1H-H
CJ-series CJ1G
C-series CQM1, C200HS,
C200HX/HG/HE(-Z)E,
CVM1/CV-series CPU
Units
CV500-LK201
CV500-LK201
C200H-LK201-EV1
C-series CQM1, C200HS,
C200HX/HG/HE-(Z)E,
CVM1/CV-series CPU
Units
CV500-LK201
---
CS-series CS1G/CS1H,
CS1G-H/CS1H-H
CJ-series CJ1G
Note
Cable
XM2S-2511
AWG28
×5P
IFVV-SB
CO-MA-VV-SB
5P
×28AWG
25-pin
Made by OMRON
Multi-core shielded cable
Made by Fujikura, Ltd.
Multi-core shielded cable
Made by Hitachi Cable,
Ltd.
CV500-LK201
C200H-LK201-EV1
---
---
After connecting a communications cable, always secure it with the screws.
Otherwise the cable may disconnect, causing operation to fail.
69
Connecting to the RS-232C Port at the Host
Wiring for a Host Link Unit
(25-pin) Connection
1
5
Note
Note
Section 2-6
OMRON Cables with Connectors
The OMRON cables listed below can be used when connecting with a method other than the RS-232C communications method.
Model
XW2Z-200S
XW2Z-500S
XW2Z-200T
XW2Z-500T
2 m
5 m
2 m
5 m
Cable Length Connector Specification
9-pin
⇔ 25 pin
9-pin
⇔ 9-pin
The OMRON cable listed below can be used when connecting to a personal computer using RS-232C communications.
Model
XW2Z-S002 2 m
Cable Length Connector Specification
9-pin
⇔ 9 pin
The cable’s tensile load is 30 N. Do not subject it to loads greater than this.
Otherwise a discontinuity may occur, causing operation to fail.
Applicable Units: C200H-LK201-EV1
CV500-LK201 (communications port 1)
Compatible cables with attached connectors:
XW2Z-200S (9-pin
⇔ 25-pin, 2 m)
XW2Z-500S (9-pin
⇔ 25-pin, 5 m)
CVM1/CV-series Host Link Units (CV500-LK201) have two types of connector; a 25-pin connector (communications port 1), and a 9-pin connector (communications port 2). When using communications port 2, refer to Wiring for
Other Connections (Other Than the Memory Link Method) below.
1 14
6
9
NT20
RS-232C interface
Abbreviation
FG
Pin number
Connector hood
1
Shield
2
SD
RD
RS
CS
+5V
3
4
5
5G
8
9
6
7
(9-pin type)
PLC (Host Link Unit)
(See note.)
Pin number
Connector hood
2
Abbreviation
FG
SD
3
4
5
RD
RS
CS
RS-232C interface
6
7
8
-
5G
-
-
-
-
-
-
-
-
ER
(25-pin type)
13 25
For Units that have a CTS setting selector switch, RS and CS do not have to be shorted if this switch is set to 0 V.
Wiring for Other
Connections
Applicable Units:
CV500-LK201 (communications port 2)
CS1W-SCU21 CJ1W-SCU41
CPM1-10CDR@
CPM1-30CDR-
@
CPM1-20CDR@
CPM1A-10CD @-@
CPM1A-30CD @-@
CPM2A-30CD @-@
CPM2A-60CD @-@
CPM1A-20CD
CPM1A-40CD
CPM2A-40CD
@-@
@-@
@-@
CPM2C-10 @@@@@@-@ CPM2C-20 @@@@@@-@
70
Connecting to the RS-232C Port at the Host
1
5
Note
Section 2-6
CQM1-CPU21-E
CQM1-CPU41-EV1
CQM1-CPU43-EV1
CQM1H-CPU11
CQM1H-CPU51
CS1G-CPU42-E(V1)
CS1G-CPU44-E(V1)
CS1H-CPU63-E(V1)
CS1H-CPU65-E(V1)
CS1H-CPU67-E(V1)
CS1G-CPU42H
CS1G-CPU44H
CS1H-CPU63H
CS1H-CPU65H
CS1H-CPU67H
CJ1G-CPU44
C200HS-CPU21-E, -EC
C200HS-CPU31-E
C200HE-CPU32-(Z)E
C200HG-CPU33-(Z)E
C200HG-CPU53-(Z)E
C200HX-CPU34-(Z)E
C200HX-CPU54-(Z)E
C200HX-CPU65-ZE
CVM1-CPU01-EV2
CVM1-CPU21-EV2
SRM1-C02-V2
CQM1-CPU42-EV1
CQM1-CPU44-EV1
CQM1H-CPU21
CQM1H-CPU61
CS1G-CPU43-E(V1)
CS1G-CPU45-E(V1)
CS1H-CPU64-E(V1)
CS1H-CPU66-E(V1)
CS1G-CPU43H
CS1G-CPU45H
CS1H-CPU64H
CS1H-CPU66H
CJ1G-CPU45
C200HS-CPU23-E
C200HS-CPU33-E
C200HE-CPU42-(Z)E
C200HG-CPU43-(Z)E
C200HG-CPU63-(Z)E
C200HX-CPU44-(Z)E
C200HX-CPU64-(Z)E
C200HX-CPU85-ZE
CVM1-CPU11-EV2
Compatible cables with attached connectors:
XW2Z-200T (9-pin
⇔ 9-pin, 2 m)
XW2Z-500T (9-pin
⇔ 9-pin, 5 m)
CPU Units of CVM1/CV-series PLCs without the suffix -EV @ cannot be connected by any connection method.
6
1
6
9
NT20
RS-232C interface
Abbreviation
FG
-
Pin number
Connector hood
1
SD 2
RD
RS
CS
+5V
-
-
SG
3
4
5
6
7
8
9
(9-pin type)
PLC
Shield
(See note.)
Pin number
Connector hood
Abbreviation
FG
2 SD
3
4
5
RD
RS
CS
-
8
9
6
7
-
-
SG
RS-232C interface
(9-pin type)
5
9
For Units that have a CTS setting selector switch, RS and CS do not have to be shorted if this switch is set to 0 V.
Wiring for a RS-232C
Connection
Compatible cables with attached connectors:
XW2Z-S002 (9-pin
⇔9-pin, 2 m)
Prepare the adapter cable while referring to the following diagram.
71
Connecting to the RS-232C Port at the Host
1
5
6
9
RS-232C interface
NT20
Abbreviation
FG
-
Pin number
Connector hood
1
2
+5V
-
-
SG
SD
RD
RS
CS
8
9
6
7
3
4
5
(9-pin type)
Shield
PLC
Abbreviation
Connector hood
SD
RD
RS-232C interface
RS
CS
SG
Section 2-6
72
Communicating with the PLC Using C200H Direct Communications
Section 2-7
2-7 Communicating with the PLC Using C200H Direct
Communications
Connect an NT20-ST121-E and PLC made by OMRON with an I/O cable.
2-7-1 Applicable PLC Units
Before making the connection, check the series and model of the PLC to which the connection is to be made. A list of the PLCs that can be connected to an NT20 using C200H direct communications is presented below.
CPU Unit
C20H/C28HC40H/C60H C @@H
C200H-CPU01-E C200H
C200H-CPU03-E
Model Name
C200H-CPU11-E
C200H-CPU21-E
C200H-CPU23-E
C200H-CPU31-E
C200HS-CPU01-E
C200HS-CPU03-E
C200HS-CPU21-E
C200HS-CPU23-E
C200HS
C200HS-CPU31-E
C200HS-CPU33-E
C200HE-CPU11-E
C200HE-CPU32-E
C200HE-CPU42-E
C200HG-CPU33-E
C200HG-CPU43-E
C200HG-CPU53-E
C200HG-CPU63-E
C200HX-CPU34-E
C200HX-CPU44-E
C200HX-CPU54-E
C200HX-CPU64-E
C200HE
C200HG
C200HX
!Caution With systems in which the user program operates according to the PLC cycle time, since there is some fluctuation in the PLC cycle time, the system operation may not be consistent, and this should be born in mind when designing the system.
2-7-2 Connection Method
The NT20 PT is connected to the PLC using the NT20-IF001 and NT600M-
LB122-V1.
The connection conditions are different for C200H/HS, C200HX/HG/HE and
C @@H.
73
Communicating with the PLC Using C200H Direct Communications
Mounting the NT20-IF001
Section 2-7
1.
As shown in the following diagram, connect the NT20 connector on the back of the NT20-IF001 to the expansion interface connector on the NT20
PT.
2.
After connecting the connector, secure the NT20-IF001 with the two screws. The tightening torque is 0.6 N
• m.
3.
As shown in the following diagram, hold the Interface Unit with the notch on the left and press the Interface Unit into the NT20-IF001 until it clicks into place.
Notch
4.
Connect the ground screw on the NT20-IF001 to the NT20 using a short wire (100 mm max.), and connect the ground through the NC terminal.
Reference:
The NC terminal on the NT20 also serves as a functional ground. Do not connect this terminal when using only the NT20 (grounding is not required).
!Caution Always turn off the power at the PLC and PT before connecting the C200H interface cable. Otherwise the system may operate unpredictably.
!Caution Make sure that the power supply to the PT is OFF before connecting or disconnecting the Interface Unit. After mounting an NT20-IF001, be sure to tighten its two screws. Do not touch the PCB (printed circuit board) with bare hands.
!Caution After connecting the communications cable, always secure it with the screws.
Otherwise the cable may disconnect, causing operation to fail.
74
Communicating with the PLC Using C200H Direct Communications
Section 2-7
Connection to C200H/
C200HS and C200HX/HG/
HE
I/O Connecting Cable
Use the following models of I/O Connecting Cable.
For connecting C200H/HS/HE/HG/HX
For connecting C @@H
Model
C200H-CN311
NT20M-CNP711
C200H-CN711
NT20M-CNP221
C200H-CN221
NT20M-CNP521
C200H-CN521
NT20M-CNP131
C200H-CN131
C20H-CN312
NT20M-CNP712
C20H-CN712
NT20M-CNP222
C20H-CN222
Cable Length (L)
30 cm
70 cm
2 m
5 m
10 m
30 cm
70 cm
2 m
Note
The C200H interface connector of NT20M-CNP @@@ has been downsized.
!Caution Keep the total length of I/O cables used within 12 m (6 m for C
@@H).
!Caution The cable's tensile load is 30 N. Do not subject it to loads greater than this.
Otherwise a discontinuity may occur, causing operation to fail.
Reference:
If a C200H-CN
@@@
or C20H-CN
@@@
is used as the I/O Connecting Cable, the connector will project beyond the bottom face of the NT20.
If the I/O cable is passed through a hole or other opening, the diameter of the hole or opening must be at least 53 mm
φ. Removing the top cover reduces this requirement to 33 mm
φ or larger. During installation, this cover must be replaced before securing the PT.
Connect the CPU Rack or Expansion I/O Rack with an I/O cable. The following restrictions apply when making this connection.
• A maximum of one CPU Rack and one Expansion I/O Rack can be connected. Connection to two Expansion I/O Racks is not possible.
• Connection to a Remote Rack is not possible.
75
Communicating with the PLC Using C200H Direct Communications
Section 2-7
• There is only one C200H interface unit interface connector. This means that it is not possible to connect an NT20 between a CPU Rack and an
Expansion I/O Rack. It must be the final connection in the system.
CPU Rack
Expansion I/O Rack
Expansion I/O Cable
(C200H-CN @@1)
1 Rack max.
(Rear face of NT20)
Connection to C
@@
H
Expansion I/O Cable
(NT20M-CNP
@@1/
C200H-CN @@1)
Host interface connector
Connect the CPU Unit with an I/O Connecting Cable. The following restrictions apply when making this connection.
• A maximum of one CPU Unit can be connected.
• Up to two I/O Units can be connected for the one CPU unit, but Expansion
I/O Units cannot be connected.
76
Communicating with the PLC Using C200H Direct Communications
Section 2-7
• It is not possible to connect a C @@H I/O Unit after the NT20. It must be the final connection in the system.
CPU Unit
I/O Connecting Cable
(C20H-CN @@2)
I/O Unit
I/O Connecting Cable
(C20H-CN
@@2)
I/O Unit
2 Units max.
(Rear face of NT20)
I/O Connecting Cable
(NT20M-CNP @@2
/C20H-CN
Host interface connector
Note
When connecting a C
@@H, always install a noise filter.
1.
Insert the noise filter in the power supply line of the C @@H.
2.
Make the distance between the noise filter and the C @@H as short as possible and separate it from the power supply line.
3.
Install the noise filter case on the FG face.
4.
Use a ZGB2202-01U (manufactured by TDK) or equivalent as the noise filter.
Noise filter
1 4
+
+24 V IN OUT 24 V
2 3
–
2-7-3 Turning the Power ON/OFF When Using C200H Direct
Communications
The NT20-ST121-E functions as an expansion I/O unit of the PLC. Use the following procedure to turn the power ON and OFF.
Power ON
!Caution Depending on the method used to turn the power ON and OFF, the entire system may stop. Follow the procedure described below to turn the power ON and OFF.
Turn the power ON as follows:
Turn ON the power to the NT20.
“Connecting to Host” is displayed on the NT20 screen.
77
Communicating with the PLC Using C200H Direct Communications
Power OFF
Note
Note
Section 2-7
↓
Turn ON the power to the PLC.
After “Connecting to Host” has been displayed for approximately 1 second, normal operation starts.
(1) If the power to the PLC is turned ON first, the CPU Unit of the PLC is subjected to a system reset, making operations such as programming console impossible. Then, when the power to the NT20 is turned ON,
“Connecting to Host” is displayed on the NT20 screen for approximately
1 second, after which normal operation starts.
(2) If the I/O Connecting Cable is disconnected during system operation, an
I/O bus error occurs at the PLC and operation stops. If this happens, connect the I/O Connecting Cable and cancel the error.
Turn the power OFF as follows:
Turn OFF the power supplies to the PLC and NT20 simultaneously.
The next time the power is turned ON, the NT20 displays the screen that was displayed when the power was turned OFF.
If the power to the NT20 is turned OFF first, the CPU Unit of the PLC is subjected to a system reset, making operations such as programming console impossible.
Turn OFF the system temporarily before replacing the NT20 (when a fault occurs, for example). If the power to the NT20 only is turned OFF, the system stops immediately and this could cause an accident or damage machinery.
78
Host Connections by RS-232C (NT20-ST128)
Section 2-8
2-8 Host Connections by RS-232C (NT20-ST128)
Connect the NT20-ST128 with an RS-232C Interface Unit installed to the host computer with an RS-232C cable.
An RS-232C connection allows a single NT20 to be connected to the host.
A computer or other control device with a built-in RS-232C interface is a suitable host for connection to the NT20.
2-8-1 Host Computer Communications Settings
Set the host communications conditions according to the following table.
Item
Baud rate
Data bits
Stop bits
Parity Even, Odd, None
Flow control RS/CS control
XON/XOFF control
None
Setting
Set to the same baud rate as the NT20: 2400, 4800, 9600, 19200
7 bits/8 bits
1 bit/2 bits
Note
Set the same communications conditions at the NT20 and Host.
Refer to the appropriate instruction manuals for the method of setting the Host communications conditions.
Set to the maximum baud rate supported by both the NT20 and Host.
The communications condition settings of the NT20-ST128 are set with the
RS-232C communications conditions memory switches.
2-8-2 Connector Pin Arrangement
The RS-232C connection between the NT20 and Host is described below.
NT20 Interface Unit
The connector specifications are described below.
Electrical characteristics: Conforms to EIA RS-232C specifications.
Signal direction: Signal input and output are relative to the host computer.
1 6
5 9
Connector pin #
4
5
2
3
Signal name
Send data
Receive data
Request to send
Clear to send
Abbreviation
SD (TXD)
RD (RXD)
RS (RTS)
CS (CTS)
→
←
→
←
Signal direction
NT20
← → Host
79
Host Connections by RS-232C (NT20-ST128)
Section 2-8
Connecting to the Host
Computer
Note
Connector pin #
6
9
Signal name
+5 V output, 150 mA max.
Signal ground
Abbreviation
+5 V
SG (GND)
→
Signal direction
NT20
← → Host
---
Note
Unlisted pins are not used.
For cable parts and the wiring method, refer to Appendix C Transporting and
Use a cable that is compatible with the RS-232C connector of the host to connect the NT20 and the host (see the example in the figure below).
In the example shown here, the cable connects the 9-pin connector of the
NT20 and 25-pin connector of the host. If the host has a 9-pin RS-232C connector, use an RS-232C cable with 9-pin connectors at both ends.
NT20
9-pin connector
Host Interface connector
(RS-232C, 9-pin type)
RS-232C cable
25-pin connector
!Caution When making the connection, turn OFF the power to the NT20 and PLC before disconnecting or connecting any connector.
!Caution After connecting the communications cable, always secure it with the screws.
Otherwise the cable may disconnect, causing operation to fail.
Note
If using the +5 V supply of pin No.6, check first that the equipment that is to receive the supply has a current capacity no greater than 150 mA. The +5 V output of the NT20 is +5 V DC
±5%, 150 mA max.
Do not use both port’s +5 V output at the same time.
80
Download
Advertisement
Key features
Downsized body
Construction best suited to the FA environment
A Host Link I/F Unit, Screen Data Memory, and a System ROM Are All Incorporated
Touch Switch Operation
Compatibility with NT20M/NT20S
Character display
Figure display
Memory data display
Bar graph display
Lamp display
Frequently asked questions
The NT20 is a programmable terminal used to display and transmit information in an FA site. It can be easily installed and used.
The NT20 has a downsized body, is built with construction best suited to the FA environment, incorporates a Host Link I/F Unit, Screen Data Memory, and a System ROM, supports Touch Switch Operation, and is compatible with NT20M/NT20S.
The NT20 supports Host Link (direct) and NT Link communications methods. The NT20-ST128 also supports RS-232C communications.