SECTION 3 System Menu Operation. Omron NT 600M-LB122-V1, NT 20M-DT121-V2, NT 20-IF001, NT 20-ST128, NT 20, NT 20M, NT 20-ST122-V1, NT 20-ST121-EV3, NT 20-ST121-E, NT 20S
Below you will find brief information for Programmable Terminal NT NT20, Programmable Terminal NT NT20S, Programmable Terminal NT NT20M. The NT20 is a programmable terminal used to display and transmit information in an FA site. It can be easily installed and used. NT20, NT20S and NT20M support features and functionality to display, receive data from a host and send data to a host. It also gives the operation examples and characteristics of the NT20.
Advertisement
Advertisement
SECTION 3
System Menu Operation
This section describes the operation of the System Menu focusing on the procedure to start up the NT20. Functions which will be convenient to use the NT20 and those which are useful for the system maintenance are also explained here.
3-1 Operation Flow by the System Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2-1 Changing the System Settings or Screen Data . . . . . . . . . . . . . . . . .
3-3 Operation Modes and the System Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3-1 System Menu and the Operation Modes. . . . . . . . . . . . . . . . . . . . . .
3-3-3 Operations with the System Menu . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-1 Initialization by Using the System Menu . . . . . . . . . . . . . . . . . . . . .
3-4-2 Initialization by Using the DIP Switch (Forced Initialization). . . . .
Setting the Conditions of Communications with the Host by Using the Memory Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5-1 Selecting the Host Communications Method . . . . . . . . . . . . . . . . . .
3-5-2 Selecting the Host Communications Port . . . . . . . . . . . . . . . . . . . . .
3-5-3 Selecting the Host Link Communications Speed . . . . . . . . . . . . . . .
3-5-4 Selecting the NT Link (1:N) Communications Speed . . . . . . . . . . .
3-5-5 Selecting Unit Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5-6 Selecting the Automatic Reset Function. . . . . . . . . . . . . . . . . . . . . .
3-5-7 Setting RS–232C Communications Conditions (NT20-ST128). . . .
3-8-1 Setting the Key Press Sound . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-8-3 Backlight OFF Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-8-4 Language Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-8-5 Support Tool Mode Setting (NT20-ST121-E) . . . . . . . . . . . . . . . . .
3-8-6 Lamp Bit Control (NT20-ST128). . . . . . . . . . . . . . . . . . . . . . . . . . .
3-9-2 Checking the PT Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-9-3 Checking the NT20 DIP Switch Settings . . . . . . . . . . . . . . . . . . . . .
81
Operation Flow by the System Menu
Section 3-1
3-1 Operation Flow by the System Menu
Follow the procedure below when using the NT20 for the first time or when changing the system.
Create the Screen Data
Create the screen data to be displayed on the NT20 by using the Support
Tool.
For the screen data creation, refer to the “NT Support Tool for Windows Operation Manual” (V061-E1@).
Start Up the NT20 (Display the System Menu.) (page 84)
Turn ON the power to the NT20.
When no screen data has been registered, the “SYSTEM MENU” will be displayed. If the NT20 enters the RUN mode, press appropriate touch switches to display the System Menu.
Select a System Menu and initialize the NT20 unit memory.
Memory Switch Settings (page 91)
Select the System Menu and make settings such as the communications conditions for communications with the Host by setting the memory switches.
Registering the Screen Data (page 102)
Connect the Support Tool to the NT20 and transfer the screen data from the
Support Tool to the NT20.
For the connection of the Support Tool, refer to 2-4 Connecting the NT Sup-
Starting the Operation
Connect to the PLC/Host and start the operation.
If an error has occurred during operation, check the I/Os, settings, etc. referring to this guide.
82
Starting the NT20
Section 3-2
3-2 Starting the NT20
When the NT20 is started, it will enter the RUN mode if system settings and screen data registration have been completed. If no screen data has been registered or the screen data are destroyed, the System Menu will be displayed.
Before turning ON the power, check the following DIP switch settings on the
NT20.
• SW2-3 “Switch to the System Menu enabled/disabled” is set to OFF
(enabled).
• SW2-1 “Screen data forced initialize Yes/No” is set to No (ineffective).
For the DIP switch settings of the unit, refer to the 2-1-2 Operation Status DIP
3-2-1 Changing the System Settings or Screen Data
Follow the procedure below to change the system settings or screen data contents.
Note
(1) Turn ON the power to the NT20.
The NT20 will enter the RUN mode and the start-up screen will be displayed. The start-up screen varies according to registered screen data.
(2) Press appropriate touch switches to display the System Menu, and change system settings. For the method for calling the System Menu, re-
fer to the 3-3-3 Operations with the System Menu on page 86.
(3) If the NT20 has failed to start up normally; an error message is displayed or no screen is displayed, memory needs to be initialized.
For the memory initializing procedure, refer to 3-4 Initializing Memory on page 88.
83
Operation Modes and the System Menu
Section 3-3
3-3 Operation Modes and the System Menu
The NT20 operates in either “RUN”, “Transmit”, or “Maintenance” mode. The operation modes can be changed by using the System Menu.
3-3-1 System Menu and the Operation Modes
Select an operation mode by pressing the corresponding touch switch in the
System Menu. The operation modes with respect to the System Menu are related to each other as shown below.
For the operations with the System Menu, refer to the 3-3-3 Operations with
RUN mode
The NT20 runs in this state. Controls from the
Host are enabled and various indications and
I/O operations are made.
Power ON
When system settings and screen data registration have been completed
To change system settings or screen data contents
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance mode
Transmit mode
Screen data and other data are transmitted between the NT20 and a support tool.
Maintenance mode
The NT20 maintenance operations such as memory initialize and setting check are executed.
3-3-2 Menu Tree
The System Menu allows to effect various NT20 functions by using the touch switches. The NT20’s functions with respect to the System Menu are related as shown below.
For the operations with the System Menu, refer to the 3-3-3 Operations with
84
Operation Modes and the System Menu
Section 3-3
SYSTEM MENU
Quit
Transmit Mode (page 86)
Maintenance Mode
MAINTENANCE MENU
Quit
PT Setting (page 107)
I/O Check
Init. Memory
Memory Switch
DIP-SW Status (page 109)
Note
I/O CHECK MENU
Quit
LED Check (page 105)
Buzzer (page 104)
Touch Switch (page 99)
Data Memory (page 106)
LCD Display (page 103)
Comm. Check
Host Link, NT Link, C200H
Direct Communications
COMM. CHECK MENU
Quit
Tool I/F
RS-232C (NT20-ST128)
COMM. CHECK MENU
INITIALIZE MEMORY MENU
Quit
Init. Screen (page 88)
Host Link, NT Link
MEMORY SWITCH MENU
Quit
Tool I/F (page 101)
RS-232C I/F
Comm. Type
Key Sound
Buzzer Sound
BK light Off
Tool Mode
Automatic Reset
Unit No.
Baud Rate
Comm. Port
Language
First screen
Second screen
C200H Direct Communications
MEMORY SWITCH MENU
Comm. Type
Key Sound
Buzzer Sound
BK light Off
Tool Mode
Language
Automatic Reset
RS-232C (NT20-ST128)
MEMORY SWITCH MENU
First screen
Second screen
Key Sound
Buzzer Sound
BK light Off
Tool Mode
Automatic Reset
Data Bits
Stop Bits
Partiy Check
Flow Control
Baud Rate
LMP Bit Control
Comm. Port
Lanugage
First screen
Second screen
Third screen
The unit number must be set only for 1:N NT Link communications.
85
Operation Modes and the System Menu
Section 3-3
3-3-3 Operations with the System Menu
The following gives the procedure to call the System Menu, select the menu items, and other operations with the System Menu.
Make sure that DIP SW2-3 “Switch to the System Menu enabled/disabled” is set to OFF (enabled). If the setting is ON (disabled), the System Menu will not be displayed by following the procedure given below.
Displaying the System
Menu
Press appropriate touch switches to display the System Menu as described below. The “RUN” LED goes off when the System Menu is displayed.
The NT20 display screen has four touch switches to display the System Menu in the four corners (about 9 mm x 9 mm size). Press any two of these switches at the same time to call the System Menu screen.
RUN mode
Press any two of these four corners at the same time.
[SYSTEM MENU]
Quit
Transmit Mode
Maintenance mode
Note that the touch switches used to call the System Menu are not displayed on the screen. If a touch switch displayed in a corner is pressed first, the touch switch will function and the System Menu will not be displayed. To successfully call the System Menu, first press a corner where no touch key is displayed, and then, press any other corner regardless of the presence of a touch key.
If a screen has the touch switches registered at all of the four corners, it is impossible to call the System Menu from the screen.
A “system key” function can be assigned to a touch switch. Pressing the touch switch so assigned on the screen can easily display the System Menu. For the
relationship between the system key and the touch switch, refer to the 4-7-3
System Key Functions (page 154).
86
Operation Modes and the System Menu
Selecting the Menu Items
Section 3-3
Press (touch) a menu item on the screen to select the item.
Menu items allow to make the ON/OFF selection or to call subsequent menu or screen.
Example 1
To call the “Maintenance mode menu” by pressing the “Maintenance Mode” on the System Menu screen:
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
System Menu Items
Switching from the
System Menu to the RUN
Mode
[ MAINTENANCE MENU ]
Quit DIP-SW Status
PT Setting
I/O Check
Init. Memory
Memory Switch
The System Menu items and the functions are as given below.
Quit
Menu Item Function
The System Menu screen is cleared and the NT20 will return to the RUN mode.
Transmit Mode The Transmit Mode screen will be displayed to allow the transmission of the screen data between the NT20 and the Support
Tool. For the transmission of the screen data, refer to3-6 Regis-
tering the Screen Data (page 102).
Maintenance Mode The MAINTENANCE MENU will be displayed to allow the maintenance of the NT20 system.
The NT20 will exit the System Menu and switch to the RUN mode in the cases described below.
• Selecting “Quit” in the System Menu.
• The screen (touch switches) is not pressed for over 10 seconds.
87
Initializing Memory
Section 3-4
3-4 Initializing Memory
If the NT20 is used for the first time or if the screen data is ruined and the
NT20 cannot be normally started, the memory needs to be initialized.
The memory initialization is required in the cases described below.
• When the NT20 is used for the first time or when an error message indicating that the screen data is ruined etc. when the NT20 is started.
➡
Use the “Maintenance Mode” – “Init. Memory” in the System Menu.
• When the NT20 has made a buzzer sound and the screen has disappeared during the start-up or operation.
➡
Use the NT20 DIP SW2-1 “Screen data forced initialize Yes/No”.
When an error has occurred, the error messages such as “Screen data corrupted” will be displayed. For the error messages displayed on the screen,
refer to 7-2 Responding to Displayed Error Messages.
Note
Initializing the screen data memory will erase entire screen data registered in the NT20. Make sure that there are backup copies of the screen data on floppy disks before starting the initialization.
• Data of the NT20 to Be Initialized
Screen data
System memory
Memory tables
Mark data
Direct information
3-4-1 Initialization by Using the System Menu
Initialize the screen data memory by following the procedure given below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit DIP-SW Status
PT Setting
I/O Check
Init. Memory
Memory Switch
Select “Init. Memory”.
88
Initializing Memory
[ INITIALIZE MEMORY MENU ]
Quit
Init. Screen
Section 3-4
Select “Init. Screen”.
Initialize Screen Memory?
Yes
No
Select “Yes”.
The screen data memory is initialized. During the initialization, the “Initializing” message will be displayed.
If “No” is selected, the memory initialization will be canceled and the NT20 returns to the “operation mode”.
No direct information is set!
Use the Support Tool to set the PT Control Area and PT Notify Area
Example:
Direct information is also initialized. Set the direct information with the Support
Tool.
After initialization of the screen data memory, the system enters the operation mode. At this point, nothing is displayed on the screen of the NT20. Return to the System Menu, select the Transmit Mode, and transmit the screen data from the Support Tool.
If the screen data cannot be initialized for any reason, the message “An Error
Occur Initializing Memory” is displayed.
89
Initializing Memory
Section 3-4
3-4-2 Initialization by Using the DIP Switch (Forced Initialization)
Note
Be sure to turn the power OFF before setting the NT20 DIP switch.
Set the DIP switch as follows to initialize the screen data memory.
1,2,3...
1.
Set DIP SW2-1 on the NT20 to ON and turn the power ON or reset the
NT20.
Initialize Screen Memory?
Yes
Select “Yes”.
The screen data memory is initialized. During the initialization, the “Initializing” message will be displayed.
No
Initialized the
Screen Data Memory.
Turn OFF the DIP Switch 2-1 and push the Reset Switch, then return to RUN mode.
Note
2.
Turn the NT20 power to OFF.
3.
Set NT20 DIP SW2-1 to OFF and turn the power ON.
(1) Selecting “No” will cancel the memory initialization. In either case, when changing the system settings or registering screen data, display the system menu after setting DIP switch SW2-1 to the OFF position while the
NT20 power is OFF, then switching the power back ON.
(2) The NT20 DIP SW2-1 is used to set “Screen data forced initialize Yes/
No”. Setting this to Yes selects “effective”, and No “ineffective”.
90
Setting the Conditions of Communications with the Host by Using the Memory Switches
Section 3-5
3-5 Setting the Conditions of Communications with the Host by Using the Memory Switches
The communications between the NT20 and a PLC/Host are called the host communications.
The NT20 PTs can be connected to the host using the following communications methods.
NT20-ST121-E: Host Link or NT Link (both direct connections)
NT20-ST121-E + NT20-IF001 + NT600M-LB122-V1:
C200H direct communications (direct connection)
NT20-ST128: RS-232C communications (command control)
With the NT20-ST121-E, the Host Link, 1:1 NT Link, or 1:N NT Link communications method is set using a memory switch. Other settings, such as the band rate and automatic resetting of communications, are also set with memory switches. This section describes the communications condition settings using the memory switches.
Memory Switches
The NT20 has the memory areas used to store the PLC connection method, communications conditions, system settings, etc. which can be used as the switches and called the “memory switches”. Since the memory switches use the flash memory, the stored data can be held even when the power supply is turned OFF.
If the memory switch memory is corrupted for any reason, a message will be displayed when the operating mode is changed. Press the Write touch switch and initialize the memory.
Setting Functions and the
Memory Switch Menu
The memory switches can be set easily by using the memory switch menu in the System Menu.
The following settings can be made with the memory switches. Refer to the
subsequent pages and 3-8 Various System Settings for details on each set-
ting and function.
• Host Link Method
[ MEMORY SW MENU ]
(1/2)
Comm. Type Host Link
Key Sound
Buzzer Sound
Bk light Off
OFF
OFF
None
Tool Mode NT20
• NT Link (1:1) Method
Quit
Page
WRT&
EXIT
[ MEMORY SW MENU ]
(2/2)
Automatic Reset
No
Baud Rate
Comm. Port
Language
9600bps
Port B
English
Quit
Page
WRT&
EXIT
[ MEMORY SW MENU ]
(1/2)
Comm. Type
NT Link
Key Sound
Buzzer Sound
OFF
OFF
Bk light Off
Tool Mode
None
NT20
Quit
Page
WRT&
EXIT
[ MEMORY SW MENU ]
(2/2)
Automatic Reset
No
Comm. Port
Language
Port B
English
Quit
Page
WRT&
EXIT
91
Setting the Conditions of Communications with the Host by Using the Memory Switches
• NT Link (1:N) Method
[ MEMORY SW MENU ] (1/2)
Comm. Type
NT Link 1: N
Key Sound
Buzzer Sound
OFF
OFF
Quit
Page
Bk light Off
Tool Mode
None
NT20
WRT&
EXIT
• C200H Direct Communications
[ MEMORY SW MENU ]
(1/2)
Comm. Type C200H
Key Sound
Buzzer Sound
Bk light Off
OFF
OFF
None
Tool Mode NT20S
• RS-232C (NT20-ST128)
[ MEMORY SW MENU ]
(1/3)
Key Sound
ON
Buzzer Sound
Bk light Off
ON
10 min
Tool Mode
Automatic Reset
NT20S
Yes
Quit
Page
WRT&
EXIT
Quit
Page
WRT&
EXIT
Section 3-5
[ MEMORY SW MENU ]
(2/2)
Automatic Reset
No
Unit No.
7
Comm. Speed
Comm. Port
Language
Standard
Port B
English
Quit
Page
WRT&
EXIT
[ MEMORY SW MENU ]
(2/2)
Automatic Reset
No
Language
English
Quit
Page
WRT&
EXIT
[ MEMORY SW MENU ] (2/3)
Data Bits 8 bits
1bit
Stop Bits
Parity Check
Flow Control
Baud Rate
Even
RS/CS
9600 bps
Quit
Page
WRT&
EXIT
[ MEMORY SW MENU ]
LMP Bit Control
Comm. Port
(3/3)
Enable
Port B
Language English
Quit
Page
WRT&
EXIT
92
Setting the Conditions of Communications with the Host by Using the Memory Switches
Section 3-5
3-5-1 Selecting the Host Communications Method
The NT20 can be connected to a PLC by the Host Link, the NT link, or the
C200H Direct communications. Either link can be selected by setting the
“Comm. Type” memory switch. The factory setting has been made to the
“Host link”.
Select the host communications method by the menu operation from the System Menu as described below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit DIP-SW Status
PT Setting
I/O Check
Init. Memory
Memory Switch
Select “Memory Switch”.
Note
[ MEMORY SW MENU ]
(1/2)
Quit
Comm. Type
Key Sound
Host Link
OFF
Page
Buzzer Sound
Bk light Off
Tool Mode
OFF
None
NT20S
WRT
&
EXIT
Repeatedly pressing the
“Comm. Type” touch switch causes the setting to cycle through the options “Host link”, “NT link”, “NT Link
1:N”, and “C200H” in that order.
To set and quit the menu, press the [WRT&EXIT] touch switch. To quit without setting, press [Quit].
The communications method must be selected according to the method that the connecting PLC supports.
93
Setting the Conditions of Communications with the Host by Using the Memory Switches
Section 3-5
3-5-2 Selecting the Host Communications Port
Note
There are two communications ports in NT20. Either of them can be set for communications. But Port A can be set to communications with either the host
(Host link, NT link 1:1, NT link 1:N, RS-232C) or Support Tool and Port B can only be set to communications with the host (Host link, NT link 1:1, NT link
1:N, RS-232C).
The NT20 can not communicate with both two ports at one time.
The factory setting has been made at “Port B”.
Select the host communications port by the menu operation from the System
Menu as described below. (e.g., Host Link)
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit
PT Setting
I/O Check
Init. Memory
Memory Switch
DIP-SW Status
Select “Memory Switch”.
[ MEMORY SW MENU ]
(1/2)
Comm. Type
Host Link
Key Sound
OFF
Buzzer Sound
OFF
Quit
Page
Bk light Off
Tool Mode
None
NT20S
WRT
&
EXIT
Select “Page”.
[ MEMORY SW MENU ]
(2/2)
Automatic Reset
No
Baud Rate
9600bps
Comm. Port
Port B
Quit
Page
Language
English
WRT
&
EXIT
Each time the “Comm.
Port” touch switch is pressed, the setting option alternates between “Port A” and “Port B”.
To set and quit the menu, press the [WRT&EXIT] touch switch. To quit without setting, press [Quit].
94
Setting the Conditions of Communications with the Host by Using the Memory Switches
Section 3-5
3-5-3 Selecting the Host Link Communications Speed
When using the NT20 with the host link, the baud rate of the communications with the PLC can be set. Use the “Baud Rate” switch and select 9600 bps,
19200 bps, 38400 bps, 57600 bps, or 115200 bps.
The factory setting has been made at 9600 bps.
Select the baud rate of the communications with the PLC by the menu operation from the System Menu as described below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit
PT Setting
I/O Check
Init. Memory
Memory Switch
DIP-SW Status
Select “Memory Switch”.
[ MEMORY SW MENU ]
(1/2)
Comm. Type
Host Link
Key Sound
OFF
Buzzer Sound
OFF
Quit
Page
Bk light Off
Tool Mode
None
NT20S
WRT
&
EXIT
Select “Page”.
If the host link is not selected, press the “Comm.
Type” touch switch and select “Host link”.
[ MEMORY SW MENU ]
(2/2)
Automatic Reset
No
Baud Rate
9600bps
Comm. Port
Port B
Quit
Page
Language
English
WRT
&
EXIT
Each time “Baud Rate” is pressed, the setting that is displayed will change.
To set and quit the menu, press the [WRT&EXIT] touch switch. To quit without setting, press [Quit].
95
Setting the Conditions of Communications with the Host by Using the Memory Switches
Section 3-5
3-5-4 Selecting the NT Link (1:N) Communications Speed
When using the NT20 with the NT Link (1:N), the baud rate of the communications with the PLC can be set. Use the “Comm. Speed” switch and select High or Standard.
Select the speed of the communications with the PLC by the menu operation from the System Menu as described below.
Select “Maintenance
Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit
DIP-SW Status
PT Setting
I/O Check
Init. Memory
Memory Switch
Select “Memory Switch”.
[ MEMORY SW MENU ]
(1/2)
Comm. Type
NT Link 1:N
Key Sound
OFF
Buzzer Sound
OFF
Quit
Page
Bk light Off
Tool Mode
None
NT20
WRT
&
EXIT
Select “Page”.
If the NT Link 1:N is not selected, press the “Comm.
Type” touch switch and select “NT Link 1:N”.
[ MEMORY SW MENU ]
(2/2)
Automatic Reset
Unit No.
No
7
Quit
Page
Comm. Speed
Comm. Port
Language
Standard
Port B
English
WRT
&
EXIT
Each time the “Comm.
Speed” touch switch is pressed, the setting option alternates between “High” and “Standard”.
To set and quit the menu, press the [WRT&EXIT] touch switch. To quit without setting, press [Quit].
96
Setting the Conditions of Communications with the Host by Using the Memory Switches
Section 3-5
3-5-5 Selecting Unit Numbers
When using NT20 with the NT link (1:N) communications method, set unit numbers.
When using NT link (1:N), unit numbers are used to identify each of the multiple PTs connected to a single PLC port. Set a different unit number for each of the PTs connected to the port.
The unit numbers that can be set differ according to the type of host PLC as follows.
C200HE: Unit Nos. 0 to 3
C200HG, C200HX: Unit Nos. 0 to 7
Set the unit numbers by following the menu operation from the System Menu described below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit
PT Setting
I/O Check
Init. Memory
Memory Switch
DIP-SW Status
Select “Memory Switch”.
[ MEMORY SW MENU ]
(1/2) Quit
Comm. Type
NT Link 1:N
Key Sound
OFF
Page
Buzzer Sound
OFF
Bk light Off
Tool Mode
None
NT20S
WRT
&
EXIT
Press the “Comm Type” touch switch to select “NT link (1:N)”.
Select “Page”.
97
Setting the Conditions of Communications with the Host by Using the Memory Switches
Section 3-5
[ MEMORY SW MENU ]
(2/2)
Automatic Reset
No
Unit No.
Comm. Speed
7
Standard
Quit
Page
Comm. Port
Language
Port B
English
WRT
&
EXIT
Repeatedly pressing the
“Unit No.” touch switch cycles through the numbers that can be set.
To set and quit the menu, press the [WRT & EXIT] touch switch. To quit without setting, press [Quit]. The run mode will be established.
3-5-6 Selecting the Automatic Reset Function
The “Automatic Reset” memory switch is used to set whether or not the communications are automatically reset after the occurrence of a communications error.
The factory setting has been made at “No”.
Select the baud rate of the communications with the PLC by the menu operation from the System Menu as described below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit DIP-SW Status
PT Setting
I/O Check
Init. Memory
Memory Switch
Select “Memory Switch”.
[ MEMORY SW MENU ]
(1/2)
Comm. Type
Host Link
Key Sound
OFF
Quit
Page
Buzzer Sound
OFF
Bk light Off
Tool Mode
None
NT20S
WRT
&
EXIT
Select “Page”.
98
Setting the Conditions of Communications with the Host by Using the Memory Switches
Section 3-5
[ MEMORY SW MENU ]
(2/2)
Automatic Reset
No
Baud Rate
Comm. Port
9600bps
Port B
Quit
Page
Language
English
WRT
&
EXIT
Each time the “Automatic
Reset” touch switch is pressed, the setting option
“Yes” alternates with “No”.
To set and quit the menu, press the [WRT&EXIT] touch switch. To quit without setting, press [Quit].
• “No”: If a communications error has occurred, corresponding error message is displayed and the operation stops.
• “Yes”: If a communications error has occurred, corresponding error message will not be displayed and the operation will be automatically reset.
3-5-7 Setting RS–232C Communications Conditions (NT20-ST128)
When using an NT20-ST128 (using the RS-232C interface for communications with the host), set the following communications conditions.
• Data Bits
• Stop Bits
• Parity Check
• Flow Control
• Baud Rate
Set the same communications conditions at the host and the NT20. You are recommended to set the highest baud rate that can be used by the host and
NT20.
The factory settings are as follows:
• Data Bits 8 bits
• Stop Bits 2 bits
• Parity Check Even
• Flow Control None
• Baud Rate 9600 bps
Set the conditions of the communications with the Host by the menu operation from the System Menu as described below.
Select “Maintenance Mode”.
[SYSTEM MENU]
Quit
Transmit Mode
Maintenance Mode
99
Setting the Conditions of Communications with the Host by Using the Memory Switches
Section 3-5
[MAINTENANCE MENU]
Quit
DIP-SW Status
PT Setting
I/O Check
Init. Memory
Memory Switch
Select “Memory Switch”.
[MEMORY SW MENU]
(1/3)
Key Sound
ON
Buzzer Sound
ON
Bk light Off
10 min
Quit
Page
Tool Mode
Automatic Reset
NT20S
Yes
WRT
&
EXIT
[MEMORY SW MENU]
(2/3)
Data Bits
8 bits
Stop Bits
1 bit
Quit
Page
Parity Check
Flow Control
Baud Rate
Even
RS/CS
19200 bps
WRT
&
EXIT
[MEMORY SW MENU]
(3/3)
LMP Bit Control
Enable
Comm. Port
Port B
Language
English
Quit
Page
WRT
&
EXIT
The selected option displayed when the corresponding touch switch is pressed: the options for each switch are indicated below:
• Data Bits:
• Stop Bits:
7 bits/8 bits
1 bit/2 bits
• Parity Check: None/Even/Odd
100
Setting the Conditions of Communications with the Host by Using the Memory Switches
Note
Section 3-5
• Flow Control: None/RS/CS/XON/XOFF
• Baud Rate: 2400 bps/4800 bps/9600 bps/19200 bps
• LMP Bit Control: Enable/Disable
Use the same condition settings as set for the host. It is recommended that the highest baud rate possible is selected for both the host and the NT20.
For details on lamp bit control, refer to 3-8 Various System Settings on page page 106.
101
Registering the Screen Data
Section 3-6
3-6 Registering the Screen Data
The screen data is created by using the Support Tool and registered to the
NT20 screen data memory. This section describes the procedure to register the screen data to the NT20. For the screen data creation and the Support
Tool operation, refer to the NT-series Support Tool Operation Manual (Cat. No.
V061).
Note
The screen data transmission speed can be increased by setting “Hi speed” for “Communications Mode” on the Tool Settings screen of the Support Tool.
Unit of Screen Transmission – Transmission in File Units
The NT20 uses several screens which are switched on its display. The screen data of one NT20 unit corresponds to the files created by using the Support
Tool. Select a file which contains the screen data to be transmitted when selecting the screen data to be transmitted to the NT20 so that the required screen data can be transmitted to the NT20.
Screen data file
Screen 1
Screen 2
:
NT20
Screen 1
Screen 2
:
Screen N
All screen data is transmitted by one operation.
Screen N
Memory tables Memory tables
Mark data Mark data
System memory System memory
(Direct information) (Direct information)
When the screen data is transmitted from the Support Tool to the NT20, the screen data already existing in the NT20 will be erased.
If an error message and the System Menu are displayed immediately after the
NT20 has been started, the screen data memory needs to be initialized.
Data Transmission in Screen Units
The NT20 allows the transmission of data for specified screens. By selecting the screen number of the screen to be transmitted using the Support Tool, it is possible to transmit the required screen only to the NT20 (it is also possible to transmit multiple screens in a batch).
When changes have also been made to the memory table entries or direct connection information, transmit the changed data to the NT20 too, for example by using transmission in screen units.
Support Tool NT20
Screen 2
Screen 1
Screen 2
:
Only the required screen data is transmitted.
Screen N
Memory tables
(Direct information)
!Caution When screen data transmission is in screen units, if there is data other than screen data, for example memory table or direct access changes, transmit this data also.
102
Registering the Screen Data
Section 3-6
Note
Transmitting the Screen Data from the Support Tool
To transmit the screen data from the Support Tool to the NT20, connect the
NT20 to the computer on which the Support Tool is being used, and follow the procedure below.
Note
When screen data is transmitted to an NT20, it is written into a free area of the memory without overwriting the existing data. This means that if data transmission in screen units is performed frequently, there will come a time when there is no more free area in the memory and further transmission is impossible. If this happens, transmit the data in file units to reorganize the contents of the NT20 memory.
When the screen data transmission is attempted, the screen data memory in the NT20 is automatically initialized before new screen data is transmitted. It is not necessary to initialize the screen data memory by using the menu before the screen data transmission.
The NT20-ST121-E/ST128 uses the same connector for screen data transmission and connection to the Host. If this connector is currently connected to the host, disconnect the cable from it and connect it to the Support Tool (personal computer) before attempting screen data transmission.
1,2,3...
1.
Connect the NT20 to a PLC in which the Support Tool has been installed and turn on the power to the NT20.
2.
Turn ON the computer and start up the Support Tool.
3.
Enter the “Transmit Mode” by operating the menu of the NT20 as described below.
Select “Transmit Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ TRANSMIT MODE ]
The transmit mode is established. When using an NT20, the “Support Tool mode” setting will be displayed on the bottom line of the screen, as shown in the figure to the left.
ABORT
Tool Mode NT20S
4.
Select a screen data to be transmitted to the NT20 in the File Selection screen of the Support Tool, and press the Send key.
5.
The NT20 will display the following screen when the screen data is being transmitted.
103
Registering the Screen Data
Section 3-6
[ TRANSMIT MODE ]
Tool
→ PT
Screen Data
0 KB
ABORT
Tool Mode NT20S
6.
When the screen data transmission is completed, the Support Tool will display the following screen.
Note
7.
Press any key on the Support Tool to return to the File Selection screen.
8.
Pressing the ABORT touch switch in the Transmit Mode screen of the
NT20 will exit the Transmit Mode and enter the RUN Mode.
Press the “Abort” touch switch on the NT20 when the screen data transmission is completed. Unless this touch switch is pressed, the screen data will not be correctly registered. If the “Abort” touch switch is pressed during transmission, the screen data will not be correctly registered.
If screen data cannot be transmitted from the Support Tool, confirm normal communications between the NT20 and the Support Tool (Personal computer). Use the tool communications check function in the Maintenance Mode
of the NT20 to check communications with the Support Tool. Refer to Check-
ing the Communications with the Support Tool on page 116.
Precautions to Be Observed during Screen Data Transmission
When any of the following or a system error occurs during the screen data transmission, the transmitted screen data will not be registered correctly to the NT20. If an error message is displayed in the System Menu and the RUN
Mode cannot be selected, the screen data memory needs to be initialized.
• The power to the NT20 is interrupted or reset.
• The power to the computer on which the Support Tool is running is interrupted or reset.
• The cable connecting the NT20 to the computer on which the Support
Tool is running is interrupted or reset.
• The “Abort” touch switch on the NT20 screen is pressed to end the transmission.
• The ESC key on the Support Tool is pressed to end the transmission.
When the power to the NT20 is turned ON or reset, the screen data is checked. However, if any of the above occurs during the screen data transmission, the screen may disappear and other unexpected problems may occur.
In the case of such problems, set DIP SW2-1 to ON to initialize the memory.
For the memory initialization by using the DIP switch, refer to the 3-4-2 Initial-
ization by Using the DIP Switch (Forced Initialization) on page 90.
104
Starting the Operation
Section 3-7
3-7 Starting the Operation
After completing the screen data transmission and setting the communications conditions, connect the NT20 to the Host and start operation.
Switching to RUN Mode
Note
Press the Quit touch switch in the System Menu. The start-up screen in the
RUN mode will be displayed.
If the NT20 has failed to start correctly; e.g., the start-up screen is not displayed, an error message is displayed, or the screen is not displayed at all,
refer to 7-2 Responding to Displayed Error Messages and take appropriate
action.
When using Host Link, NT Link, or C200H Direct communications, the screen displayed on startup is the one specified in the screen switch setting of the PT status control area.
When using an NT20-ST128, the startup screen is specified with the Support
Tool when creating the screen data. If no startup screen is specified, screen
No.1 becomes the startup screen. If no screen data is registered for the startup screen, the error message “Screen not registered” is displayed. For details
on screen numbers, see 4-3 Screen Display on page 140.
Confirming the Communications between the NT20 and the PLC/Host
When using the NT20-ST128, use the RS-232C communications check function in Maintenance Mode to confirm normal communications between the
NT20 and the host. Refer to Checking the Communications with the Host
When using the NT20, run the Host program and check that the following operations are executed normally.
• Confirm that the NT20 screens switch according to the Host program execution.
If the screens do not switch correctly, check the connection between the
NT20 and the Host and also check the settings.
Refer to SECTION 2 Hardware Settings and Connections.
• Confirm that the information selected by the NT20 touch switches has been correctly sent to the PLC by displaying the information of bits and words by using a Programming Device (e.g., CX-Programmer). If the information sent from the NT20 has not been correctly received by the
PLC, check the screen data settings (specifically the switch settings).
For details on the screen data creation, refer to the NT Support Tool for
Windows Operation Manual (Cat. No. V061).
105
Various System Settings
Section 3-8
3-8 Various System Settings
The NT20 can set a variety of functions to the memory switches which are convenient during the operation. This section describes the memory switch settings related to the operation environment.
3-8-1 Setting the Key Press Sound
Whether or not the key press sound is given when the NT20 touch switch is pressed can be set with the memory switch.
The factory setting has been set to give the key press sound when the touch key is pressed.
Set the key press sound by the menu operation from the System Menu as described below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit DIP-SW Status
PT Setting
I/O Check
Init. Memory
Memory Switch
Select “Memory Switch”.
[ MEMORY SW MENU ]
(1/2)
Comm. Type
Host Link
Key Sound
OFF
Buzzer Sound
OFF
Bk light Off
None
Tool Mode
NT20S
Quit
Page
WRT
&
EXIT
Each time the “Key Sound” touch switch is pressed, the setting option “ON” alternates with “OFF”.
106
Various System Settings
Section 3-8
To set and quit the menu, press the [WRT & EXIT] touch switch. To quit without setting, press [Quit].
• ON: The key press sound will be given for 0.2 second when a touch switch is pressed.
• OFF: The key press sound will not be given when a touch key is pressed.
3-8-2 Using the Buzzer
The NT20 can set a buzzer to indicate the occurrence of an emergency or an
NT20 error.
Setting the Buzzer
Stopping the Buzzer
Note
Note
Except when the buzzer has been set so as not to sound at all, the buzzer will sound when an error occurs. To set the buzzer to sound in other cases, the following two procedures can be used.
• Controlled by the Host
It is possible to control the NT20 from the Host to sound the buzzer during the operation.
Refer to 5-4 NT20 Status Control on page 203.
• Set the buzzer as a screen data attribute by using the Support Tool.
When creating the screen data by using the Support Tool, set the buzzer as a screen attribute so that the buzzer will sound. When the screen in which this attribute has been set is displayed, the NT20 will give the buzzer sound.
If the control by the Host and the display of the screen in which the buzzer attribute has been set are executed simultaneously, the priority is given to the control by the Host. Refer to the NT Support Tool for Windows Operation Manual (Cat . No.V061-E1@).
The buzzer sound can be stopped by the following operation.
• Control by the Host
• Switch the screen to a screen which does not have a buzzer attribute.
• Press the touch switch to which the buzzer stop attribute has been set.
If a buzzer stop attribute has been set to a touch switch created on the screen in which the buzzer attribute has been set, such touch switch can be used to stop the buzzer sound. For details on setting buzzer attributes for touch
switches, see Allocation of System Key Functions on page 154.
107
Various System Settings
Types of Buzzer Sounds
Setting the Buzzer
Section 3-8
Note
The following buzzer sounds can be set.
• Continuous sound: The buzzer continues to sound.
• Intermittent sound: The buzzer sounds intermittently at constant intervals.
If both the continuous buzzer and the intermittent buzzer are instructed by the
Host, the continuous buzzer will sound.
Use the memory switches to set whether or not the buzzer sounds when the buzzer sound has been instructed by the Host or with a screen attribute or when an error has occurred.
The factory setting is “ON”, which means that the buzzer will sound when a command is received from the host, when a screen for which the buzzer attribute is set is displayed, and when errors occur.
Set the buzzer sound by the menu operation from the System Menu as described below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit DIP-SW Status
PT Setting
I/O Check
Init. Memory
Memory Switch
Select “Memory Switch”.
[ MEMORY SW MENU ]
(1/2)
Comm. Type
Host Link
Key Sound
OFF
Buzzer Sound
OFF
Quit
Page
Bk light Off
Tool Mode
None
NT20S
WRT
&
EXIT
Repeatedly pressing the
“Buzzer Sound” touch switch cycles through the setting options “ON”, “ERR ON”, and
“OFF”, in that order.
108
Various System Settings
Section 3-8
Note
To set and quit the menu, press the [WRT&EXIT] touch switch. To quit without setting, press [Quit].
• OFF: The buzzer will not sound at all during the operation.
• When “ON” is set, the buzzer will sound when a command is received from the host, when a screen for which the buzzer attribute is set is displayed, and when errors occur.
• When “ERR ON” has been set, the buzzer will sound only when an error has occurred.
The buzzer will sound when “Buzzer check” is selected in the Maintenance
Mode regardless of the buzzer setting.
3-8-3 Backlight OFF Function
The NT20 has a function that turns off the backlight of the LCD panel to maximize its service life if no operation is performed for a certain period of time.
Turning ON the Backlight
When a touch switch on the NT20 is pressed or a screen is switched or redisplayed by the PLC when the backlight is off by the backlight off function, the backlight will turn on. Any changes of numeric values or characters displayed on the screen will not effect the backlight to turn on again.
Setting the Backlight OFF Function
Use the memory switches to set whether or not the backlight off function is used and the length of time to turn off the backlight.
The factory setting has been made so as to turn off the backlight if no operation has been performed for 10 minutes.
Set the backlight off function by the menu operation from the System Menu as described below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit DIP-SW Status
PT Setting
I/O Check
Init. Memory
Memory Switch
Select “Memory Switch”.
109
Various System Settings
Section 3-8
[ MEMORY SW MENU ]
(1/2)
Comm. Type
Host Link
Key Sound
OFF
Buzzer Sound
OFF
Quit
Page
Bk light Off
Tool Mode
None
NT20S
WRT
&
EXIT
Repeatedly pressing the
“BK light Off” touch switch cycles through the setting options “10 min”, 1 hour, and None, in that order.
To set and quit the menu, press the [WRT&EXIT] touch switch. To quit without setting, press [Quit].
• None: The backlight off function is not used. As long as no operation is performed, the same screen remains to be displayed.
• 10 minutes: The backlight will be turned off when no operation has been performed for 10 minutes.
• 1 hour: The backlight will be turned off when no operation has been performed for 1 hour.
!Caution Do not press touch switches carelessly while the backlight is off or while nothing is displayed on the screen.
Otherwise the system may operate unpredictably.
Only press touch switches after confirming system safety.
Note
Continuous display of the same pattern for an extended time (as a guide, about 1 hour) will lead to the formation of an afterimage.
In order to prevent this, either use the screen saver function or periodically switch screens.
3-8-4 Language Function
The language selection items will be different according to the DIP-SW2-2.
When DIP-SW2-2 is pushed to ON, the language is fixed to English. That is, user can't choose other language but English.
When DIP-SW2-2 is pushed to OFF, the languages can be switched in this language item in Memory SW Menu. Both Japanese and English are available.
DIP-SW2-2 is ON.
(Host link) (NT Link (1:1))
[ MEMORY SW MENU ]
(2/2)
Automatic Reset
No
Baud Rate
Comm. Port
9600bps
Port B
Quit
Page
Language English
WRT
&
EXIT
[ MEMORY SW MENU ]
(2/2)
Automatic Reset No
Comm. Port
Port B
Language
English
Quit
Page
WRT
&
EXIT
110
Various System Settings
Section 3-8
(NT Link (1:N))
[ MEMORY SW MENU ]
(2/2)
Automatic Reset
No
Unit No.
Comm. Speed
7
Standard
Quit
Page
Comm. Port
Language
Port B
English
WRT
&
EXIT
DIP-SW2-2 is OFF.
(Host link) (NT Link (1:1))
[ MEMORY SW MENU ]
(2/2)
Automatic Reset
No
Baud Rate
Comm. Port
9600bps
Port B
Quit
Page
Language
English
WRT
&
EXIT
(NT Link (1:N))
[ MEMORY SW MENU ]
(2/2)
Automatic Reset
No
Unit No.
Comm. Speed
Comm. Port
Language
7
Standard
Port B
English
Quit
Page
WRT
&
EXIT
[ MEMORY SW MENU ]
(2/2)
Automatic Reset No
Comm. Port
Port B
Language
English
Quit
Page
WRT
&
EXIT
3-8-5 Support Tool Mode Setting (NT20-ST121-E)
By setting “Tool Mode” to “NT20M”, the NT20 can be used in the same way as the conventional NT20M/NT20S, and it becomes possible to use the NT
Series Support Tool (version 2.
@).
However, the following restrictions apply when “NT20M” is set:
• Version 5 of the direct connection function cannot be used.
• The PT type setting must be “NT20M”.
• High-speed data transfer with the Support Tool is not possible.
• It is not possible to transfer the direct information alone.
• When screen data transmission is in screen units, simultaneous transmission of multiple screens is not possible. An attempt to transmit multiple screens may destroy the screen data.
• When screen data transmission is in screen units, transmission with verification set is not possible.
• The image data memory must be initialized before starting transfer in file units.
• Screen data for RS-232C communications cannot be used.
111
Various System Settings
Section 3-8
Set the Support Tool mode by the menu operation from the system menu shown below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit DIP-SW Status
PT Setting
I/O Check
Init. Memory
Memory Switch
Select “Memory Switch”.
[ MEMORY SW MENU ]
(1/2)
Comm. Type
Host Link
Key Sound
OFF
Buzzer Sound
OFF
Bk light Off
None
Tool Mode
NT20S
Quit
Page
WRT
&
EXIT
Each time the “Tool Mode” touch switch is pressed, the setting option alternates between “NT20”, “NT20S”, and “NT20M”.
(The figure to the left shows the NT20-ST121 @-E screen.)
To quit after setting the selected item, press the WRT & EXIT touch switch. To quit without setting, press the Quit touch switch. The NT20 will enter the RUN mode.
• When “NT20M” or “NT20S” is set, the NT20M/NT20S compatible mode is established and the terminal can be used as an NT20M/NT20S.
• When “NT20” is set, the terminal can be used as an NT20.
Note
Before uploading screen data from the NT20 to the Support Tool, confirm that the model information for the screen data in the NT20 and the Tool's transfer mode match. If they do not match, the upload may fail or data may change, preventing correct operation.
3-8-6 Lamp Bit Control (NT20-ST128)
When using the NT20-ST128 (using the RS-232C interface for communications with the host), you can select whether lamp status is controlled by bit designation or not.
The factory setting for this function is “Enable” (lamps numbered 0 to 31 controlled by bits).
112
Various System Settings
Section 3-8
Set the lamp bit control function by the menu operation from the System Menu as described below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit DIP-SW Status
PT Setting
I/O Check
Init. Memory
Memory Switch
Select “Memory Switch”.
[MEMORY SW MENU]
(1/3)
Key Sound
ON
Buzzer Sound
ON
Bk light Off
10 min
Quit
Page
Tool Mode
Automatic Reset
NT20S
Yes
WRT
&
EXIT
Select “Page down”.
[MEMORY SW MENU]
(2/3)
Data Bits
8 bits
Stop Bits
1 bit
Parity Check
Even
Flow Control
RS/CS
Baud Rate
19200 ps
Quit
Page
WRT
&
EXIT
Select “Page down”.
113
Various System Settings
Section 3-8
[MEMORY SW MENU]
(3/3)
LMP Bit Control
Enable
Comm. Port
Port B
Language
English
Quit
Page
WRT
&
EXIT
Each time the “LMP Bit Control” touch switch is pressed, the setting option “Enable” alternates with “Disable”.
To set and quit the menu, press the [WRT&EXIT] touch switch. To quit without setting, press [Quit].
• When “Disable” is set, the control of lamp display status by bits is not possible. The lamps numbered 0 to 31 can be controlled only by specifying lamp numbers.
• When “Enable” is set, lamp control by bits is possible. This means that the lamps numbered 0 to 31 can be controlled by specifying either lamp numbers or bits. However, it is not possible to make “lit”/”flashing” status selections by specifying lamp numbers: the selection made when the screen data was created remains effective.
114
System Maintenance
Section 3-9
3-9 System Maintenance
The NT20 has the self maintenance functions such as I/O check and setting status check.
3-9-1 I/O Check
The I/O operations for the following items of the NT20 are checked by the I/O check function.
• Touch Switch
• Communications with the Support Tool
• Communications with the Host (NT20-ST128 RS-232C only)
• LCD
• LED Check
• The Screen Data Memory
• Buzzer
Checking the Touch Switches
Execute a touch switch check by the menu operation from the System Menu as described below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit DIP-SW Status
PT Setting
I/O Check
Init. Memory
Memory Switch
Select “I/O Check”.
[ I/O CHECK MENU ]
Quit LCD Display
Comm. Check LED Check
Buzzer
Touch Switch
Data Memory
Select “Touch Switch”.
115
System Maintenance
Section 3-9
A panel of 6-row x 12-column touch switches, each switch sized 1 x 1 cm, will be displayed.
"EXIT" switch to exit the touch switch check menu.
The touch switch is normal if it is highlighted while it is pressed.
Note
Checking the
Communications with the
Support Tool
• Press a touch switch on the screen. If the touch switch is highlighted while it is pressed, the touch switch is normally functioning.
• When the check is finished, press the EXIT touch switch. The I/O check menu will be redisplayed.
If memory switch setting for the key press sound has been made for ON, the key press sound will be made when a touch switch is pressed.
The status of touch switches pressed during an I/O check is not sent to the host.
Execute a NT20-to-Support Tool communications check by the menu operation from the System Menu as described below.
The NT20-ST121-E/ST128 uses the same connector (Port A) for connection to the Support Tool and connection to the Host. If this connector is currently connected to the host, disconnect the cable from it and connect it to the Support Tool (personal computer) before attempting screen data transmission.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit DIP-SW Status
PT Setting
I/O Check
Init. Memory
Memory Switch
Select “I/O Check”.
116
System Maintenance
Section 3-9
[ I/O CHECK MENU ]
Quit LCD Display
Comm. Check LED Check
Buzzer
Touch Switch
Data Memory
Select “Comm. Check”.
Select “Tool I/F”.
[ COMM. CHECK MENU ]
Quit
Tool I/F
[ TOOL I/F INPUT CHECK ]
The data received from the connected Support Tool are displayed in hexadecimal numbers.
Checking the
Communications with the
Host (NT20-ST128)
EXIT
When the check is finished, press the Exit touch switch. The NT20 will enter the I/O CHECK MENU.
Execute a NT20-to-Host communications check by the menu operation from the System Menu as described below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
117
System Maintenance
Section 3-9
[ MAINTENANCE MENU ]
Quit DIP-SW Status
PT Setting
I/O Check
Init. Memory
Memory Switch
Select “I/O Check”.
[ I/O CHECK MENU ]
Quit LCD Display
Comm. Check LED Check
Buzzer
Touch Switch
Data Memory
Select “Comm.Check.
[ COMM. CHECK MENU ]
Quit
Tool I/F
RS-232C I/F
[ RS-232C I/F INPUT MENU ]
Checking the LCD
118
Exit
When the check is finished, press the EXIT touch switch. The NT20 will enter the RUN mode.
Check the NT20 LCD by using the menu operation from the System Menu as described below.
System Maintenance
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
Section 3-9
Select “Maintenance Mode”.
Checking the Buzzer
[ MAINTENANCE MENU ]
Quit DIP-SW Status
PT Setting
I/O Check
Init. Memory
Memory Switch
Select “I/O Check”.
[ I/O CHECK MENU ]
Quit LCD Display
LED Check Comm. Check
Buzzer
Touch Switch
Data Memory
Select “LCD Display”.
Select “RS-232C I/F”.
• The LCD displays dots (segments of the screen) line by line beginning with the top left corner. If all the dots are displayed normally, the NT20 will enter the I/O CHECK MENU after all the dots have been turned off.
• To cancel the LCD indication check, press any touch switch (anywhere) on the screen. The I/O Check Menu will be redisplayed.
Check the NT20 buzzer by using the menu operation from the System Menu as described below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
119
System Maintenance
Section 3-9
[ MAINTENANCE MENU ]
Quit DIP-SW Status
PT Setting
I/O Check
Init. Memory
Memory Switch
Select “I/O Check”.
Checking the LED
Note
Select “Buzzer”.
[ I/O CHECK MENU ]
Quit LCD Display
Comm. Check LED Check
Buzzer
Touch Switch
Data Memory
• If the buzzer function is normal, the continuous buzzer sound will be made.
• To stop the buzzer, press “EXIT” touch switch in the buzzer check screen.
The NT20 will enter the I/O CHECK MENU.
Though memory switch setting for the buzzer has been made for OFF, the buzzer will sound when the buzzer check is executed.
Check the LED by using the menu operation from the System Menu as described below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit DIP-SW Status
PT Setting
I/O Check
Init. Memory
Memory Switch
Select “I/O Check”.
120
System Maintenance
Section 3-9
[ I/O CHECK MENU ]
Quit LCD Display
Comm. Check LED Check
Buzzer
Touch Switch
Data Memory
Select “LED Check”.
The “RUN” LED on the front face of the NT20 will flash. Flashing cycle is about
1 s (500 ms ON and 500 ms OFF).
• To quit the LED check, press the “EXIT” touch switch. The NT20 will enter the I/O CHECK MENU.
Checking the Screen Memory
Check the screen memory by using the menu operation from the System
Menu as described below.
Note
When the screen data memory is checked, the memory is initialized and all the screen data is lost. Check that the screen data has been backed up using the Support Tool before executing a screen data memory check.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit DIP-SW Status
PT Setting
I/O Check
Init. Memory
Memory Switch
Select “I/O Check”.
121
System Maintenance
[ I/O CHECK MENU ]
Quit LCD Display
Comm. Check LED Check
Buzzer
Touch Switch
Data Memory
Section 3-9
Select “Data Memory”.
[ SCREEN DATA MEMORY CHECK ]
Caution!!
This test will destroy
the Screen Data.
Press “TEST START”.
Pressing “Cancel” will cancel the memory check.
TEST
START
CANCEL
The screen memory check will start.
While the screen memory is checked, the “Memory checking...” message will be displayed.
• If the memory check has been normally completed, the “Memory is OK” message will be displayed.
• To quit the memory check, press the “Cancel” touch switch. The NT20 will enter the I/O CHECK MENU.
• If the “Memory error!” message is displayed, the screen data memory may have been used up to its service life or there may be a hardware fault. In that case, initialize the screen data memory and check the memory again. If the same error message is displayed again, consult the
OMRON Service Center.
3-9-2 Checking the PT Setting
Display the NT20 settings by using the menu operation from the System Menu as described below.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
Select “Maintenance Mode”.
122
System Maintenance
Section 3-9
[ MAINTENANCE MENU ]
Quit DIP-SW Status
PT Setting
I/O Check
Init. Memory
Memory Switch
Select “PT Setting”.
(Host link)
[ PT SETTING ]
PT Control Area DM0000
PT Notify Area DM0010
Comm. Type
Baud Rate
Host Link
9600bps
EXIT
(NT Link (1:N))
(NT Link (1:1))
[ PT SETTING ]
PT Control Area DM0000
PT Notify Area DM0010
Comm. Type NT Link
EXIT
[ PT SETTING ]
PT Control Area
PT Notify Area
Comm. Type
Unit No.
EXIT
(C200H)
DM0000
DM0010
NT Link 1:N
7
(RS-232C) (NT20-ST128)
[ PT SETTING ]
PT Control Area DM0000
PT Notify Area DM0010
Comm. Type C200H
Unit No. 0
EXIT
[ PT SETTING ]
Data Bits
Stop Bits
Parity Check
Flow Control
Baud Rate
EXIT
8 bits
1 bit
Even
RS/CS
19200 bps
• The current PT settings will be displayed.
• Pressing the “EXIT” touch switch will exit the PT settings display, and the
NT20 will return to the RUN Mode.
123
System Maintenance
Section 3-9
3-9-3 Checking the NT20 DIP Switch Settings
Display the NT20 DIP switch settings by using the menu operation from the
System Menu as described below.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
Select “Maintenance Mode”.
[ MAINTENANCE MENU ]
Quit DIP-SW Status
PT Setting
I/O Check
Init. Memory
Memory Switch
Select “DIP-SW Status”.
[ DIP-SWITCH STATUS ]
1. Forced Init. No
2. Lanugage Select Enable
3. Mode Change Enable
(1/2)
Page
[SW2]
1
2 3 4
5
6
ON
OFF
EXIT
[ DIP-SWITCH STATUS ]
4. Reserved
5. Resouce Init.
6. System Init.
OFF
Disable
Disable
(2/2)
Page
[SW2]
1 2
3 4
5
6
ON
OFF
EXIT
• The NT20 DIP switch status is displayed.
• Pressing the EXIT touch switch clears the DIP switch status display from the screen and causes the NT20 to enter the RUN mode.
124
System Maintenance
Note
Section 3-9
If the DIP switch settings have been changed when the NT20 is powered, reset the power to the NT20. The changes with the DIP switches become effective only after the power supply is reset.
125
Transferring the System Program
Section 3-10
3-10 Transferring the System Program
The system program of the NT20 can be changed by the System Transfer
Tool.
The system transfer tool is automatically installed in the personal computer when the NT20 support tool is installed.
For details on how to start up the System Transfer Tool, and the system transfer tool operation, refer to the NT-series Support Tool Operation Manual
(V061-E1@).
Transferring the System
Program from the System
Transfer Tool
Operation
Note
An NT20 which has no system program registered in it will be able to execute only the installation function.
For details on System Transfer Tool operations, refer to the NT-series Support
Tool Operation Manual (V061-E1@).
In order to transfer the system program from the System Transfer Tool, first connect the NT20 to a personal computer running the System Transfer Tool using the appropriate cable, then proceed as follows.
Reference
The NT20 uses the same connector (Port A) for connection to the Support
Tool and connection to the host. If this connector is currently connected to the host, disconnect the cable from the host and connect it to the Support Tool
(personal computer) before attempting to transfer the system program.
1.
Connect the NT20 to the personal computer running the System Transfer
Tool, then turn ON the power to the NT20.
2.
Turn ON the power to the personal computer and start up the System
Transfer Tool.
3.
When the power to the NT20 is turned ON, the screen shown below will be displayed.
[System Installer V1.00]
-Download System Program-
Ready for downloading.
Yes
4.
Press the Yes button to enter the system transfer mode, as shown below.
[System Installer V1.00]
-Download System Program-
Downloading…
Abort
5.
The NT20 is now on standby for reception. Start transfer of the program by using the System Transfer Tool.
When the NT20 starts reception, the screen shown below will be displayed.
126
Transferring the System Program
[System Installer V1.00]
-Download System Program-
Downloading…
Section 3-10
Abort
6.
When transfer of the system program has been completed, the NT20 will display the screen shown below.
[System Installer V1.00]
-Download System Program-
Downloading is completed
Points to Observe during
Transfer of the System
Program
Method for Erasing the
System Program
Operation
Run System
7.
Press the Run system Button when using the system transfer tool to return to run mode.
If any of the following events or a system error occurs during transfer of the system program, the program will not be installed in the NT20 correctly.
• The power to the NT20 is turned OFF, or the NT20 is reset during transfer.
• The power to the personal computer that is running the System Transfer
Tool is turned OFF, or the personal computer is reset, during transfer.
• The cable connecting the personal computer running the System Transfer
Tool and the NT20 becomes disconnected or sustains a wire breakage during transfer.
• Transfer is terminated by pressing the Abort Button on the NT20.
• Transfer is terminated by pressing the ESC key of the personal computer running the System Transfer Tool.
In the event of any of the above, there is a possibility that the NT20 will not operate or that unpredictable malfunctions will occur.
To prevent this, turn ON DIP switch SW2-6 to erase the system program after the problem has occurred. For details on erasing the system program with the
DIP switch, refer to Method for Erasing the System Program (page 127).
In order to erase the system program, the system program area must be cleared.
If a system program already exists, it must be erased before the new one can be transferred.
Use the following procedure to erase the system program.
1.
Set DIP SW2-6 to the ON position and turn ON the power or reset. The following screen will be displayed.
127
Transferring the System Program
Section 3-10
Exit
-Download System Program-
Erase system program.
Are you sure?
Yes
2.
Press the Exit key if you want to quit without erasing the program. If you do want to erase the program, press Yes Button. This will start erasure of the program.
During erasure, the screen shown below will be displayed:
[System Installer V1.00]
-Download System Program-
Erasing…
3.
On completion of erasure, the screen shown below will be displayed. At this point, set DIP SW2-6 to the OFF position and reset the NT20.
-Download System Program-
Erasing is completed.
Set DIP-SW2-6 to OFF, and
Power OFF/ON.
128
Transferring the Resource Data
Section 3-11
3-11 Transferring the Resource Data
The resource data of the NT20 can be changed using the System Transfer
Tool.
The System Transfer Tool is automatically installed in the personal computer when the NT20 Support Tool is installed.
For details on how to start up the System Transfer Tool, and the System
Transfer Tool operation, refer to the NT-series Support Tool Operation Manual
(V061-E1@).
Transferring the Resource
Data from the System
Transfer Tool
Operation
Note
An NT20 which has no resource data registered in it will display a resource error screen.
For details on System Transfer Tool operations, refer to the NT-series Support
Tool Operation Manual (V061-E1@).
In order to transfer the resource data from the System Transfer Tool, first connect the NT20 to a personal computer running the System Transfer Tool using the appropriate cable, then proceed as follows.
Reference
The NT20 uses the same connector (Port A) for connection to the Support
Tool and connection to the host. If this connector is currently connected to the host, disconnect the cable from the host and connect it to the Support Tool
(personal computer) before attempting to transfer the resource data.
1.
Connect the NT20 to the personal computer running the System Transfer
Tool, then turn ON the power to the NT20.
2.
Turn ON the power to the personal computer and start up the System
Transfer Tool.
3.
When the power to the NT20 is turned ON, the screen shown below will be displayed.
[ Resource Transmit ]
Erase resource
Download resource
4.
Press the Download resource Button to enter the resource transfer mode, as shown below.
[ Download Resource ]
ABORT
5.
The NT20 is now on standby for reception. Start transfer of the program using the System Transfer Tool.
129
Transferring the Resource Data
Section 3-11
When the NT20 starts reception, the screen shown below will be displayed.
[ Download Resource ]
Downloading
0KB
ABORT
6.
When transfer of the system program has completed, the NT20 will be displays the screen shown below.
Downloading is completed.
Turn OFF the DIP Switch 2-5
And push the Reset Switch.
Then return to RUN mode.
Points to Observe during
Transfer of the Resource
Data
Method for Erasing the
Resource Data
Operation
If any of the following events or a system error occurs during transfer of the resource data, the program will not be installed in the NT20 correctly.
• The power to the NT20 is turned OFF or the NT20 is reset during transfer.
• The power to the personal computer that is running the System Transfer
Tool is turned OFF or the personal computer is reset during transfer.
• The cable connecting the personal computer running the System Transfer
Tool and the NT20 becomes disconnected or sustains a wire breakage during transfer.
• Transfer is terminated by pressing the ABORT Button on the NT20.
• Transfer is terminated by pressing the ESC key of the personal computer running the System Transfer Tool.
In the event of any of the above, a resource error will occur.
To prevent this, turn ON DIP switch SW2-5 to erase the resource data after the problem has occurred. For details on erasing the resource data with the
DIP switch, refer to Method for Erasing the Resource Data.
In order to erase the resource data, the resource data area must be cleared. If resource data already exists, it must be erased before the new data can be transferred.
Use the following procedure to erase the resource data.
1.
Set DIP SW2-5 to the ON position and turn ON the power or reset. The following screen will be displayed.
130
Transferring the Resource Data
[ Resource Transmit ]
Erase resource
Download resource
Section 3-11
2.
If you do want to erase the resource data, press the Erase resource Button. The following screen will be displayed.
Erase resource?
Yes
No
3.
Press the No Button if you want to quit without erasing the resource data.
If you do want to erase the resource data, press the Yes Button. This will start erasure of the resource data.
During erasure, the screen shown below is displayed:
Erase resource?
Yes
Erasing
No
4.
On completion of erasure, the screen shown below will be displayed.
[ Resource Transmit ]
Erase resource
Download resource
131
Transferring the Resource Data
Section 3-11
132
Download
Advertisement
Key features
Downsized body
Construction best suited to the FA environment
A Host Link I/F Unit, Screen Data Memory, and a System ROM Are All Incorporated
Touch Switch Operation
Compatibility with NT20M/NT20S
Character display
Figure display
Memory data display
Bar graph display
Lamp display
Frequently asked questions
The NT20 is a programmable terminal used to display and transmit information in an FA site. It can be easily installed and used.
The NT20 has a downsized body, is built with construction best suited to the FA environment, incorporates a Host Link I/F Unit, Screen Data Memory, and a System ROM, supports Touch Switch Operation, and is compatible with NT20M/NT20S.
The NT20 supports Host Link (direct) and NT Link communications methods. The NT20-ST128 also supports RS-232C communications.