Schneider Electric Quantum NOE 771 x0 Ethernet Modules User Guide
Reklama
Reklama
Quantum
NOE 771 x0 Ethernet Modules
User Guide
840 USE 116 00 Version 1.0
October 1999
Preface
Preface
The data and illustrations found in this book are not binding. We reserve the right to modify our products in line with our policy of continuous product development. The information in this document is subject to change without notice and should not be construed as a commitment by Schneider Electric.
Schneider Electric assumes no responsibility for any errors that may appear in this document. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without express written permission of the Publisher, Schneider Electric.
CAUTION!
All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to assure compliance with documented system data, repairs to components should be performed only by the manufacturer.
Failure to observe this precaution can result in injury or equipment damage.
MODSOFT® is a registered trademark of Schneider Electric
.
The following are trademarks of Schneider Electric:
Concept
Modbus
FactoryCast ProWORX NxT
Modbus Plus Modicon 984 Quantum
DIGITAL® and DEC® are registered trademarks of Compaq Computer Corp.
IBM® and IBM AT® are registered trademarks of International Business Machines
Corporation.
Microsoft® and MS-DOS® and Windows® are registered trademarks of Microsoft
Corporation.
©Copyright 1999, Schneider Electric Printed in U.S.A.
840 USE 116 00 Version 1.0
840 USE 116 00 Version 1.0
Contents
Chapter 1
Chapter 2
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
About this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Document Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Who Should Use this Manual . . . . . . . . . . . . . . . . . . . . . . . . . 3
How this Manual is Organized . . . . . . . . . . . . . . . . . . . . . . . . 4
Appendices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
System Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Minimum System Requirements . . . . . . . . . . . . . . . . . . . . . . 6
Related Documentation and Customer Support . . . . . . . . . . . . . . 7
Related Paper Documentation . . . . . . . . . . . . . . . . . . . . . . . . 7
Related Electronic Documentation . . . . . . . . . . . . . . . . . . . . . 7
Customer Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Product Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
NOE 771 x0 Module Overview . . . . . . . . . . . . . . . . . . . . . . . . . 10
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Key Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Front Panel Components . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Front View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
LED Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
LED Indicator Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Run LED Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
840 USE 116 00 Version 1.0
v
Contents vi
Connectors and Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
10/100 BASE-T Twisted Pair Connector . . . . . . . . . . . . . . . 15
100 BASE-FX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
I/O Scanner (140 NOE 771 00 only) . . . . . . . . . . . . . . . . . . . . . 16
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Peer Cop Based I/O Scanner . . . . . . . . . . . . . . . . . . . . . . . 16
Enhanced Modbus I/O Scanner . . . . . . . . . . . . . . . . . . . . . . 17
Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Peer-to-Peer Communications . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
MSTR Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Modbus/TCP Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Limitations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
FTP and HTTP Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
FTP Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
HTTP Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
BOOTP Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Your NOE BOOTP Server . . . . . . . . . . . . . . . . . . . . . . . . . . 22
SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Manager/Agent Paradigm . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Simple Network Management Protocol . . . . . . . . . . . . . . . . 23
The MIB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
ASN.1 Naming Scheme . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
The Object Identifier (OID) . . . . . . . . . . . . . . . . . . . . . . . . . . 24
SNMP Protocol Data Units . . . . . . . . . . . . . . . . . . . . . . . . . . 25
GetRequest PDU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
SetRequest PDU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Trap PDU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Version & Community Identifiers . . . . . . . . . . . . . . . . . . . . . 26
What can be Configured . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
840 USE 116 00 Version 1.0
Chapter 3
840 USE 116 00 Version 1.0
Contents
Installing the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Initial Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Determining the Appropriate
Ethernet Address Parameters. . . . . . . . . . . . . . . . . . . . . . . 28
Verifying the Network Topology . . . . . . . . . . . . . . . . . . . . . . 29
Cabling Schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Twisted Pair Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Cabling with Traditional Hubs . . . . . . . . . . . . . . . . . . . . . . . . 31
10 BASE-T Cable Distances . . . . . . . . . . . . . . . . . . . . . . . . . 31
100 BASE-T Cable Distances . . . . . . . . . . . . . . . . . . . . . . . . 31
100 BASE-FX Cable Distances . . . . . . . . . . . . . . . . . . . . . . 32
Fiber Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Security. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Types of Firewalls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Network-Level Firewalls . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Application-Level Firewalls . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Port Numbers Used by NOE . . . . . . . . . . . . . . . . . . . . . . . . . 33
Installing the Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Backplane Slot Placement . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Tools Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Mounting the Module in the Backplane . . . . . . . . . . . . . . . . 34
Connecting the Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Shielded Twisted Pair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Fiber Optic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Assigning Ethernet Address Parameters . . . . . . . . . . . . . . . . . . 36
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Using a BOOTP Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
How an unconfigured (“as shipped”) module
obtains an IP address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Using the Default IP Address . . . . . . . . . . . . . . . . . . . . . . . . 37
Specifying Address Parameters . . . . . . . . . . . . . . . . . . . . . . 38 vii
Contents
Chapter 4
viii
Assigning an IP address Via Concept’s
“Specify IP Address” option. . . . . . . . . . . . . . . . . . . . . . . . . 39
Assigning an IP address Via Concept’s
“Use Bootp Server” option . . . . . . . . . . . . . . . . . . . . . . . . . 39
If BOOTP Server Responds . . . . . . . . . . . . . . . . . . . . . . . . . 39
If BOOTP Server Doesn’t Respond . . . . . . . . . . . . . . . . . . . 39
NOE 771 00 Duplicate IP Address Test . . . . . . . . . . . . . . . . 40
Gratuitous ARP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Establishing the FTP Password . . . . . . . . . . . . . . . . . . . . . . . . . 41
Establishing the FTP Password . . . . . . . . . . . . . . . . . . . . . . 41
Introduction to Accessing the Web Server . . . . . . . . . . . . . 41
How to Access It . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Schneider Web Utility Home Page . . . . . . . . . . . . . . . . . . . . 42
Modifying the FTP Server Password . . . . . . . . . . . . . . . . . . 43
FTP Username and Password Modify Page Overview . . . . 44
Change the Username and Password . . . . . . . . . . . . . . . . . 44
Modify FTP Server User Name and Password Message . . . 45
Establishing the HTTP Password . . . . . . . . . . . . . . . . . . . . . . . 46
Modifying the HTTP Password . . . . . . . . . . . . . . . . . . . . . . 46
Modify Web Server User Name and
Password Page Overview . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Change the Username and Password . . . . . . . . . . . . . . . . . 47
Modify Web Server Username and
Password Page Message . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Using BOOTP Lite to Assign Address Parameters . . . . . . . . . . 49
BOOTP Lite Utility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Configuring the Module with Concept . . . . . . . . . . . . . . 51
Selecting Your PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Next. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Setting the Number of NOEs . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Memory Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Next. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
840 USE 116 00 Version 1.0
Chapter 5
840 USE 116 00 Version 1.0
Contents
Accessing and Editing the I/O Map . . . . . . . . . . . . . . . . . . . . . . 59
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Next . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Configuring the Ethernet Address Parameters . . . . . . . . . . . . . 63
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
How the Module Derives It’s IP Address . . . . . . . . . . . . . . . 65
Transferring Data with the I/O Scanner
140 NOE 771 00 only . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
I/O Scanner Concepts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
I/O Scan List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
I/O Scanner Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Peer Cop and Enhanced Modbus/TCP Scanners . . . . . . . . 69
Peer Cop I/O Scanner Features . . . . . . . . . . . . . . . . . . . . . . 70
Enhanced Modbus I/O Scanner Features . . . . . . . . . . . . . . 70
I/O Scanner Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Configuring the I/O Scan List Using Concept . . . . . . . . . . . . . . . 72
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
IP Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Unit ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Health Timeout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Rep Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Read . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Write . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Read and Write . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Configuring the Health Block . . . . . . . . . . . . . . . . . . . . . . . . 75
Starting Location of Health Block . . . . . . . . . . . . . . . . . . . . . 75
Completing the I/O Configuration . . . . . . . . . . . . . . . . . . . . . . . . 76
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Copy and Paste . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Cut and Paste . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Delete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 ix
x
Contents
C
hapter 6
Sort . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Fill Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Configuring the I/O Scan List Using ProWORX NxT . . . . . . . . . 79
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Selecting Your PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Accessing and Editing the Traffic Cop . . . . . . . . . . . . . . . . . 83
Setting the Number of NOE’s and
Configuring the Ethernet Address Parameters . . . . . . . . . . 85
Setting Up the I/O Scanner Using ProWORX NxT . . . . . . . 88
Specify the Specific I/O Groups to be Scanned . . . . . . . . . . 88
Configure the Transaction Parameters . . . . . . . . . . . . . . . . . 89
Establishing Configuration Extension Memory for Peer Cop . . . 90
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
How Much Memory? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Configuring the I/O Scan List Using Modsoft . . . . . . . . . . . . . . . 94
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Current Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Storage Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Specific Input/Output Configuration . . . . . . . . . . . . . . . . . . . 96
Specific Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Specific Input/Output Summary . . . . . . . . . . . . . . . . . . . . . . 99
Other Menu Selectable Support Functions . . . . . . . . . . . . . . 99
The GoToNode Function . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
The AddNode Function . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
The Timeout Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Health Bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
OnError Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Device IP Address Generation . . . . . . . . . . . . . . . . . . . . . . 101
Transferring Data with the MSTR Instruction . . . . . . . 103
MSTR Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
MSTR Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
No. of MSTR Instructions Allowed . . . . . . . . . . . . . . . . . . . 104
840 USE 116 00 Version 1.0
840 USE 116 00 Version 1.0
Contents
MSTR Characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
MSTR Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
MSTR Ladder Logic Representation . . . . . . . . . . . . . . . . . . . . 106
Ladder Logic Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Top Node Content . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Middle Node Content . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Bottom Node Content . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
MSTR Function Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Where Displayed. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
TCP/IP Ethernet Error Codes . . . . . . . . . . . . . . . . . . . . . . . 108
TCP/IP Ethernet Network Errors . . . . . . . . . . . . . . . . . . . . 109
CTE Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Read and Write MSTR Operations . . . . . . . . . . . . . . . . . . . . . 111
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Control Block Utilization . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Get Local Statistics MSTR Operation . . . . . . . . . . . . . . . . . . . 112
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Control Block Utilization . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Clear Local Statistics MSTR Operation . . . . . . . . . . . . . . . . . . 113
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Control Block Utilization . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Get Remote Statistics MSTR Operation . . . . . . . . . . . . . . . . . 114
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Control Block Utilization . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Clear Remote Statistics MSTR Operation . . . . . . . . . . . . . . . . 115
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Control Block Utilization . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Peer Cop Health MSTR Operation . . . . . . . . . . . . . . . . . . . . . 116
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Control Block Utilization . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Peer Cop Communications Health Status Information . . . . 117
Peer Cop Communications Health Bit State . . . . . . . . . . . 119 xi
Contents
Chapter 7
xii
Reset Option Module MSTR Operation . . . . . . . . . . . . . . . . . . 120
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Control Block Utilization . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Read CTE (Config Extension Table) MSTR Operation . . . . . . 121
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Control Block Utilization . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
CTE Display Implementation . . . . . . . . . . . . . . . . . . . . . . . 122
Write CTE (Config Extension Table) MSTR Operation . . . . . . 123
CTE Write Implementation . . . . . . . . . . . . . . . . . . . . . . . . . 123
Network Implementation . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Control Block Utilization . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
CTE Display Implementation . . . . . . . . . . . . . . . . . . . . . . . 124
TCP/IP Ethernet Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Board Status Word Bit Definition . . . . . . . . . . . . . . . . . . . . 126
Board Status Word Bit Definition by Module Type . . . . . . . 126
Embedded Web Pages . . . . . . . . . . . . . . . . . . . . . . . . . 127
Accessing the Web Utility Home Page . . . . . . . . . . . . . . . . . . 128
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
How to Access It . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Schneider Web Utility Home Page . . . . . . . . . . . . . . . . . . . 129
Quantum Welcome Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Quantum Welcome Page Overview . . . . . . . . . . . . . . . . . . 130
Quantum Welcome Page Links . . . . . . . . . . . . . . . . . . . . . 131
Quantum Local Rack Page . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Quantum Local Rack Page Overview . . . . . . . . . . . . . . . . 132
Quantum Local Rack Page Links . . . . . . . . . . . . . . . . . . . . 132
CPU Configuration Screen Page . . . . . . . . . . . . . . . . . . . . . . . 133
CPU Configuration Screen Page Overview . . . . . . . . . . . . 133
Description Fields . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Register Fields . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
ASCII Fields . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
CPU Configuration Screen Page Links. . . . . . . . . . . . . . . . 135
840 USE 116 00 Version 1.0
840 USE 116 00 Version 1.0
Contents
Ethernet Module Statistics Page . . . . . . . . . . . . . . . . . . . . . . . 136
Ethernet Module Statistics Page Overview . . . . . . . . . . . . . 136
Ethernet Module Statistics Page Links . . . . . . . . . . . . . . . . 137
Remote I/O Communication Status Page . . . . . . . . . . . . . . . . 138
Remote I/O Communication Status Page Overview . . . . . . 138
Remote I/O Communications Status Page Links . . . . . . . . 139
Quantum PLC Data Monitor Page . . . . . . . . . . . . . . . . . . . . . . 140
Quantum PLC Data Monitor Page Overview . . . . . . . . . . . 140
Quantum PLC Data Monitor Page Links . . . . . . . . . . . . . . 141
Configure NOE Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Configure NOE Page Overview . . . . . . . . . . . . . . . . . . . . . 142
Configure NOE Page Links . . . . . . . . . . . . . . . . . . . . . . . . 142
Configure SNMP Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Configure SNMP Page Overview . . . . . . . . . . . . . . . . . . . . 143
SNMP Page Fields . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Configure SNMP Page Links . . . . . . . . . . . . . . . . . . . . . . . 144
Completion Message . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Configure BOOTP Process . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Configure BOOTP Initial Page . . . . . . . . . . . . . . . . . . . . . . 146
Bootp Node Configuration Form Page . . . . . . . . . . . . . . . . 147
Initial Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
Adding to the BOOTP Database File . . . . . . . . . . . . . . . . . 148
Changing the BOOTP Database File . . . . . . . . . . . . . . . . . 148
Deleting from the BOOTP Database File . . . . . . . . . . . . . . 148
Resetting the Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Displaying the BOOTP Database File . . . . . . . . . . . . . . . . 149
Bootp Node Configuration Form Links . . . . . . . . . . . . . . . . 150
NOE Properties Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
NOE Properties Page Overview . . . . . . . . . . . . . . . . . . . . . 151
NOE Properties Page Links . . . . . . . . . . . . . . . . . . . . . . . . 151
NOE Diagnostics Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
NOE Diagnostics Page Overview . . . . . . . . . . . . . . . . . . . 152
NOE Diagnostics Page Links . . . . . . . . . . . . . . . . . . . . . . . 152 xiii
Contents
Chapter 8
Chapter 9
xiv
Crash Log Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
Crash Log Diagnostics Page . . . . . . . . . . . . . . . . . . . . . . 153
Crash Log Diagnostics Links . . . . . . . . . . . . . . . . . . . . . . . 154
Contacting Schneider Automation Page. . . . . . . . . . . . . . . . . . 155
Contacting Schneider Automation Page Overview . . . . . . 155
Using the Network Options Ethernet Tester . . . . . . . . 157
Installing the Network Options Ethernet Tester . . . . . . . . . . . . 158
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Installation Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Establishing a Connection with an Ethernet Module . . . . . . . . 159
What You Must Know . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Getting and Clearing Statistics . . . . . . . . . . . . . . . . . . . . . . . . 162
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
Statistics Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
Reading Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
Reading Registers Procedure. . . . . . . . . . . . . . . . . . . . . . . 168
Writing Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
Writing Registers Procedure . . . . . . . . . . . . . . . . . . . . . . . 169
Read or Write Request Error . . . . . . . . . . . . . . . . . . . . . . . 170
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
Responding to Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
Detecting Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
Active LED Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
Ready LED Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Link LED Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Kernel LED Error. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
Fault LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
Collision LED Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
Collision LED, Normal Condition . . . . . . . . . . . . . . . . . . . . 176
Run LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
Application LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
840 USE 116 00 Version 1.0
Contents
Reading and Clearing the Crash Log . . . . . . . . . . . . . . . . . . . 177
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
The Crash Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Reading the Crash Log . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Reading the Crash Log via FTP . . . . . . . . . . . . . . . . . . . . . 177
Clearing the Crash Log . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
Clearing the Crash Log via FTP . . . . . . . . . . . . . . . . . . . . . 178
Downloading a New NOE Exec . . . . . . . . . . . . . . . . . . . . . . . . 179
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
The Concept Exec Loader . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
Downloading a new NOE Exec via FTP . . . . . . . . . . . . . . . . . . 185
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
Appendix A NOE 771 00 Module Specifications . . . . . . . . . . . . . . . 187
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
Specification Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
Appendix B Ethernet Developers Guide . . . . . . . . . . . . . . . . . . . . . . 189
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
What the Sample Application Does. . . . . . . . . . . . . . . . . . . 190
Development Environment . . . . . . . . . . . . . . . . . . . . . . . . . 191
Class Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
List of Classes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
The CSample_doc Class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
The CSample_View Class . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
What it Does . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Accessing TCP/IP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Application Message Format . . . . . . . . . . . . . . . . . . . . . . . 196
840 USE 116 00 Version 1.0
xv
Contents
Timers and Transaction Processing . . . . . . . . . . . . . . . . . . . . 197
Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Transaction Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Transmit State Machine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
Receive State Machine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
Displaying on the Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
Appendix C Quantum Ethernet TCP/IP
Modbus Application Protocol . . . . . . . . . . . . . . . . . . . 205
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
Modbus Application Protocol PDU . . . . . . . . . . . . . . . . . . . . . . 207
Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
Modbus Application Protocol Service Classes . . . . . . . . . . . . 209
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
Data Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
Online Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
Image Download/Upload . . . . . . . . . . . . . . . . . . . . . . . . . . 209
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
Device Execution State Control . . . . . . . . . . . . . . . . . . . . . 209
Modbus Application Protocol PDU Analysis . . . . . . . . . . . . . . 210
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210
Analysis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210
TCP/IP Specific Issues . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
Broadcast/Multicast . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
TCP Port Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
Reference Documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213 xvi
840 USE 116 00 Version 1.0
Contents
Appendix D NOE 771 00 Module
I/O Scanner Performance Statistics . . . . . . . . . . . . . . 215
140 NOE 771 00 I/O Scanner Performance . . . . . . . . . . . . . . 216
Quantum 113 CPU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216
Quantum 213 CPU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
Quantum 424 CPU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
Quantum 534 CPU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
840 USE 116 00 Version 1.0
xvii
Contents xviii
840 USE 116 00 Version 1.0
Introduction
At a Glance
Introduction
This chapter contains general information about the manual
What’s in this
Chapter
This chapter contains the following topics.
Topic
About this manual
System Requirements
Related Documentation and Customer Support
Page
2
6
7
1
840 USE 116 00 Version 1.0
1
Chapter 1 Introduction
About this Manual
Document Scope
This manual describes all the features of the Quantum 140 NOE 771 00,10/100
Megabit Ethernet module and the Quantum 140 NOE 771 10 Factory/Cast module.
It should provide you with the knowledge to begin using a Quantum Programmable
Logic Controller (PLC) to communicate with devices over an Ethernet network.
The manual covers: z
The hardware architecture of a Quantum Ethernet TCP/IP module designed to fit into a single slot on the standard Quantum backplane.
z
The capabilities of the NOE 771 x0 modules.
z
The installation of the NOE 771 x0 module on a Quantum backplane.
z
Instructions on configuring the module from your programming panel using
Concept.
z
Instructions on setting up the module for I/O scanner capabilities (-00 only), including procedures for configuring the I/O scan list using Concept, ProWORX
NxT, and Modsoft.
z
Instructions on how to set up the modules to transfer data to and from nodes on a TCP/IP network through the use of a special master instruction (MSTR).
z
How to use a World Wide Web embedded server to access diagnostics and online configurations for the module and its associated controller (PLC). z
How to use the FactoryCast web server to customize your configuration via embedded web pages (-10 module only) z
Instructions on using the Network Options Ethernet Tester with a Windows based PC to monitor the network.
Note: NOE 771 x0 is used in this manual when the information applies to both the
NOE 771 00 and NOE 771 10 modules.
Continued on next page
2
840 USE 116 00 Version 1.0
Chapter 1 Introduction
About this Manual, continued
Who Should Use this Manual
This manual is intended to support anyone using a Quantum Programmable Logic
Controller that needs to communicate with devices over an Ethernet network. You are expected to have a knowledge of the use of Programmable Logic Controller systems and possess of a working knowledge of either the Concept, ProWORX
NxT, or Modsoft programming tools. You also need to understand the use of an
Ethernet network and TCP/IP.
Continued on next page
840 USE 116 00 Version 1.0
3
Chapter 1 Introduction
About this Manual, continued
How this Manual is Organized
This manual is organized as follows:
Chapter
Chapter 1
I ntroduction
Chapter 2
Product Description
Chapter 3
Installing the Module
Chapter 7
Embedding Web
Pages
Chapter 8
Using the Network
Options Ethernet
Tester
Chapter 9
Maintenance
Description
Presents an introduction to this manual--its scope, who should use it, how it is organized, and a listing of related publications.
Describes the hardware makeup of the NOE 771 x0, 10/100
Megabit Ethernet Module, and discusses the capabilities of the features.
Describes how to physically install the NOE 771 x0 module into a
Quantum backplane, and how to configure its IP parameters,
SNMP agent, and BOOTP server.
Describes how to configure the NOE 771 module from your programming panel using Concept 2.2 or later.
Chapter 4
Configuring the
Module with Concept
Chapter 5
Transferring Data with the I/O Scanner
Chapter 6
Transferring Data with the MSTR Instruction
Discusses the NOE 771 00 module’s I/O scanner capabilities and includes procedures for configuring the I/O scan list using Concept,
ProWORX NxT, and Modsoft. Module configuration with ProWORX
NxT and Modsoft is also described here.
Describes how to transfer data to and from nodes on a TCP/IP network through the use of a special MSTR (master instruction).
The operational statistics and error codes for reading and writing the controller information are also included.
Discusses how to use an embedded web server to access diagnostics and through embedded web pages view and change configurations of the module and its associated controller (PLC).
Describes how to use the Network Options Ethernet Tester with a
Windows based PC to monitor the network by supplying you with operational statistics and providing the capability of reading and writing PLC registers.
Describes how to obtain information for system maintenance including accessing and clearing the crash log and downloading the new NOE Exec.
Continued on next page
4
840 USE 116 00 Version 1.0
Chapter 1 Introduction
About this Manual, continued
Appendices
The manual contains the following Appendices:
Appendix
Appendix A
NOE 771 x0 Module
Specifications
Appendix B
Ethernet Developers
Guide
Description
Describes the main specifications for the Quantum 140 NOE 771
Ethernet Module.
Describes a sample TCP/IP application named Network Options
Ethernet Tester (NOET) used to verify the installation of the
Quantum Ethernet TCP/IP modules and serves as a sample application for developers.
Describes the Modbus Application Protocol used to transport
Modbus Application Protocol PDUs over TCP/IP.
Appendix C
Quantum Ethernet
TCP/IP Modbus
Application Protocol
Appendix D
NOE 771 00 Module
I/O Scanner
Performance
Statistics
Provides graphs of performance statistics for the I/O Scanner used with various CPUs.
840 USE 116 00 Version 1.0
5
Chapter 1 Introduction
System Requirements
Minimum System
Requirements
The following table details the minimum versions for systems used with the NOE
771 x0 modules:
System
Quantum Executive
Concept
Modlink
Modsoft
ProWORX NxT
Minimum Version Number
2.0
2.2
2.0
2.6
2.0 IP Address Configuration
2.1 I/O Scanning
6
840 USE 116 00 Version 1.0
Chapter 1 Introduction
Related Documentation and Customer Support
Related Paper
Documentation
In addition to the manual, the following documents may prove helpful to you: z
Concept 2.2 User’s Manual, 840 USE 483 00 z
BOOTP Lite User Documentation, 31002087 z
FactoryCast User Guide, 890 USE 152 00 z
Ladder Logic Library User Guide, 890 USE 100 00 z
Modbus Protocol Reference Guide, PI-MBUS-300 z
Open Modbus Specification, www.modicon.com/openmbus z
ProWORX NxT User Guide, 372 SPU 680 01 NMAN z
RIO Manual, 890 USE 101 00
Related
Electronic
Documentation
The NOE 771 x0 contains an embedded web server to provide online diagnostics, configuration, and support. The NOE 77710 module has additional functionality provided by the FactoryCast module.
Customer
Support
If you have any problems, please consult the documentation listed above or MS-
Windows documentation first. If you still have a question or need assistance, help is available from our Schneider hotline: z
Tel: USA and Canada 800-468-5342 z
Tel: International 978-975-9557 z
Fax: All 978-975-9301 z
BBS: Bulletin Board 978-975-9779
When calling the Schneider 800 telephone number, you will get a recording asking you to enter a one-digit code for the type of service you request, provided you use a touch tone telephone.
Continued on next page
840 USE 116 00 Version 1.0
7
Chapter 1 Introduction
Related Documentation and Customer Support, continued
Customer
Support,
continued
Visit Our Web Site: Please access the Schneider web site, www.modicon.com or schneider.com for the most up-to-date NOE Ethernet Controller information, such as resolutions to product issues, and product announcements. When you access the web site, look under technical information, and choose Quantum from the list of cross-product families. Then access Resolutions for resolutions to product issues,
Product Manuals for the most recently published user documentation, and so on.
8
840 USE 116 00 Version 1.0
Product Description
2
At a Glance
Introduction
This chapter presents a product overview of the Quantum 140 NOE 771 00 10/100
Megabit Ethernet Module and the Quantum 140 NOE 771 10 FactoryCast Module.
What’s in this
Chapter
This chapter contains the following topics.
Topic
NOE 771 x0 Module Overview
LED Indicators
Connectors and Cabling
I/O Scanner
Peer-to-Peer Communications
Modbus/TCP Server
FTP and HTTP Services
BOOTP Server
SNMP
16
18
19
20
Page
10
13
15
22
23
9
840 USE 116 00 Version 1.0
Chapter 2 Product Description
NOE 771 x0 Module Overview
General
Description
The Quantum 140 NOE 771 00,10/100 Ethernet module, shown below, is the latest model in a line of Quantum Ethernet TCP/IP modules designed to make it possible for a Quantum Programmable Logic Controller (PLC) to communicate with devices over an Ethernet network. The NOE 771 x0 module’s electronics are contained in a standard Quantum single width housing that takes up one slot in a Quantum backplane. The module can be plugged into any available slot in the backplane and is capable of being hot swapped.
The NOE 771 00 provides real-time peer-to-peer communications, as well as, I/O scanning, and a Modbus/TCP server. The included HTTP services provide maintenance and configuration utilities to the module.
The NOE 771 10 provides all the services of the -00 except the I/O
Scanner. It also has the following additional features: z
user programmable web pages z
the FactoryCast application, including:
creating and viewing of graphic real-time templates using Java beans
creating and viewing of text realtime templates in spreadsheet format
use of Concept symbols or direct addresses.
10
Continued on next page
840 USE 116 00 Version 1.0
Chapter 2 Product Description
NOE 771 x0 Module Overview, continued
Key Features
The NOE 771 x0 module provides the following key features: z
Integrated 10/100BASE-TX, full duplex capable, shielded twisted pair port z
Integrated 100BASE-FX multimode, full duplex capable, fiber optic port z
Embedded HTTP server z
BOOTP client and server z
SNMP V2 agent z
Flash file system z
Modbus I/O scanner (-00 only) z
Field upgradeable software over TCP/IP z
Modbus/TCP client z
Modbus/TCP server z
User Programmable Web Pages (-10 only) z
FactoryCast Application (-10 only)
Front Panel
Components
840 USE 116 00 Version 1.0
The front panel of NOE 771 x0 module contains identification marking, color code, and LED display. A writable area for an Internet Protocol (IP) address, a global address label, and two Ethernet cable connectors are located behind the removable front panel door. The following table provides a description of the front panel components which are shown on the opposite page.
Component Description
LED indicator Panel Indicates the operating status of the module, and the fiber optic and Modbus communications networks it is connected to. (See
LED Indicators
in this chapter.)
IP Address Writable
Area
Provides a writable area to record the module’s assigned IP address.
Global Address Label Indicates the module’s global Ethernet MAC address assigned at the factory.
100 BASE-FX
Connector
10/100BASE-T
Connector
Provides an MT-RJ receptacle for connection to a 100 megabit fiber optic Ethernet cable.
Provides an RJ-45 receptacle for connection to a shielded, twisted pair Ethernet cable.
Continued on next page
11
Chapter 2 Product Description
NOE 771 x0 Module Overview, continued
Front View
The front of the NOE 771 00 Ethernet module is shown below. The 140 NOE 771
10 is identical, with the exception of the Module Description, which reads 140 NOE
771 10 FactoryCast.
Model Number
Module Description
Color Code
LED Display
IP Address
Writable Area
140
NOE 771 00
Ethernet 10/100
Active
Fault Ready
Run
Coll
Link
Tx Act
Rx Act
10MB
100MB Fduplex
Kernel Appl
Removable Door
Global Address Label
100 Base Fx
MT-RJ Cable Connector
10/100 Base-T
RJ-45 Cable Connector
Base
Fx
00
-T
12
840 USE 116 00 Version 1.0
Chapter 2 Product Description
LED Indicators
LED Indicator
Panel
The LED indicator panel, shown below, provides continuous operating information about the NOE 771 x0 module and its connection to the network. The functions of the LED indicators are described in the following table
LED
Active
Ready
Fault
Run
Coll.
Link
Tx Act
Rx Act
Color Description
Green Indicates the backplane is configured.
Green Indicates module is healthy.
Red Indicates when the NOE is in a crash state
Green Flashes to indicate diagnostic code, as described in “Run LED Status” (below).
Red
Green
Green
Green
Flashes when Ethernet collisions occur.
On when Ethernet link is active.
Flashes to indicate Ethernet transmission.
Flashes to indicate Ethernet reception.
Kernel
10MB
Amber On when in Kernel Mode.
Green On when the module is connected to a 10
Megabit network.
100MB Green On when the module is connected to a
100 Megabit network.
Fduplex On when Ethernet is operating in the full duplex mode.
Appl Green On when crash log entry exists.
Ready
Run
Link
Tx Act
Rx Act
Active
Fault
Coll
10MB
100MB
Kernel
Fduplex
Appl
Continued on next page
840 USE 116 00 Version 1.0
13
Chapter 2 Product Description
LED Indicators, continued
Run LED Status
The state of the Run LED indicator provides the following diagnostic information:
Indicator State Status
On (steady) Normal operation: The NOE module is ready for network communication.
Number of flashes in sequence one two three four five six seven
Not used
Not used
No Link: the network cable is not connected or is defective
Duplicate IP address: The module will stay off-line.
No IP address: The module is attempting to obtain an IP address from a BOOTP server.
Using default IP address
No valid executive NOE present
14
840 USE 116 00 Version 1.0
Chapter 2 Product Description
Connectors and Cabling
10/100 BASE-T
Twisted Pair
Connector
The NOE 771 x0 module’s 10/100 BASE-T connector (shown below) is a standard
RJ-45 twisted pair receptacle.
Pins
8
1
Schneider Automation recommends that you use Category 5 STP cabling, which is rated to 100 Mbps, with an RJ-45 connector.
The eight pins are arranged vertically and numbered in order from the bottom to the top. The RJ-45 pinout used by this module is: z
Receive Data (+) 3 z
Receive Data (-) 6 z
Transmit Data (+) 1 z
Transmit Data (-) 2
100 BASE-FX
The NOE 771 x0 module’s 100 BASE-FX connector is a MT-RJ receptacle with it’s mating fiber optic cable connector (see figure on page 4).
For the NOE 771 x0, you may need an MT-RJ to SC (Duplex) Multimode fiber optic cable assembly 62.5/125
µ m. Schneider Electric recommends Cable Number
490NOC00005 to connect to fiber hubs/switches.
Note: The NOE 771 x0 is a one channel device. It is capable of communicating over either a 10/100BASE-T or a 100BASE-FX Ethernet network at any given time, but not both at the same time.
840 USE 116 00 Version 1.0
15
Chapter 2 Product Description
I/O Scanner (140 NOE 771 00 only)
Introduction
The functionality of your NOE 771 00 module is further enhanced by the addition of a Modbus I/O Scanner which you can configure with either the Modsoft or Concept programming panel. This allows you a way to transfer data between network nodes without using the MSTR instruction.
You can configure the NOE 771 Modbus I/O Scanner by either of two methods: z
Peer Cop z
Ethernet I/O Scanner
Note: It is recommended that the enhanced Modbus I/O Scanner be used for all new installations. Peer Cop functionality is provided only on as an easy migration path for an existing installation. The enhanced Modbus I/O Scanner provides greater functionality than the Peer Cop based I/O scanner.
Peer Cop Based
I/O Scanner
The Peer Cop based Modbus I/O Scanner has the following characteristics:
Parameter
Max. No. of Devices
Max. No. of Input Words
Max. No. of Output Words
Value
64
500
500
HealthTimeout Value
Input TimeOutState
IP Address
Global Setting (20 Msec to 2 Secs in 20 mSec increments)
Global Setting (Zero or Hold)
Derived from Modbus Address (must be on NOE’s Subnet)
Remote Register Reference Not configurable - 400001 is used
Continued on next page
16
840 USE 116 00 Version 1.0
Chapter 2 Product Description
I/O Scanner (140 NOE 771 00 only), continued
Enhanced
Modbus I/O
Scanner
The Enhanced based Modbus I/O Scanner has the following characteristics
Parameter
Max. No. of Devices
Value
64
Max. No. of Input Words 4,000
Max. No. of Output Words 4,000
HealthTimeout Value
Input TimeOutState
Individual Setting (1 Msec to 2 Secs in 1 mSec increments)
Individually Settable
IP Address Individually Settable
Remote Register Reference Configurable
Min. Update Rate Settable
Refer to Chapter 5 to learn how to configure the Modbus I/O Scanner.
Refer to Appendix D for detailed performance data.
Performance
Refer to Appendix D for detailed performance data.
840 USE 116 00 Version 1.0
17
Chapter 2 Product Description
Peer-to-Peer Communications
Introduction
All NOE 771 x0 Quantum Ethernet TCP/IP modules provide the user with the capability of transferring data to and from nodes on a TCP/IP network through the use of a special MSTR (master instruction). All PLCs that support networking communication capabilities over Ethernet can use the MSTR ladder logic instruction to read or write controller information.
MSTR
Operations
The MSTR instruction allows you to initiate one of 12 possible network communications operations over the network. Each operation is designated by a code. The following table lists the 12 operations and indicates those that are supported on an Ethernet TCP/IP network.
MSTR Operation
Write data
Read Data
Get local statistics
Clear local statistics
Write global database
Read global database
Get remote statistics
Clear remote statistics
Peer Cop health
Reset Option Module
Read CTE(config extension)
Write CTE (config extension)
8
9
10
11
12
6
7
4
5
2
3
Code TCP/IP Ethernet Support
1 supported supported supported supported not supported not supported supported supported supported supported supported supported
Performance
Performance information to be inclused in manual revision 1.1.
Refer to Chapter 6 for the Number of MSTR Instructions allowed.
18
840 USE 116 00 Version 1.0
Chapter 2 Product Description
Modbus/TCP Server
Introduction
All NOE 771 x0 Quantum Ethernet TCP/IP modules provide the user with the ability to access data from the controller using the standard Modbus/TCP protocol. Any device: PC, HMI package, another PLC, or any Modbus/TCP compliant device can access data from the PLC. The Modbus/TCP Server also allows Programming
Panels to login into the controller over Ethernet.
L
Limitations
The NOE 771 x0 supports up to 32 simultaneous Modbus/TCP Server connections.
The NOE 771 x0 allows only one Programming Panel to be logged in at a time to guarantee consistency of changes to the controller configuration.
The following Modbus/TCP commands are supported by the NOE: z
Read Data z
Write Data z
Read/Write Data z
Get Remote Statistics z
Clear Remote Statistics z
Modbus 125 Commands (used by Programming Panels to download a new
Exec to the NOE)
Performance
The NOE 771 x0’s Modbus/TCP Server has the following performance characteristics:
Parameter
Typical Response Time (mSec)
Number of Modbus/TCP Server Connections
Number of Simultaneous Login Channels
Value
0.6
32
1
Note: NOE 771 x0 Modbus/TCP performance measurements made with
140 CPU 534 14.
840 USE 116 00 Version 1.0
19
Chapter 2 Product Description
FTP and HTTP Services
FTP Server
The NOE 771 x0’s File Transfer Protoc Protocol (FTP) server is available as soon as the module has received an IP address. Any FTP client can logon to the module if it has the correct user name and password. The FTP server provides the following services:
• update the NOE’s firmware by downloading a new Exec
• error log visibility by uploading error log files
• upload/download BOOTP server and SNMP configuration files
The default user name is USER, and the default password is USERUSER. Both the user name and password are case sensitive. Refer to Chapter 3 for instructions on how to change the password, and add or delete user names to the FTP server.
There should be only one FTP client per module.
Continued on next page
20
840 USE 116 00 Version 1.0
Chapter 2 Product Description
FTP and HTTP Services, continued
HTTP Server
The NOE 771 x0’s HyperText Transport Protocol (HTTP) server is available as soon as the module has received an IP address. It can be used with version 4.0 or greater, of either the Internet Explorer or Netscape browsers, and allows you to see:
• module Ethernet statistics
• controller and I/O information
• BOOTP server information
The HTTP server’s HTML pages allow you to configure the module’s BOOT server and SNMP Agent.
The HTTP server is protected with a default name and password. The default name and password are both USER, and both are case sensitive. They can both be changed via the Configuration page on the NOE 771 x0’s Web Embedded Pages
(see Chapter 3).
The NOE 771 x0 supports a maximum of 32 HTTP instantaneous connections.
Note: Browsers may open multiple connections so 32 HTTP connections does not indicate 32 simultaneous users.
Note: The NOE 771 00 module does not support user downloaded Web pages.
You will need to purchase the 140 NOE 771 10 module in order to support that requirement.
840 USE 116 00 Version 1.0
21
Chapter 2 Product Description
BOOTP Server
Introduction
The BOOTstrap Protocol (BOOTP) software, compliant with RFC 951, is used to assign IP addresses to nodes on an Ethernet network. Devices (hosts) on the network issue BOOTP requests during their initialization sequence and a BOOTP server that receives the requests will extract the required IP address information from its database and place it in BOOTP response messages to the requesting devices. The devices will use the assigned IP addresses, received from the
BOOTP server, for all communication occurring on the network.
Your NOE
BOOTP Server
Your NOE 771 x0 module comes supplied with a BOOTP server. This feature allows you to provide IP addresses to all the I/O devices being serviced by the NOE
771 00. Providing a BOOTP server that is built into your NOE 771 x0 module, eliminates the need for you to have a dedicated PC on your IO network acting as a
BOOTP server.
Note: The NOE 771 x0’s BOOTP server cannot be used to provide it’s own IP address.
You can configure your NOE 771 x0’s BOOTP server from the module’s HTTP web page. Using this feature allows you to add, remove, and edit devices to the BOOTP server’s database which is maintained on the module’s non-volatile memory. Refer to Chapter 7 to learn how to configure the BOOTP server’s database.
22
840 USE 116 00 Version 1.0
Chapter 2 Product Description
SNMP
Introduction
Network management software allows a network manager to monitor and control network components and thus make it possible to isolate problems and find their causes. It allows a manager to: z
interrogate devices such as host computer, routers, switches, and bridges to determine their status, and z obtain statistics about the networks to which they attach.
Manager/Agent
Paradigm
Network management software follows the conventional client-server model. To avoid confusion with other network communication protocols that use the client/ server terminology, network management software uses the terms; z manager for the client application that runs on the manager’s computer z agent for the application that runs on a network device.
The manager uses conventional transport protocols (e.g., TCP or UDP) to establish communication with the agent and they then exchange request and responses according to the network management protocol.
Simple Network
Management
Protocol
Your NOE 771 x0 module is configured with the Simple Network Management
Protocol (SNMP) which is the standard protocol used to manage a local area network (LAN). It defines exactly how a manager communicates with an agent,
(i.e., the format of the requests that a manager sends to an agent and the format of the replies that the agent returns to the manager).
The MIB
Each object to which SNMP has access must be defined and given a unique name.
Also, both the manager and agent programs must agree on the names and the meanings of fetch and store operations. The set of all objects SNMP can access is known as a Management Information Base (MIB).
Continued on next page
840 USE 116 00 Version 1.0
23
Chapter 2 Product Description
SNMP, continued
ASN.1 Naming
Scheme
Objects in a MIB are defined with the
ASN.1 naming scheme, which assigns each object a long prefix that guarantees the name will be unique. For example, an integer that counts the number or IP datagrams a device has received is named: iso.org.dod.internet.mgmt.mib.ipIn-
Receives
This object name is represented in an
SNMP message by assigning each part an integer. So, the above message would appear as follows:
1.3.6.1.2.1.4.3 with each integer having the following meaning:
1 = ISO (International Organization for Standardization
3 = identified organization — one of branches under the ISO root
6 = U. S. Department of Defense
(DOD) — one of the children under branch1.3
1 = the Internet subtree under 1.3.6
2 = the mgm branch — (one of seven) of the Internet subtree. It is managed by the Internet Assigned Numbers Authority, and includes the standard MIBs.
1 = mib-2(1) group of managed objects
4 = ip — the mib-2(1) IP group (one of 11)
3 = ipinReceivers — the MIB object
The Object
Identifier (OID)
24
In the above example, the MIB object identified by the notation 1.3.6.1.2.1.4.3 is referred to as the Object Identifier or OID. All OIDs can be envisioned as part of a tree structure which begins at the root (ISO) and branches out with each subtree identified by an integer.
Continued on next page
840 USE 116 00 Version 1.0
Chapter 2 Product Description
SNMP, continued
SNMP Protocol
Data Units
SNMP uses Protocol Data Units (PDUs) to carry the requests and responses, between the manager and the agents, for the information contained in an OID. As the following figure shows, the SNMP message is the innermost part of a typical network transmission frame.
The PDUs within the SNMP initiate the communication between the manager and the agents. The SNMP installed on your NOE 771 00 module uses three PDUs:
• GetRequest
• SetRequest
• Trap
GetRequest PDU
The GetRequest (shortened to Get) PDU is used by the SNMP manager to retrieve the value of one or more objects (OIDs) from an agent.
SetRequest PDU
The SetRequest (shortened to Set) PDU is used by the SNMP manager to assign a value to one or more objects (OIDs) residing in an agent.
Trap PDU
The Trap PDU is used by the agent to alert the manager that a predefined event has occurred.
Continued on next page
840 USE 116 00 Version 1.0
25
Chapter 2 Product Description
SNMP, continued
Version &
Community
Identifiers
The version identifies the version number of the SNMP software being used by the manager and the agent. Your NOE 771 x0 supports Version 2 of the SNMP. The community is an identifier that you assign to your SNMP network. If community names for the manager and the agent don’t agree, the agent will send an authentication failure trap message to the manager. If the community names and version number agree, the SNMP PDU will be processed.
What can be
Configured
Your NOE 771 x0 module can be configured to send an authentication trap to two
SNMP managers if it receives a community name in a Get/Set request that does not match the configured name. Also, you can configure the Sys Contact and Sys
Location via the configuration page in the module’s Embedded Web pages. Please refer to Chapter 7 to learn how to configure the NOE 771 x0 SNMP.
26
840 USE 116 00 Version 1.0
Installing the Module
3
At a Glance
Introduction
This chapter describes how to physically install the NOE 771 x0 module into a
Quantum backplane, and configure its IP parameters, SNMP agent, and BOOTP server.
What’s in this
Chapter
This chapter contains the following topics.
Topic
Before You Begin
Cabling Schemes
Security
Installing the module
Connecting the Cable
Assigning Ethernet Address Parameters
Establishing the FTP Password
Establishing the HTTP Password
Using BOOTP Lite to Assign Address Parameters
34
35
36
41
Page
28
30
33
46
49
27
840 USE 116 00 Version 1.0
Chapter 3 Installing the Module
Before You Begin
Initial Checks
Before you install your module, you need to: z determine how the NOE 771 x0 module will be assigned its Ethernet address parameters (the default method is BOOTP) z verify that your Ethernet network is properly constructed
CAUTION
DUPLICATE ADDRESS HAZARD
Do not connect the module to your network until you have ensured that its IP address will be unique on the network. Having two devices with the same IP address can cause unpredictable operation of your network.
Failure to observe this precaution can result in network disruption leading to possible injury or equipment damage.
Determining the
Appropriate
Ethernet
Address
Parameters
Consult your system administrator to determine if you must configure a new IP address and appropriate gateway and subnet mask addresses, or whether the module will obtain its Ethernet address parameters from a BOOTP server. If the administrator assigns new address parameters, follow the directions in Chapter 4 to configure the module from your programming panel.
Note: If you will be changing the default configuration, you should stop the controller, then install the module, then change the configuration before starting the controller again.
The NOE 771 x0 module only reads its configuration data at power-up and when it is reset. Whenever the configuration data is changed, the module must be reset, either by hot swapping or through a reset command in the MSTR block (see Reset
Option Module MSTR Operation section in Chapter 6). Once the module is installed, stopping and restarting the controller will not reset it.
Continued on next page
28
840 USE 116 00 Version 1.0
Chapter 3 Installing the Module
Before You Begin, continued
Verifying the
Network
Topology
You should not connect an Ethernet web embedded server module directly to another device with a length of cable. For the network to operate properly, you must route the cable for each device through an Ethernet hub/switch. Hubs/switches are widely available and can be purchased from many suppliers.
NOE
NOE
NOE
Improper Network Topologies
NOE
Hub/Switch
NOE
Proper Network Topology
840 USE 116 00 Version 1.0
29
Chapter 3 Installing the Module
Cabling Schemes
Introduction
In a standard Ethernet cabling scheme, each device connects via a cable to a port on a central Ethernet hub/switch.
Twisted Pair
Length
The maximum length of cable between devices depends on the type of device used, as shown in the following table:
Type of Device Max. Cable from
Device to Hub
Hub
Switch
100 m
100 m
Max. Hubs Between
Any Two Nodes
Max. Cable Between Most
Distant Nodes on Network
4
Unlimited
500 m
Unlimited
For Fast Ethernet (100 Base-T) specifications, please refer to the IEEE 802.3u
Standard available from the IEEE (www.IEEE.org).
Continued on next page
30
840 USE 116 00 Version 1.0
Chapter 3 Installing the Module
Cabling Schemes, continued
Cabling with
Traditional Hubs
The following illustration and tables show the maximum number of hubs and the maximum cable length between devices when using hubs.
10 BASE-T Cable
Distances
The illustration below is for 10 BASE-T cable:
100 BASE-T
Cable Distances
The 100 BASE-T cabling allows for two hubs with a link maximum distance of
100 m (325 ft), and a total network diameter of 205 m (665 ft).
The following table details the maximum distance parameters with 100 BASE-T:
Model
DTE-DTE (no repeater)
One Class I repeater
One Class II repeater
Two Class II repeaters
Length max. in Twisted pair TX-T2-T4
100 m (325 ft)
200 m (650 ft)
200 m (650 ft)
205 m (665 ft)
Continued on next page
840 USE 116 00 Version 1.0
31
Chapter 3 Installing the Module
Cabling Schemes, continued
100 BASE-FX
Cable Distances
The 100 BASE-FX cabling allows for two hubs with a link maximum distance of
412 m (1339 ft).
The following table details the maximum distance parameters with 100 BASE-FX and 100 BASE TX-FX:
Model Length max. Twisted pair TX and Fiber FX
DTE-DTE (no repeater) n.a.
One Class I repeater 260.8 m (1)
One Class II repeater 308.8 m (1)
Two Class II repeaters 216.2 m (2)
Length max.
Fiber FX
412 m (1339 ft)
272 m (884 ft)
320 m (1040 ft)
228 m (741 ft)
(1) Mixed twisted pairs and fiber assumes a 100 m (325 ft) twisted pair links
(2) Mixed twisted pairs and fiber assumes a 105 m (340 ft) twisted pair links
Fiber Length
The maximum length for 850 nm/Multimode cable is 2 KM.
32
840 USE 116 00 Version 1.0
Chapter 3 Installing the Module
Security
Overview
To restrict access to your Ethernet controller and I/O network, you may want to consider a firewall. A firewall is a gateway which controls access to your network.
Types of
Firewalls
There are two types of firewalls: z
Network-level firewalls z
Application-level firewalls
Network-Level
Firewalls
Network-level firewalls are frequently installed between the Internet and a single point of entry to an internal, protected network.
Application-
Level Firewalls
An application-level firewall acts on behalf of an application. It intercepts all traffic destined for that application and decides whether to forward that traffic to the application. Application-level firewalls reside on individual host computers.
Port Numbers
Used by NOE
The following table contains the port numbers used by NOE.
Protocol
Modbus/TCP
HTTP
SNMP
FTP
Port Number
TCP 502
TCP 80
UDP 61
TCP 21
You may need to provide this information to your system administrator to configure the firewall to allow access to your PLC from outside of your facility.
840 USE 116 00 Version 1.0
33
Chapter 3 Installing the Module
Installing the Module
Before You
Begin
Locate the backplane that the NOE 771 module will be mounted in. Ensure that an open slot is available to mount the module in.
Note: The NOE 771 x0 module can only be installed in a local backplane.
Backplane Slot
Placement
The modules may be placed in any slot in the backplane. They do not have to be placed next to each other.
Tools Required
You will need one Phillips head screw driver-medium size.
Mounting the
Module in the
Backplane
Perform the following steps to mount the NOE 771 x0 module in a Quantum backplane..
Step
1
Action
Holding the module at an angle, mount it on to the two hooks located near the top of the backplane.
34
2
3
Swing the module down so its connector engages the backplane connector.
Using a Phillips head screw driver, tighten the screw at the bottom of the module between 2 and 4 in-lbs of torque.
840 USE 116 00 Version 1.0
Chapter 3 Installing the Module
Connecting the Cable
+
Shielded
Twisted Pair
Note: The 140 NOE 771 x0 is capable of communicating over either a 10/
100BASE-T or a 100BASE-FX Ethernet network at any given time, but not both at the same time
If you are using shielded twisted pair cable, Schneider Electric recommends
Category 5, which is rated to 100 Mbps. The following table specifies the Schneider
Electric part numbers:
Purpose/Description Part Number
Connection of a device to an Ethernet hub/switch
Shielded Twisted Pair Cable
(SFTP, Cat 5, RJ-45,
Low Smoke Free Halogen)
490NTW000 nn
(where nn is the length in meters)
Connection of the Ethernet hub/switch together
Shielded Twisted Pair crossed
Cable (SFTP, Cat 5, RJ-45,
Low Smoke Free Halogen)
490NTC000 nn
(where nn is the length in meters)
Available Lengths in meters
02, 05, 12, 40, 80
05,15,40, 80
Use RJ-45 connectors. Slip the connector into the port. It should snap into place.
Fiber Optic
Remove the protective plug from the module’s MT-RJ connector port and the protective cap from the tip of the black connector on the MT-RJ fiber optic cable
(see figure below). Note the position of the keyway on the module’s connector port and the matching key on the cable connector, and then insert the connector into the port. It should snap into place.
35
840 USE 116 00 Version 1.0
Chapter 3 Installing the Module
Assigning Ethernet Address Parameters
Overview
As shipped from the factory, the NOE 771 x0 module does not contain an IP address. This is also true if you have not programmed the unit with an Ethernet configuration extension. In this condition, when the module starts up, it will attempt to obtain an IP address from the network’s BOOTP server.
You can use Concept to assign an IP address, default gateway and sub network mask. See Configuring the Ethernet Address Parameters in Chapter 4.
You can also assign IP address parameters using the BOOTP Lite software utility.
See Using BOOTP Lite to Assign Address Parameters in this chapter.
CAUTION
DUPLICATE ADDRESS HAZARD
Be sure that your NOE 771 x0 module will receive a unique IP address. Having two or more devices with the same IP address can cause unpredictable operation of your network.
Failure to observe this precaution can result in injury or equipment damage.
Using a BOOTP
Server
A BOOTP server is a program which manages the IP addresses assigned to devices on the network. Your system administrator can confirm whether a BOOTP server exists on your network and can help you use the server to maintain the adapter’s IP address.
How an unconfigured
(“as shipped”) module obtains an IP address
On startup, an unconfigured NOE 771 x0 module will attempt to obtain an IP address by issuing BOOTP requests. When a response from a BOOTP server is obtained, that IP address will be used. If there is no BOOTP response received in two minutes, the module will use the default IP Address.
Continued on next page
36
840 USE 116 00 Version 1.0
Chapter 3 Installing the Module
Assigning Ethernet Address Parameters, continued
Using the Default
IP Address
To use the default IP address with your PC, set up an active route from your PC. To do this with either Windows 95 or Windows NT, use the following procedure.
2
3
Step
1
4
Action
Be sure the NOE module is running
Obtain the default IP address of the NOE
Open an MS-DOS Window
Print the current active routes by typing:
C:\>route print
5 Add an active route for the local NOE by typing:
C:\>route add 84.0.0.0 mask 255.0.0.0 205.217.193.205
The result is that Windows 95/98/ NT will now talk to any address that starts with an 84 that is directly connected to a hub or switch directly accessible to your machine, or that can be seen by the route/gateway specified.
Continued on next page
840 USE 116 00 Version 1.0
37
Chapter 3 Installing the Module
Assigning Ethernet Address Parameters, continued
Using the Default
IP Address,
continued
Step
6
Action
Confirm that there is a new entry in the active route table by typing:
C:>route print
7 Verify that a connection is made by typing
C:\>ping 84.0.0.2
Specifying
Address
Parameters
Consult your system administrator to obtain a valid IP address and appropriate gateway and subnet mask, if required. Then follow the instructions in Configuring the Ethernet Address Parameters in Chapter 4.
Continued on next page
38
840 USE 116 00 Version 1.0
Chapter 3 Installing the Module
Assigning Ethernet Address Parameters, continued
Assigning an IP address Via
Concept’s
“Specify IP
Address” option.
You can select the NOE 771 x0 module’s “Specify IP Address” mode via Concept to assign an IP address (as well as default gateway and sub network mask) to the module.
Assigning an IP address Via
Concept’s “Use
Bootp Server” option
You can select the NOE 771 x0 module’s “Use Bootp Server” mode via Concept to instruct the module to obtain its IP address from a network BOOTP server. In this mode, only an address obtained from a BOOTP server will be accepted by the module.
If BOOTP Server
Responds
If the server responds with address parameters, the NOE 771 x0 module will use those parameters as long as power remains applied to the module.
If the server doesn’t respond, the module will retry its request for two minutes.
If BOOTP Server
Doesn’t Respond
If no BOOTP response is received, the NOE 771 x0 module will use the default IP
Address.
During this time the Run indicator will display a pattern of three flashes.
840 USE 116 00 Version 1.0
39
Chapter 3 Installing the Module
Assigning Ethernet Address Parameters, continued
NOE 771 00
Duplicate IP
Address Test
In all cases, when the NOE 771 x0 module receives an IP address, it will test for duplicate addresses by sending broadcast ARP requests three times at 5 second intervals.
If a Duplicate IP Address is found on the network, the NOE 771 x0 will stay off-line to avoid a network disruption. It will display a pattern of four flashes to indicate a
Duplicate IP Address detection.
Gratuitous ARP
If there are no replies to its requests, it will send gratuitous ARP three times at 2 second intervals to announce its presence on the network.
40
840 USE 116 00 Version 1.0
Chapter 3 Installing the Module
Establishing the FTP Password
Establishing the
FTP Password
The FTP Password is established using the Embedded Web Server. This section contains information on initially accessing the web server. The first thing the system administrator should do upon accessing the web server is change the FTP password. Doing this restricts access to the web server functionality to the system administrator.
This section contain information on how to access the web server for purposes of changing the FTP and HTTP passwords. Chapter 7 contains detailed information on the web server pages and their functionality.
Introduction to
Accessing the
Web Server
Each Quantum 140 NOE 771 x0 10/100 Megabit Ethernet module contains a
World Wide Web embedded server that allows you to access diagnostics and online configurations for the module and it’s associated controller (PLC).
The web pages can only be viewed across the World Wide Web using version 4.0 or greater of either Netscape Navigator or Internet Explorer, both of which support
JDK 1.1.4 or higher.
For information on the additional functionality provided by the FactoryCast system in the 140 NOE 771 10 module, see the FactoryCast Manual, 890 USE 152 00.
How to Access It
Before you can access the module’s home page, you must enter the full IP address or URL in the Address or Location box in the browser window.
For example: http://hostname (hostname is full IP address or DNS host name.)
Once you do this the Schneider Automation Web Utility home page will appear.
Continued on next page
840 USE 116 00 Version 1.0
41
Chapter 3 Installing the Module
Establishing the FTP Password, continued
Schneider Web
Utility Home
Page
From this page you can do the following: z
Access the pages to change the FTP password z
Access the pages to change the HTTP password z
Access the pages for diagnostic and configuration information, see Chapter 7
Embedded Web Pages for further information.
Continued on next page
42
840 USE 116 00 Version 1.0
Chapter 3 Installing the Module
Establishing the FTP Password, continued
Modifying the
FTP Server
Password
The following step details how to link to the web page that allows the modifying of the FTP Password:
Step
1
Action
Enter the URL, for example: http:// hostname /secure/embedded/ftp_passwd_config.htm
Result: The user is requested to supply a user name and password.
Upon supplying the user name, password, and clicking the <OK> button, the
Modify FTP Server User Name and Password Page appears.
Note: The default User Name is USER, and the default Password is
USERUSER. Both should be changed by the system administrator during module installation.
Continued on next page
840 USE 116 00 Version 1.0
43
Chapter 3 Installing the Module
Establishing the FTP Password, continued
FTP Username and Password
Modify Page
Overview
This page is used for modifying the FTP user name and password.
Change the
Username and
Password
At this point the system administrator should change the Username and Password to restrict future access to the system. The steps to do this are:
Step
1
2
3
Action
Type in the new Username in the New User Name block
Type in the new Password in the New Password block
Click on the Submit FTP Password Change button
Continued on next page
44
840 USE 116 00 Version 1.0
Chapter 3 Installing the Module
Establishing the FTP Password, continued
Modify FTP
Server User
Name and
Password
Message
The following message is generated when you click on the Submit FTP Password
Change button:
Clicking the Reboot Device button will reset the Username and Password for the
NOE 771 x0 board.
Note: The Reboot will take approximately 40 seconds.
840 USE 116 00 Version 1.0
45
Chapter 3 Installing the Module
Establishing the HTTP Password
Modifying the
HTTP Password
The following step details how to link to the web page that allows the modifying of the HTTP Password:
Step
1
Action
Enter the URL, for example: http:// hostname /secure/embedded/http_passwd_config.htm
Result: The user is requested to supply a user name and password.
Upon supplying the user name, password, and clicking the <OK> button, the
Modify HTTP Server User Name and Password Page appears.
Note: The default User Name is USER. and the default Password is USER. Both should be changed by the system administrator during module installation.
Continued on next page
46
840 USE 116 00 Version 1.0
Chapter 3 Installing the Module
Establishing the HTTP Password, continued
Modify Web
Server User
Name and
Password Page
Overview
This page is used for modifying the HTTP user name and password.
Change the
Username and
Password
At this point the system administrator should change the Username and Password to restrict future access to the system. The steps to do this are:
Step
1
2
3
Action
Type in the new Username in the New User Name block
Type in the new Password in the New Password block
Click on the Submit Password Change button
Continued on next page
840 USE 116 00 Version 1.0
47
Chapter 3 Installing the Module
Establishing the HTTP Password, continued
Modify Web
Server Username and Password
Page Message
The following message is generated when you click the Submit Password Change button:
Clicking the Reboot Device button will reset the Username and Password for the
NOE 771 x0 board.
Note: The Reboot will take approximately 40 seconds.
48
840 USE 116 00 Version 1.0
Chapter 3 Installing the Module
Using BOOTP Lite to Assign Address Parameters
BOOTP Lite
Utility
CAUTION
INCORRECT MAC ADDRESS HAZARD
Be sure to verify the MAC address of the target device before invoking BOOTP Lite. If you do not enter the correct parameters of the target controller, it will run in its old configuration. An incorrect MAC address may also result in an unwanted change to another device and cause unexpected results.
Failure to observe this precaution can result in injury or equipment damage.
Instead of a BOOTP server, Schneider Electric’s BOOTP Lite utility software can be used to provide the IP address, subnet mask and default gateway to the NOE 771 x0 module.
Refer to the BOOTP Lite user documentation for instructions.
Note: BOOTP Lite and the user document are available for download at www.modicon.com.
840 USE 116 00 Version 1.0
49
Chapter 3 Installing the Module
50
840 USE 116 00 Version 1.0
Configuring the Module with
Concept
4
At a Glance
Introduction
This chapter describes how to configure the NOE 771 module from your programming panel using Concept 2.2 or later. This is used to configure the module’s IP parameters using Concept. The module can function as a network interface to the CPU without I/O services, as long as the IP parameters are provided by a BOOTP server, or with the module’s default IP address.
What’s in this
Chapter
This chapter contains the following topics.
Topic
Selecting your PLC
Setting the Number of NOEs
Accessing and Editing the I/O Map
Configuring the Ethernet Address Parameters
Page
52
56
59
63
840 USE 116 00 Version 1.0
51
52
Chapter 4 Configuring the Module with Concept
Selecting Your PLC
Procedure
+
Once the NOE 771 module has been installed in a Quantum backplane (refer to
Chapter 3), you can begin to configure it using Concept 2.2. You start by selecting your CPU (PLC).
Note: For complete details on the use of Concept, refer to the set of manuals shipped with the software.
Perform the following steps to select a CPU.
Step
1
2
Action
Open Concept 2.2 on your programming panel (PC)
From the File menu, select New project.
Result: A new project is opened and the file name (untitled) appears over the menu bar.
3 From the Project menu, select Configurator.
Continued on next page
840 USE 116 00 Version 1.0
Chapter 4 Configuring the Module with Concept
Selecting Your PLC
, continued
Procedure, continued
Step
3,
(con’t)
Action
Result: The PLC Configuration screen appears.
840 USE 116 00 Version 1.0
Continued on next page
53
Chapter 4 Configuring the Module with Concept
Selecting Your PLC
, continued
Procedure, continued
Step
4
Action
Double click on the Type field in the PLC section of the Configure menu.
Result: The PLC Selection dialog box appears. The default selection is Quantum.
54
5 From the CPU/Executive scroll box, select the CPU that is installed in your
Quantum backplane
+
Note:
Depending on the CPU selected, you may need to select the correct memory size applicable to it in the Memory Size dialog Box.
Continued on next page
840 USE 116 00 Version 1.0
Chapter 4 Configuring the Module with Concept
Selecting Your PLC, continued
Initial Setup
Procedure, continued
Step
6
Action
Click the <OK> button.
Result: Your PLC type and default configuration parameters are displayed in the
PLC Configuration screen.
Next
Next, you must configure the number of Ethernet modules that your system will contain.
840 USE 116 00 Version 1.0
55
Chapter 4 Configuring the Module with Concept
Setting the Number of NOEs
Introduction
You may configure from two to six Ethernet modules in a single controller, depending on the model. A 140 CPU 113 or 213 will accept a total of two network option modules, including NOE, NOM, NOP, and CRP 811. A 140 CPU 424, 434 or
534 will accept six. Refer to the table in the I/O Scanner Concepts section in
Chapter 5 regarding the mix of I/O scanners and NOE modules per CPU.
Memory
Requirements
The first Ethernet TCP/IP module configured requires 20 words of memory. Each additional module requires an additional 16 words of memory.
Continued on next page
56
840 USE 116 00 Version 1.0
Chapter 4 Configuring the Module with Concept
Setting the Number of NOEs, continued
Procedure
From the PLC Configuration screen, follow the steps below to select the number of
NOE modules.
Step
1
Action
From the Configure menu, select Config extensions or, double-click anywhere in the Config Extensions region of the screen.
840 USE 116 00 Version 1.0
Result: The Configuration Extension dialog box appears (next page).
Continued on next page
57
Chapter 4 Configuring the Module with Concept
Setting the Number of NOEs, continued
Procedure, continued
Step
2
Action
In the TCP/IP Ethernet scroll box, select the number of NOE modules to be configured.
3 Click on the <OK> button.
Result: The Ethernet status changes from 0 to the number selected in Step 2.
Next
58
Next, you need to create an I/O map for the NOEs in your configuration.
840 USE 116 00 Version 1.0
Chapter 4 Configuring the Module with Concept
Accessing and Editing the I/O Map
Introduction
This procedure is required to determine the number of NOEs in the system and their slot numbers.
As part of the configuration process, you need to create an I/O Map for the local backplane including the NOE 771 x0 module. This step is required to determine the number of NOEs in the system and their slot locations.
Procedure
Perform the following steps to access and edit an I/O Map from the PLC
Configuration screen.
Step
1
Action
From the Configure menu, select I/O map.
840 USE 116 00 Version 1.0
Continued on next page
59
Chapter 4 Configuring the Module with Concept
Accessing and Editing the I/O Map, continued
Procedure, continued
Step
1,
(con’t)
Action
Result: The I/O Map dialog box appears:
2 Click the <Edit> button at the end of the Quantum I/O row.
Result: The Local Quantum Drop I/O dialog box appears.
60
Continued on next page
840 USE 116 00 Version 1.0
Accessing and Editing the I/O Map, continued
Chapter 4 Configuring the Module with Concept
Procedure, continued
Step
3
Action
Click on the ... button under Module.
Result: The I/O Module Selection dropdown menu appears.
840 USE 116 00 Version 1.0
Continued on next page
61
Chapter 4 Configuring the Module with Concept
Accessing and Editing the I/O Map, continued
Procedure, continued
Step
4
Action
Click on NOE-771-00 that appears in the Special column and then click on the
<OK> button.
Result: The Local Quantum Drop I/O dialog box reappears and the NOE-771-00 is now listed under Module and is described in the Description column
Next
5
6
Repeat Steps 3 and 4 if other modules need to be added to the I/O map.
Click the <OK> buttons to return to the PLC Configuration screen.
Next, you will configure the Ethernet address parameters from the Ethernet/ I/O
Scanner screen.
62
840 USE 116 00 Version 1.0
Configuring the Ethernet Address Parameters
Chapter 4 Configuring the Module with Concept
Introduction
The NOE 771 x0 module’s Ethernet address parameters, consisting of Internet,
Subnet mask, and Gateway addresses, are accessible from the Ethernet/ I/O
Scanner dialog box. Prior to performing the following procedure, consult your system administrator to determine if you must configure new Ethernet address parameters, or whether the module will obtain them from the BOOTP server.
CAUTION
DUPLICATE ADDRESS HAZARD
Always obtain your IP addresses from your system administrator to avoid the possibility of duplicate addresses. Having two devices with the same IP address can cause unpredictable operation of your network.
Failure to observe this precaution can result in network disruption leading to possible injury or equipment damage.
Procedure
Perform the following steps to configure the Ethernet Address Parameters.
Step
1
Action
From the Configure menu, select Ethernet/ I/O Scanner
840 USE 116 00 Version 1.0
Continued on next page
63
Chapter 4 Configuring the Module with Concept
Configuring the Ethernet Address Parameters, continued
Procedure, continued
Step
1,
(con’t)
Action
Result: The Ethernet/ I/O Scanner dialog box appears.
2 To configure new Ethernet address parameters, click on the Specify IP Address radio button.
64
3
4
Type in the new IP, Subnet Mask, and Gateway addresses in the applicable text boxes.
Select the correct Internet frame type from the Frame Type scroll box.
Continued on next page
840 USE 116 00 Version 1.0
Chapter 4 Configuring the Module with Concept
Configuring the Ethernet Address Parameters, continued
Procedure, continued
Step
5
Action
If the Ethernet address parameters are to be assigned by the module’s BOOTP server, click on the Use Bootp Server radio button
+
Note: If you select this option, the address parameter text boxes will be grayed out and will not display the addresses.
How the Module
Derives It’s IP
Address
+
During initialization, the NOE 771 module attempts to read the address parameter information from the PLC and determines it’s IP Address in the following fashion: z
If the PLC has the IP Address and the BOOTP server is not selected, the module will use the configured IP address that you assigned in Step 2 of the above procedure.
z
If the BOOTP server was selected in Step 5 of the above procedure, the module will send BOOTP requests to receive it’s IP Address.
z
If no Configuration Extension exists, the NOE sends out BOOTP requests. If the module does not receive it’s IP Address from the BOOTP server after 2 minutes, it will then use the IP Address derived from it’s MAC address.
Note: The MAC address is assigned at the factory and is recorded on a label on the front panel, above the cable connector. This is a unique 48-bit global assigned address. It is set in PROM. The Ethernet address is recorded on the label in hexadecimal, in the form 00.00.54.xx.xx.xx
65
840 USE 116 00 Version 1.0
Chapter 4 Configuring the Module with Concept
66
840 USE 116 00 Version 1.0
Transferring Data with the
I/O Scanner
140 NOE 771 00 only
5
At a Glance
Introduction
This chapter discusses the NOE 771 00 module’s I/O scanner capabilities and includes procedures for configuring the I/O scan list using Concept 2.2, ProWORX
NxT 2.1, and Modsoft.
What’s in this
Chapter
This chapter contains the following topics.
Topic
I/O Scanner Concepts
Configuring the I/O Scan List Using Concept
Completing the I/O Configuration
Configuring the I/O Scan List Using ProWORX NxT
Establishing Configuration Extension Memory for Peer Cop
Configuring the I/O Scan List Using Modsoft
Page
68
72
76
79
90
94
67
840 USE 116 00 Version 1.0
Chapter 5 Transfering Data with the I/O Scanner
I/O Scanner Concepts
Introduction
All NOE 771 00 modules provide an I/O scanner which the user configures with the
Concept 2.2, ProWORX NxT 2.1, or Modsoft programming panel. This allows the user a way to configure data and transfer it between network nodes without using the MSTR instruction.
I/O Scan List
The I/O Scanner is a feature of the NOE module, which allows the reading and/or writing to Input/Output devices repetitively.
The I/O scan list is a configuration table which identifies the targets with which repetitive communication is authorized. The list contains enough information for each target to construct the Modbus message addressed to that particular remote device and to designate where on the local controller the input and output data is to be mapped at the end of the scan. While the controller is running the NOE module transfer data to and from the controller’s registers and coils as indicated by the I/O scan list.
The user configures the I/O scan list with the Concept, ProWORX NxT, or Modsoft programming panel. There can be multiple instances of the I/O scan list (Peer
Coop restrictions apply). The individual scan lists for each module are identified by the Quantum backplane slot number where the NOE is installed.
Continued on next page
68
840 USE 116 00 Version 1.0
Chapter 5 Transfering Data with the I/O Scanner
I/O Scanner Concepts, continued
I/O Scanner
Definitions
The following defined terms are used to describe the I/O Scanner operation.
Term
Scan List
Specific Input
Specific Output
Peer Cop
Ethernet I/O Scanner
Definition
The list of input and/or output devices which the NOE module is configured to scan.
Input to the controller, on the backplane where the NOE resides.
Output from the controller, on the backplane where the NOE resides.
Legacy I/O Scanner support to upgrade Modbus Plus I/O applications to Ethernet.
Provides high performance cyclic communication service to the controller.
Peer Cop and
Enhanced
Modbus/TCP
Scanners
The NOE 771 00 module’s design provides you with the ability to configure it’s
Modbus I/O Scanner as either a Peer Cop or Enhanced Modbus scanner. The determination as to which scanner is used depends on the programming package that is installed on your system. If you presently are using Modsoft, than you must configure the I/O Scanner for Peer Cop operation. If your are presently using
Concept 2.2 or ProWORX NxT 2.1, than you can configure the I/O Scanner for either Peer Cop or enhanced Modbus/TCP operation.
Continued on next page
840 USE 116 00 Version 1.0
69
Chapter 5 Transfering Data with the I/O Scanner
I/O Scanner Concepts, continued
Peer Cop I/O
Scanner
Features
The Peer Cop based Modbus I/O Scanner has the following characteristics:
Parameter
Max. No. of Devices
Max. No. of Input Words
Max. No. of Output Words
Value
64
500
500
Timeout Value
Input TimeOutState
Global Setting (20 Msec to 2 Secs in 20 mSec increments)
Global Setting (Zero or Hold)
IP Address Derived from Modbus Address (must be on NOE’s Subnet)
Remote Register Reference Not configurable - 400001 is used
Destination ID
Operation thru a Modbus
Plus to Ethernet bridge
Not settable, set to 0
Not supported
Enhanced
Modbus I/O
Scanner
Features
The Enhanced Modbus I/O Scanner has the following characteristics
Parameter
Max. No. of Devices
Max. No. of Input Words
Max. No. of Output Words
Value
64
4,000
4,000
Timeout Value
Input TimeOutState
Individual Setting (1 Msec to 2 Secs in 1 mSec increments)
Global set to zero. Individual set table with Concept 2.5.
IP Address Individually Settable
Remote Register Reference Configurable
Min. Update Rate
Destination ID
Operation thru a Modbus
Plus to Ethernet bridge
Settable
Not settable, set to 0
Not supported
Continued on next page
70
840 USE 116 00 Version 1.0
Chapter 5 Transfering Data with the I/O Scanner
I/O Scanner Concepts, continued
I/O Scanner
Support
A maximum of two NOE modules can be configured as I/O scanners per controller.
The mix of I/O scanners and NOE modules per CPU is summarized in the following table.
Quantum CPU
Type
No. of
NOEs
Supported
140 CPU 113 02
140 CPU 113 03
140 CPU 213 04
140 CPU 424 02
140 CPU 434 12
140 CPU 534 14
2
2
2
6
6
6
Max No. of NOEs
Configured as
Peer Cop I/O
Scanners
Max No. of NOEs
Configured as
Ethernet I/O
Scanners
2
2
2
2
2
2
2
2
2
6
6
6
840 USE 116 00 Version 1.0
71
Chapter 5 Transfering Data with the I/O Scanner
Configuring the I/O Scan List Using Concept
Introduction
Once the NOE 771 00 has been configured using Concept (see Chapter 4), you can assign parameters for I/O scanning. This involves creating the I/O scan list containing all the input and output devices that the NOE module will scan.
IP Address
Type the IP address of the slave module in the IP address column. This address will be stored in a pulldown menu, so that you may use it in another row by clicking on the down arrow and selecting it, as shown:
Unit ID
If the slave module is an I/O device attached to the specified slave module, use the
Unit ID column to indicate the device number. The Unit ID is used with the Modbus
Plus to Ethernet bridge to route to Modbus Plus networks.
Health Timeout
The Health Timeout is used for setting the health bit. If the response arrives before the HealthTimeout, the health bit is set, otherwise it is cleared. If the Health
Timeout is zero, the health bit is set true once communications is established, and it is never cleared.
Continued on next page
72
840 USE 116 00 Version 1.0
Chapter 5 Transfering Data with the I/O Scanner
Configuring the I/O Scan List Using Concept, continued
Rep Rate
Read
Use this column to specify the lower bound in milliseconds (ms) between transactions to this node. Valid values are 0 ... 65,000 ms (1 min). The NOE module takes this value and rounds up to a multiple of 17 ms. Since the update of I/
O is synchronized to the CPU scan, if the CPU scan is greater than the configured lower bound, then the actual update rate will be at the rate of the CPU scan. To obtain the maximum rate specify a zero.
For example, if a user specifies 10 ms, then it is rounded up to 17 ms. If the controller’s scan time is 5 ms, then the time between transactions must be greater than or equal to 17 ms. On the other hand, if the controller’s scan time is 200 ms, the time between transactions must be greater than or equal to 200 ms.
Use the read function to read data from the remote node. The Read Ref Slave column specifies the first 4x register of the remote node to be read. The Read
Count column specifies the number of registers to read. The Read Ref Master column specifies the local address for the read response.
Continued on next page
840 USE 116 00 Version 1.0
73
Chapter 5 Transfering Data with the I/O Scanner
Configuring the I/O Scan List Using Concept, continued
Write
.
Use the write function to write data to the remote node. The Write Ref Master column specifies the local address of the write data. The Write Count column specifies the number of registers to write. The Write Ref Slave column specifies the first 4x register to be written to the remote node
Read and Write
You may include read and write commands on the same line, as shown:
Description
You can type a brief description (up to 32 characters) of the transaction in the
Description column.
Continued on next page
74
840 USE 116 00 Version 1.0
Chapter 5 Transfering Data with the I/O Scanner
Configuring the I/O Scan List Using Concept, continued
Configuring the
Health Block
The Health Block is located at a block of 3x registers or 1x coils. For 1x coils it must start on a 16-bit boundary. Each device that is configured has a corresponding health bit in the Health Block. If the health bit is one, the remote device is healthy. It the health bit is 0 (zero), the remote device is unhealthy.
Each row that is configured is mapped to a bit position as shown below.
Word 1 Bit Positions
1 2 3 4
Word 2 Bit Positions
5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
Word 3 Bit Positions
33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
Word 4 Bit Positions
49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
Starting Location of Health Block
To specify the starting 1x/3x location of the Health Block, enter the desired address into the Health Block text box as shown below.
840 USE 116 00 Version 1.0
75
Chapter 5 Transfering Data with the I/O Scanner
Completing the I/O Configuration
Introduction
This section describes how to complete your Ethernet I/O configuration using the
Copy, Cut, Paste, Delete, Sort, and Fill Down buttons.
Copy and Paste
To save time when typing similar read and write commands, you may copy and paste entire rows within your configuration. Follow the steps in the table below:
Step
1
Action
Select the row you want to copy by clicking on the row number at the far left.
2
3
4
Click the Copy button above the I/O configuration list.
Select the row where you would like to paste the data (by clicking on the row number at the far left).
Click the Paste button above the I/O configuration list.
76
Continued on next page
840 USE 116 00 Version 1.0
Completing the I/O Configuration, continued
Chapter 5 Transfering Data with the I/O Scanner
Cut and Paste
To move a row within the configuration list, follow the directions for copying, only use the Cut button instead of the Copy button.
Delete
Sort
To delete a row from the configuration list, select the row by clicking on the row number at the far left. Then click the Delete button.
To sort the I/O configuration list, select a column by clicking on the column heading
(i.e.. Read Ref Master). Then click the Sort button.
Continued on next page
840 USE 116 00 Version 1.0
77
Chapter 5 Transfering Data with the I/O Scanner
Completing the I/O Configuration, continued
Fill Down
To copy part of any row to the next row or to a series of adjoining rows, use the Fill
Down button, following the steps in the table below:
Step
1
Action
Use your mouse to select the data you would like to copy and the cells you would like to copy it to.
Note: You must select one contiguous block of cells, with the data to be copied in the first row. You cannot select two separate blocks.
2 Click the Fill Down button.
Result: The data from the first row is copied to the selected cells below.
78
840 USE 116 00 Version 1.0
Chapter 5 Transfering Data with the I/O Scanner
Configuring the I/O Scan List Using ProWORX NxT
Introduction
This section discusses how to configure the NOE 771 module from your programming panel using ProWORX NxT program. This process assumes you have switched to an Ethernet network so you can choose I/O Scanner instead of the Peer Cop. This allows you to configure data blocks to be transferred between controllers on a TCP/IP network.
There are three procedures to the configuration process: z
Selecting Your PLC z
Accessing and Editing the Traffic Cop z
Setting the Number of NOE’s and Configuring the Ethernet Address
Parameters
Continued on next page
840 USE 116 00 Version 1.0
79
Chapter 5 Transfering Data with the I/O Scanner
Configuring the I/O Scan List Using ProWORX NxT, continued
Selecting Your
PLC
Perform the following steps to select a CPU.
Step
1
Action
Open ProWORX NxT on your programming panel (PC).
Result: ProWORX NxT initial screen will appear.
2 From the File menu, select New.
Result: The New dialogue box appears.
80
Continued on next page
840 USE 116 00 Version 1.0
Chapter 5 Transfering Data with the I/O Scanner
Configuring the I/O Scan List Using ProWORX NxT, continued
Selecting Your
PLC
continued
Step
3
Action
Type a file name in the File Name text box. Select the drive from the drop down box labeled “Drivers” . Select the file folder where you want to save the new database labeled “Folders”. Press the <OK> button
Result: The Database Setup screen appears.
4 Fill in the text boxes as you require. Press the <OK> button.
Result: The Select Controller Type dialog box appears.
840 USE 116 00 Version 1.0
Continued on next page
81
Chapter 5 Transfering Data with the I/O Scanner
Configuring the I/O Scan List Using ProWORX NxT, continued
Selecting Your
PLC
continued
Step
5
Action
From the Controller Groups list box on the left, select the Quantum group.
From the Controllers list box on the right, select the CPU that is installed in your Quantum backplane. Click the <OK> button.
Result: The Controller Configuration screen appears.
82
6 You must define a value in the Conf Extension Size on the right side of the
Controller Configuration screen. This value is the amount of memory you require. Press the <OK> button.
Continued on next page
840 USE 116 00 Version 1.0
Chapter 5 Transfering Data with the I/O Scanner
Configuring the I/O Scan List Using ProWORX NxT, continued
Accessing and
Editing the
Traffic Cop
Perform the following steps to access and edit the Traffic Cop.
Step
1
Action
From the Configuration menu, select Traffic Cop.
Result: the Traffic Cop screen appears.
840 USE 116 00 Version 1.0
2 From the Quantum Traffic Cop menu on the left, click the “+” sign to expand the
Traffic Cop tree. Choose the Rack and Slot where you want the NOE 771 module inserted.
Continued on next page
83
Chapter 5 Transfering Data with the I/O Scanner
Configuring the I/O Scan List Using ProWORX NxT, continued
Accessing and
Editing the
Traffic Cop
continued
Step
3
Action
From the Net Adpt menu of the Traffic Cop screen, select NOE 771,
Result: The NOE 771 module is inserted into the specified location, within the
Edit Drop field of the Traffic Cop screen.
84
4 Press the <OK> button.
Continued on next page
840 USE 116 00 Version 1.0
Chapter 5 Transfering Data with the I/O Scanner
Configuring the I/O Scan List Using ProWORX NxT, continued
Setting the
Number of
NOE’s and
Configuring the
Ethernet
Address
Parameters
From the Configuration Expansion screen, follow the steps below to do the following: z
Select the number of NOE 771 modules z
Configure the Ethernet Address Parameters, TCP/IP
Step
1
Action
From the Configuration menu, select Config Extensions.
Result: The Config Extension screen appears.
840 USE 116 00 Version 1.0
Continued on next page
85
Chapter 5 Transfering Data with the I/O Scanner
Configuring the I/O Scan List Using ProWORX NxT, continued
Setting the
Number of
NOE’s and
Configuring the
Ethernet
Address
Parameters
continued
Step
2
Action
Click the Add Extension button.
Result: The Add Configuration Extension dialog box appears.
3 Select TCP/IP from the list and click the <OK> button.
Result: The TCP/IP Configuration Extension is added to the left menu of the Configuration Extensions screen.
86
Continued on next page
840 USE 116 00 Version 1.0
Chapter 5 Transfering Data with the I/O Scanner
Configuring the I/O Scan List Using ProWORX NxT, continued
Setting the
Number of
NOE’s and
Configuring the
Ethernet
Address
Parameters
continued
Step
4
Action
Click the TCP/IP Config Extension in the left menu.
Result: The details of the TCP/IP configuration appear on the right of the
Configuration Extension screen.
5
Select the Card Number (Rack Number) by pressing the
840 USE 116 00 Version 1.0
6 button in the Card Number combo box.
Complete the fields for each Card Number. The Head Number text box represents the Rack in which the NOE 771 module is located.
Click the <OK> button when complete.
Continued on next page
87
Chapter 5 Transfering Data with the I/O Scanner
Configuring the I/O Scan List Using ProWORX NxT, continued
Setting Up the
I/O Scanner
Using ProWORX
NxT
At this point you are ready to set up the I/O Scanner. The I/O Scanner provides data transfer between two or more NOE 771 00 and other Modbus or TCP/IP devices. It allows you to simultaneously configure up to 64 connections. To configure the I/O Scanner, follow the steps below to do the following: z
Specify the specific I/O groups to be scanned z
Configure the transaction parameters z
Set the hardware clock for when the data is to be collected
Specify the
Specific I/O
Groups to be
Scanned
Follow the steps below to specify the I/O groups to be scanned:
Step
1
2
3
4
5
Action
From the Network Editor, on the Configuration menu, click Config
Extensions. The Configurations Extensions dialog box appears.
In the Config Extensions tree, right-click on Config Extensions and select Add
Extension.
Select Ethernet I/O Scanner. The parameters for the CDE appear in the details area.
In the Health Block field, type a 1xxxxx or 3xxxxx address.
Note: All 1xxxxx addresses are based on a 16-bit boundary. For example: 100001, 100017, 100033, etc.
Double-click on an empty transaction to add a new transaction or double-click on an existing transaction to edit it. The Transaction dialog box appears.
Continued on next page
88
840 USE 116 00 Version 1.0
Chapter 5 Transfering Data with the I/O Scanner
Configuring the I/O Scan List Using ProWORX NxT, continued
Configure the
Transaction
Parameters
Follow the steps below to configure the transaction parameters:
Step
1
2
Action
Double-click on an empty transaction to add a new transaction or double-click on an existing transaction to edit it. The Transaction dialog box appears.
Configure the transaction parameters.
840 USE 116 00 Version 1.0
89
Chapter 5 Transfering Data with the I/O Scanner
Establishing Configuration Extension Memory for Peer Cop
Introduction
By default, the Peer Cop capability is disabled. If you want to use Peer Cop to handle Modbus Plus communications, you need to enable this capability and adjust the amount of configuration extension memory.
Note: If you are upgrading your network to Ethernet, you should consider the option of ignoring Peer Cop and instead, configuring extension memory to use the enhanced Modbus/TCP IO Scanner feature of your NOE 771 00 module. (See
Chapter 6.)
How Much
Memory?
The minimum Peer Cop memory requirement is 20 words; the maximum is 1366 words.
Follow these guidelines for estimating the amount of extension memory you will need for your Peer Cop database:
For...
Overhead
Global output
Global input
Specific output
Specific input
Add...
9 words
5 words number of words= number of devices x
(1 + 2 x number of device subentries)
Up to a maximum of...
--
--
1088 words
2 words for every device entry in Peer Cop 128 words
2 words for every device entry in Peer Cop 128 words
Continued on next page
90
840 USE 116 00 Version 1.0
Chapter 5 Transfering Data with the I/O Scanner
Establishing Configuration Extension Memory for Peer Cop, continued
Procedure
From the PLC Configuration screen, follow the steps below to enable Peer Cop and adjust the amount of Configuration Extension memory.
Step
1
Action
From the Configure menu, select Config extensions or, double-click anywhere in the Config Extensions region of the screen.
840 USE 116 00 Version 1.0
Result: The Configuration Extension dialog box appears.
Continued on next page
91
Chapter 5 Transfering Data with the I/O Scanner
Establishing Configuration Extension Memory for Peer Cop, continued
Procedure,
continued
Step
2
Action
Click on the check box next to Peer Cop, then click the <OK> button.
Result: Peer Cop status changes from Disabled to Enabled in the PLC
Configuration screen.
Continued on next page
92
840 USE 116 00 Version 1.0
Chapter 5 Transfering Data with the I/O Scanner
Establishing Configuration Extension Memory for Peer Cop, continued
Procedure,
Continued
Step
3
Action
From the Configure menu, select Peer Cop.
Result: The Peer Cop dialog box appears.
840 USE 116 00 Version 1.0
4
5
Modify the amount of configuration extension memory allocated to Peer Cop by typing a new value in the Expansion Size field or, by adjusting the sliding scale next to the field.
Click the <OK> button.
93
Chapter 5 Transfering Data with the I/O Scanner
Configuring the I/O Scan List Using Modsoft
Introduction
The Peer Cop input screens in the Modsoft program will be used to configure the
I/O scan list.
The Peer Cop configuration extension allows you to configure certain continuous, fixed format communications between the controller (in which its is defined) and all other nodes on the same subnet.
Each Peer Cop configured communication specifies a source data block. The source data block is of fixed location and length and is continuously moved, to a fixed destination data block. This data transfer type is useful for transferring state information between controllers and for communicating with slave devices on the
Ethernet.
Peer Cop communication is not appropriate for sequence dependent communication that must be performed exactly once. The standard MSTR element is used for those logic dependent requirements with certain restrictions.
Like the I/O Map, the Peer Cop can only be configured with the controller stopped.
Once the PLC is configured and started, the transfers are performed automatically.
A menu item in the Peer Cop is available to delete the current node on the screen.
A warning is given and the node is deleted if (Y) is answered. If the last node is deleted, a window opens to allow entry of a node. This condition is identical to the initial screen of an empty Peer Cop.
Continued on next page
94
840 USE 116 00 Version 1.0
Chapter 5 Transfering Data with the I/O Scanner
Configuring the I/O Scan List Using Modsoft, continued
Current
Limitations
The following table describe the limitations of the operating parameters, as well as, the recommended settings for other parameters.
Parameter
Maximum Input Length
Maximum Output Length 32 Words
Total I/O Scan Data Length 500 Words
IP Address
Limitation/Special Recommendation
32 Words
An I/O device is currently limited to having an IP address in the form of AAA.BBB.CCC.DDD, where AAA.BBB.CCC are the same as the NOE’s IP address and the subnet address of
DDD is limited to 1 ... 64
Not supported Operation thru a Modbus
Plus to Ethernet bridge
Destination ID Not user supportable; fixed at 0
Storage
Requirements
Before selecting Peer Cop from the Cfg Ext pulldown list, you must use ExtSize to set the memory storage requirements.
Note: The remainder of the CfgExt pulldown functions remain disabled until the
ExtSize is set.
Continued on next page
840 USE 116 00 Version 1.0
95
Chapter 5 Transfering Data with the I/O Scanner
Configuring the I/O Scan List Using Modsoft, continued
Storage
Requirements, continued
z
There are four types of Peer Cop requests: z
Global data input (not supported) z
Global data output (not supported) z
Specific data input z
Specific data output
CAUTION
GLOBAL DATA EXTENSION HAZARD
For the Ethernet TCP/IP network operations, only the specific data input and output are supported. Do not fill in the Global input or Global output. The NOE ignores global data configuration.
Failure to observe this precaution can result in injury or equipment damage.
Depending on your requirements you can estimate the memory needed where: z
If Specific Output is configured, then add 2 words for each device entry (64 maximum. Maximum is 64 x 2 = 128 words z
If Specific Input is configured, then add 2 words for each device entry (64 maximum). Maximum is 64 x 2 = 128 words. Based on the above, the minimum size Peer Cop could be 20 words while the maximum could be 1366 words for each of up to 3 links.
Specific
Input/Output
Configuration
The default screen for Peer Cop entry is labeled “Peer Cop” (see figure on next page). The screen is a data entry template comprising all four data types and providing a summary of settings that apply to the specific link/node as well as timeout, error handling and statement of memory words used.
96
840 USE 116 00 Version 1.0
Chapter 5 Transfering Data with the I/O Scanner
Configuring the I/O Scan List Using Modsoft, continued
Specific
Input/Output
Configuration, continued
Summary
Information
The cursor is initially in the Head Slot field. If you are not editing an initial template you may press the Esc key which re-positions the cursor to the SPECIFIC INPUT field. To traverse the Heads and Nodes you can re-display the Add Node select box from the main Menu line.
Specific Output
Specific output comes from the Controller, located in the same rack, where the
NOE resides. Specific out data can be set from the NOE to the remote node on the subnet by a Modbus Write. The source of each specific output block is a contiguous region of 0x, 1x, 3x or 4x state RAM, which varies from 1 to 32 words in length. If discretes are used, they must start on a word boundary (00001, 00017, 00033, etc.).
The Type default (BIN or BCD) is put in by the controller. Where different types can be specified, you make the entry from a display list displayed by keying the return key while the cursor is on the TYPE field.
Note: The NOE 771 00 ignores the BIN BCDs setting and always uses a BIN format.
Continued on next page
840 USE 116 00 Version 1.0
97
Chapter 5 Transfering Data with the I/O Scanner
Configuring the I/O Scan List Using Modsoft, continued
Specific Input
Specific input goes to the Controller in which the NOE resides. NOE obtains specific input data from a remote node on the subnet with a Modbus read. You can specify all Specific Input blocks, sent to this controller, from the specified other stations on the node. The destination of each block of specific input is a contiguous region of 0x, 1x, 3x or 4x state RAM, which varies from 1 to 32 words in length. If discretes are used, they must start on a word boundary (00001, 00017, 00033, etc.).
98
In the above figure, the Quantum NOE is configured to write 1 word from 400050, to the Momentum EIO at IP Address 198.202.137.2, and read 1 word from the EIO into register 400100.
The Modsoft menu that reflects the above situation, is shown on the figure appearing on the next page. It provides an example of the Length, Source and
Type data fields and illustrates the above example completely filling in the template fields.
Continued on next page
840 USE 116 00 Version 1.0
Chapter 5 Transfering Data with the I/O Scanner
Configuring the I/O Scan List Using Modsoft, continued
Specific Input, continued
.
Specific Input/
Output Summary
Given the proper configuration, if you complete the above template for node 2 with a specific input of length of 1 and Specific output Length of 1 will result in: z reading of 1 word from node 2, destination of data is 400100 z writing of 1 word to node 2, source of data is 400050
Other Menu
Selectable
Support
Functions
In addition to the Standard Utility Menu line entry, you have Peer Cop related functions available from the
GoToNode,AddNode,Timeout
and
OnError
entries.
The GoToNode
Function
GoToNode
- Displays the Peer Cop menu that allows you to configure that node.
This function has a pulldown as shown in the figure on the following page.
Continued on next page
840 USE 116 00 Version 1.0
99
Chapter 5 Transfering Data with the I/O Scanner
Configuring the I/O Scan List Using Modsoft, continued
The GoToNode
Function, continued
If you select GoToNode and the node number you enter is not found you are asked if it should be created for you. You can also transverse the node structure using the PgUp and Pg dn keys.
The AddNode
Function
This is very similar to GoToNode in that you select the Link and Node number that you want to add parameters for.
The Timeout
Function
100
This field allows you to specify a value for the Health Time–out interval. The default value is 500 Milliseconds. You can change it to any value in the range of 60ms. to 2 seconds. The value you use specifies the minimum time period that a Peer Cop configured communication must fail before the associated health bit is cleared. You should choose values in 20 ms. increments to account for implementation latency i.e., the configured time plus the time to assure the health bit is cleared.
For example, if your choice is 60 ms. the health bit is cleared no sooner than 60 ms. and no later than 79 ms. after communication has been lost.
Continued on next page
840 USE 116 00 Version 1.0
Chapter 5 Transfering Data with the I/O Scanner
Configuring the I/O Scan List Using Modsoft, continued
Health Bits
There is a health bit for each Peer Copped node. If Peer Cop Data is successfully communicated within the set timeout, the associated bit is set to 1. Otherwise, it is set to 0 and all data associated with that group is cleared (to 0). You must use the
MSTR element with proper sub-function code (0009) to retrieve the peer cop health information. (See Peer Cop Health MSTR Operation in Chapter 6.)
Note: All configured Specific output health bits are initialized to 1 for the first few scans to allow complete synchronization between controller, health bit time factor and line latency
OnError
Function
Device IP
Address
Generation
You have the choice of Clearing (CLEAR) the last set of received values or retaining the last set of received values (HOLD) if any error is detected.
z
DelNode - Once Deleted, you can re-enter node information, or you can exit.
Exit with the node deleted removes it. When the
DelNode
is selected, and the
Key Verification UPF entry is selected, you are prompted to confirm the intent to clear the node. The default will be
“N”
for NO. Pressing
“
Y”
for YES and
Enter
will perform the clear
The IP addresses of the I/O devices in the Scan Table are calculated from the
Modbus Address entered in the Peer Cop Configuration Extension, as well as, the
IP address of the NOE. Currently, the I/O devices are required to be on the same subnet as the NOE. The device’s IP address is calculated by AND’ing the NOE’s IP address with the NOE’s subnet mask, and then OR’ing the result with the devices’s
MB address from the configuration extension table.
The following example illustrates the device IP generation.
NOE IP Address:
Subnet Mask:
Device’s Modbus
Address from
Configuration Extension
(Range of 1 ... 64):
Resulting Device
IP Address:
AAA.BBB.CCC.DDD
255.255.255.0
MB
AAA.BBB.CCC.MB
840 USE 116 00 Version 1.0
101
Chapter 5 Transfering Data with the I/O Scanner
102
840 USE 116 00 Version 1.0
Transferring Data with the MSTR
Instruction
6
At a Glance
Introduction
This chapter describes how to transfer data to and from nodes on a TCP/IP network through the use of a special MSTR (master instruction). Included in this chapter are the operational statistics and error codes for reading and writing the controller information.
What’s in this
Chapter
This chapter contains the following topics.
Topic
MSTR Description
MSTR Characteristics
MSTR Ladder Logic Representation
MSTR Function Error Codes
Read and Write MSTR Operations
Get Local Statistics MSTR Operation
Clear Local Statistics MSTR Operation
Get Remote Statistics MSTR Operation
Clear Remote Statistics MSTR Operation
Peer Cop Health MSTR Operation
Reset Option Module MSTR Operation
Read CTE (Config Extension Table) MSTR Operation
Write CTE (Config Extension Table) MSTR Operation
TCP/IP Ethernet Statistics
Page
115
116
120
121
123
125
111
112
113
114
104
105
106
108
840 USE 116 00 Version 1.0
103
Chapter 6 Transfering Data with the MSTR Instruction
MSTR Description
Introduction
All NOE 771 x0 Quantum Ethernet TCP/IP modules provide the user with the capability of transferring data to and from nodes on a TCP/IP network through the use of a special MSTR (master instruction). All PLCs that support networking communication capabilities over Modbus Plus and Ethernet can use the MSTR ladder logic instruction to read or write controller information.
MSTR
Operations
The MSTR instruction allows you to initiate one of 12 possible network communications operations over the network. Each operation is designated by a code. The following table lists the 12 operations and indicates those that are supported on an Ethernet TCP/IP network.
MSTR Operation TCP/IP Ethernet Support
Write data
Read Data
Get local statistics
Clear local statistics
Write global database
Read global database
Get remote statistics
Clear remote statistics
Peer Cop health
Reset Option Module
Read CTE(config extension)
Write CTE (config extension)
7
8
9
10
11
12
5
6
3
4
1
2
Operation
Type
supported supported supported supported not supported not supported supported supported supported supported supported supported
No. of MSTR
Instructions
Allowed
Up to16 MSTR instructions can be simultaneously serviced in a ladder logic program per NOE. More than 16 MSTRs may be programmed to be enabled by the logic flow as one active MSTR block releases the resources it has been using and becomes deactivated, the next MSTR operation encountered in logic can be activated.
104
840 USE 116 00 Version 1.0
Chapter 6 Transfering Data with the MSTR Instruction
MSTR Characteristics
MSTR
Characteristics
The characteristics of the MSTR instruction are described below.
Size: Three nodes high
PLC Compatibility: z
Standard in PLCs that have built-in Modbus Plus capabilities (Modbus Plus functionality only) z
Standard in all Quantum PLCs with Modbus Plus functionality and/or TCP/IP
Ethernet option modules z
Available as a loadable in chassis mount PLCs (Modbus Plus functionality only)
Opcode: BF hex
840 USE 116 00 Version 1.0
105
Chapter 6 Transfering Data with the MSTR Instruction
MSTR Ladder Logic Representation
Ladder Logic
Diagram
The MSTR Block is represented in Ladder Logic diagrams as shown in the figure below and described the in the paragraphs that follow the figure.
Enables selected
MSTR operation
Operation is active
Terminates active
MSTR operation control block data area
MSTR
length
Operation terminated unsuccessfully
Operation successful
Inputs
Outputs
The MSTR instruction has two control inputs: z the input to the top node enables the instruction when it is ON z the input to the middle node terminates the active operation when it is ON
The MSTR instruction can produce three possible outputs: z the output from the top node echoes the state of the top input - it goes ON while the instruction is active z the output from the middle node echoes the state of the middle input - it goes
ON if the MSTR operation is terminated prior to completion or if an error occurs in completing the operation z the output from the bottom node goes ON when an MSTR operation has been completed successfully
All outputs are zero is an indication that four MSTR instructions are already in progress.
Continued on next page
106
840 USE 116 00 Version 1.0
Chapter 6 Transfering Data with the MSTR Instruction
MSTR Ladder Logic Representation, continued
Top Node
Content
The 4x register entered in the top node is the first of several (network dependent) holding registers that comprise the network control block. The control block structure differs according to the network in use. For the TCP/IP Ethernet network the control block structure is as follows:
Register
Displayed
First implied
Second implied
Third implied
Fourth implied
Fifth implied
Sixth implied
Seventh implied
Eight implied
Content
Identifies one of ten MSTR operations legal for TCP/IP
(1 ... 4 and 7 ... 12).
Displays error status.
Displays length (number of registers transferred).
Displays MSTR operation-dependent information.
High byte: Destination index.
Low byte: Quantum backplane slot address of the NOE module.
Byte 4 of the 32-bit destination IP Address.
Byte 3 of the 32-bit destination IP Address.
Byte 2 of the 32-bit destination IP Address.
Byte 1 of the 32-bit destination IP Address.
Middle Node
Content
The 4x register entered in the middle node is the first in a group of contiguous holding registers that comprise the data area. For operations that provide the communication processor with data such as a Write operation, the data area is the source of the data. For operations that acquire data from the communication processor, such as a Read operation, the data area is the destination for the data.
In the case of the Ethernet Read and Write CTE operations (see pages 121 and
123), the middle node stores the contents of the Ethernet configuration extension table in a series of registers.
Bottom Node
Content
The integer value entered in the bottom node specifies the length - the maximum number of registers in the data area. The length must be in the range 1 ... 100.
840 USE 116 00 Version 1.0
107
Chapter 6 Transfering Data with the MSTR Instruction
MSTR Function Error Codes
Where Displayed
If an error occurs during an MSTR operation, a hexadecimal error code will be displayed in the first implied register in the control block (the top node). Function error codes are network-specific.
TCP/IP Ethernet
Error Codes
An error in an MSTR routine over TCP/IP Ethernet may produce one of the following errors in the MSTR control block:
2003
2004
2005
2006
3000
30ss*
4001
F001
Hex Error Code Meaning
1001 User has aborted the MSTR element.
2001
2002
An unsupported operation type has been specified in the control block .
One or more control block parameters has been changed while the
MSTR element is active (applies only to operations that take multiple scans to complete). Control block parameters may be changed only when the MSTR element is not active.
Invalid value in the length field of the
Invalid value in the offset field of the control block .
control block .
Invalid values in the length and offset fields of the
Invalid slave device data area.
Generic Modbus fail code.
Modbus slave exception response.
Inconsistent Modbus slave response.
Option Module not responding control block .
* The ss subfield in error code 30ss is shown in the following table
.
04
05
06
ss Hex value
01
02
03
07
Meaning
Slave device does not support the requested operation.
Nonexistent slave device registers requested.
Invalid data value requested.
Slave has accepted long-duration program command.
Function can’t be performed now; a long-duration command is in effect.
Slave rejected long-duration program command.
Continued on next page
108
840 USE 116 00 Version 1.0
Chapter 6 Transfering Data with the MSTR Instruction
MSTR Function Error Codes, continued
TCP/IP Ethernet
Network Errors
An error on the TCP/IP Ethernet network itself may produce one of the following errors in the MSTR control block:
31
32
33
34
2D
2E
2F
30
35
36
37
29
2A
2B
2C
16
17
20
28
09
0C
0D
11
Hex Error Code Meaning
04 Interrupted system call.
05
06
I/O error.
No such address.
The socket descriptor is invalid.
Not enough memory.
Permission denied.
Entry exists.
An argument is invalid.
An internal table has run out of space.
The connection is broken.
Destination address required
Protocol wrong type for socket
Protocol not available
Protocol not supported
Socket type not supported
Operation not supported on a socket
Protocol family not supported
Address family not supported
Address already in use
Can’t assign requested address
Socket operation on a non-socket
Network is unreachable
Network dropped connection on reset
Network caused connection abort
Connection reset by peer
No buffer space available
Continued on next page
840 USE 116 00 Version 1.0
109
Chapter 6 Transfering Data with the MSTR Instruction
MSTR Function Error Codes, continued
TCP/IP Ethernet
Network Errors,
continued
Hex Error Code Meaning
44
45
46
47
40
41
42
43
3C
3D
3E
3F
38
39
3A
3B
Socket is already connected
Socket is not connected
Can’t send after socket shutdown
Too many references, can’t splice
Connection timed-out
Connection refused
Network is down
Text file busy
Too many levels of links
No route to host
Block device required
Host is down
Operation now in progress
Operation already in progress
Operation would block
Function not implemented
CTE Error Codes
The following error codes are returned if there is a problem with the Ethernet configuration extension table (CTE) in your program configuration.
Hex Error Code Meaning
7001 There is no Ethernet configuration extension.
7002
7003
The CTE is not available for access.
The offset is invalid.
7004
7005
The offset + length is invalid.
Bad data field in the CTE.
110
840 USE 116 00 Version 1.0
Chapter 6 Transfering Data with the MSTR Instruction
Read and Write MSTR Operations
Introduction
An MSTR Write operation (operation type 1 in the displayed register of the top node) transfers data from a master source device to a specified slave destination device on the network. An MSTR Read operation (operation type 2 in the displayed register of the top node) transfers data from a specified slave source device to a master destination device on the network. Read and Write use one data master transaction path and may be completed over multiple scans
Note: TCP/IP Ethernet routing must be accomplished via standard third-party
Ethernet IP router products.
Control Block
Utilization
The registers in the MSTR control block (the top node) contain the Read or Write information as described in the following table:
Register
Displayed
First Implied
Register
Second implied
Third implied Slave device data area
Fourth implied Low byte
Fifth ... eighth implied
Function
Operation Type
Error status
Function
Length
Destination
Content
1 = Write, 2 = Read.
Displays a hex value indicating an MSTR error.
Exception response, where response size is incorrect.
Exception code
+ 3000
Exception response where response size is incorrect.
4001
Read Write
Content
Write = number of registers to be sent to slave.
Read = number of registers to be read from slave.
Specifies starting 4x register in the slave to be read from or written to (1 = 4001, 49 =40049).
Quantum backplane slot address of the NOE module.
Each register contains one byte of the 32-bit IP address.
840 USE 116 00 Version 1.0
111
Chapter 6 Transfering Data with the MSTR Instruction
Get Local Statistics MSTR Operation
Introduction
The Get Local Statistics operation (operation type 3 in the display register of the top node) obtains information related to the local node where the MSTR has been programmed. (See page 125 for a listing of the TCP/IP Ethernet Network
Statistics).
Control Block
Utilization
The registers in the MSTR control block (the top node) contain the Get Local
Statistics information as described in the following table
Register
Displayed
First implied
Function
Operation Type
Error status
Second implied Length
Third implied Offset
Fourth implied Low byte
Content
3
Displays a hex value indicating an MSTR error, when relevant.
Starting from offset , the number of words of statistics from the local processor’s statistics table; the length must be > 0 < data area .
An offset value relative to the first available word in the local processor’s statistics table. If the offset is specified as 1, the function obtains statistics starting with the second word in the table.
Quantum backplane slot address of the NOE module.
Fifth .. Eighth implied
Not applicable
112
840 USE 116 00 Version 1.0
Chapter 6 Transfering Data with the MSTR Instruction
Clear Local Statistics MSTR Operation
Introduction
The Clear LocalStatistics operation (operation type 4 in the displayed register of the top node) clears statistics relative to the local node where the MSTR has been programmed.
Control Block
Utilization
The registers in the MSTR control block (the top node) contain the Clear Local
Statistics information as described in the following table
Register
Displayed
First implied
Function
Operation Type
Error status
Content
4
Displays a hex value indicating an MSTR error, when relevant.
Second implied Not applicable
Third implied Not applicable
Fourth implied Low byte Quantum backplane slot address of the NOE module.
Fifth ... Eighth implied
Not applicable
840 USE 116 00 Version 1.0
113
Chapter 6 Transfering Data with the MSTR Instruction
Get Remote Statistics MSTR Operation
Introduction
Control Block
Utilization
The Get Remote Statistics operation (operation type 7 in the displayed register of the top node) obtains information relative to remote nodes on the network. This operation may require multiple scans to complete and does not require a master data transaction path. (See page 125 for a listing of the TCP/IP Ethernet Network
Statistics).
The remote Ethernet module always returns its complete statistics table when a request is made, even if the request is for less than the full table. The MSTR instruction then copies only the amount of words you have requested to the designated 4x registers.
Note: TCP/IP Ethernet routing must be accomplished via standard third-party
Ethernet IP router products.
The registers in the MSTR control block (the top node) contain the Get Remote
Statistics information as described in the following table:
Register
Displayed
First implied
Function
Operation Type
Error status
Second implied Length
Third implied Offset
Fourth implied High byte
Fifth ... Eighth implied
Destination
Content
7
Displays a hex value indicating an MSTR error, when relevant.
Starting from an offset , the number of words of statistics from the local processor’s statistics table. The length must be > 0 < data area
.
Specifies an offset value relative to the first available word in the local processor’s statistics table. If the offset is specified as 1, the function obtains statistics starting with the second word in the table.
Destination index.
Each register contains one byte of the 32-bit IP address.
114
840 USE 116 00 Version 1.0
Clear Remote Statistics MSTR Operation
Chapter 6 Transfering Data with the MSTR Instruction
Introduction
The Clear Remote Statistics operation (operation type 8 in the displayed register of the top node) clears statistics relative to a remote network node from the data area in the local node. This operation may require multiple scans to complete and uses a single data master transaction path.
Control Block
Utilization
The registers in the MSTR control block (the top node) contain the Clear Remote
Statistics information as described in the following table.
Register
Displayed
First implied
Function
Operation Type
Error status
Content
8
Displays a hex value indicating an MSTR error, when relevant.
Second implied Not applicable
Third implied Not applicable
Fourth implied High byte
Fifth ... Eighth implied
Destination
Destination index.
Each register contains one byte of the 32-bit IP address.
840 USE 116 00 Version 1.0
115
Chapter 6 Transfering Data with the MSTR Instruction
Peer Cop Health MSTR Operation
Introduction
The Peer Cop Health operation (operation type 9 in the displayed register of the top node) reads selected data from the peer cop communications health table and loads that data to specified 4x registers in state RAM. The Peer Cop communications health table is12 words long, and the words are indexed via this
MSTR operation as words 0 ... 11.
Note: The Peer Cop Health MSTR block is only operational when a Peer Cop based I/O Scanner has been configured.
Control Block
Utilization
The registers in the MSTR control block (the top node) contain information for a
Peer Cop Health operation as described in the following table:
Register
Displayed
First implied
Function
Operation Type
Error status
Second implied Data Size
Third implied Index
Fourth implied Low byte
Content
9
Displays a hex value indicating an MSTR error, when relevant.
Number of words requested from Peer Cop table
(range 1 ... 12).
First word from the table to be read (range 0 ...
11, where 0 = the first word in the Peer Cop table and 11 = the last word in the table).
Quantum backplane slot address of the NOE module.
Fifth ... Eighth implied
Destination Each register contains one byte of the 32-bit IP address.
Continued on next page
116
840 USE 116 00 Version 1.0
Chapter 6 Transfering Data with the MSTR Instruction
Peer Cop Health MSTR Operation, continued
Peer Cop
Communications
Health Status
Information
The Peer Cop communications health table (shown on next page) comprises 12 contiguous register that can be indexed in an MSTR operation as words 0 ... 11.
Each bit in each of the table words is used to represent an aspect of communications health relative to a specific node on the TCP/IP network: z
The bits in words 0 ... 3 represent the health of the global input communication expected from nodes 1 ... 64. Since global input is not supported these bits are set to zero. z
The bits in words 4 ... 7 represent the health of the output from a specific node. z
The bits in words 8 ... 11 represent the health of the input to a specific node.
Continued on next page
840 USE 116 00 Version 1.0
117
Chapter 6 Transfering Data with the MSTR Instruction
Peer Cop Health MSTR Operation, continued
Peer Cop
Communications
Health Status
Information,
continued
Type of
Status
Word
Index
Global
Input
0
1
Bit-To-Network Node Relationship
0
0
0 0 0 0 0 0 0 0
0 0 0 0 0 0
0 0 0 0 0 0 0
2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
3
Specific
Output
4
5
6
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
3 2 3 1 3 0 2 9 2 8 2 7 2 6 2 5 2 4 2 3 2 2 2 1 2 0 1 9 1 8 1 7
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
7
Specific
Input
8
9
16 15 14 13 12 11 10 9 8
7
6
5 4 3 2
1
3 2 3 1 3 0 2 9 2 8 2 7 2 6 2 5 2 4 2 3 2 2 2 1 2 0 1 9 1 8 1 7
10
11
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
Continued on next page
118
840 USE 116 00 Version 1.0
Chapter 6 Transfering Data with the MSTR Instruction
Peer Cop Health MSTR Operation, continued
Peer Cop
Communications
Health Bit State
The state of a Peer Cop health bit reflects the current communication status of its associated node: z
A health bit is set when data is successfully exchanged with its corresponding node.
z
A health bit is cleared when no communication has occurred with the corresponding node within the configured Peer Cop health time-out period.
z
All health bits are cleared at PLC start time. The health bit for a given node is always zero when its associated Peer Cop entry is null.
z
All global health bits are always reported as zero.
840 USE 116 00 Version 1.0
119
Chapter 6 Transfering Data with the MSTR Instruction
Reset Option Module MSTR Operation
Introduction
The Reset Option Module operation (operation type 10 in the displayed register of the top node) causes a Quantum NOE option module to enter a reset cycle to reset its operational environment.
Control Block
Utilization
The registers in the MSTR control block (the top node) contain the Reset Option
Module information as described in the following table:
Register
Displayed
First implied
Function
Operation Type
Error status
Content
10
Displays a hex value indicating an MSTR error, when relevant.
Second implied Not applicable
Third implied Not applicable
Fourth implied Low byte Quantum backplane slot address of the NOE module.
Fifth ... Eighth implied
Not applicable
120
840 USE 116 00 Version 1.0
Chapter 6 Transfering Data with the MSTR Instruction
Read CTE (Config Extension Table) MSTR Operation
Introduction
The Read CTE operation (operation type 11 in the displayed register of the top node) reads a given number of bytes from the Ethernet configuration extension table to the indicated buffer in PLC memory. The bytes to be read begin at a byte offset from the beginning of the CTE. The content of the Ethernet CTE table is displayed in the middle node of the MSTR block.
Control Block
Utilization
The registers in the MSTR control block (the top node) contain the Read CTE information as described in the following table:
Register
Displayed
First implied
Function
Operation Type
Error status
Content
11
Displays a hex value indicating an MSTR error, when relevant.
Second implied Not applicable
Third implied Not applicable
Fourth implied Low byte Quantum backplane slot address of the NOE module.
Fifth ... Eight implied
Not applicable
Continued on next page
840 USE 116 00 Version 1.0
121
Chapter 6 Transfering Data with the MSTR Instruction
Read CTE (Config Extension Table) MSTR Operation, continued
CTE Display
Implementation
The values in the Ethernet configuration extension table (CTE) are displayed in a series of registers in the middle node of the MSTR instruction when a Read CTE operation is implemented. The middle node contains the first of 11 contiguous 4x registers. The registers display the following CTE data:
Parameter
Frame type
IP Address
Subnetwork mask
Gateway
Register
Displayed
First implied
Second implied
Third implied
Fourth implied
Fifth implied
Sixth implied
Seventh implied
Eighth implied
Ninth implied
Tenth implied
Eleventh implied
Content
1 = 802.3
2 = Ethernet
First byte of the IP address
Second byte of the IP address
Third byte of the IP address
Fourth byte of the IP address
Hi word
Low word
First byte of the gateway
Second byte of the gateway
Third byte of the gateway
Fourth byte of the gateway
High byte Low byte
Software defined Module Type
(Ignored by M1 and NOE modules)
0 = NOE211
1 = NOE251
2 = NOE77100
3 = NOE77110
4 = M1
IP Address Algorithm
0: Take IP Address from above definition (default)
(All modules support this)
1: Always take IP Address from
BOOTP Server
(M1 and NOE 771 x0 support this)
2: Disable Ethernet functionality
(M1 only)
122
840 USE 116 00 Version 1.0
Chapter 6 Transfering Data with the MSTR Instruction
Write CTE (Config Extension Table) MSTR Operation
CTE Write
Implementation
The Write CTE operation writes an indicated number of bytes from PLC memory, starting at a specified byte address, to an indicated Ethernet configuration extension table at a specified offset. The content of the Ethernet CTE table is contained in the middle node of the MSTR block.
Network
Implementation
The Write CTE operation (type 12 in the displayed register of the top node) can be implemented for TCP/IP Ethernet networks, via the appropriate network adapter.
Note: Modbus Plus networks do not use this operation.
Control Block
Utilization
In a Write CTE operation, the registers in the MSTR control block (the top node) differ according to the network in user. The following table displayed the registers in the Control Block for TCP/IP Ethernet:
Register
Displayed
First implied
Second implied
Third implied
Function
Operation type
Error status
Not applicable
Content
12
Displays a hex value indicating an MSTR error, when relevant
Fourth implied
Map index
Slot ID
Either a value displayed in the high byte of the register or not used
Number displayed in the low byte, in a range
1 ... 16 indicating the slot in the local backplane where the option resides.
Fifth ... Eighth implied Not applicable
Continued on next page
840 USE 116 00 Version 1.0
123
Chapter 6 Transfering Data with the MSTR Instruction
Write CTE (Config Extension Table) MSTR Operation, continued
CTE Display
Implementation
The values in the Ethernet configuration extension table (CTE) are displayed in a series of registers in the middle node of the MSTR instruction when a Write CTE operation is implemented. The middle node contains the first of 11 contiguous 4x registers. The registers display the following CTE data:
Parameter
Frame type
Register
Displayed
Content
1 = 802.3
IP Address
Subnetwork mask Fifth implied
Gateway
First implied
Second implied
Third implied
Fourth implied
Sixth implied
Seventh implied
Eighth implied
Ninth implied
Tenth implied
2 = Ethernet
First byte of the IP address
Second byte of the IP address
Third byte of the IP address
Fourth byte of the IP address
Hi word
Low word
First byte of the gateway
Second byte of the gateway
Third byte of the gateway
Fourth byte of the gateway
Eleventh implied
High byte
Software defined Module Type
(Ignored by M1 and NOE modules)
0 = NOE211
1 = NOE251
2 = NOE77100
3 = NOE77110
4 = M1
Low byte
IP Address Algorithm
0: Take IP Address from above definition (default)
(All modules support this)
1: Always take IP Address from
BOOTP Server
(M1 and NOE 771 x0 support this)
2: Disable Ethernet functionality (M1 only)
124
840 USE 116 00 Version 1.0
Chapter 6 Transfering Data with the MSTR Instruction
TCP/IP Ethernet Statistics
Introduction
04 and 05
06 and 07
08 and 09
10 and 11
12 and 13
14 and 15
16 and 17
18 and 19
20 and 21
22 and 23
24 and 25
26 and 27
28 and 29
30 and 31
32 and 33
34 and 35
A TCP/IP Ethernet board responds to “Get Local Statistics” and “Set Local
Statistics” commands with the following information:
Word
00 ... 02
03
Meaning
MAC address
Board Status (see following table for Board
Status Bit Definition)
Number of receiver interrupts
Number of transmitter interrupts
Transmit _ timeout error count
Collision_detect error count
Missed packets
Memory error
Number of times driver has restarted
Receive framing error
Receiver overflow error
Receive CRC error
Receive buffer error
Transmit silo underflow
Late collision
Lost carrier
Number of retries
IP address
Continued on next page
840 USE 116 00 Version 1.0
125
Chapter 6 Transfering Data with the MSTR Instruction
TCP/IP Ethernet Statistics, continued
Board Status
Word Bit
Definition
The following table details the word bit definitions for the Board Status
Bit #
15
14
13
Definition
0 = 10 Mbit, 1 = 100 Mbit
0 = Twisted Pair, 1 = Fiber
0 = APPL LED off, 1 = APPL LED on
12 0 = Link LED off, 1 = Link LED on
11 ... 4 Module Type
(See Module Type table below.)
3
2
1 ... 0
0 = CPU Stopped, 1 = CPU Running
0 = PLC Not Configured, 1 = PLC Configured
Reserved
Board Status
Word Bit
Definition by
Module Type
The following table defines the values of the Module Types:
1
2
3
Value of Bits 11...4
Module Type
0 NOE 2x1
ENT
M1E
NOE 771 00
4
5 ... 9
10
ETY 410
Currently Reserved
NOE 771 10
126
840 USE 116 00 Version 1.0
Embedded Web Pages
7
At a Glance
Introduction
What’s in this
Chapter
This chapter presents the contents of the embedded web pages contained in the
Quantum 140 NOE 771 x0. These web pages enable you to access diagnostic information, view configuration information, and change the online configurations for the module.
This chapter contains the following topics:
Topic
Accessing the Web Utility Home Page
Quantum Welcome Page
Quantum Local Rack Page
CPU Configuration Screen Page
Ethernet Module Statistics Page
Remote I/O Communications Status Page
Quantum PLC Data Monitor Page
Configure NOE Page
Configure SNMP Page
Configure BOOTP Process
NOE Properties Page
NOE Diagnostics Page
Crash Log Diagnostics Page
Contacting Schneider Automation Page
Page
143
146
151
152
153
155
136
138
140
142
128
130
132
133
840 USE 116 00 Version 1.0
127
Chapter 7 Embedded Web Pages
Accessing the Web Utility Home Page
Introduction
Each Quantum 140 NOE 771 x0 10/100 Megabit Ethernet module contains a
World Wide Web embedded server that allows you to access diagnostics and online configurations for the module and it’s associated controller (PLC). Pages on the embedded web site display: z configurable menus for the BOOTP server and SNMP z the Ethernet statistics for the node z crash file log statistics z the controller’s configuration (Controller Status on menu) z the controller’s register values z the status, configuration and register values of remote I/O z the status, configuration and register values of distributed I/O
The web pages can only be viewed across the World Wide Web using version 4.0 or greater of either Netscape Navigator or Internet Explorer, both of which support
JDK 1.1.4 or higher.
For information on the additional functionality provided by the FactoryCast system in the 140 NOE 771 10 module, see the FactoryCast Manual, 890 USE 152 00.
How to Access It
Before you can access the module’s home page, you must learn its full IP address or URL from your system administrator. Type the address or URL in the Address or
Location box in the browser window. Once you do this the Schneider Automation
Web Utility home page will appear (see next page).
Continued on next page
128
840 USE 116 00 Version 1.0
Accessing the Web Utility Home Page, continued
Schneider Web
Utility Home
Page
Chapter 7 Embedded Web Pages
Click on the “Diagnostics and Online Configuration”.
Result: The user is requested to supply a user name and password.
840 USE 116 00 Version 1.0
Upon supplying the user name, password, and clicking the <OK> button, the
Quantum Welcome Page appears.
Note: The default User Name is USER. and the default Password is USER. Both may be changed.
Result: The Quantum Welcome Page which provides the links to all the Quantum
Configuration and Diagnostic Pages and to the Run-Time Data Editor.
129
Chapter 7 Embedded Web Pages
Quantum Welcome Page
Quantum
Welcome Page
Overview
The Quantum Welcome Page provides links to all the Configuration and Diagnostic
Pages and to the Run-Time Data Editor.
Continued on next page
130
840 USE 116 00 Version 1.0
Chapter 7 Embedded Web Pages
Quantum Welcome Page, continued
Quantum
Welcome Page
Links
The following table details the links on the Quantum Welcome Page :
Link
Home
Configured
Local Rack
Controller Status
Ethernet Statistics
RIO Status
Data Monitor
Configure NOE
NOE Properties
NOE Diagnostics
Support
Results
Restarts the process
Displays the Quantum Local Rack with NOE and CPU
Displays the CPU Configuration.
Displays the Ethernet Module Statistics with the Reset Counters link
Displays the Remote I/O Communications
Status
Allows access to the Quantum PLC Data with editing capabilities.
Provides the ability to configure and change the NOE through the Ethernet Configuration page
Provides information on the NOE properties
Displays the links to Ethernet Statistics and the Crash Log File Diagnostics
Displays contact information for technical assistance, sales, and feedback
To view the pages related to each of these topics, click on the topic.
840 USE 116 00 Version 1.0
131
Chapter 7 Embedded Web Pages
Quantum Local Rack Page
Quantum Local
Rack Page
Overview
The Quantum Local Rack page displays a visual of the current configuration.
Quantum Local
Rack Page Links
The following table details the links on the Quantum Local Rack Page:
Link
Home
Controller Status
Ethernet Statistics
RIO Status
Data Monitor
Results
Displays the Quantum Welcome Page
Displays the CPU Configuration
Displays the Ethernet Module Statistics with the Reset Counters link
Displays the Remote I/O Communications
Status
Allows access to the Quantum PLC Data with editing capabilities
132
840 USE 116 00 Version 1.0
CPU Configuration Screen Page
CPU
Configuration
Screen Page
Overview
Chapter 7 Embedded Web Pages
840 USE 116 00 Version 1.0
The top eight fields identify the CPU Configuration. See the following tables for further information on the content of the other fields.
Continued on next page
133
Chapter 7 Embedded Web Pages
CPU Configuration Screen Page, continued
Description
Fields
Field
System Memory [Kb]
Information Supplied
Amount of system memory used
Extended Memory [Kb] Amount of Extended Memory used
Total Memory (Bytes) Total memory used in bytes
I/O Map Words
Segments
DCP Drop ID
Memory Protect
Constant Sweep
Optimize
Number of I/O words mapped.
Number of segments
Drop number for Distributed Control
Position of the Memory Protect Switch
Current status of Constant Sweep
Current status of Optimization
Register Fields
Field
0xxxxx
1xxxxx
3xxxxx
4xxxxx
6xxxxx
Battery Coil
Timer Register
Time of Day Clock
Stopped Codes
Information Supplied
Valid Address of 0x
Valid Address of 1x
Valid Address of 3x
Valid Address of 4x
Valid Addres of 6x
Address of Battery Coil
Address of Timer Register
Address of Time of Day Clock
Reason for controlled stopping
ASCII Fields
This column contains information concerning the ASCII fields.
Continued on next page
134
840 USE 116 00 Version 1.0
Chapter 7 Embedded Web Pages
CPU Configuration Screen Page, continued
CPU
Configuration
Screen Page
Links
The following table details the links on the CPU Configuration Screen Page
Link
Home
Results
Displays the Quantum Welcome Page
Configured Local Rack Displays the Quantum Local Rack with NOE and CPU
Ethernet Statistics
RIO Status
Displays the Ethernet Module Statistics with the Reset Counters link
Displays the Remote I/O Communications
Status
Data Monitor Allows access to the Quantum PLC Data with editing capabilities
840 USE 116 00 Version 1.0
135
Chapter 7 Embedded Web Pages
Ethernet Module Statistics Page
Ethernet Module
Statistics Page
Overview
136
These statistics are for information only. If you wish to retain the information, you must copy it offline. The counters may be reset to zero by clicking the Reset
Counter button.
Continued on next page
840 USE 116 00 Version 1.0
Chapter 7 Embedded Web Pages
Ethernet Module Statistics Page, continued
Ethernet Module
Statistics Page
Links
The following table details the links on the Ethernet Module Statistics Page:
Link
Home
Results
Displays the Quantum Welcome Page
Configured Local Rack Displays the Quantum Local Rack with NOE and CPU
Controller Status
RIO Status
Displays the CPU Configuration
Displays the Remote I/O Communications
Status
Data Monitor Allows access to the Quantum PLC Data with editing capabilities
840 USE 116 00 Version 1.0
137
Chapter 7 Embedded Web Pages
Remote I/O Communication Status Page
Remote I/O
Communication
Status Page
Overview
138
Note: The Graphic Editor Link is only available on the 140 NOE 771 10.
This page is for information only. There are no fields you can change. The following tables discuss the information supplied for each cable.
For more information concerning the Remote I/O Communications Status, see the
RIO Manual, 890 USE 101 00.
840 USE 116 00 Version 1.0
Chapter 7 Embedded Web Pages
Remote I/O Communication Status Page, continued
Remote I/O
Communications
Status Page
Links
The following table details the links on the Remote I/O Communication Status
Page:
Link
Home
Configured Local Rack Displays the Quantum Local Rack with NOE and CPU
Controller Status
Ethernet Statistics
Results
Displays the Quantum Welcome Page
Displays the CPU Configuration
Displays the Ethernet Module Statistics with the Reset Counters link
Data Monitor Allows access to the Quantum PLC Data with editing capabilities
840 USE 116 00 Version 1.0
139
Chapter 7 Embedded Web Pages
Quantum PLC Data Monitor Page
Quantum PLC
Data Monitor
Page Overview
This is the web page that allows you to alter the displayed Quantum PLC data.
140
You can insert additional rows of data by clicking on the Insert Rows button.
You can delete specific rows of data by clicking on the Cut Rows button.
You can copy in rows of data by clicking on the Paste Rows button.
Continued on next page
840 USE 116 00 Version 1.0
Chapter 7 Embedded Web Pages
Quantum PLC Data Monitor Page, continued
Quantum PLC
Data Monitor
Page Links
The following table details the links on the Quantum PLC Data Monitor Page:
Link
Home
Results
Displays the Quantum Welcome Page
Configured Local Rack Displays the Quantum Local Rack with NOE and CPU
Controller Status
Ethernet Statistics
Displays the CPU Configuration
Displays the Ethernet Module Statistics with the Reset Counters link
RIO Status Displays the Remote I/O Communications
Status
840 USE 116 00 Version 1.0
141
Chapter 7 Embedded Web Pages
Configure NOE Page
Configure NOE
Page Overview
This page provides links to individual configuration pages for the NOE.
Configure NOE
Page Links
The following table details the links on the Configure NOE Page:
Link
Configure SNMP
Configure BOOTP
Home
NOE Properties
NOE Diagnostics
Support
Results
Provides the ability to configure the SNMP
Agent in the NOE
Provides the ability to configure the BOOTP
IP assignments including showing the
BOOTP database
Returns you to the Quantum Welcome Page
Provides information on NOE properties
Displays links to Ethernet Statistics and the
Crash Log File Diagnostics
Provides you with contact information for technical assistance, sales, and feedback
142
840 USE 116 00 Version 1.0
Configure SNMP Page
Configure SNMP
Page Overview
Chapter 7 Embedded Web Pages
840 USE 116 00 Version 1.0
If the SNMP is not configured, enter the appropriate information in the fields.
To display the current SNMP configuration, click on Show SNMP Configuration.
To change the SNMP configuration, change the information on the page and click on Update SNMP. The NOE must also be reset for the change to take affect, see the Successful Update Message Screen.
To clear the fields, click on Reset the Form.
Continued on next page
143
Chapter 7 Embedded Web Pages
Configure SNMP Page, continued
SNMP Page
Fields
The following SNMP configuration fields can be changed on the Configure SNMP
Page:
Field
Manager I
Information to be Supplied
IP Address of first SNMP Manager
Manager II IP Address of second SNMP Manager
Location [SysLocation] Location of the module
Contact [SysContact]
Set
Get
Trap
Authentication Failure
Trap Enabled
Name of the responsible systems engineer
Designation of level of user who can set the configuration
Designation of level of user who can view the configuration
Designation of level of user who can capture information
Turns on Community Name Checking
Configure SNMP
Page Links
The following table details the links on the Configure SNMP Page:
Link
Home
Configure NOE
NOE Properties
NOE Diagnostics
Support
Results
Returns you to the Quantum Welcome Page
Provides the ability to configure and change the NOE through the Ethernet Configuration
Page
Provides information on NOE properties
Displays links to Ethernet Statistics and the
Crash Log File Diagnostics
Provides you with contact information for technical assistance, sales, and feedback
Continued on next page
144
840 USE 116 00 Version 1.0
Chapter 7 Embedded Web Pages
Configure SNMP Page, continued
Completion
Message
Clicking on the Update SNMP button results in a new page with the following message:
The NOE module has to be reset for the changes to take effect.
This page contains the same links as the Configure SNMP Page.
840 USE 116 00 Version 1.0
145
Chapter 7 Embedded Web Pages
Configure BOOTP Process
Configure
BOOTP Initial
Page
he BOOTP Database File does not exist, this page will display so a BOOTP
Database File can be created.
Press the Configure Bootp Entry button to configure a BOOTP Database File.
The result will be the Bootp Node Configuration Form Page.
Continued on next page
146
840 USE 116 00 Version 1.0
Configure BOOTP Process, continued
Bootp Node
Configuration
Form Page
Chapter 7 Embedded Web Pages
Initial
Configuration
If this is an initial BOOTP configuration fill in the fields on the Bootp Node
Configuration Form and press the Add a New Entry.
Field
Hostname
Host IP address
Host Mac Address
Subnet Mask
Gateway
Information to be Supplied
Text to identify device
IP Address from System Administrator - read from sticker on device
IEEE Global Address
Supplied by system
Define the address of route to access nodes off the devices subnet
Continued on next page
840 USE 116 00 Version 1.0
147
Chapter 7 Embedded Web Pages
Configure BOOTP Process, continued
Adding to the
BOOTP
Database File
If you want to add an entry to the BOOTP Database File, complete the fields on the form, and press the Add a New Entry button.
Changing the
BOOTP
Database File
Use the following steps to change an entry in the BOOTP Database File:
Step
1
2
3
4
5
6
Action
Enter the new information on the Bootp Node Configuration Page
Click on the Change an Entry button
Result: The a new entry will be made at the bottom of the
Database Table and you will get a successful entry message.
Click on Configure NOE to return to Configure NOE page
Click on Configure BOOTP
Enter the information to be old information
Click on Delete an Entry
Deleting from the
BOOTP
Database File
Use the following steps to delete an entry on the BOOTP Database File:
Step
1
2
3
4
5
Action
Enter the information for the item to be deleted
Click on the Delete an Entry button
Result: A delete successful message.
Click on Configure NOE
Click on Configure BOOTP
Click on Refresh Bootp Database Table to view revised
Database file.
Continued on next page
148
840 USE 116 00 Version 1.0
Chapter 7 Embedded Web Pages
Configure BOOTP Process, continued
Resetting the
Form
To clear the fields in the Bootp Node Configuration Form, press the Reset the Form button. You will then be able to fill in the information of Database File entries to be added, changed, or deleted.
Displaying the
BOOTP
Database File
To display the current BOOTP Database File, press the Show Bootp Database button.
840 USE 116 00 Version 1.0
Continued on next page
149
Chapter 7 Embedded Web Pages
Configure BOOTP PROCESS, continued
Bootp Node
Configuration
Form Links
The following table details the links on the Bootp Node Configuration Form Page:
Link
Home
Configure NOE
NOE Properties
NOE Diagnostics
Support
Results
Returns you to the Quantum Welcome Page
Provides the ability to configure and change the NOE through the Ethernet Configuration
Page
Provides information on NOE properties
Displays links to Ethernet Statistics and the
Crash Log File Diagnostics
Provides you with contact information for technical assistance, sales, and feedback
150
840 USE 116 00 Version 1.0
Chapter 7 Embedded Web Pages
NOE Properties Page
NOE Properties
Page Overview
The NOE Properties Page displays the Exec, Kernel, Web Pages versions being used, and the Physical Media in use.
This is for information only. The fields cannot be changed.
NOE Properties
Page Links
The following table details the links on the NOE Properties Page:
Link
Home
Configure NOE
NOE Diagnostics
Support
Results
Returns you to the Quantum Welcome Page
Provides the ability to configure and change the NOE through the Ethernet Configuration
Page
Displays links to Ethernet Statistics and the
Crash Log File Diagnostics
Provides you with contact information for technical assistance, sales, and feedback
840 USE 116 00 Version 1.0
151
Chapter 7 Embedded Web Pages
NOE Diagnostics Page
NOE Diagnostics
Page Overview
NOE Diagnostics
Page Links
The following table details the links on the NOE Diagnostics Page:
Link
Ethernet Statistics
Crash Log File
Diagnostics
Home
Configure NOE
NOE Properties
Support
Results
Displays the Ethernet Module Statistics Page where you can display the Ethernet statistics and reset the counters.
Displays the Crash Log entries for use in diagnosing the cause of crashes.
Returns you to the Quantum Welcome Page
Provides the ability to configure and change the NOE through the Ethernet Configuration
Page
Provides information on NOE properties
Provides you with contact information for technical assistance, sales, and feedback
152
840 USE 116 00 Version 1.0
Chapter 7 Embedded Web Pages
Crash Log Diagnostics
Crash Log
Diagnostics
Page
Following is an example of a Crash Diagnostics Page:
840 USE 116 00 Version 1.0
Press Clear Crash Log File to clear the file.
If there have been no crashes, the following message displays.
Continued on next page
153
Chapter 7 Embedded Web Pages
Crash Log Diagnostics, continued
Crash Log
Diagnostics
Links
The following table details the links on the Crash Log Diagnostics Page:
Link
Home
Configure NOE
NOE Properties
NOE Diagnostics
Support
Results
Returns you to the Quantum Welcome Page
Provides the ability to configure and change the NOE through the Ethernet Configuration
Page
Provides information on NOE properties
Displays links to Ethernet Statistics and the
Crash Log File Diagnostics
Provides you with contact information for technical assistance, sales, and feedback
154
840 USE 116 00 Version 1.0
Chapter 7 Embedded Web Pages
Contacting Schneider Automation Page
Contacting
Schneider
Automation
Page Overview
The Contacting Schneider Automation Page contains information on how to obtain support for the NOE 771 x0 modules.
840 USE 116 00 Version 1.0
155
Chapter 7 Embedded Web Pages
156
840 USE 116 00 Version 1.0
Using the Network Options
Ethernet Tester
8
At a Glance
Introduction
This chapter describes how to use the Network Options Ethernet Tester with a
Windows based PC to monitor the network by supplying you with operational statistics and to provide the capability of reading and writing PLC registers.
What’s in this
Chapter
This chapter contains the following topics.
Topic
Installing the Network Options Ethernet Tester
Establishing a Connection with an Ethernet Module
Getting and Clearing Statistics
Statistics
Reading Registers
Writing Registers
Page
158
159
162
166
168
169
157
840 USE 116 00 Version 1.0
Chapter 8 Using the Network Options Ethernet Tester
Installing the Network Options Ethernet Tester
Introduction
An Ethernet module may act as a client or as a server.
If it will be acting as a client -- that is, initiating transactions on the network for its
Quantum controller -- then you must program an MSTR block in ladder logic. For details about the MSTR block, please refer to Chapter 6.
The Ethernet module may also act as a server, responding to requests and commands from devices on the network for its Quantum controller.
The Network Options Ethernet Tester utility allows you to get and clear statistics and to read and write registers over the network, using a Windows-based PC.
You may also create your own program using the Ethernet module as a server. For guidance in creating your own program, refer to Appendix B.
Note: In its capacity as server, the Ethernet module can only accept 32 connections at any one time. If a new connection is attempted and the server has already reached its limit, it will terminate the least used connection in order to make room for the new one.
Installation
Procedure
The Network Options Ethernet Tester is supplied to you on a utility diskette. To install the tester on your PC perform the following steps:
2
3
Step Action
1 Insert the Network Options Ethernet Tester utility disk into drive A:
4
Select Run from the Program Manager file menu.
Type
A:\SETUP
and click on the OK button–the Welcome dialog will appear.
Click on the Next button and follow the instructions that appear in each of the dialogs to complete the installation.
Note: Each installation dialog has Back and Next buttons that allow you to move back to the previous dialog or move forward to the next dialog.
158
840 USE 116 00 Version 1.0
Chapter 8 Using the Network Options Ethernet Tester
Establishing a Connection with an Ethernet Module
What You Must
Know
To establish a connection with an Ethernet module using the Network Options
Ethernet Tester, you must know the module’s IP network address or host name.
Procedure
Perform the following steps to establish a connection with an Ethernet module using the Network Options Ethernet Tester:
Step Action
1 From the initial menu, select File and choose New from the options in the pulldown menu or click on the new connection button in the toolbar .
840 USE 116 00 Version 1.0
Clear statistics
Get statistics
Write register
Read register
Disconnect
Connect
Create new connection
This will bring up the Remote IP Address dialog box.
Continued on next page
159
Chapter 8 Using the Network Options Ethernet Tester
Establishing a Connection with an Ethernet Module, continued
Procedure,
continued
Step Action
2 Type the module’s IP network address or host name in the IP Address box.
Click on the OK button. This dedicates a connection from your PC to the designated Ethernet module and brings you to the main menu.
160
3 You may establish several connections with the same module or with other modules by repeating step 2 for each new connection.
Continued on next page
840 USE 116 00 Version 1.0
Chapter 8 Using the Network Options Ethernet Tester
Establishing a Connection with an Ethernet Module, continued
Procedure,
continued
Step Action
4 When you are ready to disconnect, select Management and choose Disconnect from the pulldown menu:
5 or click on the disconnect button in the toolbar.
After disconnecting from one module, you may reassign its dedicated connection by selecting Management and choosing Set IP Addr from the pulldown menu.
Type the new IP network address or host name in the box provided.
840 USE 116 00 Version 1.0
161
Chapter 8 Using the Network Options Ethernet Tester
Getting and Clearing Statistics
Procedure
To get statistics from the Ethernet module using your Network Options Ethernet
Tester, perform the following steps:
Step Action
1 Establish a connection with the Ethernet module (see previous procedure).
2 Select Messages from the main menu and choose Get Stats from the pulldown menu:
3 or click on the get statistics button in the toolbar. The Get Statistics dialog box will appear.
Type a polling interval (the number of seconds between transactions) in the box provided and click on the OK button.
Continued on next page
162
840 USE 116 00 Version 1.0
Getting and Clearing Statistics, continued
Chapter 8 Using the Network Options Ethernet Tester
Procedure,
continued
Step Action
4 Complete statistics for the module will be printed in the window for this connection.
5 To change the polling interval without interrupting communication with the
Ethernet module, select Messages and choose Poll Interval.
840 USE 116 00 Version 1.0
Continued on next page
163
Chapter 8 Using the Network Options Ethernet Tester
Getting and Clearing Statistics, continued
Procedure,
continued
Step Action
6
Type the new polling interval in the box provided, and click on the OK button
.
7 To clear statistics, select Messages and choose Clear Stats from the pulldown menu: or click on the clear statistics button in the toolbar.
Continued on next page
164
840 USE 116 00 Version 1.0
Getting and Clearing Statistics, continued
Chapter 8 Using the Network Options Ethernet Tester
Procedure,
continued
Step Action
8
When the Clear Statistics dialog box appears, click on the OK button. This will bring up the Clear Statistics Request for the connection.
840 USE 116 00 Version 1.0
165
Chapter 8 Using the Network Options Ethernet Tester
Statistics
Statistics
Description
166
The Network Options Ethernet Tester will provide the following statistics: z
Total Transaction Count. How many transactions have been completed.
z
IP Address.
z
Status Information in the following form:
Parameter Information
Model:
Media:
Model number
10 BASE-T
100 BASE-T
100 BASE-FX
HALF DUPLEX
DUPLEX
Controller: Running
Stopped
Crash Log Empty?
Yes
No - there is a crash log entry present z
Receive Interrupts and Transmit Interrupts. The number of times the PCNET controller chip has generated interrupts.
z
Transmit timeout errors. The number of times the transmitter has been on the channel longer than the interval required to send the maximum length frame of
1519 bytes. This is also known as a babble error.
z
Collision errors. The number of collisions detected by the Ethernet chip.
z
Missed packet errors. The number of times a received frame was dropped because a receive descriptor was not available.
z
Memory errors. The number of times an Ethernet controller chip experienced an error accessing shared RAM. A memory error will cause a restart.
z
Restart count. The number of times the Ethernet controller chip was restarted due to fatal runtime errors, including memory errors, transmit buffer errors and transmit underflow.
z
Framing error. The number of times an incoming frame contained a noninteger multiple of eight bits.
z
Overflow errors. The number of times the receiver has lost part or all of an incoming frame, due to an inability to store the frame in memory before the internal FIFO overflowed.
z
CRC errors. The number of times a CRC (FCS) error was detected on an incoming frame.
Continued on next page
840 USE 116 00 Version 1.0
Chapter 8 Using the Network Options Ethernet Tester
Statistics, continued
Statistics,
continued z
Receive buffer errors. The number of times a receive buffer was not available while data chaining a received frame.
z
Transmit buffer errors. The number of times the end packet flag on the current buffer was not set and the Ethernet controller did not own the next buffer. A transmit buffer error causes a restart.
z
Silo Underflow. The number of times a packet was truncated due to data late from memory. A Silo Underflow will cause a restart.
z
Late Collision. The number of times a collision was detected after the slot time of the channel had elapsed.
z
Lost Carrier. The number of times a carrier was lost during a transmission.
z
Transmit retries. The number of times the transmitter has failed after 16 attempts to transmit a message, due to repeated collisions.
These statistics also may be obtained from the MSTR block. Refer to the Ladder
Logic Block Library User Guide, 890 USE 100 00 for details.
840 USE 116 00 Version 1.0
167
Chapter 8 Using the Network Options Ethernet Tester
Reading Registers
Reading
Registers
Procedure
To read registers from the Ethernet module using your Network Options Ethernet
Tester, perform the following steps:
2
3
Step Action
1 Establish a connection with the Ethernet module (see procedure on page __).
Select Messages from the main menu.
Choose Read Register from the pulldown menu:
4 or click on the read register button in the toolbar. The Read Register dialog box will appear.
Type in a polling interval (the number of seconds between transactions) in the
Polling Interval box.
168
5
6
7
Type in the number of the first 4x register you want to read in the Starting 4x
Register box. When typing the 4 x register number, omit the leading 40 or 400, as shown in the figure above.
Type in the number of register to read in the Number of registers to read box.
Click on the <OK> button. The register values will be displayed in the window for this connection. Five values will be listed in each row, with the number of the first register at the beginning of the row.
840 USE 116 00 Version 1.0
Chapter 8 Using the Network Options Ethernet Tester
Writing Registers
Writing
Registers
Procedure
To write registers from the Ethernet module using your Network Options Ethernet
Tester, perform the following steps:
2
3
Step Action
1 Establish a connection with the Ethernet module (see procedure on page __).
Select Messages from the main menu.
Choose Write Register from the pulldown menu:
4 or click on the write register button in the toolbar. The Write Register dialog box will appear.
Type in a polling interval (the number of seconds between transactions) in the
Polling Interval box.
840 USE 116 00 Version 1.0
5
6
Type in the number of the first 4x register you want to write in the First 4x
register to write box. When typing the 4 x register number, omit the leading 40 or
400, as shown in the figure above.
Type in the number of register to write in the Number of registers to write box.
Continued on next page
169
Chapter 8 Using the Network Options Ethernet Tester
Writing Registers, continued
Writing
Registers
Procedure,
continued
Step Action
7 Type in the data to be written to those registers in the Write Data box.
8
9
Click on the Increment Write Data box if you want the data you have entered to be increased by one with each transaction.
Click on the OK button. The register values will be displayed in the window for this connection.
Read or Write
Request Error.
If you try to read or write registers and an error occurs, the NOE Tester will display a Read Request Error or Write Request Error. The error codes correspond with
MSTR block error codes. For more information, refer to the Ladder Logic Block
Library User Guide, 890 USE 100 00.
170
840 USE 116 00 Version 1.0
Maintenance
9
At a Glance
Introduction
This chapter details information on system maintenance including accessing and clearing the Crash Log and downloading the new NOE Exec.
What’s in this
Chapter
This chapter contains the following topics.
Topic
Responding to Errors
Reading and Clearing the Crash Log
Downloading a new NOE Exec
The Concept Exec Loader
Downloading a new NOE Exec via FTP
Page
172
177
179
180
185
171
840 USE 116 00 Version 1.0
Chapter 9 Maintenance
Responding to Errors
Detecting Errors
When faults occur, the NOE 771 x0 LED display can help you determine what went wrong. During normal operation, the LEDs should display the following pattern:
The Run indicator will be solid. The Coll LED may flash, indicating that collisions are occurring on the
Ethernet network. Such collisions are normal.
140
NOE 771 00
ETHERNET TCP/IP
Active
Ready
Run
Link
If a fault has occurred, the normal LEDs may be extinguished or other indicators may light. This section will discuss errors reported by the Active,
Ready, Coll, Link, Kernel, Appl and Fault indicators.
For each type of error, try the suggested remedies in the order given. If no remedy suggested here overcomes the error, call your local service representative or call Schneider Electric customer service at 1-800-468-5342 for further directions.
Certain error codes are recorded in the MSTR block. For instructions on how to read and interpret those codes through
ProWORX NxT, Modsoft, or Concept, please refer to MSTR Function Error Codes on page 108.
Active LED Error
When the Active LED fails to light, then the NOE 771 00 module is not communicating with with the backplane. Perform the following checks:
2
3
Step
1
Action
Make sure the NOE 771 module and the controller are installed properly.
Verify that the controller is functioning. If it isn’t, replace it.
If neither the new controller nor the NOE 771 module will function, replace the backplane.
Continued on next page
172
840 USE 116 00 Version 1.0
Chapter 9 Maintenance
Responding to Errors, continued
Active LED Error, continued
Step
4
5
6
Action
Make sure that no more than two network option modules -- including NOE,
NOM, NOP and CRP 811 modules -- have been installed in the backplane with a
140 CPU 113 or 213; no more than six network option modules with a 140 CPU
424 or 534.
Check the version of the controller executive. You must have version 2.0 or greater to support the Ethernet module. Earlier versions do not recognize the module.
If steps 4 and 5 above check ok, replace the NOE 771 module.
Ready LED Error
The Ready LED fails to light, the NOE 771 module has failed internal diagnostic tests. Perform the following checks:
Step
1
2
Action
Make sure that power has been applied to the backplane.
If step 1 checks ok, replace the NOE 771 module.
Link LED Error
If the Link LED fails to light, the NOE 771 module is not communicating with the
Ethernet hub/switch. Perform the following checks:
2
3
Step
1
Action
Make sure that the cable has been installed correctly and the module is functioning properly.
Verify that the hub/switch is working properly.
If steps 1 and 2 above check ok , replace the NOE 771 module.
Continued on next page
840 USE 116 00 Version 1.0
173
Chapter 9 Maintenance
Responding to Errors, continued
Kernel LED Error
Check for the following Kernel LED error conditions:
If
The Ready LED is on and the Kernel
LED is flashing,
The Ready LED is on and the Kernel
LED is shining steadily,
Either of the above conditions exist,
Then
the module has detected an invalid software image.
an attempt to download a software image has failed and the module is in kernel mode.
download a new NOE Exec (see page
179).
Fault LED
The Fault LED will flash briefly following an error as the module attempts to recover.
140
NOE 771 00
ETHERNET TCP/IP
Active
Fault
Link
Appl
174
840 USE 116 00 Version 1.0
Chapter 9 Maintenance
Responding to Errors, continued
Collision LED
Error
If the twisted pair cable has not been connected properly, the Coll LED will shine steadily and the Link LED will be extinguished. (This condition does not occur with fiber optic modules.)
140
NOE 771 00
ETHERNET TCP/IP
Active
Ready
Coll
Perform the following checks:
Step
1
2
Action
Make sure the cable has been installed properly and is working properly.
Verify that the Ethernet hub/switch is functioning properly.
Continued on next page
840 USE 116 00 Version 1.0
175
Chapter 9 Maintenance
Responding to Errors, continued
Collision LED,
Normal
Condition
140
NOE 771 00
ETHERNET TCP/IP
Active
Ready
Run
Link
Coll
If the Coll LED is flashing, the module is reporting collisions on the Ethernet network. While such collisions are normal, the frequency of the flashes is an indication of the volume of traffic on the network. The flashes may be so frequent that the
LED appears to be shining steadily. Heavy traffic will slow communications. If response time is important to your application, you should consider segmenting your network to reduce the frequency of collisions.
Run LED
The following table indicates the action to be taken if the Run LED is flashing. The action depends on the number of flashes in sequence.
# of Flashes in Sequence Action
Three
Four
Five
Six
Seven
Check Ethernet connection
Change IP address
Provide IP address
Connect using default IP address and configure
Download NOE Executive
Application LED
If the module crashes, it will note the reason in a log. If the module is able to recover, the Appl LED will light, indicating that an entry has been made in the crash log. To learn how to read and clear the crash log, refer to the section below.
176
840 USE 116 00 Version 1.0
Chapter 9 Maintenance
Reading and Clearing the Crash Log
Introduction
The crash log provides you with the ability to capture conditions that lead to an anomalous condition. By providing the crash log to Schneider Electric technical support, you can facilitate their assistance in resolving your problems.
Note: The crash log is provided with the understanding that with a complex product in thousands of customer applications, there may be conditions that require advance diagnostics. The crash log is one of the tools used to solve complex problems.
The Crash Log
If the Appl indicator is lit, entries have been made in the crash log. The log may hold up to 64K of entries.
Reading the
Crash Log
The crash log can be read from the Embedded Web Pages (see Chapter 7) or via
FTP.
Reading the
Crash Log via
FTP
Perform the following steps to access the crash log via FTP.
2
3
Step
1
Action
Log into the module’s FTP Server
Change the directory to wwwroot/conf/diag
Perform an FTP to get the crash log: get crash log
Continued on next page
840 USE 116 00 Version 1.0
177
Chapter 9 Maintenance
Reading and Clearing the Crash Log, continued
Clearing the
Crash Log
The crash log can be cleared from the Embedded Web Pages (see Chapter 7) or via FTP
Clearing the
Crash Log via
FTP
Perform the following steps to clear the crash log via FTP.
2
3
Step
1
Action
Log into the module’s FTP Server
Change the directory to wwwroot/conf/diag
Perform an FTP rm crash.log to delete the crash log file
178
840 USE 116 00 Version 1.0
Chapter 9 Maintenance
Downloading a New NOE Exec
Introduction
The following tools can be used to download of new NOE Exec: z
Concept Exec Loader z
FTP
These tools provide you with the ability to download a new NOE Exec.
840 USE 116 00 Version 1.0
179
Chapter 9 Maintenance
The Concept Exec Loader
Process
The following steps detail downloading a new NOE Exec using the Concept Exec
Loader.
Step
1
2
Action
Activate the Exec Loader program.
Click on the Next button to start the Exec Loader process
Result: The EXECLoader - Communication Protocol screen is displayed.
180
Click on TCP/IP [Ethernet}
Continued on next page
840 USE 116 00 Version 1.0
Chapter 9 Maintenance
The Concept Exec Loader, continued
Process,
continued
Step
3
Action
Click on the Next button
Result: The EXECLoader - TCP/IP Target screen is displayed.
840 USE 116 00 Version 1.0
Click on Direct Device
Continued on next page
181
Chapter 9 Maintenance
The Concept Exec Loader, continued
Process,
continued
Step
4
Action
Click on the Next button
Result: The EXECLoader - Operation screen is displayed.
182
5
Click on Transfer EXEC to Device
Use Browser to select the file name.
Continued on next page
840 USE 116 00 Version 1.0
Chapter 9 Maintenance
The Concept Exec Loader, continued
Process,
Step
6
Action
Click on the Next button
Result: The EXECLoader - File and Device Info screen is displayed.
840 USE 116 00 Version 1.0
Continued on next page
183
Chapter 9 Maintenance
The Concept Exec Loader, continued
Process,
continued
Step
7
Action
Click on the Next button
Result: The EXECLoader - Progress screen is displayed.
184
When the process is completed, you can click on the Close button.
Continued on next page
840 USE 116 00 Version 1.0
Chapter 9 Maintenance
Downloading a new NOE Exec via FTP
Procedure
Use the following steps to download a new NOE Exec via FTP:
6
7
4
5
Step
1
2
3
Action
FTP IP Address
: USER
FTP Password cd wwwroot/conf/exec put
<local file> NOE 77100.bin
<remote file> NOE 77100.bin
Following is an example:
840 USE 116 00 Version 1.0
185
Chapter 9 Maintenance
186
840 USE 116 00 Version 1.0
NOE 771 00 Module
Specifications
At a Glance
What’s in this
Appendix
This appendix covers the following topics.
Topic
Specifications
Page
188
A
840 USE 116 00 Version 1.0
187
Appendix A NOE 771 00 Module Specifications
Specifications
Specification
Table
The main specifications for the Quantum 140 NOE 771 x0 Ethernet Module are described in the following table.
Communication Ports
Bus Current Required
Power Dissipation
Fuse
One auto-sensing 10/100Base-T shielded twisted pair (RJ-45 connector) port and one 100Base-FX (MT-RJ connector) port.
Both ports transmit and receive Modbus commands encapsulated in TCP/IP protocol.
750 mA
3.8 W
None
Programming Software
Type and version Concept, Ver. 2.2, or higher
Modlink, Ver. 2.0, or higher
Modsoft, Ver. 2.6, or higher
ProWORX NxT, Ver. 2.1, or higher
Firmware
CPU Type and version
NOE Upgradeable
Operating Conditions
Temperature
Humidity
Altitude
Vibration
Storage Conditions
Temperature
Humidity
Free Fall
Shock
Quantum Executive, Ver. 2.0, or higher
Field Upgradeable via FTP or Programming Panel.
0 to +60° C
0 to 95% Rh non condensing @ 60° C
15,000 ft (4500 m)
10-57 Hz @ 0.0075 mm d.a.
57-150 Hz @ 1 g
-40 to +85
°
C
0 to 95% Rh non condensing @ 60
°
C
1 m unpackaged
3 shocks / axis, 15 g, 11 ms
188
840 USE 116 00 Version 1.0
Ethernet Developers Guide
B
At a Glance
What’s in this
Appendix
This appendix covers the following topics.
Topic
Overview
Class Descriptions
The CSample_doc Class
The CSample_View Class
Timers and Transaction Processing
Transmit State Machine
Receive State Machine
Displaying on the Screen
Page
190
192
194
195
197
198
201
203
189
840 USE 116 00 Version 1.0
Appendix B Ethernet Developers Guide
Overview
Introduction
This appendix describes the design of the sample TCP/IP application named
Network Options Ethernet Tester (NOET). The NOET application is a multiple document interface windows application that verifies the installation of the
Quantum Ethernet TCP/IP module and also serves as a sample application for developers.
TCP/UDP system port number 502 is used with ASA protocol_id of 0.
References
Inside Visual C++, Second Edition, David J. Kruglinski
Window Sockets, An Open Interface for Network Programming under Microsoft®
Windows Version 1.1
What the Sample
Application Does
The sample application performs the following steps: z
Calls the window socket function socket to create a socket. z
Calls the window socket function setsockopt to set the socket attributes. z
Calls the window socket function connect to establish a connection. z
Encodes the request. The request consists of a header followed by a Modbus message. The header contains an invoke identifier, a protocol type, the command length, and a destination identifier z
.
Invoke Identifier Protocol Type Command Length Destination ID Modbus Message z
Calls the window socket function send to transmit the request to the remote node. z
Calls the window socket function recv to receive the response from the remote node. z
Calls the window socket function closesocket to close the connection and release the socket.
The winsock.lib import library provided by the installation is used to link the window socket calls.
Continued on next page
190
840 USE 116 00 Version 1.0
Appendix B Ethernet Developers Guide
Overview, continued
Development
Environment
The sample application was developed with Microsoft Visual C++, version 1.52.
The sample application uses Microsoft Foundation Class. The initial application was generated by the Visual C++ application wizard.
840 USE 116 00 Version 1.0
191
Appendix B Ethernet Developers Guide
Class Descriptions
List of Classes
6.
CSample_app. The Csample_app is the application class. This application was generated by the application wizard, and the source is in the file sam_app.cpp. The class declaration is in sam_app.h.
7.
CMainFrame. The CMainFrame is derived from the MFC class CMDI-
FrameWnd and is the application’s main window frame. The source for
CMainFrame is in mainfrm.cpp, and the declaration is in mainfrm.h. The code for CMainFrame was initially generated by the application wizard, and was modified to process window timer messages.
8.
CSample_doc. The CSample_doc is the document class. The declaration is in sam_doc.h and the implementation is in sam_doc.cpp.
9.
CSample_View. The CSample_View is the view of the document. It is derived from the CScrollView class. The declaration is in the sam_vw.h class, and it is implemented in the sam_vw.cpp, disp.cpp, tcp_hlp.cpp, and the tx_rx.cpp files.
10. CIP_dig. The CIP_dlg class is the dialog class for getting the IP address. It is derived from the CDialog class. The declaration is in the cip_dlg.h file and the implementation is in the cip_dlg.cpp file. Both of these files were generated by
The Visual C++ class wizard.
11. ClrStatsDlg. The ClrStatsDlg class is the dialog class for clearing statistics. It is derived from the CDialog class. The declaration is in the cstatdlg.h file and the implementation is in the cstatdlg.cpp. Both of these files were generated by
The Visual C++ class wizard.
12. GetStatsDlg. The GetStatsDlg class is the dialog class for get statistics. It is derived from the CDialog class. The declaration is in the gstatdlg.h file and the implementation is in the gstatdlg.cpp file. Both of these files were generated by The Visual C++ class wizard.
13. CPollDlg. The CPollDlg class is the dialog class for determining the poll period. It is derived from the CDialog class. The declaration is in the polldlg.h file, and the implementation is in the polldlg.cpp file. Both of these files were generated by The Visual C++ class wizard.
Continued on next page
192
840 USE 116 00 Version 1.0
Appendix B Ethernet Developers Guide
Class Descriptions, continued
List of Classes, continued
14. CReadDlg. The CReadDlg class is the dialog class for determining the registers to read. It is derived from the CDialog class. The declaration is in the readdlg.h file, and the implementation is in the readdlg.cpp file. Both of these files were generated by The Visual C++ class wizard.
15. CWriteDlg. The CWriteDlg class is the dialog class for determining the registers to write and the write data. It is derived from the Cdialog class. The declaration is in the writedlg.h and the implementation is in the writedlg.cpp file.
Both of these files were generated by The Visual C++ class wizard.
16. CAboutDlg. The CAboutDlg class is the dialog class for about. Both the declaration and its implementation are in the sam_app.cpp file.
840 USE 116 00 Version 1.0
193
Appendix B Ethernet Developers Guide
The CSample_doc Class
Description
The CSample_doc (the document class) contains the user data used by the
CSample_View class. The user data consists of the remote node’s IP address, the transaction type and its associated values. The different transaction types are read register, write register, clear statistics, and get statistics. In addition to the transaction type and the associated values, the document class also contains the poll interval.
A user modifies the user data via a menu or tool bar. The CSample_doc processes the menu or tool bar window command message by invoking the corresponding dialog. The state of the various menu items and tool bar buttons depends on the connection state between the application and the remote node. The
CSample_View class maintains the connection state, and hence sets the state of the menu items and tool bar buttons.
194
840 USE 116 00 Version 1.0
Appendix B Ethernet Developers Guide
The CSample_View Class
What it Does
The CSample_View class manages the TCP/IP connection, sends requests to remote nodes, and displays either connection state, or the results of a transaction.
In addition it sets the states of the tool bar buttons and menu items.
Accessing
TCP/IP
840 USE 116 00 Version 1.0
The CSample_View interfaces with window sockets via its application programming interface, and via messages sent by the window sockets DLL to the
CSample_View window. The reference for the window socket API is given above.
The first call made to the window sockets DLL must be WSAStartup. This call is made by InitInstance member function of the CSample_app class. The last call to the window socket DLL must be WSACleanup. This call is made by the
ExitInstance member function of the Csample_app class.
The CSample_View allocates and sets the socket attributes. The attributes it sets are: z
Set Linger to cause a hard close z
Receive out of band data in the normal data stream z
Disable Nagel algorithm for send coalescing
When the Nagel algorithm is disabled, if the stack receives an application message, it will immediately pass the message to the application and will send a
TCP/IP acknowledgment message. Although this can generate more traffic, the application receives the message sooner then if Nagel algorithm is enabled. The member function tcpip_setsocket_options sets the socket attributes.
The window socket interface provides the WSAAsyncSelect function which notifies the window of network events. The member function tcpip_setsocket_options calls
WSAAsyncSelect function. The different events are given by the following table
Event
FD_READ
FD_WRITE
FD_OOB
FD_CONNECT
FD_CLOSE
Description
A socket can read data
A socket can write data
A socket can read out of band data
A connect response has been received
The connection has been closed
Continued on next page
195
Appendix B Ethernet Developers Guide
The CSample_View Class, continued
Accessing TCP/
IP, continued
One of the parameters to the WSAAsyncSelect is a user defined message the window socket DLL sends to the window. The sample application user message is
WM_TCPIP_EVENT and is defined in the file wn_msh.h. MFC architectural framework calls the CSample_View tcpip_event member function to process this message. Like all functions which process messages, tcpip_event parameters are a word and a long word. The word parameter is the socket, and the long word parameter contains the network event , and an error code. Tcpip_event examines the network event and calls the member function indicated in the following table.
Network Event
FD_READ
FD_WRITE
FD_OOB
FD_CONNECT
FD_CLOSE
Member Function
OnTcpIpRead()
OnTcpIpWrite()
OnTcpIpOob()
⁄
OnTcpIpConnect
OnTcpIpClose()
Application
Message Format
TCP/IP transmits a message as a stream. There is no indication of the start of a message nor the end of the message. The NOE option module adds a header to determine the message boundaries. The message is a Modbus message. The header contains the following fields. z
Invoke Identifier. This two byte field associates a request with the response.
The client application picks the invoke identifier, and server returns the same invoke identifier in the response. z
Protocol Type. This two byte field identifies the protocol type. Currently, the only protocol supported is Modbus. z
Command Length. This two byte field is the size of the rest of the message. z
Destination Identifier. This one byte field is reserved for future use.
The Modbus message follows the header. The message does not contain the address field, instead, the first byte is the Modbus function code.
The data structure for the header is declared in modbus.h and the CSample_View encode_header function encodes the header. The member functions encode_clear_stats, encode_read_stats, encode
196
840 USE 116 00 Version 1.0
Appendix B Ethernet Developers Guide
Timers and Transaction Processing
Timers
CSample_View requires to periodically receive a timer message. This message triggers the CSample_View to transmit a message. Since window timers are a limited resource, the window associated with CMainFrame class receives the timer messages. CMainFrame member AddTimerList function will place a window on its timer list. When CMainFrame processes the WM_TIMER message, it sends each window on its time list the user defined WM_POLL_INTERVAL message.
MFC calls CSample_View member OnInitalUpdate function when it is first being created. OnInitialUpdate calls CMainFrameís AddTimerList in order to receive the
WM_POLL_INTERVAL message. MFC architectural framework calls
CSample_View OnPollInterval member function to process this message.
Transaction
Processing
CSample_View transaction processing consists of establishing a connection, transmitting the request, receiving the response, and displaying the response.
CSample_View uses both a transmit and a receive state machine to advance a transaction.
840 USE 116 00 Version 1.0
197
Appendix B Ethernet Developers Guide
Transmit State Machine
Description
The transmit state machine establishes a connection, and periodically transmits a request. The different states for the transmit state machine are as follows. z
IDLE. In the IDLE state, there is no connection. z
RESOLVING_NAME. In the RESOLVING_NAME state, CSample_View is waiting for the window socket DLL to convert a node’s name into an IP address. z
CONNECTING. In the CONNECTING state, CSample_View is waiting for the window socket DLL to generate the FD_CONNECT event. This event indicates if the attempt to establish a connection succeeded or failed. z
CONNECTED. The CONNECTED state indicates that a connection has been successfully established. z
WAIT_TO_TX. In the WAIT_TO_TX state, CSample_View is waiting to transmit the message. It transmits the message, when the time from the last transmit exceeds the specified poll interval. z
BLOCKED. When CSample_View attempts to send a message, the window socket DLL may not be able to transmit the complete message. This is a flow control condition, and CSample_View enters the BLOCKED state. The window socket DLL generates the FD_WRITE event when it can send more data. z
TX_DONE. CSample_View enters the TX_DONE when it has completed transmitting the request.
If the CSample_View is in the IDLE state, and user selects either the connect menu item, or the connect tool bar button, CSample_View OnManagConnect function attempts to establish connect with its tcpip_initate_connection function. This function examines the remote destination and determines if it’s a name or an IP address. If it’s a name, OnManagConnect changes the transmit state to
RESOLVING_NAME, and it invokes the window sockets DLL
WSAAsyncGetHostByName function to resolve the name. Window sockets DLL will generate the user defined WM_TCPIP_NAME_RESOLVED message which indicates if the name has been resolved. The OnTcpIpNameResolved member function process the WM_TCPIP_NAME_RESOLVED message. If the name is not resolved, OnTcpIpNameResolved changes the transmit state back to IDLE.
Continued on next page
198
840 USE 116 00 Version 1.0
Appendix B Ethernet Developers Guide
Transmit State Machine, continued
Description, continued
If the remote node is an IP address, or if it’s a name that has been resolved, then
CSample_View tcpip_connect_rq function is called to initiate a connect request to the remote node. The listen port for the connect request is five hundred and two, and is defined by the constant MBAP_LISTEN_PORT in modbus.h. If tcpip_connect_rq succeeded in initiating a connect request, then tcpip_connect_rq changes the transmit state to CONNECTING, otherwise it changes the transmit state to IDLE.
The window sockets DLL generates a FD_CONNECT event which indicates if the connect request succeeded or failed. CSample_View OnTcpIpConnect function processes the FD_CONNECT event. If the connect request succeeded,
OnTcpIpConnect changes the transmit state to CONNECTED, otherwise it changes the state to IDLE.
Recall that MFC architectural framework calls CSample_View OnPollInterval member function to processes WM_POLL_INTERVAL message sent as result of
CMainFrame class processing a WM_TIMER message. OnPollInterval examines the transmit state. If the transmit state is CONNECTED, and the user has selected a transaction type, then OnPollInterval calls CSample_View TransmitUserRequest function.
TransmitUserRequest encodes a request based on the transaction type, saves the current time, and calls CSample_View TransmitMessage function. OnPollInterval uses the saved time to determine when to transmit the next request.
TransmitMessage attempts to send a message to the remote side. To send the message, TransmitMessage enters a loop. In the body of the loop transmit message calls the window socket DLL send function. The following lists the outcomes of the send function and the actions taken. z
The message was sent successfully. TransmitMessage changes the transmit state to TX_DONE and exits the loop. z
Only part of the message was sent. TransmitMessage reenters the loop. z
Send function returns an error indicating there is no buffer space within the transport system. TransmitMessage changes the transmit state to BLOCKED and exists the loop. z
Send function returns some other error. TransmitMessage closes the connection, changes the transmit state to IDLE, and exits the loop.
Continued on next page
840 USE 116 00 Version 1.0
199
Appendix B Ethernet Developers Guide
Transmit State Machine, continued
Description, continued
When buffer space within the transport system becomes available to transmit messages, the window socket DLL generates a FD_WRITE event. CSample_View
OnTcpWrite function processes the FD_WRITE function by calling
TransmitMessage.
The receive state machine (which is described below) processes the response to a request. When the receive state machine has completed receiving the response, it changes the transmit state machine from the TX_DONE state to the WAIT_TO_TX state.
Recall that the TransmitUserRequest saves the time. CSample_View
OnPollInterval uses this saved time to determine if a new request needs to be transmitted. OnPollInterval is called by MFC architectural framework to process the WM_POLL_INTERVAL sent when CMainFram class processes the window timer message, WM_TIMER. OnPollInterval examines the transmit state. If the transmit state is WAIT_TO_TX, and the elapsed time from the previous transmit request exceeds the poll interval, then OnPollInterval calls TransmitUserRequest to start another transaction.
200
840 USE 116 00 Version 1.0
Appendix B Ethernet Developers Guide
Receive State Machine
Description
The receive state machine receives a response to a transaction by first reading the header, determining the size of the rest of the message, and then reading the body of the message. The different states of the receive state machine are as follows. z
RX_HEADER. In the RX_HEADER state, the receive machine is receiving the message header. z
RX_BODY. In the RX_HEADER state, the receive machine is receiving the response message associated to the requested transaction. z
DUMP_BODY. In the DUMP_BODY state, the receive message is receiving a message, but there is no associated transaction with respect to this message.
The window socket DLL generates the FD_READ event whenever there is data to be read. If only part of the data is read, it generates another event. CSample_View
OnTcpIpRead function processes the FD_READ event, and drives the receive state machine.
When a FD_READ event is generated it is possible that the complete message is not present. The remote node may have attempted to send a 100 byte response, but the transport system may have only had buffer space to transmit three bytes.
The receiver will get a FD_READ for the three bytes. OnTcpIpRead calls
CSample_View rx_msg to read the receive data into the buffer. There are three parameters to rx_msg. The first parameter is a pointer to a receive buffer. The second input parameter is the receive size. The third parameter is both an input and output parameter. On both input and output the third parameter is the number of bytes read. These parameters allow the processing of a partially received message.
The receive state machine maintains a variable which is the number of bytes received. Initially the receive state machine is in the RX_HEADER state, and the number of bytes received is zero.
When OnTcpIpRead is called and the receive state is RX_HEADER OnTcpIpRead calls rx_msg with receive size equal to the header size. On return OnTcpIpRead examines the number of bytes received. If the number of bytes received is not equal to the header size, then receive machine remains in the RX_HEADER state, and OnTcpIpRead returns.
840 USE 116 00 Version 1.0
201
Appendix B Ethernet Developers Guide
Receive State Machine, continued
Description, continued
If upon return, the number of bytes received is the same size as the header size, then the header has been received. OnTcpIpRead sets the number of bytes received to zero, and the receive size is obtained from the header. These two values will be used the next time rx_msg is called. OnTcpIpRead also obtains the transaction identifier and the protocol type from the header. If the transaction identifier matches the transmit request identifier and the protocol type is MODBUS, then OnTcpIpRead changes the receive state to RX_BODY. However if either transaction identifier does not match or the protocol is not MODBUS, then
OnTcpIpRead changes the receive state to DUMP_BODY.
When OnTcpIpRead is called and the receive state is RX_BODY, OnTcpIpRead calls rx_msg with receive size equal to the value obtained from the header. On return OnTcpIpRead examines the number of bytes received. If the number of bytes received is not equal to the receive size, then the receive machine remains in the RX_HEADER state, and OnTcpIpRead returns.
If upon return the number of bytes received is the same as the receive size, then
OnTcpIpRead has read the response to a transaction. OnTcpIpRead saves the results and invalidates the client area which causes the results to be display.
OnTcpIpRead also changes the transmit state to WAIT_TO_TX, and resets the state receive state machine by setting the state to RX_HEADER and the number of bytes received to zero. It then returns.
When OnTcpIpRead is called and the receive state is DUMP_BODY,
OnTcpIpRead calls rx_msg with receive size equal to the value obtained from the header. On return OnTcpIpRead examines the number of bytes received. If the number of bytes received is not equal to the receive size, then the receive machine remains in the RX_HEADER state, and OnTcpIpRead returns.
If upon return the number of bytes received is the same as the receive size, the
OnTcpIpRead has completed reading the message. Since this message does not correspond to an transaction, the only processing OnTcIpRead performs is resetting the receive state machine.
The member function rx_msg calls the window socket recv function to read data.
The recv function either returns a non negative number that is the number of bytes read or it returns an error. If the number bytes read is zero, then the connection no longer exits, and rx_msg closes the socket, and sets the transmit state to IDLE. If the recv function returns the error indicating that no receive data is available, then rx_msg just returns. For any other recv function error, rx_msg closes the socket, and sets the transmit state to IDLE.
202
840 USE 116 00 Version 1.0
Appendix B Ethernet Developers Guide
Displaying on the Screen
Description
CSample_View m_display member indicates the display type. The different types of the displays and the CSample_View member functions for showing the display are as follows.
1 . Displaying the connection state. The different connection states displayed are
IDLE, RESOLVING NAME, and CONNECTING. ConnPaint member function displays the connection state.
2.
GetStatsPaint member function displays the results of a get statistics request.
3.
ClearStatsPaint member function displays the results of a clear statistics request.
4.
ReadRegPaint member function displays the results of a read register request.
5.
WriteRegPaint member function displays the results of a write register request.
MFC architectural framework calls CSample_View OnDraw member function to process the window WM_PAINT message. OnDraw examines m_display member variable and calls the corresponding member function described in the previous paragraph. Whenever CSample_View needs to display a result, it calls Cview
Invalidate function which causes a WM_PAINT message.
CSample_View is derived from MFC CScrollView class. This class handles the scroll logic. To perform the scroll logic, CScrollView requires the size of the document. It is informed of the document size via its SetScrollSizes member function.
CSample_View UpdateScrollSizes member function based on the display type calculates the document size, and then calls SetScrollSizes. CSample_View calls
UpdateScrollSizes when the display type changes or when the user changes the window size.
840 USE 116 00 Version 1.0
203
Appendix B Ethernet Developers Guide
204
840 USE 116 00 Version 1.0
Quantum Ethernet TCP/IP
Modbus Application Protocol
C
At a Glance
What’s in this
Appendix
This appendix covers the following topics.
Topic
Overview
Modbus Application Protocol PDU
Modbus Application Protocol Service Classes
Modbus Application Protocol PDU Analysis
TCP/IP Specific Issues
Reference Documents
Page
206
207
209
210
212
213
205
840 USE 116 00 Version 1.0
Appendix C Quantum Ethernet TCP/IP Modbus Application Protocol
Overview
Introduction
The Modbus Application Protocol (MBAP) is a layer-7 protocol providing peer-topeer communication between programmable logic controllers (PLCs) and other host-based nodes on a LAN. Collectively these nodes implement all or part of a control application used for industrial automation applications in the automotive, tire and rubber, food and beverage, and utilities industries, to name a few.
Modbus protocol transactions are typical request-response message pairs.
Modbus requests contain function codes representing several classes of service including data access, online programming, and program download and upload classes. Modbus responses can be ACKs with and without data, or NACKs with error information.
The Modbus Application Protocol can be transmitted over any communication system that supports messaging services. However, the current Quantum implementation transports Modbus Application Protocol PDUs over TCP/IP. Both
Ethernet II and IEEE 802.3 framing are accommodated, although Ethernet II framing is the default.
For more information, consult the Modbus Protocol Reference Guide (PI-MBUS-
300).
206
840 USE 116 00 Version 1.0
Appendix C Quantum Ethernet TCP/IP Modbus Application Protocol
Modbus Application Protocol PDU
The Modbus Application Protocol PDU, mbap_pdu, is received at TCP port number
502. The current maximum size of the mbap_pdu for this class of services is 256 bytes. The structure and content of the mbap_pdu is defined to be: mbap_pdu ::={ inv_id[2], proto_id[2], len[2],dst_idx[1], data=mb_pdu }
The header is seven bytes long and includes the following fields: inv_id [2 bytes] invocation id used for transaction pairing proto_id [2 bytes] used for intra-system multiplexing, default is 0 for
Modbus services len [2 bytes] the len field is a byte count of the remaining fields and includes the dst_id and data fields
The remainder of the pdu includes two fields: dst_idx [1 byte] destination index is used for intra-system routing of packets (currently not implemented) data [n bytes] this is the service portion of the Modbus pdu, mb_pdu and is defined below
The service portion of the Modbus Application Protocol, called mb_pdu, contains two fields: mb_pdu ::={ func_code[1], data[n] } func_code[1 byte] Modbus function code data [n bytes] this field is function code dependent and usually contains information such as variable references, variable counts and data offsets
The size and content of the data field are dependent on the value of the function code.
Continued on next page
840 USE 116 00 Version 1.0
207
Appendix C Quantum Ethernet TCP/IP Modbus Application Protocol
Modbus Application Protocol PDU, continued
Example
Here are the values for a sample mbap_pdu for reading a register:
00 01 00 00 00 06 01 03 00 00 00 01
This example has the folowing structure and content: inv_id 00 01 proto_id 00 00 len 00 00 dst_idx 01 func_code03 data 00 00 00 01
208
840 USE 116 00 Version 1.0
Appendix C Quantum Ethernet TCP/IP Modbus Application Protocol
Modbus Application Protocol Service Classes
Introduction
There are several classes of service that are part of the Modbus Application
Protocol. Each of these classes is described below.
Data Access
Read/write both discrete and analog data values from PLC register files.
Online
Programming
Services make relatively minor alterations to ladder logic programs with a highly controlled introduction of these changes into the executing program.
Image Download/
Upload
Image download services support the downloading of a ladder logic control program to the PLC. Image upload services support the uploading of a ladder logic control program from a PLC to PC host for archival/backup purposes.
Configuration
Configuration services allow the user to define parameter values which affect the
PLC’s register files, I/O map, communication port configuration and scan attributes, to name a few.
Device
Execution State
Control
The class of service allows the user to start/stop the PLC scan execution. These services require the user to be in an application login context which is obtained through other Modbus services.
840 USE 116 00 Version 1.0
209
Appendix C Quantum Ethernet TCP/IP Modbus Application Protocol
Modbus Application Protocol PDU Analysis
Introduction
An analysis of the Modbus Application Protocol is described in the following paragraphs
Analysis
210
The Modbus Application Protocol PDU is transmitted over a TCP/IP Ethernet stack.
Both Ethernet II and IEEE 802.3 framing will be accommodated. Ethernet II framing is the default.
. . . from the wire in for IEEE 802.3 framing . . .
. . . is IEEE 802.3 framing if length <=1500 . . .
802.3_pdu ::= {dst_addr[6], src_addr[6], length[2], data=802.2_pdu}
*an IEEE 802.3 PDU has a maxFrameSize of 1518 octets
*an IEEE 802.3 PDU has a minFrameSize of 64 octets
802.2_pdu : {dsap[1], ssap[1], frm_cntrl[1], snap_hdr[5], data=ip_pdu}
*the snap_hdr is associated with a “well-known” 802.2 sap snap_hdr
::={org_code[3], ethertype[2] }
*the snap hdr (sub network access protocol) allows the older style
Ethernet protocols to run on the newer IEEE 802.2 interface. The ethertype parameter indicates the service, ex. ip or arp. IP has a value
0x800.
. . . from the wire in for Ethernet II framing . . .
. . . is Ethernet II framing if length >1500 . . .
802.3_pdu ::= {dst_addr[6], src_addr[6], length[2], data=ip_pdu}
. . . the common part of the packet begins here . . .
ip_pdu ::= {ip_hdr[20], data=tcp_pdu} tcp_pdu ::= {tcp_hdr[24], data=appl_pdu=mbap_pdu}
The mbap_pdu is the Modbus Application Protocol whose messages are received at a well-known port. The current maximum size of the mbap_pdu for this class of services in 256 bytes.
Continued on next page
840 USE 116 00 Version 1.0
Appendix C Quantum Ethernet TCP/IP Modbus Application Protocol
Modbus Application Protocol PDU Analysis, continued
Analysis, continued
The structure and content of the mbap_pdu is defined to be: mbap_pdu ::={ inv_id[2], proto_id[2], len[2], dst_idx[1], data=mb_pdu }The header is 7 bytes long, and includes the following fields: inv_id[2 bytes] invocation id used for transaction pairing proto_id[2 bytes] used for intra-system multiplexing,default is 0 for Modbus services len[2 bytes] the len field is a byte count of the remaining fields and includes the dst_id and data fields.
The remainder of the pdu includes two fields: dst_idx[1 byte] destination index is used for intra-system routing of packets. (currently not implemented) data[n bytes] this is the service portion of the Modbus pdu, mb_pdu, and is defined below
The service portion of the Modbus Application Protocol, called mb_pdu, contains 2 fields: mb_pdu ::= { func_code[1], data[n] } func_code[1 byte] MB function code data[n bytes] this field is function code dependent and usually contains information such as variable references, variable counts, and data offsets.
The size and content of the data field are dependent on the value of the function code.
840 USE 116 00 Version 1.0
211
Appendix C Quantum Ethernet TCP/IP Modbus Application Protocol
TCP/IP Specific Issues
Broadcast/
Multicast
TCP Port
Number
Although broadcast and/or multicast are supported by both IP network address and
IEEE 802.3 MAC address, the Modbus Application Protocol does not support either broadcast or multicast at the application layer.
Schneider Electric’s Quantum PLCs use broadcast addressing because they use
ARP as the means of locating the destination node. The client interface to the
Modbus Application Protocol service on the PLC, the MSTR block, requires the user to provide the destination IP address. Also the embedded stack does use a pre-configured default gateway IP address in the case where ARP does not succeed.
Schneider Electric has obtained a well-known system port from an Internet
Authority. Schneider Electric’s well-known system port number is 502. The
Internet Authority assigned the system port number 502 to asa-appl-proto with
Dennis Dubé as the company point of contact.
This port number allows Schneider Electric to transport various application protocols over with TCP or UDP. The particular protocol is indicated by the value of the proto_id parameter in the mbap_pdu. Currently the only assignment is 0 meaning Modbus Application Protocol.
212
840 USE 116 00 Version 1.0
Appendix C Quantum Ethernet TCP/IP Modbus Application Protocol
Reference Documents
Introduction
The following reference documents may prove helpful to you.
[1] ANSI/IEEE Std 802.3-1985, ISO DIS 8802/3, ISBN - 0-471-82749-5, May 1988
[2] ANSI/IEEE Std 802.2-1985, ISO DIS 8802/2, ISBN 0-471-82748-7, Feb 1988
[3] RFC793, TCP (Transmission Control Protocol) DARPA Internet Program
Protocol Specification, Sep 1981
[4] RFC 791, IP (Internet Protocol) DARPA Internet Protocol Specification, Sep
1981
[5] RFC826, An Ethernet Address Resolution Protocol (ARP), David Plummer, NIC
Sep 1982
[6] RFC1042, A Standard for the Transmission of IP Datagrams over IEEE 802.2
Networks, Postel & Reynolds, ISI, Feb 1988
[7] RFC 792, ICMP (Internet Control Message Protocol) DARPA Internet C Control
Message Protocol Specification, Jon Postel, Sep 1981
[8] RFC951, BOOTSTRAP PROTOCOL (BOOTP), Bill Croft and John Gilmore ,
September 1985
[9] RFC783, The Trivial File Transfer Protocol (TFTP) rev 2, K.R. Sollins MIT, June
1981
840 USE 116 00 Version 1.0
213
Appendix C Quantum Ethernet TCP/IP Modbus Application Protocol
214
840 USE 116 00 Version 1.0
NOE 771 00 Module I/O Scanner
Performance Statistics
D
At a Glance
What’s in this
Appendix
This appendix covers the following topics.
Topic
140 NOE 771 00 With Quantum 113 CPU
140 NOE 771 00 With Quantum 213 CPU
140 NOE 771 00 With Quantum 424 CPU
140 NOE 771 00 With Quantum 534 CPU
Page
216
217
218
219
840 USE 116 00 Version 1.0
215
Appendix D NOE 771 00 Module I/O Scanner Performance Statistics
140 NOE 771 00 I/O Scanner Performance
Quantum
113 CPU
Following is the performance graph for the I/O Scanner of the 140 NOE 771 00 with the Quantum 113 CPU.
IO S canner P erfo rm ance o f the 1 4 0 N O E 7 7 1 0 0 w ith the Q uantum 1 1 3 C P U
4,000
3,500
3,000
2,500
2,000
1 ,500
1 ,000
500
0
1 2 3 4 5 6 7 8 9 1 0 1 5 20 25 30 35 40 45 50 55 60 64
M in CP U Scan
1 0 m Sec CP U Scan
20 m Sec CP U Scan
40 m Sec CP U Scan
60 m Sec CP U Scan
80 m Sec CP U Scan
1 00 mSec C PU Scan
Modbus Transactions per Scanner
Continued on next page
216
840 USE 116 00 Version 1.0
Appendix D NOE 771 00 Module I/O Scanner Performance Statistics
140 NOE 771 00 I/O Scanner Performance, continued
Quantum
213 CPU
Following is the performance graph for the I/O Scanner of the 140 NOE 771 00 with the Quantum 213 CPU.
140 NOE 771 00 IO Scanner Perform ance
CPU 213
4,000
3,500
3,000
2,500
2,000
1,500
1,000
500
0
0 10 20 30 40 50
Number of Scanned Momentum ENT Modules
Modbus Transactions per Scanner
60 70
Continued on next page
840 USE 116 00 Version 1.0
217
Appendix D NOE 771 00 Module I/O Scanner Performance Statistics
140 NOE 771 00 I/O Scanner Performance, continued
Quantum
424 CPU
Following is the performance graph for the I/O Scanner of the 140 NOE 771 00 with the Quantum 424 CPU.
140 NOE 771 00 IO Scanner Perform ance
CPU 424
5,000
4,500
4,000
3,500
3,000
2,500
2,000
1,500
1,000
500
0
1 6 11 16 21 26 31 36 41 46 51 56 61
M in C PU Scan
1 m Sec C PU Scan
2 m Sec C PU Scan
4 m Sec C PU Scan
5 m Sec C PU Scan
10 m Sec C PU Scan
20 m Sec C PU Scan
40 m Sec C PU Scan
60 m Sec C PU Scan
80 m Sec C PU Scan
100 m Sec C PU Scan
Modbus TCP/IP Transactions per Scanner
Continued on next page
218
840 USE 116 00 Version 1.0
Appendix D NOE 771 00 Module I/O Scanner Performance Statistics
140 NOE 771 00 I/O Scanner Performance, continued
Quantum
534 CPU
Following is the performance graph for the I/O Scanner of the 140 NOE 771 00 with the Quantum 534 CPU.
IO Scanner Perform ance of 140 NOE 771 00 w ith Quantum 534 CPU
4,500
4,000
3,500
3,000
2,500
2,000
1,500
1,000
500
0
1 2 3 4 5 6 7 8 9 10 15 20 25 30 35 40 45 50 60 64
Modbus Transactions per Scanner
840 USE 116 00 Version 1.0
219
Appendix D NOE 771 00 Module I/O Scanner Performance Statistics
220
840 USE 116 00 Version 1.0
Glossary
A
ACK address
API
ARP
Acknowledgement
On a network, the identification of a station. In a frame, a grouping of bits that identifies the frame’s source or destination.
Application Program Interface. The specification of functions and data used by one program module to access another; the programming interface that corresponds to the boundary between protocol layers.
Address Resolution Protocol. A network layer protocol used to determine the physical address which corresponds to the IP address for a host on the network.
ARP is a sub-protocol which operates under TCP/IP.
B
bps
BOOTP
840 USE 116 00 Version 1.0
Bits per second.
BOOTstrap Protocol. A protocol used at power-up in order to get an IP address which is provided by a BOOTP server and is based on the module’s MAC address.
221
Glossary
bridge
BSP
A device that connects two or more physical networks which use the same protocol. Bridges read frames and decide whether to transmit or block them based on their destination address.
Board Support Package. A software package that maps a specific real-time operating system (RTOS0 onto a specific hardware.
C
client
Concept
Cyclic Data
Exchange
A computer process requesting service from other computer processes.
A software package that facilitates controller configuration.
Provides data transfer between two or more NOE 771 x0 controllers on a TCP/IP network.
D
default gateway
DNS
The IP address of the network or host to which all packets addressed to an unknown network or host are sent. The default gateway is typically a router or other device.
Domain Name System. A protocol within TCP/IP used to find IP addresses based on host names.
F
FactoryCast field firewall frame
222
An embedded web server which is user customizable, permitting user access to controller diagnostics and Ethernet configuration.
A logical grouping of contiguous bits that convey one kind of information, such as the start or end of a message, an address, data or an error check.
A gateway that controls access to a network or an application.
A group of bits which form a discrete block of information. Frames contain network control information or data. The size and composition of a frame is determined by the network technology being used.
840 USE 116 00 Version 1.0
framing types
FTP full duplex
Glossary
Two common framing types are Ethernet II and IEEE 802.3.
File Transfer Protocol. A networking protocol used to exchange files between stations on a network or over the Internet.
(FDX) A method of communication in which data is transmitted in two directions at the same time.
G
gateway
A device which connects networks with dissimilar network architectures and which operates at the Application Layer. This term may refer to a router.
H
half duplex host hostname
HTTP hub
(HDX) A method of data transmission capable of communication in two directions, but only one direction at a time.
A node on a network.
A domain name given to a specific computer on a network and used to address that computer.
Hyper Text Transport Protocol. A protocol used to deliver hypertext documents over the WEB.
A device which connects a series of flexible and centralized modules to create a network.
I
ICMP
Internet
IP
840 USE 116 00 Version 1.0
Internet Control Message Protocol. A protocol within TCP/IP used to report errors in datagram transmission.
The global interconnection of TCP/IP based computer communication networks.
Internet Protocol. A common network layer protocol. IP is most often used with
TCP.
223
Glossary
IP Address
IO Map
I/O Drop
I/O Scan
I/O Scan List
Internet Protocol Address. A 32-bit address assigned to hosts using TCP/IP.
An area in the controller configuration memory used to map input and output points. Previously called traffic cop.
One or two (depending on the system type) Remote I/O Channels consisting of a fixed number of I/O points.
A procedure the processor follows to monitor inputs and control outputs.
A configuration table which identifies the targets with which repetitive communication is authorized.
L
layer
N
NACK network
224
In the OSI model, a portion of the structure of a device which provides defined services for the transfer of information.
M
MAC Address
MBAP
Modbus
Modsoft
MSTR
Media Access Control address. The hardware address of a device. A MAC address is assigned to an Ethernet TCP/IP module in the factory.
Modbus Application Protocol
A communication system that links Modicon controllers with intelligent terminals and computers over common carrier or dedicated lines.
A software package that facilitates programming the NOE module.
A special master instruction which uses ladder logic to read and write controller information.
Negative acknowledgment indicating an error.
Interconnected devices sharing a common data path and protocol for communication.
840 USE 116 00 Version 1.0
Glossary
node
NOET
O
An addressable device on a communications network.
Network Options Ethernet Tester
OSI model
Open System Interconnection model. A reference standard describing the required performance of devices for data communication. Produced by the International
Standards Organization.
P
packet
Peer Cop
PING port protocol
PLC
ProWORX NxT
The unit of data sent across a network.
Software that allows you to configure data blocks to be transferred between controllers on a Modbus Plus network.
Packet Internet Groper. A program used to test whether a destination on a network can be reached.
An access point for data entry or exit within a host using TCP services.
Describes message formats and a set of rules used by two or more devices to communicate using those formats.
Programmable Logic Controller
A software package that facilitates the use of the I/O Scanner to configure data blocks to be transferred between controllers on a TCP/IP network.
R
repeater
A device that connects two sections of a network and conveys signals between them without making routing decisions or filtering packets.
840 USE 116 00 Version 1.0
225
Glossary
router
A device that connects two or more sections of a network and allows information to flow between them. A router examines every packet it receives and decides whether to block the packet from the rest of the network or transmit it. The router will attempt to send the packet through the network by the most efficient path.
S
server
SNMP socket stack
STP subnet subnet mask switch
Provides services to clients. This term may also refer to the computer on which the service is based.
Simple Network Management Protocol
The association of a port with an IP address, serving as an identification of sender or recipient.
The software code which implements the protocol being used. In the case of the
NOE modules it is TCP/IP.
Shielded Twisted Pair. A type of cabling consisting of several strands of wire surrounded by foil shielding, twisted together.
A physical or logical network within an IP network, which shares a network address with other portions of the network.
Used to indicate which bits in an IP address identify a subnet.
A network device which connects two or more separate network segments and allows traffic to be passed between them. A switch determines whether a frame should be blocked or transmitted based on its destination address.
T
TCP
TCP/IP
Traffic Cop
226
Transmission Control Protocol.
A protocol suite consisting of the Transmission Control Protocol and the Internet
Protocol; the suite of communications protocols on which the Internet is based.
A Quantum software routine that facilitates the placement of an NOE 771 module into a specified location
840 USE 116 00 Version 1.0
Glossary
U
UDP
URL
UTP
W
Winsock
WWW
User Datagram Protocol. A protocol which transmits data over IP.
Uniform Resource Locator. The network address of a file.
Unshielded Twisted Pair. A type of cabling consisting of insulated cable strands which are twisted together in pairs.
The Microsoft implementation of the Windows Sockets networking API based on the Berkeley UNIX Sockets interface for supporting TCP/IP.
World Wide Web. A hypertext-based, distributed information system in which clients and servers are freely available.
840 USE 116 00 Version 1.0
227
Glossary
228
840 USE 116 00 Version 1.0
Index
A
B
C
B
BOOTP
Configure via web server, 146
Display via web server, 146, 149
Server features, 22
BOOTP Lite
Assigning address parameters, 49
C
Cables, twisted pair
Pin arrangements, 15
Cabling schemes
Ethernet hub/switch, 30
Concept
Configuring I/O Scan List, 68
Configuring NOE module, 52
Concept Exec Loader
Download process, 180
Configure BOOTP
Via web server, 146
Configure NOE
Via web server, 142
Configure SNMP
Via web server, 143
Configuring the Ethernet Address
Parameters, 63
Configuring the I/O Scan List
Using Concept, 72
Using Modsoft, 94
Using ProWORX NxT, 79
840 USE 116 00 Version 1.0
Configuring the Module
With Concept, 51
Connectors
100 BASE-FX, 15
Twisted pair, 15
CPU configuration
Via web server, 133
Crash log
Clearing, 178
Clearing via FTP, 178
Reading, 177
Reading via FTP, 177
CTE error codes
MSTR, 110
E
Error codes
Ethernet CTE, 110
Ethernet tester, 170
MSTR, 108
TCP/IP Ethernet, 108
Errors
Detecting, 172
LED indicators, 172
Ethernet
Developers guide, 190
Ethernet address parameters
Configuring, 63
Using ProWORX NxT, 85
Ethernet statistics
Via web server, 136
229
Index
Ethernet TCP/IP
Memory requirements, 56
Ethernet TCP/IP modules
Twisted pair connector, 15
Ethernet tester
Error codes, 170
Getting and clearing statistics, 162
Installation, 158
Network options, 158
Reading registers, 168
Requirements, 159
Statistics description, 166
Writing registers, 169
F
FactoryCast
FTP
Features, 10
Downloading a new NOE Exec, 185
Services, 20
H
Health Block
Configuring for I/O Scan List, 75
Health Timeout
I/O Scanner, 72
HTTP
Services, 21
I
I/O Map
Access and Edit, 59
I/O Scan List, 68
Configuring Using Modsoft, 94
Configuring Using ProWORX NxT, 79
Configuring with Concept, 68
I/O Scanner
Definitions, 69
Introduction, 68
Modules supported, 71
Performance statistics, 215
Installing NOE 771 x0, 27
230
L
Ladder Logic Diagram
MSTR, 106
LED
Active error, 172
Collision error, 175
Fault error, 174
Kernel error, 174
Link error, 173
Ready error, 173
LED Indicators
Panel, 13
Run Status, 13
M
MBAP
Modbus Application Protocol, 206
Memory requirements
Ethernet TCP/IP, 56
Per module, 56
Modbus Application Protocol (MBAP)
Description, 206
Modbus I/O Scanner
Features, 70
Peer Cop characteristics, 16
Modbus/TCP
Performance, 18
Modsoft
Peer Cop configuration extension, 94
840 USE 116 00 Version 1.0
MSTR
Characteristics, 105
Clear local statistics, 113
Clear remote statistics, 115
CTE Display, 124
Ethernet TCP/IP, 18
Function error codes, 108
Get local statistics, 112
Get remote statistics, 114
Inputs, 106
Ladder Logic, 106
Network communications, 18
Operations, 104
Outputs, 106
Peer Cop health, 116
Read and Write Operations, 111
Write CTE, 123
N
Network Options Ethernet Tester (NOET)
Installation, 158
NOE
Crash log diagnostics via web server, 153
Memory requirements, 56
Product support information, 155
Properties via web server, 151
Setting the number using Concept, 56
NOE 771 00
Key features, 10
Transferring Data with the I/O Scanner, 67
NOE 771 10
FactoryCast application, 10
Key features, 10
840 USE 116 00 Version 1.0
Index
NOE 771 x0
Cable connectors, 15
Configuring Ethernet address parameters, 63
Detecting errors, 172
Embedded web server, 127
Front panel components, 11
Key features, 11
LEDs, 13
Responding to errors, 172
Specifications, 188
System maintenance, 171
NOE diagnostics
Via web server, 152
NOE Exec
Downloading a new, 179
Downloading via FTP, 185
NOET
Network Option Ethernet Tester, 190
Sample application, 190
P
Password, FTP
Changing via web server, 41
Password, HTTP
Changing via web server, 46
Peer Cop
Data input/output configuration, 96
For configuring I/O Scan List, 94
Health Bits, 101
Input/output summary, 99
Memory extension, 90
Modbus I/O Scanner characteristics, 16
Modsoft initial entry screen, 96
Parameters, 98
Related functions, 99
Timeout function, 100
Peer Cop Communications
Health Bit State, 119
Health status information, 117
Peer Cop Health
MSTR Operation, 116
Peer Cop I/O Scanner
Features, 70
231
Index
PLC
Selection using Concept, 52
PLC data monitor
Via web server, 140
Port numbers
By protocol, 33
ProWORX NxT
Configuring I/O Scan List, 79
Setting number of NOEs, 85
R
Remote I/O communications status
Via web server, 138
S
Security
Protocol port numbers, 33
Types of firewalls, 33
Selecting Your PLC
Using ProWORX NxT, 80
Setting the Number of NOEs
Using Concept, 56
Using ProWORX NxT, 85
SNMP
Configure via web server, 143
Features, 23
Protocol Data Units, 25
Storage Requirements
I/O Scan List, 95
System Requirements
Minimum, 6
T
TCP/IP
Broadcast addressing, 212
TCP/IP Ethernet
Error codes, 108
TCP/IP Ethernet statistics, 125
Traffic Cop
Configuring I/O Scan List, 83
Transferring Data
With the I/O Scanner, 67
232
Twisted pair cables
Length, 30
W
Web server
Accessing, 41
Accessing the home page, 128
Configure BOOTP, 146
Configure NOE, 142
Configure SNMP, 143
CPU configuration fields, 134
CPU configuration screen, 133
Crash log diagnostics, 153
Embedded web pages, 127
Ethernet module statistics, 136
Features, 128
Home page, 129
Internet Explorer, 128
Netscape Navigator, 128
NOE diagnostics, 152
NOE properties, 151
Password request, 129
PLC data monitor, 140
Quantum local rack page, 132
Remote I/O communications status, 138
Support information, 155
Welcome page, 130
Welcome page links, 131
840 USE 116 00 Version 1.0