Appendix C Quantum Ethernet TCP/IP Modbus Application Protocol
TCP/IP Specific Issues
Broadcast/
Multicast
TCP Port
Number
Although broadcast and/or multicast are supported by both IP network address and
IEEE 802.3 MAC address, the Modbus Application Protocol does not support either broadcast or multicast at the application layer.
Schneider Electric’s Quantum PLCs use broadcast addressing because they use
ARP as the means of locating the destination node. The client interface to the
Modbus Application Protocol service on the PLC, the MSTR block, requires the user to provide the destination IP address. Also the embedded stack does use a pre-configured default gateway IP address in the case where ARP does not succeed.
Schneider Electric has obtained a well-known system port from an Internet
Authority. Schneider Electric’s well-known system port number is 502. The
Internet Authority assigned the system port number 502 to asa-appl-proto with
Dennis Dubé as the company point of contact.
This port number allows Schneider Electric to transport various application protocols over with TCP or UDP. The particular protocol is indicated by the value of the proto_id parameter in the mbap_pdu. Currently the only assignment is 0 meaning Modbus Application Protocol.
212