E: Motor Parameters. YASKAWA iQpump Micro CIMR-PW Series
Reklāma
Reklāma
5.5 E: Motor Parameters
5.5 E: Motor Parameters
E parameters cover V/f pattern and motor data settings.
u
E1: V/f Characteristics
n E1-01: Input Voltage Setting
Set the input voltage parameter to the nominal voltage of the AC power supply. This parameter adjusts the levels of some protective features of the drive (overvoltage, Stall Prevention, etc.).
NOTICE: Set parameter E1-01 to match the input voltage of the drive. Drive input voltage (not motor voltage) must be set in E1-01 for the protective features of the drive to function properly. Failure to comply could result in improper drive operation.
No.
E1-01 <1>
Parameter Name
Input Voltage Setting
Setting Range
155 to 255 V
<1> The setting range and default value shown here are for 200 V class drives. Double this for 400 V class units.
Default
230 V
E1-01 Related Values
The input voltage setting determines the over-/undervoltage detection level and the operation levels of the braking transistor as well as the KEB function and the overvoltage suppression function.
(Approximate Values)
Voltage
Setting Value of
E1-01 Voltage during KEB
(L2-11) ov Suppression /
Stall Prevention
Level
(L3-17)
200 V Class
400 V Class all settings setting ≥ 400 V setting < 400 V
410 V
820 V
740 V
394 V
788 V
708 V
190 V
(single-phase = 160
V)
380 V
350 V
240 V
480 V
440 V
370 V
740 V
660 V
Note: The braking transistor operation levels are valid for the drive internal braking transistor. If an external CDBR braking chopper is used, refer to the instruction manual of that unit.
n V/f Pattern Settings
The drive utilizes a set V/f pattern to determine the appropriate output voltage level for each relative to the frequency reference.
There are 15 different preset V/f patterns to select from with varying voltage profiles, saturation levels (frequency at which maximum voltage is reached), and maximum frequencies. Additionally, one custom V/f pattern can be set up by programming parameters E1-04 through E1-10.
V/f Pattern Setup for V/f Control
1.
Set the input voltage for the drive.
Refer to E1-01: Input Voltage Setting on page 155 .
2.
Set the V/f pattern by: a) choosing one of the 15 preset V/f patterns (E1-03 = 0 to E).
b) select the custom V/f pattern (E1-03 = F, default setting).
3.
When using one of the 15 presets, E1-04 through E1-13 are automatically set. Refer to the description below.
For a custom V/f pattern, E1-04 through E1-13 must be adjusted manually.
Refer to V/f Pattern Settings E1-04 to
.
n E1-03: V/f Pattern Selection
This parameter can only be changed when the drive is operating in V/f Control. It allows the user to select the V/f pattern from
15 predefined patterns or to create a custom V/f pattern.
No.
E1-03
Parameter Name
V/f Pattern Selection
Setting Range
0 to F
Default
F
5
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual 155
5.5 E: Motor Parameters
Setting the V/f Pattern
Choose the V/f pattern that meets the application demands from the table below. Set the correct value to E1-03. The V/f parameters E1-04 to E1-13 can only be monitored, not changed.
Note: 1.
Setting an improper V/f pattern may result in low motor torque or increased current due to overexcitation.
2.
Parameter E1-03 is not reset when the drive is initialized.
Setting
0
1
B
C
D
E
7
8
5
6
9
A
2
3
4
Specification
50 Hz
60 Hz
(default setting)
60 Hz (with 50 Hz base)
72 Hz (with 60 Hz base)
50 Hz, Heavy Duty 2
50 Hz, Heavy Duty 1
60 Hz, Heavy Duty 1
60 Hz, Heavy Duty 2
50 Hz, mid starting torque
50 Hz, high starting torque
60 Hz, mid starting torque
60 Hz, high starting torque
90 Hz (with 60 Hz base)
120 Hz (with 60 Hz base)
180 Hz (with 60 Hz base)
Table 5.11 Predefined V/f Patterns
Characteristic
Constant torque
Derated torque
High starting torque
Constant output
Application
For general purpose applications. Torque remains constant regardless of changes to speed.
For fans, pumps, and other applications that require torque derating relative to the load.
Select high starting torque when:
• Wiring between the drive and motor exceeds
150 m
• A large amount of starting torque is required
• An AC reactor is installed
When operating at greater than 60 Hz the output voltage will be constant.
The following tables show details on predefined V/f patterns.
The following graphs are for 200 V class drives; double the values for 400 V class drives.
Predefined V/f Patterns for 0.1 to 3.7 kW Drives
Table 5.12 Constant Torque Characteristics, Settings 0 to 3
Setting = 0 50 Hz Setting = 1
60 Hz
(default)
Setting = 2 60 Hz
200 200 200
Setting = 3
200
72 Hz
16
12
0 1.3 2.5
50
Frequency (Hz)
Setting = 4
200
50 Hz
35
8
0 1.3
25 50
Frequency (Hz)
16
12
0 1.5 3
Frequency (Hz)
60
16
12
0 1.5 3 50
Frequency (Hz)
60
Table 5.13 Derated Torque Characteristics, Settings 4 to 7
Setting = 5 50 Hz Setting = 6 60 Hz
200 200
50
9
0 1.3
25
Frequency (Hz)
50
35
8
0 1.5
30
Frequency (Hz)
60
16
12
0 1.5 3
Frequency (Hz)
60 72
Setting = 7
200
60 Hz
50
9
0 1.5
30
Frequency (Hz)
60
156 YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Setting = 8
200
50 Hz
19
12
0 1.3 2.5
Frequency (Hz)
50
Setting = C
200
90 Hz
Table 5.14 High Starting Torque, Settings 8 to B
Setting = 9 50 Hz Setting = A 60 Hz
200 200
24
13
0 1.3 2.5
Frequency (Hz)
50
19
12
0 1.5 3
Frequency (Hz)
60
Table 5.15 Rated Output Operation, Settings C to F
Setting = D 120 Hz Setting = E 180 Hz
200 200
5.5 E: Motor Parameters
Setting = B
200
60 Hz
24
15
0 1.5 3
Frequency (Hz)
60
Setting = F
200
60 Hz
16
12
0 1.5 3 60
Frequency (Hz)
90
16
12
0 1.5 3 60
Frequency (Hz)
120
16
12
0 1.5 3 60
Frequency (Hz)
180
16
12
0 1.5 3
Frequency (Hz)
60
Predefined V/f Patterns for 5.5 to 18.5 kW Drives
The following graphs are for 200 V class drives. Double values when using a 400 V class drive.
Setting = 0
200
50 Hz
Table 5.16 Rated Torque Characteristics, Settings 0 to 3
Setting = 1 60 Hz Setting = 2 60 Hz
200 200
Setting = 3
200
72 Hz
14
7
0 1.3 2.5
Frequency (Hz)
50
Setting = 4
200
50 Hz
35
6
0 1.3
25 50
Frequency (Hz)
Setting = 8
200
50 Hz
18
9
0 1.3 2.5
50
Frequency (Hz)
14
7
0 1.5 3
Frequency (Hz)
60
14
7
0 1.5 3 50
Frequency (Hz)
60
Table 5.17 Derated Torque Characteristics, Settings 4 to 7
Setting = 5 50 Hz Setting = 6 60 Hz
200 200
14
7
0 1.5 3 60
Frequency (Hz)
72
Setting = 7
200
60 Hz
50
7
0 1.3
25 50
Frequency (Hz)
35
6
0 1.5
30
Frequency (Hz)
60
Table 5.18 High Starting Torque, Settings 8 to B
Setting = 9 50 Hz Setting = A 60 Hz
200 200
23
11
0 1.3 2.5
50
Frequency (Hz)
18
9
0 1.5 3
Frequency (Hz)
60
50
7
0 1.5
30
Frequency (Hz)
60
Setting = B
200
60 Hz
23
13
0 1.5 3
Frequency (Hz)
60
5
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual 157
5.5 E: Motor Parameters
Setting = C
200
90 Hz
Table 5.19 Constant Output, Settings C to F
Setting = D 120 Hz Setting = E 180 Hz
200 200
Setting = F
200
60 Hz
14
7
0 1.5 3 60
Frequency (Hz)
90
14
7
0 1.5 3 60
Frequency (Hz)
120
14
7
0 1.5 3 60
Frequency (Hz)
180
14
7
0 1.5 3 60
Frequency (Hz)
Setting a Custom V/f Pattern
Setting parameter E1-03 to “F” allows to set up a custom V/f pattern by changing parameters E1-04 to E1-13.
When E1-03 is changed to “F”, the default values for parameters E1-04 to E1-13 will be equal to V/f pattern 1 of the predefined patterns.
n V/f Pattern Settings E1-04 to E1-13
Using parameters E1-04 through E1-13, the user can either monitor the V/f pattern values if E1-03 ≤ 15 or set up a custom V/
f pattern as shown in Figure 5.38
No.
E1-04
E1-05
E1-06
E1-07
E1-08
E1-09
E1-10
E1-11
E1-12
E1-13 <2>
Parameter Name
Maximum Output Frequency
Maximum Voltage
Base Frequency
Middle Output Frequency
Middle Output Frequency Voltage
Minimum Output Frequency
Minimum Output Frequency Voltage
Middle Output Frequency 2
Middle Output Frequency Voltage 2
Base Voltage
<1> Values shown are for 200 V class drives; double the value when using 400 V class drives.
<2> When E1-13 is set to 0.0 V, the drive uses the value set in E1-05 to control the voltage.
Setting Range
40.0 to 400.0 Hz
0.0 to 255.0 V <1>
0.0 to E1-04
0.0 to E1-04
0.0 to 255.0 V <1>
0.0 to E1-04
0.0 to 255.0 V <1>
0.0 to E1-04
0.0 to 255.0 V <1>
0.0 to 255.0 Hz
Default
60.0 Hz
230 V <1>
60.0 Hz
3.0 Hz
18.4 V <1>
1.5 Hz
13.8 V <1>
0.0 Hz
0.0 V
0.0 V
Output Voltage (V)
Note:
Frequency (Hz)
Figure 5.38 V/f Pattern
1.
The following condition must be true when setting up the V/f pattern: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
2.
Setting E1-11 to 0 disables both E1-11 and E1-12 and the above conditions do not apply.
3.
To make the V/f pattern a straight line set E1-09 = E1-07. In this case the E1-08 setting is disregarded.
4.
E1-03 is unaffected when the drive is initialized using parameter A1-03, but the settings for E1-04 through E1-13 are returned to their default values.
158 YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
5.5 E: Motor Parameters u
E2: Motor 1 Parameters
These parameters contain the most important motor data needed for optimal motor control. The parameters are set automatically during Auto-Tuning. Set the parameters manually when Auto-Tuning cannot be performed.
n E2-01: Motor Rated Current
Set E2-01 to the full load amps (FLA) stamped on the motor nameplate. During Auto-Tuning the value must be entered to parameter T1-04. If Auto-Tuning completes successfully, the value entered will automatically be saved to E2-01.
No.
E2-01
Parameter Name
Motor Rated Current
Setting Range
10% to 200% of the drive rated current.
(unit: 0.01 A)
Note: 1.
Display is in the following units:
BV0006 to BV0018, 2V0006 to 2V0040, and 4V0002 to 4V0023: 0.01 A units.
2V0056 to 2V0069 and 4V0031 to 4V0038: 0.1 A units.
2.
Change E2-01 only after changing the value set to E2-03. Setting E2-01 < E2-03 will trigger an oPE02 error.
n E2-02: Motor Rated Slip
Sets the motor rated slip in Hz. This value is automatically set during Rotational Auto-Tuning.
Default
Depending on o2-04
No.
E2-02
Parameter Name
Motor Rated Slip
Setting Range
0.00 to 20.00 Hz
Default
Depending on o2-04
If Auto-Tuning cannot be performed calculate the motor rated slip using the information written on the motor nameplate and the formula below:
E2-02 = f - (n x p)/120
(f: rated frequency (Hz), n: rated motor speed (r/min), p: number of motor poles) n E2-03: Motor No-Load Current
Set E2-03 to the motor no-load current at rated voltage and rated frequency. If Rotational Auto-Tuning completes successfully, this value is automatically calculated. If Auto-Tuning cannot be performed, contact the motor manufacturer for information about the no-load current.
No.
E2-03
Note:
Parameter Name
Motor No-Load Current
Setting Range
0 to [E2-01]
(unit: 0.01 A)
Default
Depending on o2-04
Display is in the following units: BV0006 to BV0018, 2V0006 to 2V0040, and 4V0002 to 4V0023: 0.01 A units. 2V0056 to 2V0069 and
4V0031 to 4V0038: 0.1 A units.
n E2-04: Number of Motor Poles
Set the number of motor poles to E2-04. If Auto-Tuning completes successfully, the value entered to T1-06 will automatically be saved to E2-04.
No.
E2-04
Parameter Name
Number of Motor Poles
Setting Range
2 to 48
Default
2 n E2-05: Motor Line-to-Line Resistance
Sets the line-to-line resistance of the motor stator winding. If the Auto-Tuning completes successfully, this value is automatically calculated. Remember this value must be entered as line-line and not line-neutral.
No.
E2-05
Parameter Name
Motor Line-to-Line Resistance
Setting Range
0.000 to 65.000 Ω
Default
Depending on o2-04
Note: The setting range becomes 0.00 to 130.00 when using BV0002, 2V0002, 4V0001 and smaller.
If Auto-Tuning is not possible, then contact the motor manufacturer to find out the line-to-line resistance or measure it manually. When using the manufacturer Motor Test Report, calculate E2-05 by the formulas below.
• E-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the Test Report at 75 °C
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual 159
5
5.5 E: Motor Parameters
• B-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the Test Report at 75 °C.
• F-type insulation: Multiply 0.87 times the resistance value (Ω) listed on the Test Report at 115 °C.
n E2-06: Motor Leakage Inductance
Sets the voltage drop due to motor leakage inductance as a percentage of motor rated voltage.
No.
Parameter Name Setting Range
E2-06 Motor Leakage Inductance 0.0 to 40.0%
Default
Depending on o2-04 n E2-10: Motor Iron Loss for Torque Compensation
This parameter sets the motor iron loss in watts.
No.
E2-10
Parameter Name
Motor Iron Loss for Torque Compensation
Setting Range
0 to 65535 W
Default
Depending on o2-04 n E2-11: Motor Rated Power
This parameter sets the motor rated power in kW. During Auto-Tuning the value must entered to parameter T1-02. If Auto-
Tuning completes successfully, the value entered will automatically be saved to E2-11.
No.
E2-11
Parameter Name
Motor Rated Power
Setting Range
0.00 to 650.00 kW
Default
Depending on o2-04
160 YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual