5.12 Q: PID Controller
5.12 Q: PID Controller
u
Q1: Preset Setpoint
n Q1-01: PID Controller Setpoint 1
Sets the PID setpoint for the controller. The drive will use the system feedback signal and modulate the pump speed to regulate the feedback at the Q1-01 setpoint. The units for Q1-01 are selected by b1-01 and the scaling is set in parameter P1-03. This parameter is active when b1-01 (Reference Source) is set to 0 (HOA keypad).
No.
Q1-01
Parameter Name
PID Controller Setpoint 1
Setting Range
0.0 to 6000.0
Default
0.0 PSI n Q1-02 to Q1-04: PID Controller Setpoint 2 to 4
Sets the PID Setpoint when the corresponding Multi Setpoint or Alternate Multi Setpoint digital inputs are closed.
No.
Q1-02 to Q1-04
Name
PID Controller Setpoint 2 to 4
Setting Range
0.0 to 6000.0
Default
0.0
n Q1-09: Setpoint MOP
Selects whether parameters Q1-01 to Q1-04 are changed via MOP using the Up and Down arrow keys on the HOA keypad.
No.
Q1-09
Name
Setpoint MOP
Setting Range
0, 1
Default
0
Setting 0: Disabled
Setting 1: Enabled u
Q3: Output Current Limit
The drive reduces the frequency reference in an attempt to limit the output current. The current limit setpoint is determined by parameter P1-11. When the actual motor current rises above the setpoint, the frequency reference is reduced by a PI controller and the minimum output frequency reference is limited to fmin. The HOA keypad will display a "Current Limit Foldback" alarm when the current limit function is active.
n Q3-01: Output Current Limit Select
Enables and disables the output current regulator.
Default
0
No.
Q3-01
Name
Output Current Limit Select
Setting Range
0, 1
Setting 0: Disabled
Setting 1: Enabled n Q3-02: Current Limit
Sets the value of the output current to which the drive will limit if the output current exceeds the value.
No.
Q3-02
Name
Current Limit
Setting Range
0.0 to 1000.0 A
Default
0.0 A n Q3-10: Ripple Regulator Selection
Enables and disables the Single Phase power DC bus ripple regulator. This function will lower the output frequency if the DC bus voltage ripple exceeds the value set in Q3-11.
No.
Q3-10
Name
Ripple Regulator Selection
Setting Range
0, 1
Default
1
5
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual 245
5.12 Q: PID Controller
Setting 0: Disabled
Setting 1: Enabled n Q3-11: Ripple Regulator Setpoint
Set as a percentage of the maximum amount of ripple allowed before an input phase loss fault is detected.
No.
Q3-11
Name
Ripple Regulator Setpoint
Setting Range
0.0 to 200.0% u
S6: Drive Protection
n S6-01: Emergency Override Speed
Sets the sped command used in emergency override mode when S6-02 = 0.
No.
S6-01
Name
Emergency Override Speed n S6-02: Emergency Override Reference Selection
Selects the emergency override speed source.
Setting Range
0.00 to 240.00 Hz
No.
S6-02
Name
Emergency Override Reference Selection
Setting Range
0, 1
Setting 0: Use S6-01 Reference
Setting 1: Use Frequency Reference u
T: Motor Tuning
Auto-Tuning automatically sets and tunes parameters required for optimal motor performance.
Refer to T: Motor Tuning on page 368
for details on Auto-Tuning parameters.
Default
95.0%
Default
0.00 Hz
Default
0
246 YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual