A.4 Drive Derating Data
A.4 Drive Derating Data
The drive can be operated at above the rated temperature, altitude, and default carrier frequency by derating the drive capacity.
u
Single-Phase Derating
iQpump Micro drives are compatible for use with both three-phase and single-phase input power supplies. The drive output to the motor is always three-phase, regardless of number of input phases.
Output capacity to the motor is derated when using single-phase input power and the drive firmware includes protection for single-phase input applications. This protection is enabled by default. Disabling this protection for single-phase input applications can void warranty and result in premature failure.
Selection of larger models always results in greater output capacity to the motor when supplying the drive with three-phase input power. However, the selection of larger models does not always yield greater output capacity when using the drive with single-phase input power.
Several factors affect the amount of derated drive output capacity when single-phase input power is supplied to the drive:
• Single-phase input voltage level
• Motor voltage rating
• Amount of input impedance.
The tables in this section assist in model selection by considering factors that affect the amount of derating in single-phase input power applications.
n Single-Phase Input Sizing
The rated output current listed in the tables allows for a 120% overload for 60 seconds. Contact Yaskawa if assistance is needed in selecting drive models with higher overload requirements. Adding more impedance than is specified will degrade performance.
Drive Model
2V0006
2V0010
2V0012
2V0020
2V0030
2V0040
2V0056
2V0069
Table A.9 240 V Single-Phase Input (-5% to +10%)
Without Input Reactor
Rated Input
Current (A)
Rated
Current (A)
Max
Motor (HP)
Yaskawa Reactor Part
Number
With Input Reactor
Rated Input
Current (A)
Rated
Current (A)
7.3
10.8
13.9
24.0
4.9
6.8
7.5
9.7
1.0
1.5
2.0
2.0
URX000303
URX000307
URX000311
URX000319
7.3
10.8
13.9
24.0
4.9
6.8
7.5
12.3
37.0
52.0
68.0
80.0
7.5
16.7
23.4
25.8
2.0
5.0
5.0
7.5
URX000326
URX000329
URX000335
URX000335
37.0
52.0
68.0
80.0
15.2
21.0
27.7
30.8
Max
Motor (HP)
1.0
1.5
2.0
3.0
3.0
5.0
7.5
10.0
Drive Model
4V0002
4V0004
4V0005
4V0007
4V0009
4V0011
4V0018
4V0023
4V0031
4V0038
9.4
14.0
20.0
24.0
2.1
4.3
5.9
8.1
38.0
44.0
Table A.10 480 V Single-Phase Input (-5% to +10%)
Without Input Reactor With Input Reactor
Rated Input
Current (A)
Output
Current (A)
1.3
2.4
3.5
3.5
5.1
5.5
4.5
5.5
7.9
11.3
Applicable
Motor (HP)
0.5
1.0
1.5
1.5
2.0
3.0
2.0
3.0
3.0
5.0
Yaskawa Reactor Part
Number
URX000292
URX000300
URX000304
URX000309
URX000308
URX000312
URX000316
URX000320
URX000327
URX000327
Rated Input
Current (A)
2.1
4.3
5.9
8.1
9.4
14.0
20.0
24.0
38.0
44.0
Output
Current (A)
1.7
2.8
3.9
5.4
5.5
7.5
8.7
10.5
13.5
16.1
Applicable
Motor (HP)
0.5
1.0
2.0
2.0
3.0
3.0
5.0
5.0
7.5
10.0
314 YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
u
Temperature Derating
As the ambient temperature for the drive is increased above the drive specification the drive should be derated. Additionally
.
n Output Current Derating Due to Ambient Temperature
Set L8-12 and L8-35 according to the installation conditions when the ambient temperature is above the drive specification
No.
L8-12
L8-35
Name
Ambient
Temperature Setting
Installation Method
Selection
Description
Adjust the drive overload (oL2) protection level when the drive is installed in an environment that exceeds its ambient temperature rating.
0: IP20/IP00 Drive
1: Side-by-Side Mounting
2: NEMA 1, UL Type 1 Drive
3: Finless Drive or External Heatsink Installation
Range
-10 to 50
0 to 3
Def.
40 °C
Dep. on o2-04
A.4 Drive Derating Data
This Page Intentionally Blank
316 YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Appendix: B
Parameter List
This appendix contains a full listing of all parameters and settings available in the drive.
B.8 H PARAMETERS: MULTI-FUNCTION TERMINALS..........................................335
B.10 N: ADVANCED PERFORMANCE SET-UP..........................................................352
B.11 O: OPERATOR RELATED PARAMETERS.........................................................353
B.13 Q: PID CONTROLLER PARAMETERS...............................................................366
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual 317
Downloaden
Advertentie