Puls PIC480.241C is a compact and reliable power supply unit designed for industrial applications. With a 24V output and 20A current, it can deliver up to 480W of continuous power. It features active PFC, high efficiency of 95.7%, and a wide input voltage range of AC 200-240V. The unit is protected against short circuit, overload, and overvoltage, and comes with a 3-year warranty. Ideal for use in process control, automation, and other critical applications where preventive function monitoring is crucial.
advertisement
![AC-Input. Puls PIC480.241C-C1, PIC480.241C | Manualzz AC-Input. Puls PIC480.241C-C1, PIC480.241C | Manualzz](http://s3.manualzz.com/store/data/064994568_1-2fd873415b91ae3f554dbcf06cda69b6-360x466.png)
PIC480.241C, PIC480.241C-C1
24V, 20A, 480W, S
INGLE
P
HASE
I
NPUT PIANO-Series
3.
AC-I
NPUT
AC input
AC input range nom.
Allowed voltage L or N to earth max.
Input frequency
Turn-on voltage
Shut-down voltage
External input protection nom. typ. typ.
AC 200-240V
180-264Vac
264-300Vac
300Vac
50–60Hz
150Vac
130Vac suitable for TN-, TT- and IT mains networks continuous operation
< 500ms continuous, IEC 62103
±6%
steady-state value, see Fig. 3-1 steady-state value, see Fig. 3-1
See recommendations in chapter 23.3.
Input current
Power factor
Crest factor **)
Rise time
*)
Start-up delay typ. typ. typ. typ. typ. typ.
2.2A
0.99
1.6
400ms
60ms
240ms
at 24V, 20A, 230Vac, see Fig. 3-3 at 24V, 20A, 230Vac, see Fig. 3-4
at 24V, 20A, 230Vac
at 24V, 20A const. current load, 0mF load capacitance,
at 24V, 20A const. current load, 20mF load capacitance,
Turn-on overshoot max. 200mV
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage range, typ. Fig. 3-2 Turn-on behavior, definitions
P
OUT
Rated input range max.
500ms
Input
Voltage
180V
V
IN
264V 300Vac
2.0
1.5
1.0
0.5
0
Fig. 3-3 Input current vs. output load at 24V
Input Current, typ.
3A
2.5
Output Current
0 2 4 6 8 10 12 14 16 18 20A
Output
Voltage
- 5%
Start-up delay
Rise
Time
Fig. 3-4 Power factor vs. output load
Power Factor, typ.
1.00
0.98
0.96
0.94
0.92
0.90
0.88
2 4 6 8 10
Output Current
12 14 16 18 20A
Mar. 2021 / Rev. 1.2 DS-PIC480.241C-EN
All parameters are typical values specified at 24V, 20A output, 230Vac input , 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany
4/19
advertisement
Related manuals
advertisement
Table of contents
- 3 Intended Use
- 3 Installation Instructions
- 4 AC-Input
- 5 DC-Input
- 5 Input Inrush Current
- 6 Output
- 7 Hold-up Time
- 7 DC-OK Relay Contact
- 8 Efficiency and Power Losses
- 8 Lifetime Expectancy and MTBF
- 9 Functional Diagram
- 9 Terminals and Wiring
- 10 Front Side and User Elements
- 12 Environment
- 13 Safety and Protection Features
- 14 Dielectric Strength
- 15 Approvals and Fulfilled Standards
- 15 Regulatory Compliance
- 16 Physical Dimensions and Weight
- 17 Accessory
- 17 YR40.242 Redundancy Module
- 17 PIRD20.241 Redundancy Module
- 18 Application Notes
- 18 Back-feeding Loads
- 18 External Input Protection
- 18 Parallel Use to Increase Output Power
- 18 Parallel Use for 1+1 Redundancy
- 19 Series Operation
- 19 Inductive and Capacitive Loads
- 19 Charging of Batteries
- 19 Operation on Two Phases
- 19 Use in a Tightly Sealed Enclosure