Hold-up Time. Puls PIC480.241C-C1, PIC480.241C
Add to My manuals19 Pages
Puls PIC480.241C is a compact and reliable power supply unit designed for industrial applications. With a 24V output and 20A current, it can deliver up to 480W of continuous power. It features active PFC, high efficiency of 95.7%, and a wide input voltage range of AC 200-240V. The unit is protected against short circuit, overload, and overvoltage, and comes with a 3-year warranty. Ideal for use in process control, automation, and other critical applications where preventive function monitoring is crucial.
advertisement
![Hold-up Time. Puls PIC480.241C-C1, PIC480.241C | Manualzz Hold-up Time. Puls PIC480.241C-C1, PIC480.241C | Manualzz](http://s3.manualzz.com/store/data/064994568_1-2fd873415b91ae3f554dbcf06cda69b6-360x466.png)
PIC480.241C, PIC480.241C-C1
24V, 20A, 480W, S
INGLE
P
HASE
I
NPUT PIANO-Series
7.
H
OLD
-
UP
T
IME
Hold-up Time typ. min. typ. min.
Fig. 7-1 Hold-up time vs. input voltage
65ms
55ms
30ms
23ms
Fig. 7-2 Shut-down behavior, definitions
Hold-up Time
80ms
70
60
50
40
30
20
10
0
102 120 a) 24V 10A typ.
b) 24V 10A min.
c) 24V 20A typ.
d) 24V 20A min.
Input Voltage a b c d
Input
Voltage
Output
Voltage
Zero Transition
Hold-up Time
- 5%
Threshold voltage
Contact closes
Contact opens
Contact ratings
Isolation voltage
155 190 230Vac
8.
DC-OK R
ELAY
C
ONTACT
This feature monitors the output voltage, which is produced by the power supply itself. It is independent of a back-fed voltage from a unit connected in parallel to the power supply output (e.g. redundant application). typ. 21.4V (fixed)
As soon as the output voltage reaches 21.4V.
As soon as the output voltage falls below 21.4V. max. 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A resistive load min. 1mA at 5Vdc
See dielectric strength table in section 18.
min. permissible load
Fig. 8-1 DC-ok relay contact behavior
Output Voltage
21.4V
open closed
Mar. 2021 / Rev. 1.2 DS-PIC480.241C-EN
All parameters are typical values specified at 24V, 20A output, 230Vac input , 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany
7/19
advertisement
Related manuals
advertisement
Table of contents
- 3 Intended Use
- 3 Installation Instructions
- 4 AC-Input
- 5 DC-Input
- 5 Input Inrush Current
- 6 Output
- 7 Hold-up Time
- 7 DC-OK Relay Contact
- 8 Efficiency and Power Losses
- 8 Lifetime Expectancy and MTBF
- 9 Functional Diagram
- 9 Terminals and Wiring
- 10 Front Side and User Elements
- 12 Environment
- 13 Safety and Protection Features
- 14 Dielectric Strength
- 15 Approvals and Fulfilled Standards
- 15 Regulatory Compliance
- 16 Physical Dimensions and Weight
- 17 Accessory
- 17 YR40.242 Redundancy Module
- 17 PIRD20.241 Redundancy Module
- 18 Application Notes
- 18 Back-feeding Loads
- 18 External Input Protection
- 18 Parallel Use to Increase Output Power
- 18 Parallel Use for 1+1 Redundancy
- 19 Series Operation
- 19 Inductive and Capacitive Loads
- 19 Charging of Batteries
- 19 Operation on Two Phases
- 19 Use in a Tightly Sealed Enclosure