Output. Puls PIC480.241C-C1, PIC480.241C
Add to My manuals19 Pages
Puls PIC480.241C is a compact and reliable power supply unit designed for industrial applications. With a 24V output and 20A current, it can deliver up to 480W of continuous power. It features active PFC, high efficiency of 95.7%, and a wide input voltage range of AC 200-240V. The unit is protected against short circuit, overload, and overvoltage, and comes with a 3-year warranty. Ideal for use in process control, automation, and other critical applications where preventive function monitoring is crucial.
advertisement
PIC480.241C, PIC480.241C-C1
24V, 20A, 480W, S
INGLE
P
HASE
I
NPUT PIANO-Series
6.
O
UTPUT
Output voltage
Adjustment range
Factory settings
Line regulation
Load regulation
Ripple and noise voltage
Output current
Output power
Overload behaviour
Short-circuit current nom. DC 24V
24-28V max. 30V ***) typ. 24.1V max. 50mV max. 150mV max. 100mVpp guaranteed at clockwise end position of potentiometer
±0.2%, at full load, cold unit
187-264Vac static value, 0A
20Hz to 20MHz, 50Ohm nom. 20A nom. 15A nom. 17.1A nom. 12.8A nom. 480W nom. 360W
ambient temperature <55°C ambient temperature <70°C
Hiccup PLUS mode **)
output voltage < 13.5Vdc, see Fig. 6-1
min. 21A *) max. 25A *) typ. cont. current
8.1A
average (R.M.S.) current, load impedance 50mOhm,
Output capacitance typ. 4 300µF included inside the power supply
*) Discharge current of output capacitors is not included.
**) Hiccup PLUS Mode
At heavy overloads (when output voltage falls below 13.5V), the power supply delivers continuous output current for 5s. After this, the output is switched off for approx. 8s before a new start attempts with duration of 1s are automatically performed. This cycle is repeated as long as the overload exists. If the overload has been cleared, the device will operate normally.
***) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not guaranteed value which can be achieved. The typical value is about 28.5V.
Fig. 6-1
Output voltage vs. output current, typ.
Fig. 6-2
Short-circuit (50mOhm) on output, Hiccup PLUS mode, typ.
Output Voltage
28V
24
20
16
12
8
4
0
0 5
Output Current
10 15 20
Adjustment
Range
25
Continuous current
Hiccup PLUS mode
30A
Output
Current
Normal operation
23A
0
5s
First pulse: 5s
8s
Short -circuit
1s 8s 1s 8s
Normal operation t
Mar. 2021 / Rev. 1.2 DS-PIC480.241C-EN
All parameters are typical values specified at 24V, 20A output, 230Vac input , 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany
6/19
advertisement
Related manuals
advertisement
Table of contents
- 3 Intended Use
- 3 Installation Instructions
- 4 AC-Input
- 5 DC-Input
- 5 Input Inrush Current
- 6 Output
- 7 Hold-up Time
- 7 DC-OK Relay Contact
- 8 Efficiency and Power Losses
- 8 Lifetime Expectancy and MTBF
- 9 Functional Diagram
- 9 Terminals and Wiring
- 10 Front Side and User Elements
- 12 Environment
- 13 Safety and Protection Features
- 14 Dielectric Strength
- 15 Approvals and Fulfilled Standards
- 15 Regulatory Compliance
- 16 Physical Dimensions and Weight
- 17 Accessory
- 17 YR40.242 Redundancy Module
- 17 PIRD20.241 Redundancy Module
- 18 Application Notes
- 18 Back-feeding Loads
- 18 External Input Protection
- 18 Parallel Use to Increase Output Power
- 18 Parallel Use for 1+1 Redundancy
- 19 Series Operation
- 19 Inductive and Capacitive Loads
- 19 Charging of Batteries
- 19 Operation on Two Phases
- 19 Use in a Tightly Sealed Enclosure