Safety and Protection Features. Puls PIC480.241C-C1, PIC480.241C
Add to My manuals19 Pages
Puls PIC480.241C is a compact and reliable power supply unit designed for industrial applications. With a 24V output and 20A current, it can deliver up to 480W of continuous power. It features active PFC, high efficiency of 95.7%, and a wide input voltage range of AC 200-240V. The unit is protected against short circuit, overload, and overvoltage, and comes with a 3-year warranty. Ideal for use in process control, automation, and other critical applications where preventive function monitoring is crucial.
advertisement
![Safety and Protection Features. Puls PIC480.241C-C1, PIC480.241C | Manualzz Safety and Protection Features. Puls PIC480.241C-C1, PIC480.241C | Manualzz](http://s3.manualzz.com/store/data/064994568_1-2fd873415b91ae3f554dbcf06cda69b6-360x466.png)
PIC480.241C, PIC480.241C-C1
24V, 20A, 480W, S
INGLE
P
HASE
I
NPUT PIANO-Series
16.
S
AFETY AND
P
ROTECTION
F
EATURES
Isolation resistance Min.
Min.
Min.
Min.
500MOhm
500MOhm
500MOhm
500MOhm
At delivered condition between input and output, measured with 500Vdc
At delivered condition between input and PE, measured with 500Vdc
At delivered condition between output and PE, measured with 500Vdc
At delivered condition between output and DC-OK contacts, measured with 500Vdc
Output over-voltage protection Typ. 30.5Vdc
Max. 32.0Vdc
In case of an internal defect, a redundant circuit limits the maximum output voltage. The output shuts down and automatically attempts to restart.
Class of protection I
Ingress protection
Over-temperature protection
IP 20
Included
According to IEC 61140
A PE (Protective Earth) connection is required
According to EN/IEC 60529
Output shut-down with automatic restart.
Temperature sensors are installed on critical components inside the unit and turn the unit off in safety critical situations, which can happen e.g. when ambient temperature is too high, ventilation is obstructed or the de-rating requirements are not followed. There is no correlation between the operating temperature and turn-off temperature since this is dependent on input voltage, load and installation methods.
Input transient protection
Internal input fuse
Touch current (leakage current) Typ.
MOV (Metal Oxide
Varistor)
Included
0.33mA / 0.69mA
Max. 0.43mA / 0.89mA
For protection values see chapter Fehler!
Verweisquelle konnte nicht gefunden werden.
(EMC).
Not user replaceable slow-blow high-braking capacity fuse
At 230Vac, 50Hz, TN-,TT-mains / IT-mains
At 264Vac, 50Hz, TN-,TT-mains / IT-mains
Mar. 2021 / Rev. 1.2 DS-PIC480.241C-EN
All parameters are typical values specified at 24V, 20A output, 230Vac input , 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany
13/19
advertisement
Related manuals
advertisement
Table of contents
- 3 Intended Use
- 3 Installation Instructions
- 4 AC-Input
- 5 DC-Input
- 5 Input Inrush Current
- 6 Output
- 7 Hold-up Time
- 7 DC-OK Relay Contact
- 8 Efficiency and Power Losses
- 8 Lifetime Expectancy and MTBF
- 9 Functional Diagram
- 9 Terminals and Wiring
- 10 Front Side and User Elements
- 12 Environment
- 13 Safety and Protection Features
- 14 Dielectric Strength
- 15 Approvals and Fulfilled Standards
- 15 Regulatory Compliance
- 16 Physical Dimensions and Weight
- 17 Accessory
- 17 YR40.242 Redundancy Module
- 17 PIRD20.241 Redundancy Module
- 18 Application Notes
- 18 Back-feeding Loads
- 18 External Input Protection
- 18 Parallel Use to Increase Output Power
- 18 Parallel Use for 1+1 Redundancy
- 19 Series Operation
- 19 Inductive and Capacitive Loads
- 19 Charging of Batteries
- 19 Operation on Two Phases
- 19 Use in a Tightly Sealed Enclosure