Dielectric Strength. Puls PIC480.241C-C1, PIC480.241C
Add to My manuals19 Pages
Puls PIC480.241C is a compact and reliable power supply unit designed for industrial applications. With a 24V output and 20A current, it can deliver up to 480W of continuous power. It features active PFC, high efficiency of 95.7%, and a wide input voltage range of AC 200-240V. The unit is protected against short circuit, overload, and overvoltage, and comes with a 3-year warranty. Ideal for use in process control, automation, and other critical applications where preventive function monitoring is crucial.
advertisement
![Dielectric Strength. Puls PIC480.241C-C1, PIC480.241C | Manualzz Dielectric Strength. Puls PIC480.241C-C1, PIC480.241C | Manualzz](http://s3.manualzz.com/store/data/064994568_1-2fd873415b91ae3f554dbcf06cda69b6-360x466.png)
PIC480.241C, PIC480.241C-C1
24V, 20A, 480W, S
INGLE
P
HASE
I
NPUT PIANO-Series
17.
D
IELECTRIC
S
TRENGTH
The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by the manufacturer. Field tests may be conducted in the field using the appropriate test equipment, which applies the voltage with a slow ramp (2s up and 2s down). Connect all input-terminals together as well as all output poles before conducting the test. When testing, set the cut-off current settings to the value in the table below.
Fig. 17-1 Dielectric strength
Type test
A B C D
60s 2500Vac 3000Vac 500Vac 500Vac
Input
L
N
B *)
DC-ok Factory test
Field test
5s
5s
2500Vac 2500Vac
2000Vac 2000Vac
500Vac
500Vac
500Vac
500Vac
+
-
Cut-off current setting 10mA 10mA 10mA 1mA
A
Earth, PE
C
B
D
Output
To fulfil the PELV requirements according to EN60204-1 § 6.4.1, we recommend that either the + pole, the – pole or any other part of the output circuit shall be connected to the protective earth system. This helps to avoid situations in which a load starts unexpectedly or can not be switched off when unnoticed earth faults occur.
B*) When testing input to DC-OK ensure that the max. voltage between DC-OK and the output is not exceeded (column D). We recommend connecting DC-OK pins and the output pins together when performing the test.
Mar. 2021 / Rev. 1.2 DS-PIC480.241C-EN
All parameters are typical values specified at 24V, 20A output, 230Vac input , 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany
14/19
advertisement
Related manuals
advertisement
Table of contents
- 3 Intended Use
- 3 Installation Instructions
- 4 AC-Input
- 5 DC-Input
- 5 Input Inrush Current
- 6 Output
- 7 Hold-up Time
- 7 DC-OK Relay Contact
- 8 Efficiency and Power Losses
- 8 Lifetime Expectancy and MTBF
- 9 Functional Diagram
- 9 Terminals and Wiring
- 10 Front Side and User Elements
- 12 Environment
- 13 Safety and Protection Features
- 14 Dielectric Strength
- 15 Approvals and Fulfilled Standards
- 15 Regulatory Compliance
- 16 Physical Dimensions and Weight
- 17 Accessory
- 17 YR40.242 Redundancy Module
- 17 PIRD20.241 Redundancy Module
- 18 Application Notes
- 18 Back-feeding Loads
- 18 External Input Protection
- 18 Parallel Use to Increase Output Power
- 18 Parallel Use for 1+1 Redundancy
- 19 Series Operation
- 19 Inductive and Capacitive Loads
- 19 Charging of Batteries
- 19 Operation on Two Phases
- 19 Use in a Tightly Sealed Enclosure