Dielectric Strength. Puls PIC480.241C-C1, PIC480.241C

Add to My manuals
19 Pages

advertisement

Dielectric Strength. Puls PIC480.241C-C1, PIC480.241C | Manualzz

PIC480.241C, PIC480.241C-C1

24V, 20A, 480W, S

INGLE

P

HASE

I

NPUT PIANO-Series

17.

D

IELECTRIC

S

TRENGTH

The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by the manufacturer. Field tests may be conducted in the field using the appropriate test equipment, which applies the voltage with a slow ramp (2s up and 2s down). Connect all input-terminals together as well as all output poles before conducting the test. When testing, set the cut-off current settings to the value in the table below.

Fig. 17-1 Dielectric strength

Type test

A B C D

60s 2500Vac 3000Vac 500Vac 500Vac

Input

L

N

B *)

DC-ok Factory test

Field test

5s

5s

2500Vac 2500Vac

2000Vac 2000Vac

500Vac

500Vac

500Vac

500Vac

+

-

Cut-off current setting 10mA 10mA 10mA 1mA

A

Earth, PE

C

B

D

Output

To fulfil the PELV requirements according to EN60204-1 § 6.4.1, we recommend that either the + pole, the – pole or any other part of the output circuit shall be connected to the protective earth system. This helps to avoid situations in which a load starts unexpectedly or can not be switched off when unnoticed earth faults occur.

B*) When testing input to DC-OK ensure that the max. voltage between DC-OK and the output is not exceeded (column D). We recommend connecting DC-OK pins and the output pins together when performing the test.

Mar. 2021 / Rev. 1.2 DS-PIC480.241C-EN

All parameters are typical values specified at 24V, 20A output, 230Vac input , 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany