City Tie (Optional City Tie Board P/N CT-1K). Faraday MPC-7000, MPC-6000, RND-2

Add to My manuals
76 Pages

advertisement

City Tie (Optional City Tie Board P/N CT-1K). Faraday MPC-7000, MPC-6000, RND-2 | Manualzz

MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL

City Tie (Optional City Tie Board P/N CT-1K)

CA Reverse Polarity: Selectable for Alarm with Trouble or Alarm only operation

• Supervised by receiver for short or open circuit

• Supervised by control unit for grounded circuit

• Voltage: 24 VDC nominal

• Current: 0.020A maximum (normal or trouble)

• Current: 0.025A maximum (shorted)

• Ripple: 1.5 VAC maximum

CT Reverse Polarity: Programmable for Trouble or Supervisory or both

• Supervised by receiver for short or open circuit

• Supervised by control unit for grounded circuit

• Voltage: 24 VDC nominal

• Current: 0.020A maximum (normal or alarm)

• Current: 0.025A maximum (shorted)

• Ripple: 1.5 VAC maximum

LE Local Energy

• Not power limited

• Supervised for open or grounded circuit by control unit

• Voltage: 24 VDC nominal

• Standby Current: 0.007A maximum

• Alarm Current: 0.400A maximum

• Ripple: 1.5 VAC maximum

• Maximum wire loop resistance: 30 ohms

• Trip coil impedance: 14.5 ohms

DACT Circuit (Optional DACT Board MPC-DACT) limited

• Supervised for short or open circuit

• Maximum Voltage: 60 VDC

• Maximum Current (shorted): 0.100A

Additional Transformer (Optional Transformer Assembly NPE-1)

• Provides an additional 3.0A of NAC power (max 1 per panel)

18