BATTERY SIZE CALCULATIONS

MPC-6000 Current Calculations

Panel and Module Current

MPC-6000 Control Unit (includes one loop driver board)

CT-1K City Tie Standby

Alarm (Table 1)

MPC-DACT DACT

Board

Standby

Alarm

Total Panel currents

Place these totals in the Total System Current Table

Go to Auxiliary Module Current calculations

RND-2 Current Calculations

Panel and Module Current

RND-2 Control Unit (no loop driver board)

CT-1K City Tie Standby

MPC-DACT DACT

Board

Alarm (Table 1)

Standby

Total Panel currents

Alarm

Place these totals in the Total System Current Table

Go to Auxiliary Module Current calculations

MPC-7000 Current Calculation

Panel and Module Current

Standby Current (A) Alarm Current (A)

0.190 0.190

0.005

+

NA

0.038

+

+

+

NA

0.054

NA +

Standby Current (A) Alarm Current (A)

0.090 0.090

0.005

+

NA

0.038

+

0.054

NA

+

+

NA

+

MPC-7000 Control Unit (includes two loop driver boards)

CT-1K City Tie Standby

Alarm (Table 1)

FDLC Loop Standby 0.100 X

Driver (on LEM-1) Alarm 0.100 X

HBC-1 Standby

1

0

Loop Expander Bd. Alarm 0

NEM-1 Standby 0.015

NAC Expander Bd. Alarm 0.250

MPC-DACT DACT Standby 0.038

0.005

Standby Current (A) Alarm Current (A)

+

NA

N/A

N/A

N/A

+

Board Alarm 0.054 NA

Total Panel currents

1

Does not include charging current of 1.9A for a fully discharged battery.

0.450

+

+

N/A

0 N/A

0.015 N/A

NA

+

0.500

0

0.250

Place totals in the Total System Current table

Go to Auxiliary Module Current calculations

53

MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL

TABLE 1

When using the CT-1K City Tie Board add the following currents for standby and alarm for features being used:

Type of City Tie Connection

1. Local Energy

Standby

+ 0.007

Reverse Polarity Alarm Output (CA)

2. Alarm

3. Alarm w/Trouble

+ 0

0

4. Reverse Polarity Trouble Output (CT) + 0

Alarm

+ 0.020

+ 0.020

+ 0.020

+ 0.020

54