MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL

QUICK TEST

If the control unit has remote connections to the Fire Department or other monitor, be sure to disable the remote signals and notify the remote monitoring station before performing test operations, since an off-normal condition will be indicated.

The Quick Test mode makes it fast and easy to test a system by eliminating the need to reset the panel after each device is activated. Quick test may be done on a loop basis (if there are multiple loops), so that the remainder of the system may continue to operate normally. Once the loop is placed into quick test, the NACs will sound for a short configurable period as each device on the loop is activated. In this way a single person is able to quickly check that each device is working and activating the system.

The printer may also be enabled or disabled during “Quick Test” as desired.

Refer to the programming manual for the details of accessing the Quick test functions.

For any required service, contact a factory-authorized representative.