Beijer Electronics X2 control is a powerful and versatile HMI (Human Machine Interface) and control system that combines the intuitive graphic iX interface with the flexibility of CODESYS control. With X2 control, you can easily create and manage HMI applications, communicate with external devices like remote I/O, and monitor and control your processes effectively.
advertisement
X2 control – Basic Start Up settings
SUEN284 2017-04
11 Important settings
Boot after Online Change and Restart of X2 control unit
This is highly recommended!
Boot application can be regarded as the compiled, executable code. Default setting when creating a new project is that, when performing an Online Change, the boot application is not overwritten automaticly but instead saved in temporary memory which will result in that the project will “return” to previous program (=before changes) on application restart.
Following should be default setting and to make sure that the online changes is always
“saved”:
Highlight the “Application” in the “Device” and right click
Select “Properties” / “Boot application”
Select “Create implicit boot application on Online Change” www.beijerelectronics.se
13 (19)
advertisement
Related manuals
advertisement
Table of contents
- 1 Introduction
- 1 Precautions
- 2 Table of Contents
- 3 Software and documention
- 4 First step
- 4 Files in “Basic Settings
- 5 System configuration Remote I/O
- 6 Setup in the Programming tools
- 7 Setup in CODESYS
- 9 Setup in iX Developer
- 10 Communication - iX Developer and CODESYS with Remote I/O
- 11 Retain and Persistent variables
- 13 Important settings
- 13 Boot after Online Change and Restart of X2 control unit
- 14 Project backup
- 14 CODESYS, create backup files
- 14 CODESYS, Project Archive
- 15 CODESYS, source Download to X2 control
- 16 CODESYS, transfer project to X2 control via USB or SD card memory
- 17 Diagnostics, CODESYS
- 17 SoftControl Direct Acsess driver
- 18 Monitor the CODESYS CPU load
- 19 Document revision