Characteristics setting for the WM type. Mitsubishi Electric AE2000-SWA, AE4000-SW, Low-Voltage Air Circuit Breakers series Type AE-SW, AE3200-SW, AE630-SW
Add to My manuals43 Pages
advertisement
![Characteristics setting for the WM type. Mitsubishi Electric AE2000-SWA, AE4000-SW, Low-Voltage Air Circuit Breakers series Type AE-SW, AE3200-SW, AE630-SW | Manualzz Characteristics setting for the WM type. Mitsubishi Electric AE2000-SWA, AE4000-SW, Low-Voltage Air Circuit Breakers series Type AE-SW, AE3200-SW, AE630-SW | Manualzz](http://s1.manualzz.com/store/data/069768442_1-dfcb447f2a4c1f8f93ad1ea64decc196-360x466.png)
Characteristics setting for the WM type
⑦ Pre-alarm current: Ip
② LTD pick-up
current: I
L
③ LTD time: T
L
⑧ Pre-alarm
time: Tp
④ STD pick-up
current: Isd
⑤ STD time: Tsd
1
2
6
3
5
4
With MCR
7 I 2 t ON
(ramp)
I 2 t OFF
⑥ INST/MCR pick-up
current: Ii
Max. breaking time
(In case of AE4000-SW~
6300-SW, it is 0.05s)
Note) The figure shows a model with an optional G1 setting module, a display, and an MCR switch.
Current (%)
Table 24
No.
①
②
③
④
Setting item
Rated current
LTD pick-up current
LTD time
STD pick-up current
Symbol
Ir
I
L
T
L
Isd
⑤
⑥
⑦
⑧
STD time
INST/MCR pick-up current
Pre-alarm current
Pre-alarm time
Tsd
Ii
Ip
Tp
Characteristic setting range Accuracy Factory default value
Set to the specified value at the factory Note 1)
1.0-1.05-1.1-1.15-1.2 x Ir
15-20-25-30-40-60s at I
L
x 1.2
1.5-2-2.5-3-3.5-4-4.5-5 x Ir
—
±5%
±20%
0.5-0.4-0.3-0.2-0.1-0.06-0.06-0.1-0.2-0.3-0.4-0.5s
(I 2 t ON) (I 2 t OFF) at Isd x 1.5
AE630-SW ~ AE1600-SW
AE2000-SW ~ AE3200-SW
AE4000-SW
16-12-10-8-6-4-2-2-4-6-8-10-12-16
(INST) (MCR)
WM1
AE2000-SWA, AE4000-SWA
AE5000-SW
12-10-8-6-4-2-2-4-6-8-10-12 x Ir
(INST) (MCR)
WM2
AE6300-SW
10-8-6-4-2-2-4-6-8-10 x Ir
(INST) (MCR)
WM3
I
L
× 0.68 to 1.0 (0.04 step) -OVER
1/2 T
L
at IL × 1.2 (PAL contact output after passing 1/2 of T
L
)
±15%
±20% Note 2)
It operates in the range between 0.04
and 0.08s when the time set at 0.06s.
±15% Note 2)
±5%
±20%
To be complied with ordering indication
1.15
20
5
0.5 (I 2 t ON)
WM1…16 (INST)
WM2…12 (INST)
WM3…10 (INST)
OVER
—
Remark (1) For WM relay only, when Pre-alarm current Ip is set a “OVER” the Ip value becomes equal to “I
L x 1.0”.
Remark (2) The table shows data obtained on the breakers provided with MCR (optional).
Systematic diagram of setting dial coordination
In (CT rating) Ir (Fixed) I
L
Ip
E-24
Ig (P.28)
Isd
Ii
Ip2 (P.29)
Load current LED (40, 60, 80, 100%)
Note 1) CT rating 250 A and 315 A can be set in 0.1 A steps, and
500 A or higher can be set in 1 A steps.
Note 2) When used without voltage applied to the control power supply (ETR power supply module) Tsd, Ii operation time may increase max. 20ms.
advertisement
Related manuals
advertisement
Table of contents
- 3 Table of contents
- 4 External view
- 5 Internal structure/Outline dimensions and product weight
- 6 Unpacking/Storage
- 7 Transportation
- 8 Installation
- 9 Installation of the drawout handle/Installation of the inter-phase barrier (BA)
- 10 Connection
- 12 Insert operation
- 14 Drawout operation
- 16 Charging operation
- 17 Open/close operation
- 19 Door interlock (DI)/Cylinder lock (CYL) and Castell lock (CAL)/OCR alarm (AL) [MRE: manual reset type]
- 20 Shutter lock (SST-LOCK)/Safety shutter nameplate
- 21 Functions of electronic trip relay (ETR) parts
- 23 Characteristics setting for the WS type
- 24 Characteristics setting for the WM type
- 25 Characteristics setting for the WB type
- 26 Characteristics setting for the WF type
- 28 Characteristics setting for the optional setting modules
- 30 Setting procedure for the electronic trip characteristics
- 32 Wiring diagram
- 34 Technical notes
- 35 Warranty
- 36 Inspection and maintenance
- 42 SERVICE NETWORK