Characteristics setting for the WF type. Mitsubishi Electric AE2000-SWA, AE4000-SW, Low-Voltage Air Circuit Breakers series Type AE-SW, AE3200-SW, AE630-SW

Add to My manuals
43 Pages

advertisement

Characteristics setting for the WF type. Mitsubishi Electric AE2000-SWA, AE4000-SW, Low-Voltage Air Circuit Breakers series Type AE-SW, AE3200-SW, AE630-SW | Manualzz

Characteristics setting for the WF type

The selectable characteristics are the following five curves.

4

5

6

2

1

3

12

8

9

10

11

(I 4 -1)t = const.

(I 3 -1)t = const.

(I 2 -1)t = const.

(I -1)t = const.

(I 0.02 -1)t = const.

16

13

15

I (current)

LTD characteristics curves

14

LTD curve can be selected by the LTD curve setting dial.

Trip indicator LED

Pre-alarm LED

Temperature alarm LED

Load current LED

RUN LED

ERR. LED

Current setting dial

LTD time setting dial

LTD curve setting dial

STD pick-up setting dial

STD time setting dial

INST/MCR pick-up current setting dial

Optional setting module

Pre-alarm current setting dial

RESET button (TEST L/S LOCK button)

TEST terminal

Note) The figure shows WF1 type with G1 module, Display (DP1) and MCR switch.

G1, DP1 and MCR are optional equipments.

[LTD curve setting "a=2"] a=2

10000

5000

4000

3000

2000

1000

1

.5

.4

.3

.2

Pre-alarm current : Ip

Ir x 0.68~1.0(0.04step)-OVER ± 5%

Current setting : Ir

0.5~1.0(0.05step) x In(CT rating)

LTD pick-up

1.10 x Ir ... Non pick-up

1.20 x Ir ... Pick-up

500

400

300

200

100

60

50

40

30

20

5

4

3

2

10

LTD operating time t

LTD

Note1 t

LTD

(4/1.1155) a

(I/1.1155Ir)

-1 a

-1

L

Accuracy : a = 2

I = load current (A)

Ir= 0.5~1.0 x In (A)

T L = 1~18 (s)

± 30%(1.5Ir load current<4Ir)

± 20%(4Ir load current)

PAL operating time t

PAL

Note2 t PAL

(I/0.97lp) a -1 a -1

L a = 2

I = load current (A)

Ip= 0.68~1.15 x Ir (A)

T

L

= 1~18 (s)

Accuracy :

± 30%(1.5Ir load current<4Ir)

± 20%(4Ir load current)

STD time : Tsd Note3

0.06-0.1-0.2-0.3-0.4-0.5(s) ± 20%

(at Isd x 1.5)

STD pick-up current : Isd

Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%

Pre-alarm time : Tp

T

L

/2 ± 20% (at Ir x 4)

LTD time : T

L

1-2-3-4-5-6-8-10-12-15-18(s) ± 20%

(at Ir x 4)

With MCR

.1

.05

.04

.03

.02

.01

1

Note1 : LTD operating time is 0.8s(FLAT)when the operating

time becomes 0.8s or less.

Note2 : PAL operating time is 0.5s(FLAT) when the operating

time becomes 0.5s or less.

Note3 : When Tsd ="0.06" setting,operating time is 0.04~0.08s.

I 2 t is selectable ON or OFF.

2 5 10 20 50

I 2

(ramp)

I 2 t OFF

INST/MCR pick-up current : Ii

Ir x 2-4-6-8-10-12-16 ±

Ir x 2-4-6-8-10-12

Ir x 2-4-6-8-10

15% : WF1

± 15% : WF2

± 15% : WF3

100 150

125 200

500

Max. breaking time

(In case of AE4000-SW~

6300-SW, it is 0.05s)

1000 2000

1600

Current (%)

5000 10000

Table 26

No.

Setting item

⑦ Current setting

LTD time

LTD curve setting

STD pick-up current

Symbol

Ir

T

L a

Isd

Characteristic setting range

0.5 ~ 1.0 (0.05step) x In (CT rating)

LTD pick-up current : 1.15 x Ir

1–2–3–4–5–6–8–10–12–15–18s

0.02–1–2–3–4

1.5–2–2.5–3–4–5–6–7–8–9–10 x Ir at Ir x 4

Accuracy

1.10 x Ir…Non Pick-up

1.20 x Ir…Pick-up

± 30% (1.5Ir

≦ load current<4Ir)

± 20% (4Ir ≦ load current)

± 15%

± 20%

It operates in the range between 0.04 and 0.08 when the time set at 0.06s.

Factory default value

1.0

18

2

10

0.5 (I 2 t ON) ⑪ STD time

INST/MCR pick-up current

Pre-alarm current

Pre-alarm time

Tsd

Ii

Ip

Tp

0.5–0.4–0.3–0.2–0.1–0.06–0.06–0.1–0.2–0.3–0.4–0.5s

(I 2 t ON) (I 2 t OFF) at Isd x 1.5

AE630-SW~AE1600-SW

AE2000-SW~AE3200-SW

AE4000-SW

AE2000-SWA, AE4000-SWA

AE5000-SW

AE6300-SW

16-12-10-8-6-4-2-2-4-6-8-10-12-16

(INST) (MCR)

12-10-8-6-4-2-2-4-6-8-10-12

(INST) (MCR)

10-8-6-4-2-2-4-6-8-10 x Ir

(INST) (MCR)

Ir x 0.68 ~ 1.0 (0.04step) –OVER

x Ir

x Ir

WF1

WF2

WF3

1/2 T

L

at Ir x 4 (after 1/2 T

L

, PAL contact output turns on.)

Remark (1) The table and the figure include both optional display and MCR.

Remark (2) For WF relay, when Pre-alarm current Ip is set at "OVER", the Ip value is "Ir x 1.15".

Relation of setting dial

In (CT rating) Ir

Ig (P.28)

E-26

Isd

Ii

Ip

Ip2 (P.29)

Load current LED (60, 80, 100%, OVER)

± 15%

± 5%

± 30% (1.5Ir

≦ load current<4Ir)

± 20% (4Ir ≦ load current)

WF1…16 (INST)

WF2…12 (INST)

WF3…10 (INST)

OVER

100

60

50

40

30

20

10

.5

.4

.3

.2

.1

5

4

3

2

1

.05

.04

.03

.02

.01

1

[LTD curve setting "a=0.02"] a=0.02

10000

5000

4000

3000

2000

Pre-alarm current : Ip

Ir x 0.68~1.0(0.04step)-OVER ± 5%

Current setting : Ir

0.5~1.0(0.05step) x In(CT rating)

LTD pick-up

1.10 x Ir ... Non pick-up

1.20 x Ir ... Pick-up 1000

500

400

300

200

2

STD time : Tsd

0.06-0.1-0.2-0.3-0.4-0.5(s) ±

Note3

20%

(at Isd x 1.5)

STD pick-up current : Isd

Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%

5

Pre-alarm time : Tp

T

L

/2 ± 20%

Note2

(at Ir x 4)

LTD time : T

L

1-2-3-4-5-6-8-10-12-15-18(s) ±

Note1

20%

(at Ir x 4)

With MCR

10 20

I 2 t ON

(ramp)

I 2 t OFF

INST/MCR pick-up current : Ii

Ir x 2-4-6-8-10-12-16 ±

Ir x 2-4-6-8-10-12 ±

15% WF1

15% WF2

Ir x 2-4-6-8-10 ± 15% WF3

50 100 150

125 200

500

Max. breaking time

(In case of AE4000-SW~

6300-SW, it is 0.05s)

1000 2000

1600

5000

Current (%)

10000

[LTD curve setting "a=3"] a=3

10000

500

400

300

200

100

60

50

40

30

20

5000

4000

3000

2000

1000

Pre-alarm current : Ip

Ir x 0.68~1.0(0.04step)-OVER ± 5%

Current setting : Ir

0.5~1.0(0.05step) x In(CT rating)

LTD pick-up

1.10 x Ir ... Non pick-up

1.20 x Ir ... Pick-up

Pre-alarm time : Tp Note2

T L /2 ± 20% (at Ir x 4)

LTD time : T L Note1

1-2-3-4-5-6-8-10-12-15-18(s) ± 20%

(at Ir x 4)

10

5

4

3

2

STD time : Tsd Note3

0.06-0.1-0.2-0.3-0.4-0.5(s) ± 20%

(at Isd x 1.5)

STD pick-up current : Isd

Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%

With MCR

1

.5

.4

.3

.2

.1

.05

.04

.03

.02

.01

1 2 5 10 20

I 2 t ON

(ramp)

I 2 t OFF

INST/MCR pick-up current : Ii

Ir x 2-4-6-8-10-12-16 ±

Ir x 2-4-6-8-10-12

Ir x 2-4-6-8-10

15% : WF1

± 15% : WF2

± 15% : WF3

Max. breaking time

(In case of AE4000-SW~

6300-SW, it is 0.05s)

50 100 150

125 200

Current (%)

500 1000 2000

1600

5000 10000

Note 1: LTD operating time t

LTD

is calculated by the following equations.

a = LTD curve setting t LTD =

(4/1.1155) a -1

(I/1.1155Ir) a -1 x T L

I = load current (A)

Ir = 0.5~1.0 x In (A)

T

L

= 1~18 (s)

The accuracy of operating time is ± 30% (1.5Ir

≦ load current<4Ir) or ± 20% (4Ir ≦ load current).

LTD operating time is 0.8s(FLAT) when the operating time becomes 0.8s or less.

Note 3: When Tsd = "0.06" setting, operating time is 0.04~0.08s.

I 2 t is selectable : ON or OFF.

100

60

50

40

30

20

10

.5

.4

.3

.2

.1

5

4

3

2

1

.05

.04

.03

.02

.01

1

[LTD curve setting "a=1"] a=1

10000

5000

4000

3000

2000

Pre-alarm current : Ip

Ir x 0.68~1.0(0.04step)-OVER ± 5%

Current setting : Ir

0.5~1.0(0.05step) x In(CT rating)

LTD pick-up 1.10 x Ir ... Non pick-up

1.20 x Ir ... Pick-up 1000

500

400

300

200

2 5

STD time : Tsd Note3

0.06-0.1-0.2-0.3-0.4-0.5(s) ± 20%

(at Isd x 1.5)

STD pick-up current : Isd

Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%

10 20

Pre-alarm time : Tp

T L /2 ± 20%

Note2

(at Ir x 4)

LTD time : T L Note1

1-2-3-4-5-6-8-10-12-15-18(s) ± 20%

(at Ir x 4)

With MCR

I 2 t ON

(ramp)

I 2 t OFF

INST/MCR pick-up current : Ii

Ir x 2-4-6-8-10-12-16

Ir x 2-4-6-8-10-12

Ir x 2-4-6-8-10

±

±

±

15% WF1

15% WF2

15% WF3

500 50 100 150

125 200

Current (%)

Max. breaking time

(In case of AE4000-SW~

6300-SW, it is 0.05s)

1000 2000

1600

5000 10000

[LTD curve setting "a=4"] a=4

10000

100

60

50

40

30

20

10

5000

4000

3000

2000

1000

500

400

300

200

Pre-alarm current : Ip

Ir x 0.68~1.0(0.04step)-OVER ± 5%

Current setting : Ir

0.5~1.0(0.05step) x In(CT rating)

LTD pick-up

1.10 x Ir ... Non pick-up

1.20 x Ir ... Pick-up

Pre-alarm time : Tp

T L /2 ± 20%

Note2

(at Ir x 4)

LTD time : T

L

1-2-3-4-5-6-8-10-12-15-18(s) ±

Note1

20%

(at Ir x 4)

5

4

3

2

1

.5

.4

.3

.2

STD time : Tsd Note3

0.06-0.1-0.2-0.3-0.4-0.5(s) ± 20%

(at Isd x 1.5)

STD pick-up current : Isd

Ir x ± 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%

With MCR

.1

.05

.04

.03

.02

.01

1 2 5 10 20

I 2 t ON

(ramp)

I 2 t OFF

INST/MCR pick-up current : Ii

Ir x 2-4-6-8-10-12-16 ±

Ir x 2-4-6-8-10-12

Ir x 2-4-6-8-10

±

15% : WF1

15% : WF2

± 15% : WF3

500 50 100 150

125 200

Current (%)

Max. breaking time

(In case of AE4000-SW~

6300-SW, it is 0.05s)

1000 2000

1600

5000 10000

Note 2: PAL operating time t

PAL

is calculated by the following equations.

a = LTD curve setting t

PAL

=

(4Ir/0.97Ip) a -1

(I/0.97Ip) a -1 x

T

L

2

I = load current (A)

Ir = 0.5~1.0 x In (A)

Ip = 0.68~1.15 x Ir (A)

T

L

= 1~18 (s)

The accuracy of operating time is ± 30% (1.5Ir

≦ load current < 4Ir) or ± 20% (4Ir ≦ load current).

PAL operating time is 0.5s(FLAT) when the operating time becomes 0.5s or less.

4

5

6

2

1

3

16

The selectable characteristics are the following five curves.

12

8

9

10

11

(I 4 -1)t = const.

(I 3 -1)t = const.

(I 2 -1)t = const.

(I -1)t = const.

(I 0.02 -1)t = const.

13

15

I (current)

LTD characteristics curves

14

LTD curve can be selected by the LTD curve setting dial.

Trip indicator LED

Pre-alarm LED

Temperature alarm LED

Load current LED

RUN LED

ERR. LED

Current setting dial

LTD time setting dial

LTD curve setting dial

STD pick-up setting dial

STD time setting dial

INST/MCR pick-up current setting dial

Optional setting module

Pre-alarm current setting dial

RESET button (TEST L/S LOCK button)

TEST terminal

Note) The figure shows WF1 type with G1 module, Display (DP1) and MCR switch.

G1, DP1 and MCR are optional equipments.

[LTD curve setting "a=2"] a=2

10000

5000

4000

3000

2000

1000

1

.5

.4

.3

.2

Pre-alarm current : Ip

Ir x 0.68~1.0(0.04step)-OVER ± 5%

Current setting : Ir

0.5~1.0(0.05step) x In(CT rating)

LTD pick-up

1.10 x Ir ... Non pick-up

1.20 x Ir ... Pick-up

500

400

300

200

100

60

50

40

30

20

5

4

3

2

10

LTD operating time t

LTD

Note1 t

LTD

(4/1.1155) a

(I/1.1155Ir)

-1 a

-1

L

Accuracy : a = 2

I = load current (A)

Ir= 0.5~1.0 x In (A)

T L = 1~18 (s)

± 30%(1.5Ir load current<4Ir)

± 20%(4Ir load current)

PAL operating time t

PAL

Note2 t PAL

(I/0.97lp) a -1 a -1

L a = 2

I = load current (A)

Ip= 0.68~1.15 x Ir (A)

T

L

= 1~18 (s)

Accuracy :

± 30%(1.5Ir load current<4Ir)

± 20%(4Ir load current)

STD time : Tsd Note3

0.06-0.1-0.2-0.3-0.4-0.5(s) ± 20%

(at Isd x 1.5)

STD pick-up current : Isd

Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%

Pre-alarm time : Tp

T

L

/2 ± 20% (at Ir x 4)

LTD time : T

L

1-2-3-4-5-6-8-10-12-15-18(s) ± 20%

(at Ir x 4)

With MCR

.1

.05

.04

.03

.02

.01

1

Note1 : LTD operating time is 0.8s(FLAT)when the operating

time becomes 0.8s or less.

Note2 : PAL operating time is 0.5s(FLAT) when the operating

time becomes 0.5s or less.

Note3 : When Tsd ="0.06" setting,operating time is 0.04~0.08s.

I 2 t is selectable ON or OFF.

I 2

(ramp)

I 2 t OFF

INST/MCR pick-up current : Ii

Ir x 2-4-6-8-10-12-16 ±

Ir x 2-4-6-8-10-12

Ir x 2-4-6-8-10

15% : WF1

± 15% : WF2

± 15% : WF3

2 5 10 20 50 100 150

125 200

500

Max. breaking time

(In case of AE4000-SW~

6300-SW, it is 0.05s)

1000 2000

1600

Current (%)

5000 10000

No.

Setting item

Current setting

LTD time

LTD curve setting

STD pick-up current

Symbol

Ir

T a

L

Isd

Characteristic setting range

0.5 ~ 1.0 (0.05step) x In (CT rating)

LTD pick-up current : 1.15 x Ir

1–2–3–4–5–6–8–10–12–15–18s

0.02–1–2–3–4

1.5–2–2.5–3–4–5–6–7–8–9–10 x Ir at Ir x 4

Accuracy

1.10 x Ir…Non Pick-up

1.20 x Ir…Pick-up

± 30% (1.5Ir

≦ load current<4Ir)

± 20% (4Ir ≦ load current)

± 15%

± 20%

It operates in the range between 0.04 and 0.08 when the time set at 0.06s.

Factory default value

1.0

18

2

10

0.5 (I 2 t ON) ⑪

STD time

INST/MCR pick-up current

Pre-alarm current

Pre-alarm time

Tsd

Ii

Ip

Tp

0.5–0.4–0.3–0.2–0.1–0.06–0.06–0.1–0.2–0.3–0.4–0.5s

(I 2 t ON) (I 2 t OFF) at Isd x 1.5

AE630-SW~AE1600-SW

AE2000-SW~AE3200-SW

AE4000-SW

AE2000-SWA, AE4000-SWA

AE5000-SW

AE6300-SW

16-12-10-8-6-4-2-2-4-6-8-10-12-16

(INST) (MCR)

12-10-8-6-4-2-2-4-6-8-10-12

(INST) (MCR)

10-8-6-4-2-2-4-6-8-10 x Ir

(INST) (MCR)

Ir x 0.68 ~ 1.0 (0.04step) –OVER

x Ir

x Ir

WF1

WF2

WF3

1/2 T

L

at Ir x 4 (after 1/2 T

L

, PAL contact output turns on.)

Remark (1) The table and the figure include both optional display and MCR.

Remark (2) For WF relay, when Pre-alarm current Ip is set at "OVER", the Ip value is "Ir x 1.15".

Relation of setting dial

In (CT rating) Ir

Ig (P.28) Isd

Ii

Ip

Ip2 (P.29)

Load current LED (60, 80, 100%, OVER)

± 15%

± 5%

± 30% (1.5Ir

≦ load current<4Ir)

± 20% (4Ir ≦ load current)

WF1…16 (INST)

WF2…12 (INST)

WF3…10 (INST)

OVER

100

60

50

40

30

20

10

.5

.4

.3

.2

.1

5

4

3

2

1

.05

.04

.03

.02

.01

1

[LTD curve setting "a=0.02"] a=0.02

10000

5000

4000

3000

2000

Pre-alarm current : Ip

Ir x 0.68~1.0(0.04step)-OVER ± 5%

Current setting : Ir

0.5~1.0(0.05step) x In(CT rating)

LTD pick-up

1.10 x Ir ... Non pick-up

1.20 x Ir ... Pick-up 1000

500

400

300

200

2

STD time : Tsd

0.06-0.1-0.2-0.3-0.4-0.5(s) ±

Note3

20%

(at Isd x 1.5)

STD pick-up current : Isd

Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%

5

Pre-alarm time : Tp

T

L

/2 ± 20%

Note2

(at Ir x 4)

LTD time : T

L

1-2-3-4-5-6-8-10-12-15-18(s) ±

Note1

20%

(at Ir x 4)

With MCR

10 20

I 2 t ON

(ramp)

I 2 t OFF

INST/MCR pick-up current : Ii

Ir x 2-4-6-8-10-12-16 ±

Ir x 2-4-6-8-10-12 ±

Ir x 2-4-6-8-10 ±

15% WF1

15% WF2

15% WF3

50 100 150

125 200

500

Max. breaking time

(In case of AE4000-SW~

6300-SW, it is 0.05s)

1000 2000

1600

5000

Current (%)

10000

[LTD curve setting "a=3"] a=3

10000

500

400

300

200

100

60

50

40

30

20

5000

4000

3000

2000

1000

Pre-alarm current : Ip

Ir x 0.68~1.0(0.04step)-OVER ± 5%

Current setting : Ir

0.5~1.0(0.05step) x In(CT rating)

LTD pick-up

1.10 x Ir ... Non pick-up

1.20 x Ir ... Pick-up

Pre-alarm time : Tp Note2

T L /2 ± 20% (at Ir x 4)

LTD time : T L Note1

1-2-3-4-5-6-8-10-12-15-18(s) ± 20%

(at Ir x 4)

10

5

4

3

2

STD time : Tsd Note3

0.06-0.1-0.2-0.3-0.4-0.5(s) ± 20%

(at Isd x 1.5)

STD pick-up current : Isd

Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%

With MCR

1

.5

.4

.3

.2

.1

.05

.04

.03

.02

.01

1 2 5 10 20

I 2 t ON

(ramp)

I 2 t OFF

INST/MCR pick-up current : Ii

Ir x 2-4-6-8-10-12-16 ±

Ir x 2-4-6-8-10-12

Ir x 2-4-6-8-10

15% : WF1

± 15% : WF2

± 15% : WF3

Max. breaking time

(In case of AE4000-SW~

6300-SW, it is 0.05s)

50 100 150

125 200

Current (%)

500 1000 2000

1600

5000 10000

Note 1: LTD operating time t

LTD

is calculated by the following equations.

a = LTD curve setting t LTD =

(4/1.1155) a -1

(I/1.1155Ir) a -1 x T L

I = load current (A)

Ir = 0.5~1.0 x In (A)

T

L

= 1~18 (s)

The accuracy of operating time is ± 30% (1.5Ir

≦ load current<4Ir) or ± 20% (4Ir ≦ load current).

LTD operating time is 0.8s(FLAT) when the operating time becomes 0.8s or less.

Note 3: When Tsd = "0.06" setting, operating time is 0.04~0.08s.

I 2 t is selectable : ON or OFF.

100

60

50

40

30

20

10

.5

.4

.3

.2

.1

5

4

3

2

1

.05

.04

.03

.02

.01

1

[LTD curve setting "a=1"] a=1

10000

5000

4000

3000

2000

Pre-alarm current : Ip

Ir x 0.68~1.0(0.04step)-OVER ± 5%

Current setting : Ir

0.5~1.0(0.05step) x In(CT rating)

LTD pick-up 1.10 x Ir ... Non pick-up

1.20 x Ir ... Pick-up 1000

500

400

300

200

2 5

STD time : Tsd Note3

0.06-0.1-0.2-0.3-0.4-0.5(s) ± 20%

(at Isd x 1.5)

STD pick-up current : Isd

Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%

10 20

Pre-alarm time : Tp

T L /2 ± 20%

Note2

(at Ir x 4)

LTD time : T L Note1

1-2-3-4-5-6-8-10-12-15-18(s) ± 20%

(at Ir x 4)

With MCR

I 2 t ON

(ramp)

I 2 t OFF

INST/MCR pick-up current : Ii

Ir x 2-4-6-8-10-12-16

Ir x 2-4-6-8-10-12

Ir x 2-4-6-8-10

±

±

±

15% WF1

15% WF2

15% WF3

500 50 100 150

125 200

Current (%)

Max. breaking time

(In case of AE4000-SW~

6300-SW, it is 0.05s)

1000 2000

1600

5000 10000

[LTD curve setting "a=4"] a=4

10000

100

60

50

40

30

20

10

5000

4000

3000

2000

1000

500

400

300

200

Pre-alarm current : Ip

Ir x 0.68~1.0(0.04step)-OVER ± 5%

Current setting : Ir

0.5~1.0(0.05step) x In(CT rating)

LTD pick-up

1.10 x Ir ... Non pick-up

1.20 x Ir ... Pick-up

Pre-alarm time : Tp

T L /2 ± 20%

Note2

(at Ir x 4)

LTD time : T

L

1-2-3-4-5-6-8-10-12-15-18(s) ±

Note1

20%

(at Ir x 4)

5

4

3

2

1

.5

.4

.3

.2

STD time : Tsd Note3

0.06-0.1-0.2-0.3-0.4-0.5(s) ± 20%

(at Isd x 1.5)

STD pick-up current : Isd

Ir x ± 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%

With MCR

.1

.05

.04

.03

.02

.01

1 2 5 10 20

I 2 t ON

(ramp)

I 2 t OFF

INST/MCR pick-up current : Ii

Ir x 2-4-6-8-10-12-16 ±

Ir x 2-4-6-8-10-12

Ir x 2-4-6-8-10

±

15% : WF1

15% : WF2

± 15% : WF3

500 50 100 150

125 200

Current (%)

Max. breaking time

(In case of AE4000-SW~

6300-SW, it is 0.05s)

1000 2000

1600

5000 10000

Note 2: PAL operating time t

PAL

is calculated by the following equations.

a = LTD curve setting t

PAL

=

(4Ir/0.97Ip) a -1

(I/0.97Ip) a -1 x

T

L

2

I = load current (A)

Ir = 0.5~1.0 x In (A)

Ip = 0.68~1.15 x Ir (A)

T

L

= 1~18 (s)

The accuracy of operating time is ± 30% (1.5Ir

≦ load current < 4Ir) or ± 20% (4Ir ≦ load current).

PAL operating time is 0.5s(FLAT) when the operating time becomes 0.5s or less.

E-27