Characteristics setting for the WF type. Mitsubishi Electric AE2000-SWA, AE4000-SW, Low-Voltage Air Circuit Breakers series Type AE-SW, AE3200-SW, AE630-SW
Add to My manuals43 Pages
advertisement
Characteristics setting for the WF type
The selectable characteristics are the following five curves.
4
5
6
2
1
3
12
8
9
10
11
(I 4 -1)t = const.
(I 3 -1)t = const.
(I 2 -1)t = const.
(I -1)t = const.
(I 0.02 -1)t = const.
16
13
15
I (current)
LTD characteristics curves
14
LTD curve can be selected by the LTD curve setting dial.
⑬
⑭
⑮
⑯
⑨
⑩
⑪
⑫
⑤
⑥
⑦
⑧
①
②
③
④
Trip indicator LED
Pre-alarm LED
Temperature alarm LED
Load current LED
RUN LED
ERR. LED
Current setting dial
LTD time setting dial
LTD curve setting dial
STD pick-up setting dial
STD time setting dial
INST/MCR pick-up current setting dial
Optional setting module
Pre-alarm current setting dial
RESET button (TEST L/S LOCK button)
TEST terminal
Note) The figure shows WF1 type with G1 module, Display (DP1) and MCR switch.
G1, DP1 and MCR are optional equipments.
[LTD curve setting "a=2"] a=2
10000
5000
4000
3000
2000
1000
1
.5
.4
.3
.2
Pre-alarm current : Ip
Ir x 0.68~1.0(0.04step)-OVER ± 5%
Current setting : Ir
0.5~1.0(0.05step) x In(CT rating)
LTD pick-up
1.10 x Ir ... Non pick-up
1.20 x Ir ... Pick-up
500
400
300
200
100
60
50
40
30
20
5
4
3
2
10
LTD operating time t
LTD
Note1 t
LTD
(4/1.1155) a
(I/1.1155Ir)
-1 a
-1
L
Accuracy : a = 2
I = load current (A)
Ir= 0.5~1.0 x In (A)
T L = 1~18 (s)
± 30%(1.5Ir load current<4Ir)
± 20%(4Ir load current)
PAL operating time t
PAL
Note2 t PAL
(I/0.97lp) a -1 a -1
L a = 2
I = load current (A)
Ip= 0.68~1.15 x Ir (A)
T
L
= 1~18 (s)
Accuracy :
± 30%(1.5Ir load current<4Ir)
± 20%(4Ir load current)
STD time : Tsd Note3
0.06-0.1-0.2-0.3-0.4-0.5(s) ± 20%
(at Isd x 1.5)
STD pick-up current : Isd
Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%
Pre-alarm time : Tp
T
L
/2 ± 20% (at Ir x 4)
LTD time : T
L
1-2-3-4-5-6-8-10-12-15-18(s) ± 20%
(at Ir x 4)
With MCR
.1
.05
.04
.03
.02
.01
1
Note1 : LTD operating time is 0.8s(FLAT)when the operating
time becomes 0.8s or less.
Note2 : PAL operating time is 0.5s(FLAT) when the operating
time becomes 0.5s or less.
Note3 : When Tsd ="0.06" setting,operating time is 0.04~0.08s.
I 2 t is selectable ON or OFF.
2 5 10 20 50
I 2
(ramp)
I 2 t OFF
INST/MCR pick-up current : Ii
Ir x 2-4-6-8-10-12-16 ±
Ir x 2-4-6-8-10-12
Ir x 2-4-6-8-10
15% : WF1
± 15% : WF2
± 15% : WF3
100 150
125 200
500
Max. breaking time
(In case of AE4000-SW~
6300-SW, it is 0.05s)
1000 2000
1600
Current (%)
5000 10000
Table 26
No.
Setting item
⑦ Current setting
⑧
⑨
⑩
LTD time
LTD curve setting
STD pick-up current
Symbol
Ir
T
L a
Isd
Characteristic setting range
0.5 ~ 1.0 (0.05step) x In (CT rating)
LTD pick-up current : 1.15 x Ir
1–2–3–4–5–6–8–10–12–15–18s
0.02–1–2–3–4
1.5–2–2.5–3–4–5–6–7–8–9–10 x Ir at Ir x 4
Accuracy
1.10 x Ir…Non Pick-up
1.20 x Ir…Pick-up
± 30% (1.5Ir
≦ load current<4Ir)
± 20% (4Ir ≦ load current)
—
± 15%
± 20%
It operates in the range between 0.04 and 0.08 when the time set at 0.06s.
Factory default value
1.0
18
2
10
0.5 (I 2 t ON) ⑪ STD time
⑫
INST/MCR pick-up current
⑭
—
Pre-alarm current
Pre-alarm time
Tsd
Ii
Ip
Tp
0.5–0.4–0.3–0.2–0.1–0.06–0.06–0.1–0.2–0.3–0.4–0.5s
(I 2 t ON) (I 2 t OFF) at Isd x 1.5
AE630-SW~AE1600-SW
AE2000-SW~AE3200-SW
AE4000-SW
AE2000-SWA, AE4000-SWA
AE5000-SW
AE6300-SW
16-12-10-8-6-4-2-2-4-6-8-10-12-16
(INST) (MCR)
12-10-8-6-4-2-2-4-6-8-10-12
(INST) (MCR)
10-8-6-4-2-2-4-6-8-10 x Ir
(INST) (MCR)
Ir x 0.68 ~ 1.0 (0.04step) –OVER
x Ir
x Ir
WF1
WF2
WF3
1/2 T
L
at Ir x 4 (after 1/2 T
L
, PAL contact output turns on.)
Remark (1) The table and the figure include both optional display and MCR.
Remark (2) For WF relay, when Pre-alarm current Ip is set at "OVER", the Ip value is "Ir x 1.15".
Relation of setting dial
In (CT rating) Ir
Ig (P.28)
E-26
Isd
Ii
Ip
Ip2 (P.29)
Load current LED (60, 80, 100%, OVER)
± 15%
± 5%
± 30% (1.5Ir
≦ load current<4Ir)
± 20% (4Ir ≦ load current)
WF1…16 (INST)
WF2…12 (INST)
WF3…10 (INST)
OVER
—
100
60
50
40
30
20
10
.5
.4
.3
.2
.1
5
4
3
2
1
.05
.04
.03
.02
.01
1
[LTD curve setting "a=0.02"] a=0.02
10000
5000
4000
3000
2000
Pre-alarm current : Ip
Ir x 0.68~1.0(0.04step)-OVER ± 5%
Current setting : Ir
0.5~1.0(0.05step) x In(CT rating)
LTD pick-up
1.10 x Ir ... Non pick-up
1.20 x Ir ... Pick-up 1000
500
400
300
200
2
STD time : Tsd
0.06-0.1-0.2-0.3-0.4-0.5(s) ±
Note3
20%
(at Isd x 1.5)
STD pick-up current : Isd
Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%
5
Pre-alarm time : Tp
T
L
/2 ± 20%
Note2
(at Ir x 4)
LTD time : T
L
1-2-3-4-5-6-8-10-12-15-18(s) ±
Note1
20%
(at Ir x 4)
With MCR
10 20
I 2 t ON
(ramp)
I 2 t OFF
INST/MCR pick-up current : Ii
Ir x 2-4-6-8-10-12-16 ±
Ir x 2-4-6-8-10-12 ±
15% WF1
15% WF2
Ir x 2-4-6-8-10 ± 15% WF3
50 100 150
125 200
500
Max. breaking time
(In case of AE4000-SW~
6300-SW, it is 0.05s)
1000 2000
1600
5000
Current (%)
10000
[LTD curve setting "a=3"] a=3
10000
500
400
300
200
100
60
50
40
30
20
5000
4000
3000
2000
1000
Pre-alarm current : Ip
Ir x 0.68~1.0(0.04step)-OVER ± 5%
Current setting : Ir
0.5~1.0(0.05step) x In(CT rating)
LTD pick-up
1.10 x Ir ... Non pick-up
1.20 x Ir ... Pick-up
Pre-alarm time : Tp Note2
T L /2 ± 20% (at Ir x 4)
LTD time : T L Note1
1-2-3-4-5-6-8-10-12-15-18(s) ± 20%
(at Ir x 4)
10
5
4
3
2
STD time : Tsd Note3
0.06-0.1-0.2-0.3-0.4-0.5(s) ± 20%
(at Isd x 1.5)
STD pick-up current : Isd
Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%
With MCR
1
.5
.4
.3
.2
.1
.05
.04
.03
.02
.01
1 2 5 10 20
I 2 t ON
(ramp)
I 2 t OFF
INST/MCR pick-up current : Ii
Ir x 2-4-6-8-10-12-16 ±
Ir x 2-4-6-8-10-12
Ir x 2-4-6-8-10
15% : WF1
± 15% : WF2
± 15% : WF3
Max. breaking time
(In case of AE4000-SW~
6300-SW, it is 0.05s)
50 100 150
125 200
Current (%)
500 1000 2000
1600
5000 10000
Note 1: LTD operating time t
LTD
is calculated by the following equations.
a = LTD curve setting t LTD =
(4/1.1155) a -1
(I/1.1155Ir) a -1 x T L
I = load current (A)
Ir = 0.5~1.0 x In (A)
T
L
= 1~18 (s)
The accuracy of operating time is ± 30% (1.5Ir
≦ load current<4Ir) or ± 20% (4Ir ≦ load current).
LTD operating time is 0.8s(FLAT) when the operating time becomes 0.8s or less.
Note 3: When Tsd = "0.06" setting, operating time is 0.04~0.08s.
I 2 t is selectable : ON or OFF.
100
60
50
40
30
20
10
.5
.4
.3
.2
.1
5
4
3
2
1
.05
.04
.03
.02
.01
1
[LTD curve setting "a=1"] a=1
10000
5000
4000
3000
2000
Pre-alarm current : Ip
Ir x 0.68~1.0(0.04step)-OVER ± 5%
Current setting : Ir
0.5~1.0(0.05step) x In(CT rating)
LTD pick-up 1.10 x Ir ... Non pick-up
1.20 x Ir ... Pick-up 1000
500
400
300
200
2 5
STD time : Tsd Note3
0.06-0.1-0.2-0.3-0.4-0.5(s) ± 20%
(at Isd x 1.5)
STD pick-up current : Isd
Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%
10 20
Pre-alarm time : Tp
T L /2 ± 20%
Note2
(at Ir x 4)
LTD time : T L Note1
1-2-3-4-5-6-8-10-12-15-18(s) ± 20%
(at Ir x 4)
With MCR
I 2 t ON
(ramp)
I 2 t OFF
INST/MCR pick-up current : Ii
Ir x 2-4-6-8-10-12-16
Ir x 2-4-6-8-10-12
Ir x 2-4-6-8-10
±
±
±
15% WF1
15% WF2
15% WF3
500 50 100 150
125 200
Current (%)
Max. breaking time
(In case of AE4000-SW~
6300-SW, it is 0.05s)
1000 2000
1600
5000 10000
[LTD curve setting "a=4"] a=4
10000
100
60
50
40
30
20
10
5000
4000
3000
2000
1000
500
400
300
200
Pre-alarm current : Ip
Ir x 0.68~1.0(0.04step)-OVER ± 5%
Current setting : Ir
0.5~1.0(0.05step) x In(CT rating)
LTD pick-up
1.10 x Ir ... Non pick-up
1.20 x Ir ... Pick-up
Pre-alarm time : Tp
T L /2 ± 20%
Note2
(at Ir x 4)
LTD time : T
L
1-2-3-4-5-6-8-10-12-15-18(s) ±
Note1
20%
(at Ir x 4)
5
4
3
2
1
.5
.4
.3
.2
STD time : Tsd Note3
0.06-0.1-0.2-0.3-0.4-0.5(s) ± 20%
(at Isd x 1.5)
STD pick-up current : Isd
Ir x ± 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%
With MCR
.1
.05
.04
.03
.02
.01
1 2 5 10 20
I 2 t ON
(ramp)
I 2 t OFF
INST/MCR pick-up current : Ii
Ir x 2-4-6-8-10-12-16 ±
Ir x 2-4-6-8-10-12
Ir x 2-4-6-8-10
±
15% : WF1
15% : WF2
± 15% : WF3
500 50 100 150
125 200
Current (%)
Max. breaking time
(In case of AE4000-SW~
6300-SW, it is 0.05s)
1000 2000
1600
5000 10000
Note 2: PAL operating time t
PAL
is calculated by the following equations.
a = LTD curve setting t
PAL
=
(4Ir/0.97Ip) a -1
(I/0.97Ip) a -1 x
T
L
2
I = load current (A)
Ir = 0.5~1.0 x In (A)
Ip = 0.68~1.15 x Ir (A)
T
L
= 1~18 (s)
The accuracy of operating time is ± 30% (1.5Ir
≦ load current < 4Ir) or ± 20% (4Ir ≦ load current).
PAL operating time is 0.5s(FLAT) when the operating time becomes 0.5s or less.
4
5
6
2
1
3
16
The selectable characteristics are the following five curves.
12
8
9
10
11
(I 4 -1)t = const.
(I 3 -1)t = const.
(I 2 -1)t = const.
(I -1)t = const.
(I 0.02 -1)t = const.
13
15
I (current)
LTD characteristics curves
14
LTD curve can be selected by the LTD curve setting dial.
⑬
⑭
⑮
⑯
⑨
⑩
⑪
⑫
⑤
⑥
⑦
⑧
①
②
③
④
Trip indicator LED
Pre-alarm LED
Temperature alarm LED
Load current LED
RUN LED
ERR. LED
Current setting dial
LTD time setting dial
LTD curve setting dial
STD pick-up setting dial
STD time setting dial
INST/MCR pick-up current setting dial
Optional setting module
Pre-alarm current setting dial
RESET button (TEST L/S LOCK button)
TEST terminal
Note) The figure shows WF1 type with G1 module, Display (DP1) and MCR switch.
G1, DP1 and MCR are optional equipments.
[LTD curve setting "a=2"] a=2
10000
5000
4000
3000
2000
1000
1
.5
.4
.3
.2
Pre-alarm current : Ip
Ir x 0.68~1.0(0.04step)-OVER ± 5%
Current setting : Ir
0.5~1.0(0.05step) x In(CT rating)
LTD pick-up
1.10 x Ir ... Non pick-up
1.20 x Ir ... Pick-up
500
400
300
200
100
60
50
40
30
20
5
4
3
2
10
LTD operating time t
LTD
Note1 t
LTD
(4/1.1155) a
(I/1.1155Ir)
-1 a
-1
L
Accuracy : a = 2
I = load current (A)
Ir= 0.5~1.0 x In (A)
T L = 1~18 (s)
± 30%(1.5Ir load current<4Ir)
± 20%(4Ir load current)
PAL operating time t
PAL
Note2 t PAL
(I/0.97lp) a -1 a -1
L a = 2
I = load current (A)
Ip= 0.68~1.15 x Ir (A)
T
L
= 1~18 (s)
Accuracy :
± 30%(1.5Ir load current<4Ir)
± 20%(4Ir load current)
STD time : Tsd Note3
0.06-0.1-0.2-0.3-0.4-0.5(s) ± 20%
(at Isd x 1.5)
STD pick-up current : Isd
Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%
Pre-alarm time : Tp
T
L
/2 ± 20% (at Ir x 4)
LTD time : T
L
1-2-3-4-5-6-8-10-12-15-18(s) ± 20%
(at Ir x 4)
With MCR
.1
.05
.04
.03
.02
.01
1
Note1 : LTD operating time is 0.8s(FLAT)when the operating
time becomes 0.8s or less.
Note2 : PAL operating time is 0.5s(FLAT) when the operating
time becomes 0.5s or less.
Note3 : When Tsd ="0.06" setting,operating time is 0.04~0.08s.
I 2 t is selectable ON or OFF.
I 2
(ramp)
I 2 t OFF
INST/MCR pick-up current : Ii
Ir x 2-4-6-8-10-12-16 ±
Ir x 2-4-6-8-10-12
Ir x 2-4-6-8-10
15% : WF1
± 15% : WF2
± 15% : WF3
2 5 10 20 50 100 150
125 200
500
Max. breaking time
(In case of AE4000-SW~
6300-SW, it is 0.05s)
1000 2000
1600
Current (%)
5000 10000
No.
⑦
⑧
⑨
⑩
Setting item
Current setting
LTD time
LTD curve setting
STD pick-up current
Symbol
Ir
T a
L
Isd
Characteristic setting range
0.5 ~ 1.0 (0.05step) x In (CT rating)
LTD pick-up current : 1.15 x Ir
1–2–3–4–5–6–8–10–12–15–18s
0.02–1–2–3–4
1.5–2–2.5–3–4–5–6–7–8–9–10 x Ir at Ir x 4
Accuracy
1.10 x Ir…Non Pick-up
1.20 x Ir…Pick-up
± 30% (1.5Ir
≦ load current<4Ir)
± 20% (4Ir ≦ load current)
—
± 15%
± 20%
It operates in the range between 0.04 and 0.08 when the time set at 0.06s.
Factory default value
1.0
18
2
10
0.5 (I 2 t ON) ⑪
⑫
⑭
—
STD time
INST/MCR pick-up current
Pre-alarm current
Pre-alarm time
Tsd
Ii
Ip
Tp
0.5–0.4–0.3–0.2–0.1–0.06–0.06–0.1–0.2–0.3–0.4–0.5s
(I 2 t ON) (I 2 t OFF) at Isd x 1.5
AE630-SW~AE1600-SW
AE2000-SW~AE3200-SW
AE4000-SW
AE2000-SWA, AE4000-SWA
AE5000-SW
AE6300-SW
16-12-10-8-6-4-2-2-4-6-8-10-12-16
(INST) (MCR)
12-10-8-6-4-2-2-4-6-8-10-12
(INST) (MCR)
10-8-6-4-2-2-4-6-8-10 x Ir
(INST) (MCR)
Ir x 0.68 ~ 1.0 (0.04step) –OVER
x Ir
x Ir
WF1
WF2
WF3
1/2 T
L
at Ir x 4 (after 1/2 T
L
, PAL contact output turns on.)
Remark (1) The table and the figure include both optional display and MCR.
Remark (2) For WF relay, when Pre-alarm current Ip is set at "OVER", the Ip value is "Ir x 1.15".
Relation of setting dial
In (CT rating) Ir
Ig (P.28) Isd
Ii
Ip
Ip2 (P.29)
Load current LED (60, 80, 100%, OVER)
± 15%
± 5%
± 30% (1.5Ir
≦ load current<4Ir)
± 20% (4Ir ≦ load current)
WF1…16 (INST)
WF2…12 (INST)
WF3…10 (INST)
OVER
—
100
60
50
40
30
20
10
.5
.4
.3
.2
.1
5
4
3
2
1
.05
.04
.03
.02
.01
1
[LTD curve setting "a=0.02"] a=0.02
10000
5000
4000
3000
2000
Pre-alarm current : Ip
Ir x 0.68~1.0(0.04step)-OVER ± 5%
Current setting : Ir
0.5~1.0(0.05step) x In(CT rating)
LTD pick-up
1.10 x Ir ... Non pick-up
1.20 x Ir ... Pick-up 1000
500
400
300
200
2
STD time : Tsd
0.06-0.1-0.2-0.3-0.4-0.5(s) ±
Note3
20%
(at Isd x 1.5)
STD pick-up current : Isd
Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%
5
Pre-alarm time : Tp
T
L
/2 ± 20%
Note2
(at Ir x 4)
LTD time : T
L
1-2-3-4-5-6-8-10-12-15-18(s) ±
Note1
20%
(at Ir x 4)
With MCR
10 20
I 2 t ON
(ramp)
I 2 t OFF
INST/MCR pick-up current : Ii
Ir x 2-4-6-8-10-12-16 ±
Ir x 2-4-6-8-10-12 ±
Ir x 2-4-6-8-10 ±
15% WF1
15% WF2
15% WF3
50 100 150
125 200
500
Max. breaking time
(In case of AE4000-SW~
6300-SW, it is 0.05s)
1000 2000
1600
5000
Current (%)
10000
[LTD curve setting "a=3"] a=3
10000
500
400
300
200
100
60
50
40
30
20
5000
4000
3000
2000
1000
Pre-alarm current : Ip
Ir x 0.68~1.0(0.04step)-OVER ± 5%
Current setting : Ir
0.5~1.0(0.05step) x In(CT rating)
LTD pick-up
1.10 x Ir ... Non pick-up
1.20 x Ir ... Pick-up
Pre-alarm time : Tp Note2
T L /2 ± 20% (at Ir x 4)
LTD time : T L Note1
1-2-3-4-5-6-8-10-12-15-18(s) ± 20%
(at Ir x 4)
10
5
4
3
2
STD time : Tsd Note3
0.06-0.1-0.2-0.3-0.4-0.5(s) ± 20%
(at Isd x 1.5)
STD pick-up current : Isd
Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%
With MCR
1
.5
.4
.3
.2
.1
.05
.04
.03
.02
.01
1 2 5 10 20
I 2 t ON
(ramp)
I 2 t OFF
INST/MCR pick-up current : Ii
Ir x 2-4-6-8-10-12-16 ±
Ir x 2-4-6-8-10-12
Ir x 2-4-6-8-10
15% : WF1
± 15% : WF2
± 15% : WF3
Max. breaking time
(In case of AE4000-SW~
6300-SW, it is 0.05s)
50 100 150
125 200
Current (%)
500 1000 2000
1600
5000 10000
Note 1: LTD operating time t
LTD
is calculated by the following equations.
a = LTD curve setting t LTD =
(4/1.1155) a -1
(I/1.1155Ir) a -1 x T L
I = load current (A)
Ir = 0.5~1.0 x In (A)
T
L
= 1~18 (s)
The accuracy of operating time is ± 30% (1.5Ir
≦ load current<4Ir) or ± 20% (4Ir ≦ load current).
LTD operating time is 0.8s(FLAT) when the operating time becomes 0.8s or less.
Note 3: When Tsd = "0.06" setting, operating time is 0.04~0.08s.
I 2 t is selectable : ON or OFF.
100
60
50
40
30
20
10
.5
.4
.3
.2
.1
5
4
3
2
1
.05
.04
.03
.02
.01
1
[LTD curve setting "a=1"] a=1
10000
5000
4000
3000
2000
Pre-alarm current : Ip
Ir x 0.68~1.0(0.04step)-OVER ± 5%
Current setting : Ir
0.5~1.0(0.05step) x In(CT rating)
LTD pick-up 1.10 x Ir ... Non pick-up
1.20 x Ir ... Pick-up 1000
500
400
300
200
2 5
STD time : Tsd Note3
0.06-0.1-0.2-0.3-0.4-0.5(s) ± 20%
(at Isd x 1.5)
STD pick-up current : Isd
Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%
10 20
Pre-alarm time : Tp
T L /2 ± 20%
Note2
(at Ir x 4)
LTD time : T L Note1
1-2-3-4-5-6-8-10-12-15-18(s) ± 20%
(at Ir x 4)
With MCR
I 2 t ON
(ramp)
I 2 t OFF
INST/MCR pick-up current : Ii
Ir x 2-4-6-8-10-12-16
Ir x 2-4-6-8-10-12
Ir x 2-4-6-8-10
±
±
±
15% WF1
15% WF2
15% WF3
500 50 100 150
125 200
Current (%)
Max. breaking time
(In case of AE4000-SW~
6300-SW, it is 0.05s)
1000 2000
1600
5000 10000
[LTD curve setting "a=4"] a=4
10000
100
60
50
40
30
20
10
5000
4000
3000
2000
1000
500
400
300
200
Pre-alarm current : Ip
Ir x 0.68~1.0(0.04step)-OVER ± 5%
Current setting : Ir
0.5~1.0(0.05step) x In(CT rating)
LTD pick-up
1.10 x Ir ... Non pick-up
1.20 x Ir ... Pick-up
Pre-alarm time : Tp
T L /2 ± 20%
Note2
(at Ir x 4)
LTD time : T
L
1-2-3-4-5-6-8-10-12-15-18(s) ±
Note1
20%
(at Ir x 4)
5
4
3
2
1
.5
.4
.3
.2
STD time : Tsd Note3
0.06-0.1-0.2-0.3-0.4-0.5(s) ± 20%
(at Isd x 1.5)
STD pick-up current : Isd
Ir x ± 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%
With MCR
.1
.05
.04
.03
.02
.01
1 2 5 10 20
I 2 t ON
(ramp)
I 2 t OFF
INST/MCR pick-up current : Ii
Ir x 2-4-6-8-10-12-16 ±
Ir x 2-4-6-8-10-12
Ir x 2-4-6-8-10
±
15% : WF1
15% : WF2
± 15% : WF3
500 50 100 150
125 200
Current (%)
Max. breaking time
(In case of AE4000-SW~
6300-SW, it is 0.05s)
1000 2000
1600
5000 10000
Note 2: PAL operating time t
PAL
is calculated by the following equations.
a = LTD curve setting t
PAL
=
(4Ir/0.97Ip) a -1
(I/0.97Ip) a -1 x
T
L
2
I = load current (A)
Ir = 0.5~1.0 x In (A)
Ip = 0.68~1.15 x Ir (A)
T
L
= 1~18 (s)
The accuracy of operating time is ± 30% (1.5Ir
≦ load current < 4Ir) or ± 20% (4Ir ≦ load current).
PAL operating time is 0.5s(FLAT) when the operating time becomes 0.5s or less.
E-27
advertisement
Related manuals
advertisement
Table of contents
- 3 Table of contents
- 4 External view
- 5 Internal structure/Outline dimensions and product weight
- 6 Unpacking/Storage
- 7 Transportation
- 8 Installation
- 9 Installation of the drawout handle/Installation of the inter-phase barrier (BA)
- 10 Connection
- 12 Insert operation
- 14 Drawout operation
- 16 Charging operation
- 17 Open/close operation
- 19 Door interlock (DI)/Cylinder lock (CYL) and Castell lock (CAL)/OCR alarm (AL) [MRE: manual reset type]
- 20 Shutter lock (SST-LOCK)/Safety shutter nameplate
- 21 Functions of electronic trip relay (ETR) parts
- 23 Characteristics setting for the WS type
- 24 Characteristics setting for the WM type
- 25 Characteristics setting for the WB type
- 26 Characteristics setting for the WF type
- 28 Characteristics setting for the optional setting modules
- 30 Setting procedure for the electronic trip characteristics
- 32 Wiring diagram
- 34 Technical notes
- 35 Warranty
- 36 Inspection and maintenance
- 42 SERVICE NETWORK