Characteristics setting for the optional setting modules. Mitsubishi Electric AE2000-SWA, AE4000-SW, Low-Voltage Air Circuit Breakers series Type AE-SW, AE3200-SW, AE630-SW
Add to My manuals43 Pages
advertisement
Characteristics setting for the optional setting modules
< Characteristics setting for the G1 module >
1
① Ground fault pick-up current: Ig
1.0
0.1
3.0±20%
2
To provide ground fault protection for a 3-pole breaker used in the 3-phase 4-wire system, a neutral pole CT (NCT) is required. For the specification, refer to the catalog.
For the installation of the NCT, refer to the instruction manual provided with the NCT.
The G1 module cannot be attached to the AE630-SW low rating models (CT rating:
500 A, 315 A, 250 A).
To set the ground fault pick-up current Ig to 0.1, the control power supply must be applied. (If the control power supply is not applied, ground fault protection cannot be provided correctly.)
Table 28-1
No.
①
Setting item
Ground fault pick-up current
Symbol
Ig
②
Ground fault operating time
– Alarm output
Tg
–
Characteristic setting range
0.1 to 1.0 × In (0.1 step)
Accuracy
±20%
Factory default value
1.0
3.0-1.5-0.8-0.5-0.3-0.15-<0.1 - <0.1-0.15-0.3-0.5-0.8-1.5-3.0 s
(TRIP) (ALARM)
(at 1.5×Ig)
TRIP: self-hold type / ALARM: automatic reset type
±20%
–
3s(TRIP)
Self-hold type(TRIP)
< Characteristics setting for the E1 module >
E1 module, in combination with an external ZCT, provides electric leakage protection.
To provide the electric leakage protection, a control power supply is required.
ZCT for load circuit
ZCT type
ZCT163
ZCT323
Breaker type, number of poles
AE630-SW ~ AE1600-SW 3-pole
AE630-SW ~ AE1600-SW 4-pole
AE2000-SW ~ AE3200-SW 3-pole
AE2000-SW ~ AE3200-SW 4-pole ZCT324
Type combinations shown in this table are for reference.
Choose the one that matches the size of the conductor to be connected.
ZCT with primary conductor
ZCT type
ZTA1200A
ZTA2000A
Breaker type, number of poles
AE630-SW ~ AE1000-SW 3-pole model
AE1250-SW ~ AE2000-SW 3-pole model
AE2000-SWA 3-pole model
The types not listed above can also be used if their rated current setting (Ir) is ZCT permissible current value or lower.
ZCT for transformer earth wire
ZT15B ZT30B
ZCT type
ZT40B ZT60B ZT80B ZT100B
Be sure to use with the ZCT specified by Mitsubishi Electric.
For the ZCT installation, refer to the instruction manual provided with the ZCT.
Table 28-2
No.
Setting item
①
ER Pick-up current
Symbol
I∆n
②
ER Operating time
Te
– Alarm output –
Characteristic setting range
1-2-3-5-10A
3-1.5-0.8-0.5-0.3-0.15-<0.1s - <0.1-0.15-0.3-0.5-0.8-1.5-3 s
(TRIP) (ALARM)
(at 1.5×I∆n)
TRIP: self-hold type / ALARM: automatic reset type
Accuracy
0%
-30%
Factory default value
10A
±20%
–
3s(TRIP)
Self-hold type(TRIP)
E-28
1
② Ground fault operating time: Tg
0.15±20%
<0.1
(0.04 to 0.1s)
Ground fault current (% of CT rating In)
1A
① ER Pick-up current: I∆n
10A
3.0s±20%
② ER Operating time: Te
0.15s±20%
<0.1s
(0.04 to 0.1s)
Electric leakage current (A)
2
< Characteristics setting for the AP module >
By combining this with the pre-alarm function installed as standard, the two-step pre-alarms can be constructed.
For the AE630-SW low rating types, be sure to apply the control power supply.
This cannot be combined with the WB type.
With the WS type
1
With the WM type
2
① 2nd pre-alarm
Current: Ip2
LTD time: T
L
12-25-50-100-150s (at Iu x 2)
① 2nd pre-alarm
Current: Ip2
LTD time: T
L
15-20-25-30-40-60 s (at I
L
x 1.2)
② 2nd pre-alarm
Time: Tp2 (FLAT)
② 2nd pre-alarm
Time: Tp2 (FLAT)
② 2nd pre-alarm
Time: Tp2 ( x T
L
)
② 2nd pre-alarm
Time: Tp2 ( x T
L
)
Current (% of Iu)
Current (% of I
L
)
Table 29
No.
Setting item
① 2nd pre-alarm current
Symbol
Ip2
②
2nd pre-alarm time
Tp2
Characteristic setting range
0.5-0.6-0.7-0.8-0.84-0.88-0.92-0.96-1.0 x Iu
0.5-0.6-0.7-0.8-0.84-0.88-0.92-0.96-1.0 x I
L
0.9-0.8-0.7-0.6-0.5-0.4-0.3 x T
L
- 5-10-15-20-30-40-60s
(x T
L
) (FLAT)
WS
WM
Accuracy
±10%
±5%
±20%
WS
WM
Factory default value
1.0
0.9(x T
L
)
< N5 module >
LTD and pre-alarm characteristics of the neutral pole are 50% of the voltage pole.
However, STD and INST characteristics are the same as for the voltage pole (100%).
For the AE630-SW low rating types, be sure to apply the control power supply.
This cannot be combined with the WB type.
E-29
advertisement
Related manuals
advertisement
Table of contents
- 3 Table of contents
- 4 External view
- 5 Internal structure/Outline dimensions and product weight
- 6 Unpacking/Storage
- 7 Transportation
- 8 Installation
- 9 Installation of the drawout handle/Installation of the inter-phase barrier (BA)
- 10 Connection
- 12 Insert operation
- 14 Drawout operation
- 16 Charging operation
- 17 Open/close operation
- 19 Door interlock (DI)/Cylinder lock (CYL) and Castell lock (CAL)/OCR alarm (AL) [MRE: manual reset type]
- 20 Shutter lock (SST-LOCK)/Safety shutter nameplate
- 21 Functions of electronic trip relay (ETR) parts
- 23 Characteristics setting for the WS type
- 24 Characteristics setting for the WM type
- 25 Characteristics setting for the WB type
- 26 Characteristics setting for the WF type
- 28 Characteristics setting for the optional setting modules
- 30 Setting procedure for the electronic trip characteristics
- 32 Wiring diagram
- 34 Technical notes
- 35 Warranty
- 36 Inspection and maintenance
- 42 SERVICE NETWORK