Characteristics setting for the optional setting modules. Mitsubishi Electric AE2000-SWA, AE4000-SW, Low-Voltage Air Circuit Breakers series Type AE-SW, AE3200-SW, AE630-SW

Add to My manuals
43 Pages

advertisement

Characteristics setting for the optional setting modules. Mitsubishi Electric AE2000-SWA, AE4000-SW, Low-Voltage Air Circuit Breakers series Type AE-SW, AE3200-SW, AE630-SW | Manualzz

Characteristics setting for the optional setting modules

< Characteristics setting for the G1 module >

1

① Ground fault pick-up current: Ig

1.0

0.1

3.0±20%

2

˜ To provide ground fault protection for a 3-pole breaker used in the 3-phase 4-wire system, a neutral pole CT (NCT) is required. For the specification, refer to the catalog.

For the installation of the NCT, refer to the instruction manual provided with the NCT.

˜ The G1 module cannot be attached to the AE630-SW low rating models (CT rating:

500 A, 315 A, 250 A).

To set the ground fault pick-up current Ig to 0.1, the control power supply must be applied. (If the control power supply is not applied, ground fault protection cannot be provided correctly.)

Table 28-1

No.

Setting item

Ground fault pick-up current

Symbol

Ig

Ground fault operating time

– Alarm output

Tg

Characteristic setting range

0.1 to 1.0 × In (0.1 step)

Accuracy

±20%

Factory default value

1.0

3.0-1.5-0.8-0.5-0.3-0.15-<0.1 - <0.1-0.15-0.3-0.5-0.8-1.5-3.0 s

(TRIP) (ALARM)

(at 1.5×Ig)

TRIP: self-hold type / ALARM: automatic reset type

±20%

3s(TRIP)

Self-hold type(TRIP)

< Characteristics setting for the E1 module >

E1 module, in combination with an external ZCT, provides electric leakage protection.

To provide the electric leakage protection, a control power supply is required.

ZCT for load circuit

ZCT type

ZCT163

ZCT323

Breaker type, number of poles

AE630-SW ~ AE1600-SW 3-pole

AE630-SW ~ AE1600-SW 4-pole

AE2000-SW ~ AE3200-SW 3-pole

AE2000-SW ~ AE3200-SW 4-pole ZCT324

Type combinations shown in this table are for reference.

Choose the one that matches the size of the conductor to be connected.

ZCT with primary conductor

ZCT type

ZTA1200A

ZTA2000A

Breaker type, number of poles

AE630-SW ~ AE1000-SW 3-pole model

AE1250-SW ~ AE2000-SW 3-pole model

AE2000-SWA 3-pole model

The types not listed above can also be used if their rated current setting (Ir) is ZCT permissible current value or lower.

ZCT for transformer earth wire

ZT15B ZT30B

ZCT type

ZT40B ZT60B ZT80B ZT100B

 Be sure to use with the ZCT specified by Mitsubishi Electric.

 For the ZCT installation, refer to the instruction manual provided with the ZCT.

Table 28-2

No.

Setting item

ER Pick-up current

Symbol

I∆n

ER Operating time

Te

– Alarm output –

Characteristic setting range

1-2-3-5-10A

3-1.5-0.8-0.5-0.3-0.15-<0.1s - <0.1-0.15-0.3-0.5-0.8-1.5-3 s

(TRIP) (ALARM)

(at 1.5×I∆n)

TRIP: self-hold type / ALARM: automatic reset type

Accuracy

0%

-30%

Factory default value

10A

±20%

3s(TRIP)

Self-hold type(TRIP)

E-28

1

② Ground fault operating time: Tg

0.15±20%

<0.1

(0.04 to 0.1s)

Ground fault current (% of CT rating In)

1A

① ER Pick-up current: I∆n

10A

3.0s±20%

② ER Operating time: Te

0.15s±20%

<0.1s

(0.04 to 0.1s)

Electric leakage current (A)

2

< Characteristics setting for the AP module >

By combining this with the pre-alarm function installed as standard, the two-step pre-alarms can be constructed.

For the AE630-SW low rating types, be sure to apply the control power supply.

This cannot be combined with the WB type.

˜ With the WS type

1

˜ With the WM type

2

① 2nd pre-alarm

Current: Ip2

LTD time: T

L

12-25-50-100-150s (at Iu x 2)

① 2nd pre-alarm

Current: Ip2

LTD time: T

L

15-20-25-30-40-60 s (at I

L

x 1.2)

② 2nd pre-alarm

Time: Tp2 (FLAT)

② 2nd pre-alarm

Time: Tp2 (FLAT)

② 2nd pre-alarm

Time: Tp2 ( x T

L

)

② 2nd pre-alarm

Time: Tp2 ( x T

L

)

Current (% of Iu)

Current (% of I

L

)

Table 29

No.

Setting item

① 2nd pre-alarm current

Symbol

Ip2

2nd pre-alarm time

Tp2

Characteristic setting range

0.5-0.6-0.7-0.8-0.84-0.88-0.92-0.96-1.0 x Iu

0.5-0.6-0.7-0.8-0.84-0.88-0.92-0.96-1.0 x I

L

0.9-0.8-0.7-0.6-0.5-0.4-0.3 x T

L

- 5-10-15-20-30-40-60s

(x T

L

) (FLAT)

WS

WM

Accuracy

±10%

±5%

±20%

WS

WM

Factory default value

1.0

0.9(x T

L

)

< N5 module >

LTD and pre-alarm characteristics of the neutral pole are 50% of the voltage pole.

However, STD and INST characteristics are the same as for the voltage pole (100%).

For the AE630-SW low rating types, be sure to apply the control power supply.

This cannot be combined with the WB type.

E-29